Ontwerp en beheer MS-net met Vision - Phase to Phase
Ontwerp en beheer MS-net met Vision - Phase to Phase
Ontwerp en beheer MS-net met Vision - Phase to Phase
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Ontwerp</strong> <strong>en</strong> <strong>beheer</strong> <strong>MS</strong>-<strong>net</strong> <strong>met</strong> <strong>Vision</strong><br />
09-010 pmo<br />
21 januari 2009<br />
<strong>Phase</strong> <strong>to</strong> <strong>Phase</strong> BV<br />
Utrechtseweg 310<br />
Postbus 100<br />
6800 AC Arnhem<br />
T: 026 352 3700<br />
F: 026 352 3709<br />
www.phase<strong>to</strong>phase.nl
2 09-010 pmo<br />
© <strong>Phase</strong> <strong>to</strong> <strong>Phase</strong> BV, Arnhem, Nederland. Alle recht<strong>en</strong> voorbehoud<strong>en</strong>.<br />
Dit docum<strong>en</strong>t bevat vertrouwelijke informatie. Overdracht van de informatie aan derd<strong>en</strong> zonder schriftelijke <strong>to</strong>estemming van of nam<strong>en</strong>s <strong>Phase</strong><br />
<strong>to</strong> <strong>Phase</strong> BV is verbod<strong>en</strong>. Hetzelfde geldt voor het kopiër<strong>en</strong> van het docum<strong>en</strong>t of e<strong>en</strong> gedeelte daarvan.<br />
<strong>Phase</strong> <strong>to</strong> <strong>Phase</strong> BV is niet aansprakelijk voor <strong>en</strong>ige directe, indirecte, bijkomstige of gevolgschade ontstaan door of bij het gebruik van de<br />
informatie of gegev<strong>en</strong>s uit dit docum<strong>en</strong>t, of door de onmogelijkheid die informatie of gegev<strong>en</strong>s te gebruik<strong>en</strong>.
3 09-010 pmo<br />
INHOUD<br />
1 Inleiding ................................................................................................................................. 4<br />
2 Oploss<strong>en</strong> van de loadflow ..................................................................................................... 4<br />
3 Belastingsmodel .................................................................................................................... 4<br />
4 Converg<strong>en</strong>tie .......................................................................................................................... 6<br />
5 Transforma<strong>to</strong>rregeling<strong>en</strong> ....................................................................................................... 7<br />
5.1 Meester-slaafregeling bij parallelle transforma<strong>to</strong>r<strong>en</strong> ............................................................ 7<br />
5.2 Stroomcomp<strong>en</strong>satie .............................................................................................................. 8<br />
5.2.1 Invloed lokale belasting<strong>en</strong> <strong>en</strong> opwekkers .............................................................................. 9<br />
5.2.2 Keuze van de comp<strong>en</strong>satie-impedantie ............................................................................... 11<br />
6 G<strong>en</strong>era<strong>to</strong>rregeling<strong>en</strong> ............................................................................................................. 11<br />
7 Eilandbedrijf .......................................................................................................................... 13<br />
8 Geleiderweerstand van kabels .............................................................................................. 16<br />
9 Mo<strong>to</strong>rstart ............................................................................................................................. 17<br />
10 Patroon .................................................................................................................................. 17<br />
Bijlage A New<strong>to</strong>n-raphson loadflow<br />
Bijlage B Spanningshuishouding van e<strong>en</strong> distributi<strong>en</strong>et
4 09-010 pmo<br />
1 INLEIDING<br />
De <strong>met</strong>hode die in <strong>Vision</strong> wordt <strong>to</strong>egepast om de spanning<strong>en</strong> <strong>en</strong> strom<strong>en</strong> in e<strong>en</strong> elektriciteitsvoorzi<strong>en</strong>ingssysteem<br />
te berek<strong>en</strong><strong>en</strong> is de loadflow volg<strong>en</strong>s New<strong>to</strong>n-Raphson. De <strong>met</strong>hode is voor het eerst beschrev<strong>en</strong> in 1961 <strong>en</strong> 1967. De<br />
loadflow convergeert snel naar e<strong>en</strong> oplossing <strong>en</strong> vanaf de introductie van sparse matrixtechniek<strong>en</strong> <strong>en</strong> optimale<br />
ord<strong>en</strong>ing t<strong>en</strong> behoeve van het eliminatieproces war<strong>en</strong> geheug<strong>en</strong>ruimte <strong>en</strong> rek<strong>en</strong>tijd ge<strong>en</strong> probleem meer. De<br />
New<strong>to</strong>n-Raphson loadflow is <strong>met</strong> succes beproefd <strong>en</strong> is wereldwijd geaccepteerd.<br />
In het <strong>net</strong>werk kom<strong>en</strong> transforma<strong>to</strong>r<strong>en</strong> <strong>en</strong> synchrone g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> <strong>met</strong> spanningsregeling voor. De regelactie van<br />
deze compon<strong>en</strong>t<strong>en</strong> beïnvloedt de spanning<strong>en</strong> in het <strong>net</strong>werk <strong>en</strong> daarmee de strom<strong>en</strong> <strong>en</strong> de belastingstrom<strong>en</strong>.<br />
Tijd<strong>en</strong>s het oploss<strong>en</strong> van de <strong>net</strong>werkvergelijking<strong>en</strong> wordt ervan uitgegaan dat eerst de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> regel<strong>en</strong> <strong>en</strong> pas<br />
daarna de trapp<strong>en</strong>schakelaars van de transforma<strong>to</strong>r<strong>en</strong>.<br />
De meeste <strong>net</strong>t<strong>en</strong> zijn gekoppeld <strong>met</strong> e<strong>en</strong> extern <strong>net</strong>, waaruit het te bestuder<strong>en</strong> <strong>net</strong> gevoed wordt. Dat externe <strong>net</strong><br />
wordt verteg<strong>en</strong>woordigd <strong>met</strong> e<strong>en</strong> <strong>net</strong>voeding, ev<strong>en</strong>tueel <strong>met</strong> e<strong>en</strong> gereduceerd model (de belangrijkste<br />
transportverbinding<strong>en</strong>) van het externe <strong>net</strong>. Indi<strong>en</strong> e<strong>en</strong> <strong>net</strong>deel niet in verbinding staat <strong>met</strong> e<strong>en</strong> <strong>net</strong>voeding, is dat<br />
<strong>net</strong>deel e<strong>en</strong> eiland. In de standaard berek<strong>en</strong>ingsmodus wordt e<strong>en</strong> eiland<strong>net</strong> niet berek<strong>en</strong>d.<br />
In de berek<strong>en</strong>ingsinstelling<strong>en</strong> kan echter word<strong>en</strong> ingesteld dat e<strong>en</strong> <strong>net</strong> in eilandbedrijf wel moet word<strong>en</strong> berek<strong>en</strong>d.<br />
<strong>Vision</strong> regelt dan het vermog<strong>en</strong> van de aanwezige synchrone g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> zodanig, dat de opwekking in balans is<br />
<strong>met</strong> de belasting in het <strong>net</strong>.<br />
2 OPLOSSEN VAN DE LOADFLOW<br />
De berek<strong>en</strong>ing van de loadflow is gebaseerd op de wett<strong>en</strong> van Kirchhoff <strong>en</strong> Ohm <strong>en</strong> op het in orde mak<strong>en</strong> van de<br />
vermog<strong>en</strong>sbalans:<br />
S <strong>net</strong>voeding = S g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> – S belasting<strong>en</strong> - S verliez<strong>en</strong><br />
Hierin is S het complexe vermog<strong>en</strong>, bestaande uit actief vermog<strong>en</strong> <strong>en</strong> blindvermog<strong>en</strong>. Het door g<strong>en</strong>era<strong>to</strong>r<strong>en</strong><br />
opgewekte vermog<strong>en</strong> wordt opg<strong>en</strong>om<strong>en</strong> door de belasting<strong>en</strong>. De <strong>net</strong>verliez<strong>en</strong> zijn e<strong>en</strong> gevolg van het transport van<br />
de elektriciteit. Aangezi<strong>en</strong> dit niet au<strong>to</strong>matisch in balans is, is de <strong>net</strong>voeding (“swingbus”) geïntroduceerd om de<br />
vermog<strong>en</strong>sbalans klopp<strong>en</strong>d te mak<strong>en</strong>.<br />
E<strong>en</strong> <strong>net</strong> heeft doorgaans één <strong>net</strong>voeding. In <strong>Vision</strong> is het weliswaar mogelijk om meerdere <strong>net</strong>voeding<strong>en</strong> <strong>to</strong>e te<br />
pass<strong>en</strong>, maar hierbij is voorzichtigheid gebod<strong>en</strong>. E<strong>en</strong> <strong>net</strong>voeding heeft e<strong>en</strong> vaste spanning in grootte <strong>en</strong> hoek. Bij<br />
koppeling van meerdere <strong>net</strong>voeding<strong>en</strong> ontstaan verschilhoek<strong>en</strong> in het <strong>net</strong> die in de praktijk anders kunn<strong>en</strong> zijn. In<br />
gekoppeld verband kan het beste slechts één <strong>net</strong>voeding <strong>to</strong>egepast word<strong>en</strong>. Indi<strong>en</strong> het <strong>net</strong> op verschill<strong>en</strong>de plekk<strong>en</strong><br />
door e<strong>en</strong> "extern <strong>net</strong>" gevoed wordt, is het het beste om te werk<strong>en</strong> <strong>met</strong> e<strong>en</strong> equival<strong>en</strong>t voor het externe <strong>net</strong>, waarin<br />
één <strong>net</strong>voeding is opg<strong>en</strong>om<strong>en</strong>.<br />
3 BELASTINGSMODEL<br />
Voor zowel het reële als imaginaire deel van de belasting, kan e<strong>en</strong> onderverdeling word<strong>en</strong> gemaakt in constant<br />
vermog<strong>en</strong> (P <strong>en</strong> Q) <strong>en</strong> constante impedantie (R <strong>en</strong> X). Door nu e<strong>en</strong> bepaalde verhouding te kiez<strong>en</strong> tuss<strong>en</strong> constante<br />
P <strong>en</strong> constante R, resp. constante Q <strong>en</strong> constante X, kan de spanningsafhankelijkheid van de belasting variër<strong>en</strong><br />
tuss<strong>en</strong> 0 <strong>en</strong> kwadratisch. Voor de belasting geldt:
5 09-010 pmo<br />
Pbelasting = P * [ (const.P / 100) + (const.R / 100)(Umod / Unom)² ]<br />
Qbelasting = Q * [ (const.Q / 100) + (const.X / 100)(Umod / Unom)² ]<br />
waarin:<br />
P, Q : belasting bij nominale knooppuntspanning<br />
: actuele knooppuntspanning<br />
U mod<br />
U nom<br />
: nominale knooppuntspanning<br />
const.P : aandeel van constant reëel vermog<strong>en</strong> in %<br />
const.Q : aandeel van constant blindvermog<strong>en</strong> in %<br />
const.R : aandeel van constante impedantie (weerstand) in %<br />
const.X : aandeel van constante impedantie (reactantie) in %<br />
<strong>en</strong><br />
const.P + const.R = 100 %<br />
const.Q + const.X = 100 %<br />
Constant vermog<strong>en</strong><br />
Bij constant vermog<strong>en</strong> zal, onafhankelijk van de berek<strong>en</strong>de knooppuntspanning U mod<br />
, het opg<strong>en</strong>om<strong>en</strong> vermog<strong>en</strong><br />
altijd constant zal blijv<strong>en</strong>. Bij e<strong>en</strong> loadflowberek<strong>en</strong>ing geldt dan:<br />
Umod neem <strong>to</strong>e:<br />
Umod neemt af:<br />
Ibelasting neemt af<br />
Pbelasting blijft constant<br />
Qbelasting blijft constant<br />
Ibelasting neemt <strong>to</strong>e<br />
Pbelasting blijft constant<br />
Qbelasting blijft constant<br />
Constante impedantie<br />
Bij constante impedantie wordt aan de hand van P belasting<br />
<strong>en</strong> Q belasting<br />
, de Z belasting<br />
bepaald bij nominale<br />
knooppuntspanning. Bij e<strong>en</strong> loadflowberek<strong>en</strong>ing geldt dan:<br />
Umod neem <strong>to</strong>e:<br />
Umod neemt af:<br />
Zbelasting blijft constant<br />
Pbelasting neemt <strong>to</strong>e<br />
Qbelasting neemt <strong>to</strong>e<br />
Zbelasting blijft constant<br />
Pbelasting neemt af<br />
Qbelasting neemt af<br />
Toepassing<br />
Het modeller<strong>en</strong> van het belastingsgedrag is gecompliceerd omdat e<strong>en</strong> algem<strong>en</strong>e belasting bestaat uit e<strong>en</strong> groot<br />
aantal diverse apparat<strong>en</strong>, zoals: mo<strong>to</strong>r<strong>en</strong>, verlichting, klimaatbehandelingsinstallaties, huishoudelijke apparatuur,<br />
elektrochemische apparatuur, elektrische ov<strong>en</strong>s, <strong>en</strong>zovoorts. De exacte sam<strong>en</strong>stelling is moeilijk te schatt<strong>en</strong> <strong>en</strong> is<br />
bov<strong>en</strong>di<strong>en</strong> seizo<strong>en</strong>safhankelijk. Het door de apparat<strong>en</strong> opg<strong>en</strong>om<strong>en</strong> actieve vermog<strong>en</strong> <strong>en</strong> blindvermog<strong>en</strong> is<br />
afhankelijk van de aangebod<strong>en</strong> spanning. Enkele voorbeeld<strong>en</strong>:<br />
• Asynchrone mo<strong>to</strong>r<strong>en</strong>: het actieve vermog<strong>en</strong> is constant bij e<strong>en</strong> spanning die maximaal 10% afwijkt van de<br />
nominale waarde; het blindvermog<strong>en</strong> volgt bij b<strong>en</strong>adering het constantestroommodel.<br />
• Gloeilamp<strong>en</strong>: het actieve vermog<strong>en</strong> wijzigt <strong>met</strong> de afwijking van de nominale spanning, <strong>to</strong>t de macht 1,5.<br />
Dit wordt bereikt <strong>met</strong> 25% constant vermog<strong>en</strong> <strong>en</strong> 75% constante admittantie; er wordt praktisch ge<strong>en</strong><br />
blindvermog<strong>en</strong> opg<strong>en</strong>om<strong>en</strong>, zodat daarvoor het model niet uitmaakt.
6 09-010 pmo<br />
• Elektrische verwarming: het actieve vermog<strong>en</strong> is kwadratisch afhankelijk van de afwijking van de nominale<br />
spanning. Dit wordt bereikt <strong>met</strong> 100% constante admittantie; er wordt praktisch ge<strong>en</strong> blindvermog<strong>en</strong><br />
opg<strong>en</strong>om<strong>en</strong>.<br />
In de literatuur (Kundur, 1994) is het belastingsgedrag voor e<strong>en</strong> klein aantal typische belasting<strong>en</strong> gegev<strong>en</strong>.<br />
Onderstaande tabel is daaruit afgeleid.<br />
Belasting<br />
Arbeidsfac<strong>to</strong>r a = ∂P/∂V b = ∂Q/∂V<br />
cos(ϕ)<br />
Woning<strong>en</strong> 0,95 1,4 2,0<br />
Zakelijk 0,90 1,3 2,0<br />
Industrieel 0,85 0,2 2,0<br />
Elektriciteitsc<strong>en</strong>trale hulpsysteem 0,80 0,1 1,6<br />
De waard<strong>en</strong> uit de tabel word<strong>en</strong> als volgt omgerek<strong>en</strong>d:<br />
Const.P = ( 1 - a / 2 ) × 100%<br />
Const.Q = ( 1 - b / 2 ) × 100%<br />
In hoogspannings<strong>net</strong>t<strong>en</strong> wordt in het algeme<strong>en</strong> het constante vermog<strong>en</strong>smodel gebruikt voor alle belasting<strong>en</strong>,<br />
omdat die belasting<strong>en</strong> zich in werkelijkheid meestal achter geregelde transforma<strong>to</strong>r<strong>en</strong> bevind<strong>en</strong>, die ervoor zorg<strong>en</strong><br />
dat spanning binn<strong>en</strong> marges constant blijft.<br />
4 CONVERGENTIE<br />
Voor de berek<strong>en</strong>ing van de loadflow wordt gebruik gemaakt van de New<strong>to</strong>n-Raphson <strong>met</strong>hode. Deze <strong>met</strong>hode komt<br />
langs iteratieve weg <strong>to</strong>t e<strong>en</strong> oplossing, waar bij elke iteratie vanuit e<strong>en</strong> <strong>to</strong>estand van het <strong>net</strong> <strong>met</strong> behulp van de<br />
afgeleide de richting naar de volg<strong>en</strong>de <strong>to</strong>estand wordt bepaald. De New<strong>to</strong>n-Raphson <strong>met</strong>hode is algeme<strong>en</strong> gebruikt<br />
<strong>en</strong> staat bek<strong>en</strong>d om zijn hoge snelheid <strong>en</strong> goede converg<strong>en</strong>tie eig<strong>en</strong>schap.<br />
Toch kan het soms voorkom<strong>en</strong> dat er ge<strong>en</strong> oplossing gevond<strong>en</strong> wordt. Hierbij wordt de melding gegev<strong>en</strong>:<br />
"maximum aantal iteraties bereikt" of "oplossing divergeert". Netwerk<strong>en</strong> waarbij e<strong>en</strong> oplossing divergeert, bezitt<strong>en</strong><br />
vaak verbinding<strong>en</strong> <strong>met</strong> relatief hoge impedanties in combinatie <strong>met</strong> relatief grote belasting<strong>en</strong>. Bij gebruik van e<strong>en</strong><br />
constant vermog<strong>en</strong>model ontstaat daarbij het probleem van e<strong>en</strong> "Voltage Collapse". E<strong>en</strong> <strong>net</strong>werk kan daarop<br />
gecontroleerd word<strong>en</strong> door de belasting<strong>en</strong> te wijzig<strong>en</strong> in het constante admittantie model.<br />
Enkele manier<strong>en</strong> om dit op te loss<strong>en</strong> zijn:<br />
• Er is e<strong>en</strong> belastingsgedrag "0% Const.PQ" gedefinieerd, waarvoor de perc<strong>en</strong>tages voor Const.P <strong>en</strong> Const.Q<br />
gelijk aan nul zijn <strong>en</strong> dus de perc<strong>en</strong>tages Const.R <strong>en</strong> Const.X gelijk aan 100%. K<strong>en</strong> vervolg<strong>en</strong>s dit<br />
belastingsgedrag (constante admittantie) <strong>to</strong>e aan alle belasting<strong>en</strong> (via: Bewerk<strong>en</strong> | Collectief | Elem<strong>en</strong>t |<br />
Belasting) <strong>en</strong> kijk of na uitvoer<strong>en</strong> van de loadflow de spanning<strong>en</strong> bijzonder hoog of laag word<strong>en</strong>.<br />
Spanning<strong>en</strong> die meer dan 20% afwijk<strong>en</strong> van de nominale spanning gev<strong>en</strong> meestal problem<strong>en</strong> bij het<br />
oploss<strong>en</strong>. Vooral als van e<strong>en</strong> of meerdere verbinding<strong>en</strong> de impedantie in verhouding <strong>to</strong>t het te<br />
transporter<strong>en</strong> vermog<strong>en</strong> groot is, zal bij constante PQ ge<strong>en</strong> oplossing mogelijk zijn <strong>en</strong> de spanning<strong>en</strong><br />
bijzonder laag kunn<strong>en</strong> word<strong>en</strong>.<br />
• De waarde van Sbasis, in de Opties te wijzig<strong>en</strong>, moet aangepast zijn aan de vermog<strong>en</strong>s die in het <strong>net</strong><br />
voorkom<strong>en</strong>. E<strong>en</strong> exacte formule is niet te gev<strong>en</strong>, maar we moet<strong>en</strong> hierbij Sbasis ongeveer dezelfde ordegrootte<br />
mak<strong>en</strong> als de vermog<strong>en</strong>s die het meest voorkom<strong>en</strong> bij opwekking, belasting <strong>en</strong> transport door de
7 09-010 pmo<br />
verbinding<strong>en</strong> in het <strong>net</strong>model. Het volstaat hierbij Sbasis te kiez<strong>en</strong> uit bijvoorbeeld 10, 100 of 1000 MVA<br />
voor respectievelijk distributie-, <strong>MS</strong>-transport- <strong>en</strong> HS-transport<strong>net</strong>t<strong>en</strong>.<br />
5 TRANSFORMATORREGELINGEN<br />
Voor alle berek<strong>en</strong>ing<strong>en</strong> wordt de transforma<strong>to</strong>r gemodelleerd volg<strong>en</strong>s onderstaande figuur. Hierin wordt R<br />
voornamelijk bepaald door P k<br />
<strong>en</strong> X voornamelijk door u k<br />
. De trapschakelaar bevindt zich meestal aan de HS-zijde<br />
(w 1<br />
).<br />
De overzetverhouding wordt, afhankelijk van de trapzijde, bepaald volg<strong>en</strong>s:<br />
Trapzijde w1: (Unom,w1 + trapstand · trapgrootte) / Unom w2<br />
Trapzijde w2: Unom,w1 / ( Unom,w2 + trapstand · trapgrootte )<br />
De impedantie van de transforma<strong>to</strong>r wordt als volgt bepaald:<br />
Impedantie Weerstand Reactantie<br />
Z<br />
2<br />
2<br />
= U<br />
k<br />
U<br />
nom<br />
eq<br />
100 ⋅<br />
Pk<br />
/1000 U<br />
nom<br />
RT<br />
= ⋅<br />
S<br />
nom<br />
S<br />
nom<br />
S<br />
nom<br />
X<br />
T<br />
=<br />
Z<br />
2<br />
eq<br />
− R<br />
2<br />
T<br />
5.1 Meester-slaafregeling bij parallelle transforma<strong>to</strong>r<strong>en</strong><br />
Meesterregeling heeft te mak<strong>en</strong> <strong>met</strong> de mogelijkheid om twee parallelle transforma<strong>to</strong>r<strong>en</strong> volg<strong>en</strong>s het "Master-slave"<br />
principe te lat<strong>en</strong> regel<strong>en</strong>, dus zodanig dat de trapp<strong>en</strong>schakelaars van de transforma<strong>to</strong>r<strong>en</strong> altijd dezelfde regelstand<br />
hebb<strong>en</strong>. Hierbij wordt de trapstand van de regelaars door één transforma<strong>to</strong>r bepaald (de "Meester"). Bij e<strong>en</strong><br />
onafhankelijke regeling kan het wel e<strong>en</strong>s voorkom<strong>en</strong> dat dat niet zo is.<br />
• Bij e<strong>en</strong> <strong>en</strong>kele transforma<strong>to</strong>r: "Eig<strong>en</strong> regeling aanwezig" <strong>en</strong> "Eig<strong>en</strong> regeling aan".<br />
• Bij twee parallelle transforma<strong>to</strong>r<strong>en</strong> bestaat de keuze uit e<strong>en</strong> onafhankelijke regeling (beide transforma<strong>to</strong>r<strong>en</strong><br />
hebb<strong>en</strong> dan "Eig<strong>en</strong> regeling aan") of voor e<strong>en</strong> afhankelijke regeling. In het geval van e<strong>en</strong> afhankelijke<br />
meester-slaafregeling moet word<strong>en</strong> gespecificeerd:<br />
• voor de "Master"-trafo: "Eig<strong>en</strong> regeling aanwezig" <strong>en</strong> "Eig<strong>en</strong> regeling aan"<br />
• voor de "Slave"-trafo: "Meesterregeling bruikbaar"; de naam van de "Master"-trafo; "Meesterregeling<br />
volg<strong>en</strong>" (de trapp<strong>en</strong>schakelaar volgt die van de meesterregeling).
8 09-010 pmo<br />
Er is nog e<strong>en</strong> optie:<br />
"Meesterregeling volg<strong>en</strong>; eig<strong>en</strong> regeling standby". Dit houdt in dat de trapp<strong>en</strong>schakelaar die van de meesterregeling<br />
volgt. In het geval dat de meesterregeling uitgeschakeld is, werkt de eig<strong>en</strong> regeling.<br />
Bij het gebruik van de meester-slaaf-regeling <strong>met</strong> parallelle transforma<strong>to</strong>r<strong>en</strong>, wordt door de slav<strong>en</strong> de<br />
overzetverhouding van de meester gekoz<strong>en</strong> of b<strong>en</strong>aderd bij ongelijke typ<strong>en</strong>.<br />
5.2 Stroomcomp<strong>en</strong>satie<br />
Stroomcomp<strong>en</strong>satie in de spanningsregeling van e<strong>en</strong> voedingstransforma<strong>to</strong>r is bedoeld om het spanningsverlies<br />
over e<strong>en</strong> verbinding te comp<strong>en</strong>ser<strong>en</strong>. In dat geval wordt de regeling gestuurd <strong>met</strong> behulp van de secundaire<br />
spanning <strong>en</strong> de belastingsstroom. De regeling is zodanig dat behalve <strong>met</strong> de spanning op de secundaire klemm<strong>en</strong><br />
van de transforma<strong>to</strong>r ook rek<strong>en</strong>ing gehoud<strong>en</strong> wordt <strong>met</strong> spanningsverliez<strong>en</strong> voorbij dit punt. De regeling is dan dus<br />
in feite ingesteld op e<strong>en</strong> fictief punt in het distributiesysteem. Deze van de belastingsstroom afhankelijke regeling<br />
wordt "compounderingsregeling" of "stroomcomp<strong>en</strong>satieregeling" g<strong>en</strong>oemd.<br />
De werking van de stroomcomp<strong>en</strong>satie licht<strong>en</strong> we kort <strong>to</strong>e <strong>met</strong> behulp van onderstaand schema. E<strong>en</strong> 50 MVA<br />
transforma<strong>to</strong>r (kortsluitspanning 14%) voedt e<strong>en</strong> richting <strong>met</strong> 5 kabelstukk<strong>en</strong> van 2 km elk. De eerste twee<br />
kabelstukk<strong>en</strong> zijn 150 mm 2 AL. De volg<strong>en</strong>de kabelstukk<strong>en</strong> zijn 95 mm 2 AL. Op elk knooppunt is e<strong>en</strong> belasting van 40<br />
A (cosϕ=0,9) aangeslot<strong>en</strong>. De spanningsregelaar is ingesteld op e<strong>en</strong> spanning tuss<strong>en</strong> 10,3 <strong>en</strong> 10,5 kV.<br />
Regeling <strong>en</strong> stroomcomp<strong>en</strong>satie:<br />
Umin = 10,2 kV<br />
Umax = 10,6 kV<br />
Totale impedantie 5 kabels:<br />
R = 2,85 Ohm<br />
X = 0,81 Ohm<br />
V<br />
HS Voeding<br />
150 kV<br />
Uk: 14 %<br />
157 / 11.5 kV<br />
<strong>MS</strong> Rail<br />
10 kV <strong>MS</strong> 1<br />
10 kV<br />
2000 m 3*150 AL GPLK 10/10 2000 m 3*150 AL GPLK 10/10<br />
Inom = 40 A<br />
<strong>MS</strong> 2<br />
10 kV<br />
2000 m 3* 95 AL GPLK 10/10<br />
Inom = 40 A<br />
<strong>MS</strong> 3<br />
10 kV<br />
Inom = 40 A<br />
<strong>MS</strong> 5<br />
10 kV<br />
2000 m 3* 95 AL GPLK 10/10<br />
<strong>MS</strong> 4<br />
10 kV<br />
2000 m 3* 95 AL GPLK 10/10<br />
Inom = 40 A<br />
Inom = 40 A<br />
Figuur 1 <strong>MS</strong>-<strong>net</strong> <strong>met</strong> verdeelde belasting<strong>en</strong><br />
De knooppuntspanning<strong>en</strong> zijn weergegev<strong>en</strong> in figuur 2. De spanning aan het uiteinde van de richting is <strong>met</strong> 9,9 kV<br />
aan de lage kant.<br />
Door de stroomcomp<strong>en</strong>satie wordt de ge<strong>met</strong><strong>en</strong> spanning gecorrigeerd <strong>met</strong> het complexe product van de secundaire<br />
stroom <strong>en</strong> de comp<strong>en</strong>satie-impedantie Z c (=R c + j X c ) volg<strong>en</strong>s vergelijking (1):<br />
U U + I ⋅ Z ⋅ 3 (1)<br />
regelaar<br />
=<br />
secundair<br />
secundair<br />
c<br />
Hierdoor "ziet" de regelaar e<strong>en</strong> lagere spanning (het complexe product heeft door de tek<strong>en</strong>afspraak e<strong>en</strong> negatieve<br />
uitwerking). Door deze correctie zal de secundaire spanning doorgaans hoger word<strong>en</strong> dan <strong>met</strong> U min <strong>en</strong> U max is opgegev<strong>en</strong>.<br />
De stroomcomp<strong>en</strong>satie zorgt ervoor dat de spanningsdaling over e<strong>en</strong> lange lijn gecomp<strong>en</strong>seerd wordt.
9 09-010 pmo<br />
Stel dat we de spanning zodanig will<strong>en</strong> corriger<strong>en</strong> dat voor de <strong>to</strong>tale belasting van 200 A de spanning aan de<br />
klemm<strong>en</strong> van de transforma<strong>to</strong>r 500 V verbetert, dan moet de absolute waarde van de impedantie van de comp<strong>en</strong>satie<br />
gelijk zijn aan:<br />
500/ 3<br />
Z<br />
c<br />
= = 1, 44Ω<br />
(2)<br />
200<br />
Rek<strong>en</strong>ing houd<strong>en</strong>d <strong>met</strong> e<strong>en</strong> cosϕ gelijk aan 0,9 krijg<strong>en</strong> we e<strong>en</strong> comp<strong>en</strong>satie-impedantie van:<br />
Z c<br />
= 1,3<br />
+ j0,<br />
63Ω<br />
(3)<br />
De spanning voor de gehele richting verbetert op die manier inderdaad <strong>met</strong> ongeveer 500 V, namelijk 3 trapstand<strong>en</strong><br />
van 150 V, afhankelijk van de tapgrootte <strong>en</strong> het ingestelde spanningsinterval. Het spanningsprofiel is weergegev<strong>en</strong> in<br />
figuur 2.<br />
11.2<br />
Spanning (kV)<br />
11<br />
10.8<br />
10.6<br />
10.4<br />
10.2<br />
10<br />
9.8<br />
9.6<br />
9.4<br />
<strong>MS</strong><br />
Rail<br />
<strong>MS</strong> 1 <strong>MS</strong> 2 <strong>MS</strong> 3 <strong>MS</strong> 4 <strong>MS</strong> 5<br />
zonder comp<strong>en</strong>satie<br />
<strong>met</strong> comp<strong>en</strong>satie<br />
Knooppunt<br />
Figuur 2 Spanningsprofiel zonder <strong>en</strong> <strong>met</strong> stroomcomp<strong>en</strong>satie.<br />
De gehele richting heeft e<strong>en</strong> <strong>to</strong>tale impedantie van 2,85 + j0,81 Ω. Op e<strong>en</strong> zodanige afstand vanaf de transforma<strong>to</strong>r,<br />
waarvoor geldt dat de "elektrische afstand" ongeveer gelijk is aan deze impedantie, zou de spanning in het<br />
ingestelde spanningsinterval moet<strong>en</strong> ligg<strong>en</strong>. Deze red<strong>en</strong>ering gaat hier niet helemaal op omdat de kabelstroom<br />
weg<strong>en</strong>s de over de knooppunt<strong>en</strong> verdeelde belasting<strong>en</strong> naar het uiteinde van de <strong>MS</strong>-richting <strong>to</strong>e afneemt.<br />
5.2.1 INVLOED LOKALE BELASTINGEN EN OPWEKKERS<br />
Het komt nogal e<strong>en</strong>s voor dat e<strong>en</strong> bijzondere belasting of e<strong>en</strong> dec<strong>en</strong>trale opwekker direct op de midd<strong>en</strong>spanningsrail<br />
van e<strong>en</strong> voedingstransforma<strong>to</strong>r wordt aangeslot<strong>en</strong>. In dat geval moet de stroom van die klant word<strong>en</strong> afgetrokk<strong>en</strong><br />
van de te comp<strong>en</strong>ser<strong>en</strong> stroom. De invloed van e<strong>en</strong> grote lokale belasting wordt <strong>to</strong>egelicht <strong>met</strong> behulp van<br />
hetzelfde <strong>net</strong>schema als in het vorige hoofdstuk, maar nu uitgebreid <strong>met</strong> e<strong>en</strong> grote belasting (figuur 3). E<strong>en</strong> 50 MVA<br />
transforma<strong>to</strong>r voedt e<strong>en</strong> dichtbij geleg<strong>en</strong> belasting <strong>en</strong> e<strong>en</strong> <strong>MS</strong>-richting <strong>met</strong> belasting. De belasting in de <strong>MS</strong>-richting<br />
is ev<strong>en</strong>redig verdeeld over vijf knooppunt<strong>en</strong>. De gedachte is om het spanningsverlies over de kabel te comp<strong>en</strong>ser<strong>en</strong>.
10 09-010 pmo<br />
V<br />
HS Voeding<br />
150 kV<br />
Regeling <strong>en</strong> stroomcomp<strong>en</strong>satie:<br />
Umin = 10,2 kV<br />
Umax = 10,6 kV<br />
Rc = 1,3 Ohm<br />
Xc = 0,63 Ohm<br />
Uk: 14 %<br />
157 / 11.5 kV<br />
<strong>MS</strong> Rail<br />
10 kV <strong>MS</strong> 1<br />
10 kV<br />
2000 m 3*150 AL GPLK 10/10 2000 m 3*150 AL GPLK 10/10<br />
Inom = 200 A<br />
Totale impedantie 5 kabels:<br />
R = 2,85 Ohm<br />
X = 0,81 Ohm<br />
Inom = 40 A<br />
<strong>MS</strong> 5<br />
10 kV<br />
2000 m 3* 95 AL GPLK 10/10<br />
<strong>MS</strong> 2<br />
10 kV<br />
<strong>MS</strong> 4<br />
10 kV<br />
2000 m 3* 95 AL GPLK 10/10<br />
Inom = 40 A<br />
<strong>MS</strong> 3<br />
10 kV<br />
Inom = 40 A<br />
2000 m 3* 95 AL GPLK 10/10<br />
Inom = 40 A<br />
Inom = 40 A<br />
Figuur 3 <strong>MS</strong>-<strong>net</strong> <strong>met</strong> verdeelde belasting<strong>en</strong> <strong>en</strong> grote lokale belasting<br />
In het schema valt op dat e<strong>en</strong> stroomcomp<strong>en</strong>satie is aangebracht <strong>met</strong> als doel het spanningsverlies over de verbinding,<br />
bestaande uit vijf kabels in serie, te comp<strong>en</strong>ser<strong>en</strong>. Wat echter ook opvalt, is dat e<strong>en</strong> grote belasting direct op<br />
de secundaire rail van de transforma<strong>to</strong>r is aangebracht. In het <strong>net</strong>je wordt de comp<strong>en</strong>satie voor de afgaande richting<br />
als het ware misleid door de last van 200 A direct op de secundaire rail (waarvoor de comp<strong>en</strong>satie niet bedoeld is),<br />
naast de te comp<strong>en</strong>ser<strong>en</strong> belasting van 200 A in de <strong>MS</strong>-richting. De invloed van de lokale belasting op de regeling is<br />
zó groot, dat de spanning in de rest van het <strong>net</strong>, dus ook op de te comp<strong>en</strong>ser<strong>en</strong> <strong>MS</strong>-richting, wordt overgecomp<strong>en</strong>seerd,<br />
soms wel leid<strong>en</strong>d <strong>to</strong>t spanning<strong>en</strong> hoger dan 11 kV. Zelfs aan het uiteinde van de richting is de spanning<br />
hoger dan het ingestelde interval (zie figuur 4).<br />
HS Voeding<br />
150.000 kV<br />
Regeling <strong>en</strong> stroomcomp<strong>en</strong>satie: Totale impedantie 5 kabels:<br />
Umin = 10,2 kV<br />
R = 2,85 Ohm<br />
X = 0,81 Ohm<br />
Umax = 10,6 kV<br />
Rc = 1,3 Ohm<br />
<strong>MS</strong> Rail<br />
Xc = 0,63 Ohm 11.371 kV <strong>MS</strong> 1<br />
11.215 kV<br />
<strong>MS</strong> 2<br />
11.090 kV<br />
V<br />
tap: -3<br />
Inom = 40 A<br />
Inom = 40 A<br />
<strong>MS</strong> 3<br />
10.950 kV<br />
Inom = 40 A<br />
Inom = 200 A<br />
<strong>MS</strong> 5<br />
10.811 kV<br />
<strong>MS</strong> 4<br />
10.857 kV<br />
Inom = 40 A<br />
Inom = 40 A<br />
Figuur 4 Overcomp<strong>en</strong>satie door grote lokale belasting<br />
Figuur 5 geeft e<strong>en</strong> beeld van de invloed van e<strong>en</strong> dec<strong>en</strong>trale opwekker, die direct op de <strong>MS</strong>-rail is aangeslot<strong>en</strong>. De<br />
spanning wordt daardoor juist te weinig gecomp<strong>en</strong>seerd <strong>en</strong> ligt voor het eerste knooppunt in de richting al b<strong>en</strong>ed<strong>en</strong><br />
het ingestelde spanningsinterval.
11 09-010 pmo<br />
HS Voeding<br />
150.000 kV<br />
Regeling <strong>en</strong> stroomcomp<strong>en</strong>satie: Totale impedantie 5 kabels:<br />
Umin = 10,2 kV<br />
R = 2,85 Ohm<br />
X = 0,81 Ohm<br />
Umax = 10,6 kV<br />
Rc = 1,3 Ohm<br />
<strong>MS</strong> Rail<br />
Xc = 0,63 Ohm 10.409 kV <strong>MS</strong> 1<br />
10.253 kV<br />
<strong>MS</strong> 2<br />
10.128 kV<br />
V<br />
tap: 4<br />
C<br />
P = 3,1 MW<br />
cos=0,85<br />
Inom = 40 A<br />
<strong>MS</strong> 5<br />
9.850 kV<br />
Inom = 40 A<br />
<strong>MS</strong> 4<br />
9.897 kV<br />
<strong>MS</strong> 3<br />
9.989 kV<br />
Inom = 40 A<br />
Inom = 40 A<br />
Inom = 40 A<br />
Figuur 5 Te weinig comp<strong>en</strong>satie door lokale dec<strong>en</strong>trale opwekker<br />
Dec<strong>en</strong>trale opwekking levert vaak oorspronkelijk niet begrep<strong>en</strong> situaties op. Sommige apparat<strong>en</strong> werk<strong>en</strong> <strong>met</strong> absolute<br />
waard<strong>en</strong> voor stroom <strong>en</strong> spanning <strong>en</strong> is dus niet richtinggevoelig. In dat geval wordt de verwarring compleet, omdat de<br />
stroomcomp<strong>en</strong>satie bij <strong>net</strong><strong>to</strong> teruglevering via de transforma<strong>to</strong>r dan het teg<strong>en</strong>gestelde effect bewerkstelligt. In die<br />
gevall<strong>en</strong> kan de stroomcomp<strong>en</strong>satie beter word<strong>en</strong> uitgeschakeld.<br />
Zeker in het geval dat de dec<strong>en</strong>trale opwekking bestaat uit e<strong>en</strong> of meerdere windturbines is het spanningsgedrag<br />
onrustig <strong>en</strong> lijkt het onvoorspelbaar. De bijdrage van deze opwekkers mag dan ook ge<strong>en</strong> onderdeel uitmak<strong>en</strong> van de te<br />
comp<strong>en</strong>ser<strong>en</strong> stroom.<br />
5.2.2 KEUZE VAN DE COMPENSATIE-IMPEDANTIE<br />
Naast de <strong>met</strong>hode van formule (2) is het ook mogelijk Z c te schatt<strong>en</strong> <strong>met</strong> behulp van de impedantie van de<br />
afgaande richting. In het hierbov<strong>en</strong> geschetste voorbeeld zou de eerste schatting uitkom<strong>en</strong> op bijvoorbeeld de helft<br />
van de <strong>to</strong>tale impedantie (1,4 + j0,8 Ω). Dat deze waarde te groot blijkt te zijn, heeft te mak<strong>en</strong> <strong>met</strong> de verdeling van<br />
de belasting. Indi<strong>en</strong> alle belasting geconc<strong>en</strong>treerd zou zijn op één punt, zou deze b<strong>en</strong>adering stukk<strong>en</strong> e<strong>en</strong>voudiger<br />
zijn.<br />
Het kiez<strong>en</strong> van de juiste impedantie is vaak e<strong>en</strong> kwestie van prober<strong>en</strong> <strong>en</strong> simuler<strong>en</strong>. In de meeste gevall<strong>en</strong> is de<br />
belasting niet zo <strong>net</strong>jes verdeeld <strong>en</strong> bestaat de richting uit kabelstukk<strong>en</strong> van diverse l<strong>en</strong>gtes <strong>en</strong> impedanties <strong>en</strong> bevat<br />
de richting aftakking<strong>en</strong>. Van tevor<strong>en</strong> moet vastligg<strong>en</strong> hoeveel knooppunt<strong>en</strong> of welke knooppunt<strong>en</strong> zeker binn<strong>en</strong> het<br />
gekoz<strong>en</strong> spanningsinterval moet<strong>en</strong> ligg<strong>en</strong>. Aandachtspunt is de mogelijkheid dat meerdere transforma<strong>to</strong>rtrapstand<strong>en</strong><br />
e<strong>en</strong> oplossing kunn<strong>en</strong> lever<strong>en</strong>.<br />
6 GENERATORREGELINGEN<br />
Cos-phi geregelde synchrone g<strong>en</strong>era<strong>to</strong>r:<br />
Bij loadflowberek<strong>en</strong>ing<strong>en</strong> wordt e<strong>en</strong> synchrone g<strong>en</strong>era<strong>to</strong>r <strong>met</strong> cos(phi)-regeling voorgesteld als e<strong>en</strong> negatieve<br />
belasting van constant vermog<strong>en</strong>.
12 09-010 pmo<br />
P belasting = -Pref<br />
Q belasting = -Pref · √(1 - cos(phi) ²) / cos(phi)<br />
of<br />
Q belasting = +Pref · √ (1 - cos(phi) ²) / cos(phi)<br />
(instelling capacitief: Q lever<strong>en</strong>)<br />
(instelling inductief: Q opnem<strong>en</strong>)<br />
Spanning geregelde synchrone g<strong>en</strong>era<strong>to</strong>r:<br />
Met U ref wordt de spanning op het knooppunt aangegev<strong>en</strong> in pu <strong>en</strong> is e<strong>en</strong> fac<strong>to</strong>r van de in het form vermelde U nom<br />
van het knooppunt. Er geldt:<br />
U mod = U ref · U nom,knooppunt<br />
De spanningsregeling bepaalt het b<strong>en</strong>odigde blindvermog<strong>en</strong> (binn<strong>en</strong> de gr<strong>en</strong>z<strong>en</strong> Q min <strong>en</strong> Q max ) voor het verkrijg<strong>en</strong><br />
van de spanning U ref . Hierbij wordt rek<strong>en</strong>ing gehoud<strong>en</strong> <strong>met</strong> statiek.<br />
( Het verloop van de functie U = f(Q g<strong>en</strong>era<strong>to</strong>r ) <strong>met</strong> statiek <strong>en</strong> de gr<strong>en</strong>z<strong>en</strong> Q min <strong>en</strong> Q max , is weergegev<strong>en</strong> in de grafiek U<br />
= f(Q g<strong>en</strong>era<strong>to</strong>r ) in het form.)<br />
Voor e<strong>en</strong> loadflowberek<strong>en</strong>ing geldt:<br />
P g<strong>en</strong>era<strong>to</strong>r is gelijk aan P ref<br />
Q g<strong>en</strong>era<strong>to</strong>r is afhankelijk van U ref , Q min , Q max <strong>en</strong> de statiek <strong>en</strong> volgt uit de <strong>to</strong>estand van het <strong>net</strong>.<br />
Als Qg<strong>en</strong>era<strong>to</strong>r tuss<strong>en</strong> de gr<strong>en</strong>z<strong>en</strong> Q min <strong>en</strong> Q max ligt, dan ligt U g<strong>en</strong>era<strong>to</strong>r tuss<strong>en</strong> U min <strong>en</strong> U max . Het verband tuss<strong>en</strong> U <strong>en</strong><br />
Q is dan gegev<strong>en</strong> door de statiek.<br />
De spanning-blindvermog<strong>en</strong>statiek is gedefinieerd in %. De waarde repres<strong>en</strong>teert de spanningsvariatie als gevolg<br />
van e<strong>en</strong> variatie in blindvermog<strong>en</strong>.<br />
U<br />
UQStatiek =<br />
Q<br />
max<br />
max<br />
−U<br />
− Q<br />
min<br />
min<br />
Q<br />
⋅<br />
U<br />
nom<br />
nom<br />
⋅100%<br />
Het minimum <strong>en</strong> het maximum van het blindvermog<strong>en</strong> dat e<strong>en</strong> g<strong>en</strong>era<strong>to</strong>r kan opwekk<strong>en</strong> bepaalt, sam<strong>en</strong> <strong>met</strong> de<br />
statiek, de extrem<strong>en</strong> in de klemspanning van de g<strong>en</strong>era<strong>to</strong>r. Uitgangspunt is de ingestelde spanning U ref .<br />
U ref<br />
U min<br />
U max<br />
Q min<br />
Q max<br />
Q min<br />
Q min<br />
U ref<br />
U min<br />
U max<br />
: minimum opgewekt blindvermog<strong>en</strong><br />
: maximum opgewekt blindvermog<strong>en</strong><br />
: ingestelde spanning<br />
: minimum klemspanning op de schuine lijn<br />
: maximum klemspanning op de schuine lijn
13 09-010 pmo<br />
De hellingshoek van de schuine lijn wordt bepaald door de UQ-statiek.<br />
Berek<strong>en</strong>ing para<strong>met</strong>ers voor meerdere g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> op hetzelfde knooppunt <strong>met</strong> behulp van gewog<strong>en</strong> gemiddelde:<br />
∑<br />
∑<br />
Snom<br />
,<br />
pu<br />
= S nom i<br />
U<br />
nom,<br />
i<br />
⋅ S<br />
nom,<br />
i<br />
Unom =<br />
Snom<br />
∑ 0.01⋅UQStatieki<br />
⋅ S<br />
statiek = ,<br />
Snom<br />
qmin =<br />
qmax =<br />
∑<br />
Q<br />
min,<br />
i<br />
Sbase<br />
∑<br />
Q<br />
max,<br />
i<br />
Sbase<br />
nom i<br />
Unom<br />
⋅ ⋅<br />
Ubase<br />
Sbase<br />
Snom<br />
De extrem<strong>en</strong> van de spanning<strong>en</strong> waartuss<strong>en</strong> de synchrone machine kan regel<strong>en</strong> volg<strong>en</strong> uit de statiek <strong>en</strong> de overige<br />
para<strong>met</strong>ers van de equival<strong>en</strong>te machine:<br />
u = | u | −statiek<br />
⋅ qmin<br />
pu<br />
u<br />
max<br />
min<br />
ref<br />
= | u | −statiek<br />
⋅ qmax<br />
pu<br />
ref<br />
pu<br />
pu<br />
pu<br />
pu<br />
Het blindvermog<strong>en</strong> van de g<strong>en</strong>era<strong>to</strong>r is dan, afhankelijk van de berek<strong>en</strong>de spanning:<br />
Q<br />
g<strong>en</strong><br />
= Q min<br />
MVA, voor u actueel ≥ u max<br />
Q<br />
g<strong>en</strong><br />
uref<br />
− uactueel<br />
= ⋅ Sbase MVA, voor u min < u actueel < u max<br />
statiek<br />
Q<br />
g<strong>en</strong><br />
= Q max<br />
MVA, voor u actueel ≤ u min<br />
7 EILANDBEDRIJF<br />
<strong>Vision</strong> kan rek<strong>en</strong><strong>en</strong> aan <strong>net</strong>t<strong>en</strong> in eilandbedrijf, zoals op schep<strong>en</strong> <strong>en</strong> boorplatforms <strong>en</strong> zoals dat kan voorkom<strong>en</strong> bij<br />
industriële <strong>net</strong>t<strong>en</strong> die soms los van het externe <strong>net</strong> kom<strong>en</strong> te staan. E<strong>en</strong> loadflowberek<strong>en</strong>ing vereist echter altijd e<strong>en</strong><br />
<strong>net</strong>voeding, waarin e<strong>en</strong> "Swingbus" is opg<strong>en</strong>om<strong>en</strong>. E<strong>en</strong> loadflow zonder swingbus werkt in principe niet, zodat er<br />
e<strong>en</strong> creatieve oplossing gevond<strong>en</strong> moet word<strong>en</strong>. In de oplossing is <strong>met</strong> name aandacht besteed aan de<br />
vermog<strong>en</strong>sverdeling over de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong>.<br />
De techniek van e<strong>en</strong> traditionele loadflow is gebaseerd op het zoek<strong>en</strong> van de knooppuntspanning<strong>en</strong> <strong>met</strong> behulp van<br />
e<strong>en</strong> systeem van <strong>net</strong>werkvergelijking<strong>en</strong>. Het <strong>net</strong>werk is gemodelleerd <strong>met</strong> ev<strong>en</strong>veel vergelijking<strong>en</strong> als er<br />
knooppunt<strong>en</strong> zijn. Op elk knooppunt kan e<strong>en</strong> vermog<strong>en</strong> word<strong>en</strong> geïnjecteerd. Dit stelsel vergelijking<strong>en</strong> kan niet<br />
word<strong>en</strong> opgelost als niet één van de onbek<strong>en</strong>d<strong>en</strong> als refer<strong>en</strong>tie g<strong>en</strong>om<strong>en</strong> wordt. Het knooppunt, waarvan de<br />
spanning als refer<strong>en</strong>tie g<strong>en</strong>om<strong>en</strong> wordt, wordt de “Swingbus” g<strong>en</strong>oemd. Van dat knooppunt ligg<strong>en</strong> de grootte <strong>en</strong> de<br />
hoek van de spanning vast. In e<strong>en</strong> traditionele loadflowberek<strong>en</strong>ing wordt de swingbus in de <strong>net</strong>voeding opg<strong>en</strong>om<strong>en</strong>.<br />
De spanning van de <strong>net</strong>voeding is daarbij e<strong>en</strong> door de gebruiker ingevoerde waarde (U ref ) maal de nominale<br />
spanning. De hoek van de spanning is meestal nul, maar kan door de gebruiker ingevoerd word<strong>en</strong>.<br />
Doordat de spanning van de <strong>net</strong>voeding vastligt, moet het complexe vermog<strong>en</strong> (P+jQ) “losgelat<strong>en</strong>” word<strong>en</strong>. Dat<br />
betek<strong>en</strong>t dat het verschil tuss<strong>en</strong> opwekking <strong>en</strong> belasting in het <strong>net</strong> altijd door de <strong>net</strong>voeding wordt aangezuiverd. De
14 09-010 pmo<br />
traditionele loadflow is dus altijd gebaseerd op vermog<strong>en</strong>suitwisseling <strong>met</strong> e<strong>en</strong> extern <strong>net</strong>, waarbij de swingbus<br />
onmisbaar is.<br />
Aangezi<strong>en</strong> er in eilandbedrijf ge<strong>en</strong> externe <strong>net</strong>voeding aanwezig is, moet er e<strong>en</strong> onzichtbare swingbus word<strong>en</strong><br />
aangebracht, <strong>en</strong> wel op zo’n manier dat die ge<strong>en</strong> merkbare invloed heeft op de <strong>to</strong>estand van het eiland<strong>net</strong>.<br />
Het vermog<strong>en</strong> dat alle belasting<strong>en</strong> in het eiland<strong>net</strong> vrag<strong>en</strong>, moet door de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> tezam<strong>en</strong> word<strong>en</strong> opgebracht.<br />
Er moet dus e<strong>en</strong> algoritme zijn ingebouwd, dat ervoor zorgt dat de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> zodanig zijn ingesteld dat de<br />
vermog<strong>en</strong>suitwisseling <strong>met</strong> de swingbus nul is. Ook moet de refer<strong>en</strong>tiespanning van de swingbus op de in het<br />
eiland<strong>net</strong> aanwezige spanning<strong>en</strong> zijn afgestemd.<br />
De kortsluitberek<strong>en</strong>ing<strong>en</strong> volg<strong>en</strong>s de <strong>met</strong>hode van de Sequ<strong>en</strong>tiële S<strong>to</strong>ringsanalyse gaat uit van de loadflowsituatie,<br />
zodat ook daar e<strong>en</strong> swingbus nodig is.<br />
Voor de kortsluitberek<strong>en</strong>ing volg<strong>en</strong>s IEC 60909 is ge<strong>en</strong> swingbus nodig.<br />
Voor de verdeling van de vermog<strong>en</strong>s over alle g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> is e<strong>en</strong> frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling aanwezig. Bij elke<br />
verandering van de belasting zal de frequ<strong>en</strong>tie iets wijzig<strong>en</strong>. De opwekkers zull<strong>en</strong> <strong>met</strong>e<strong>en</strong> reager<strong>en</strong> door meer of<br />
minder vermog<strong>en</strong> te lever<strong>en</strong>, zodat in de nieuwe <strong>to</strong>estand weer e<strong>en</strong> ev<strong>en</strong>wicht tuss<strong>en</strong> belasting <strong>en</strong> opwekking<br />
aanwezig is.<br />
E<strong>en</strong> opweke<strong>en</strong>heid <strong>met</strong> frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling gaat door de frequ<strong>en</strong>tiedaling meer vermog<strong>en</strong> lever<strong>en</strong>.<br />
Hoeveel vermog<strong>en</strong> de e<strong>en</strong>heid bijregelt, ligt vast in de statiek. De statiek is gedefinieerd als het quotiënt van de<br />
frequ<strong>en</strong>tieverandering <strong>en</strong> de vermog<strong>en</strong>sverandering.<br />
Δf<br />
/ fnom<br />
S = − ⋅100%<br />
ΔP<br />
/ P<br />
nom<br />
Hoe groter de statiek, des te minder draagt de e<strong>en</strong>heid bij aan de vermog<strong>en</strong>sverandering.<br />
De regelcoëffici<strong>en</strong>t is e<strong>en</strong> afgeleide grootheid, die aangeeft hoeveel de e<strong>en</strong>heid bijdraagt aan e<strong>en</strong> vermog<strong>en</strong>stekort.<br />
Het uiteindelijk bijgeregelde vermog<strong>en</strong> is aldus afhankelijk van de frequ<strong>en</strong>tiedaling <strong>en</strong> de regelcoëffici<strong>en</strong>t van de<br />
e<strong>en</strong>heid.<br />
P 100<br />
K<br />
T<br />
=<br />
f<br />
nom<br />
nom<br />
S<br />
⇒<br />
ΔP<br />
= −Δf<br />
⋅ K<br />
T<br />
De som van de regelconstantes van alle e<strong>en</strong>hed<strong>en</strong> wordt de Netconstante (K N ) g<strong>en</strong>oemd.<br />
Met de <strong>net</strong>constante is het mogelijk om de frequ<strong>en</strong>tieverandering in e<strong>en</strong> <strong>net</strong> als gevolg van e<strong>en</strong><br />
belastingsverandering in e<strong>en</strong> eiland<strong>net</strong> uit te rek<strong>en</strong><strong>en</strong>. Deze is gelijk aan het quotiënt van de belastingsverandering<br />
<strong>en</strong> de <strong>net</strong>constante.<br />
Δf<br />
= −<br />
n<br />
∑<br />
i=<br />
1<br />
n<br />
∑<br />
i=<br />
1<br />
ΔPi<br />
= −<br />
K<br />
i<br />
ΔP<br />
n<br />
∑<br />
i=<br />
1<br />
L<br />
K<br />
i<br />
ΔP<br />
= −<br />
K<br />
L<br />
N<br />
Ook het grote gekoppelde HS-<strong>net</strong> is e<strong>en</strong> eiland<strong>net</strong>. Elke belastingsverandering leidt <strong>to</strong>t e<strong>en</strong> frequ<strong>en</strong>tieverandering.<br />
Alle gekoppelde c<strong>en</strong>trales zijn voorzi<strong>en</strong> van e<strong>en</strong> frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling volg<strong>en</strong>s dit principe.<br />
De bijdrage van e<strong>en</strong> <strong>en</strong>kele e<strong>en</strong>heid m volgt uit de eig<strong>en</strong> regelconstante (K m ).<br />
K<br />
m<br />
Δ Pm<br />
= −Δf<br />
⋅ Km<br />
= ΔPL<br />
K<br />
N<br />
In <strong>Vision</strong> is gekoz<strong>en</strong> voor e<strong>en</strong> g<strong>en</strong>erieke aanpak. Dat houdt in dat we niet gebond<strong>en</strong> zijn aan één eiland. Elk<br />
losstaand <strong>net</strong>deel kan in eilandbedrijf word<strong>en</strong> opgelost. Daarbij word<strong>en</strong> de volg<strong>en</strong>de voorwaard<strong>en</strong> gesteld:
15 09-010 pmo<br />
• Er moet<strong>en</strong> synchrone g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> aanwezig zijn, die voorzi<strong>en</strong> zijn van e<strong>en</strong> ingeschakelde<br />
spanningsregeling <strong>en</strong> de statiek van de frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling moet zijn ingevuld.<br />
• Het in het eiland<strong>net</strong> opgestelde <strong>en</strong> ingeschakelde vermog<strong>en</strong> moet voldo<strong>en</strong>de zijn om de belasting te<br />
voed<strong>en</strong>.<br />
G<strong>en</strong>era<strong>to</strong>r<strong>en</strong>, waarvan de f/P-statiek niet is ingevuld, do<strong>en</strong> niet mee aan de regeling. Ook g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> <strong>met</strong> e<strong>en</strong> vaste<br />
cos-phi do<strong>en</strong> niet mee aan de regeling.<br />
E<strong>en</strong> gevolg voor de gekoz<strong>en</strong> aanpak is dat de keuze voor S basis belangrijker is voor het oplossingsproces. E<strong>en</strong><br />
algem<strong>en</strong>e formule voor deze waarde is niet te gev<strong>en</strong>. Indi<strong>en</strong> het oplossingsproces niet convergeert of het maximaal<br />
aantal iteraties bereikt is, kan e<strong>en</strong> andere keuze voor S basis <strong>to</strong>t betere resultat<strong>en</strong> leid<strong>en</strong>.<br />
Voorbeeld<br />
Voor de demonstratie gaan we uit van e<strong>en</strong> standaard industri<strong>en</strong>et <strong>met</strong> veel mo<strong>to</strong>rbelasting<strong>en</strong>. De nominale<br />
spanning<strong>en</strong> zijn 10 kV <strong>en</strong> 400 V. De g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> G1 <strong>en</strong> G2 hebb<strong>en</strong> e<strong>en</strong> nominaal vermog<strong>en</strong> van 10 MVA. De<br />
g<strong>en</strong>era<strong>to</strong>r G3 heeft e<strong>en</strong> nominaal vermog<strong>en</strong> van 20 MVA. Dit <strong>net</strong> kan ev<strong>en</strong>goed het <strong>net</strong> aan boord van e<strong>en</strong> schip of<br />
boorplatform zijn.<br />
Het <strong>net</strong> is gekoppeld <strong>met</strong> e<strong>en</strong> voed<strong>en</strong>d HS-<strong>net</strong>. De <strong>net</strong>voeding is gekoppeld via e<strong>en</strong> 150/10 kV transforma<strong>to</strong>r.<br />
HS-<strong>net</strong><br />
150.000 kV<br />
Inkooppunt<br />
9.980 kV<br />
-3.994 MW<br />
-1.999 Mvar<br />
-3.994 MW<br />
-1.999 Mvar<br />
4.000 MW<br />
2.001 Mvar<br />
4.000 MW<br />
2.001 Mvar<br />
Opwekking 1<br />
10.000 kV<br />
Opwekking 2<br />
10.000 kV<br />
G<br />
G1<br />
2.000 MW<br />
1.000 Mvar<br />
G G2<br />
2.000 MW<br />
1.000 Mvar<br />
G G3<br />
4.000 MW<br />
2.001 Mvar<br />
Industri<strong>en</strong>et<br />
V<br />
1.542 MW<br />
1.972 Mvar<br />
1.542 MW<br />
1.972 Mvar<br />
-1.542 MW<br />
-1.966 Mvar<br />
4.946 MW<br />
3.300 Mvar<br />
4.583 MW<br />
2.664 Mvar<br />
-4.574 MW<br />
-2.659 Mvar<br />
Fabriek 1<br />
9.956 kV<br />
-4.935 MW<br />
-3.293 Mvar<br />
0.363 MW<br />
0.632 Mvar<br />
M M1<br />
2.105 MW<br />
1.013 Mvar<br />
M M2<br />
2.105 MW<br />
1.013 Mvar<br />
-0.363 MW<br />
-0.637 Mvar<br />
Fabriek 2<br />
9.953 kV<br />
3.193 MW<br />
2.917 Mvar<br />
M3<br />
2.105 MW<br />
1.013 Mvar<br />
M<br />
LV<br />
0.386 kV<br />
-3.191 MW<br />
-2.728 Mvar<br />
M M11<br />
0.532 MW<br />
0.455 Mvar<br />
M<br />
M M13<br />
0.532 MW<br />
0.455 Mvar<br />
M<br />
M M15<br />
0.532 MW<br />
0.455 Mvar<br />
M<br />
M12<br />
0.532 MW<br />
0.455 Mvar<br />
M14<br />
0.532 MW<br />
0.455 Mvar<br />
M16<br />
0.532 MW<br />
0.455 Mvar<br />
De g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> voed<strong>en</strong> het eig<strong>en</strong> <strong>net</strong> <strong>en</strong> de onbalans wordt uit het HS-<strong>net</strong> gevoed.<br />
De <strong>to</strong>tale belasting in dit <strong>net</strong> is:<br />
P = 1,542 + 2 + 2 + 4 MW = 9,542 MW<br />
Q = 1,972 + 1 + 1 + 2,001 = 5,973 Mvar<br />
Op<strong>en</strong><strong>en</strong> van de verbinding <strong>met</strong> het voed<strong>en</strong>de HS-<strong>net</strong> leidt <strong>to</strong>t afschakeling van het achterligg<strong>en</strong>de <strong>net</strong>. In de<br />
traditionele loadflow zou dit <strong>net</strong> niet berek<strong>en</strong>d kunn<strong>en</strong> word<strong>en</strong>.<br />
De voedingstransforma<strong>to</strong>r wordt uitgeschakeld <strong>en</strong> het <strong>net</strong> gaat over in eilandbedrijf. De vermog<strong>en</strong>sverandering die<br />
de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> “zi<strong>en</strong>” is gelijk aan het weggevall<strong>en</strong> vermog<strong>en</strong> dat de <strong>net</strong>voeding leverde. De g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> voed<strong>en</strong> het<br />
eig<strong>en</strong> <strong>net</strong> <strong>en</strong> de onbalans wordt via de frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling opgevang<strong>en</strong>.<br />
De <strong>to</strong>tale opwekking in dit <strong>net</strong> is:<br />
P = 2,387 + 2,387 + 4,774 MW = 9,548 MW<br />
Q = 1,486 + 1,486 + 2,972 = 5,944 Mvar
16 09-010 pmo<br />
Deze vermog<strong>en</strong>s zijn nag<strong>en</strong>oeg gelijk aan de vermog<strong>en</strong>s in de situatie van het gekoppelde <strong>net</strong>, dus de regeling heeft<br />
goed gewerkt.<br />
De f/P-statiek van alle g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> is gelijk. Het nominale vermog<strong>en</strong> van g<strong>en</strong>era<strong>to</strong>r G3 is twee maal zo groot als dat<br />
van g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> G1 <strong>en</strong> G2.<br />
Duidelijk is te zi<strong>en</strong> dat g<strong>en</strong>era<strong>to</strong>r G3 twee keer zoveel bijdraagt aan de vermog<strong>en</strong>sverandering als g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> G1 of<br />
G2.<br />
G<strong>en</strong>era<strong>to</strong>r 1 <strong>en</strong> 2: P van 2 naar 2.387 MW<br />
G<strong>en</strong>era<strong>to</strong>r 3: P van 4 naar 4.774 MW<br />
Voor de verhouding van de bijdrag<strong>en</strong> geldt:<br />
To<strong>en</strong>ame G3 / To<strong>en</strong>ame G1 = 0.774 / 0.387 = 2<br />
HS-<strong>net</strong><br />
150.000 kV<br />
Inkooppunt<br />
9.926 kV<br />
-4.764 MW<br />
-2.966 Mvar<br />
-4.764 MW<br />
-2.967 Mvar<br />
4.774 MW<br />
2.972 Mvar<br />
4.774 MW<br />
2.973 Mvar<br />
Opwekking 1<br />
9.951 kV<br />
Opwekking 2<br />
9.951 kV<br />
G<br />
G1<br />
2.387 MW<br />
1.486 Mvar<br />
G G2<br />
2.387 MW<br />
1.486 Mvar<br />
G G3<br />
4.774 MW<br />
2.972 Mvar<br />
Industri<strong>en</strong>et<br />
V<br />
0.000 MW<br />
0.000 Mvar<br />
4.946 MW<br />
3.281 Mvar<br />
4.583 MW<br />
2.651 Mvar<br />
-4.574 MW<br />
-2.646 Mvar<br />
Fabriek 1<br />
9.902 kV<br />
-4.935 MW<br />
-3.274 Mvar<br />
0.363 MW<br />
0.626 Mvar<br />
M M1<br />
2.105 MW<br />
1.010 Mvar<br />
M M2<br />
2.105 MW<br />
1.010 Mvar<br />
-0.363 MW<br />
-0.631 Mvar<br />
Fabriek 2<br />
9.898 kV<br />
3.193 MW<br />
2.895 Mvar<br />
M3<br />
2.105 MW<br />
1.010 Mvar<br />
M<br />
LV<br />
0.384 kV<br />
-3.191 MW<br />
-2.705 Mvar<br />
M M11<br />
0.532 MW<br />
0.451 Mvar<br />
M<br />
M M13<br />
0.532 MW<br />
0.451 Mvar<br />
M<br />
M M15<br />
0.532 MW<br />
0.451 Mvar<br />
M<br />
M12<br />
0.532 MW<br />
0.451 Mvar<br />
M14<br />
0.532 MW<br />
0.451 Mvar<br />
M16<br />
0.532 MW<br />
0.451 Mvar<br />
8 GELEIDERWEERSTAND VAN KABELS<br />
De laagspanningskabels, die standaard in de kabeldatabase word<strong>en</strong> meegeleverd, hebb<strong>en</strong> e<strong>en</strong> geleiderweerstand die<br />
overe<strong>en</strong>komt <strong>met</strong> e<strong>en</strong> gespecificeerde geleidertemperatuur. De meeste kabels zijn niet continu vol belast, waardoor<br />
de temperatuur niet de maximum waarde zal bereik<strong>en</strong>. E<strong>en</strong> bedrijfspecifieke waarde kan door de gebruiker zelf<br />
word<strong>en</strong> vastgesteld. De geleiderweerstand wordt dan berek<strong>en</strong>d <strong>met</strong> onderstaande formule.<br />
R ' = R0[1<br />
+ α<br />
20<br />
( θ − 20)]<br />
waarin:<br />
R 0 : geleider gelijkstroomweerstand bij 20 grad<strong>en</strong> Celcius (opgave fabrikant)<br />
α 20 : temperatuurcoëfficiënt (0,00403 K -1 )<br />
θ: geleidertemperatuur (grad<strong>en</strong> Celsius)<br />
De berek<strong>en</strong>de waarde voor R' is de voor de temperatuur gecorrigeerde gelijkstroomweerstand. Formeel moet deze<br />
berek<strong>en</strong>de waarde nog gecorrigeerd word<strong>en</strong> <strong>met</strong> de skin effect <strong>en</strong> proximity effect fac<strong>to</strong>r<strong>en</strong> om de<br />
wisselstroomweerstand te krijg<strong>en</strong>. Deze fac<strong>to</strong>r<strong>en</strong> hebb<strong>en</strong> zo e<strong>en</strong> kleine bijdrage, dat we deze invloed<strong>en</strong> verwaarloz<strong>en</strong><br />
<strong>en</strong> de gezochte wisselstroomweerstand R gelijk stell<strong>en</strong> aan R'.
17 09-010 pmo<br />
Invloed geleiderweerstand op <strong>net</strong>spanning<br />
De spanningsval over e<strong>en</strong> kabelverbinding wordt volg<strong>en</strong>s de wet van Ohm bepaald door de stroomsterkte door <strong>en</strong><br />
door de impedantie van de kabel. De impedantie wordt bepaald door de geleiderweerstand <strong>en</strong> de zelfinductie. In<br />
laagspannings<strong>net</strong>t<strong>en</strong> <strong>met</strong> kabels heeft de geleiderweerstand de grootste invloed <strong>en</strong> speelt de zelfinductie e<strong>en</strong> veel<br />
kleinere rol. Daarom is de invloed van de temperatuur op de spanning<strong>en</strong> voornamelijk beperkt <strong>to</strong>t de laagspannings<strong>net</strong>t<strong>en</strong>.<br />
De temperatuurcoëfficiënt α 20 leidt ongeveer <strong>to</strong>t e<strong>en</strong> afwijking van 0,4 % van de geleiderweerstand per graad <strong>en</strong> <strong>to</strong>t<br />
e<strong>en</strong> ev<strong>en</strong> zo grote afwijking van de spanningsval over de betreff<strong>en</strong>de kabel.<br />
9 MOTORSTART<br />
Het aanlop<strong>en</strong> van e<strong>en</strong> mo<strong>to</strong>r gaat gepaard <strong>met</strong> e<strong>en</strong> grote aanloopstroom, waardoor spanningsdips in het <strong>net</strong><br />
ontstaan. Met e<strong>en</strong> statische berek<strong>en</strong>ing kan de dip als gevolg e<strong>en</strong> aanlop<strong>en</strong>de mo<strong>to</strong>r redelijk word<strong>en</strong> berek<strong>en</strong>d.<br />
Hierbij wordt de aanlop<strong>en</strong>de mo<strong>to</strong>r <strong>met</strong> zijn aanloopimpedantie (kortsluitimpedantie) gemodelleerd. De<br />
<strong>net</strong>voeding<strong>en</strong> <strong>en</strong> synchrone g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> word<strong>en</strong> gemodelleerd als e<strong>en</strong> equival<strong>en</strong>te spanningsbron achter hun<br />
subtransiënte impedanties.<br />
Na selecter<strong>en</strong> van mo<strong>to</strong>rstart kunn<strong>en</strong> bij de gelijknamige tab de te start<strong>en</strong> asynchrone <strong>en</strong> synchrone mo<strong>to</strong>r<strong>en</strong><br />
word<strong>en</strong> geselecteerd. Er word<strong>en</strong> 3 berek<strong>en</strong>ing<strong>en</strong> uitgevoerd waarvan de resultat<strong>en</strong> word<strong>en</strong> weergegev<strong>en</strong>:<br />
• situatie zonder de geselecteerde mo<strong>to</strong>r<strong>en</strong><br />
• situatie bij inschakeling van geselecteerde mo<strong>to</strong>r<strong>en</strong><br />
• situatie na de mo<strong>to</strong>rstart (<strong>met</strong> gestarte mo<strong>to</strong>r<strong>en</strong>).<br />
10 PATROON<br />
De functionaliteit die patron<strong>en</strong> combineert in de loadflowberek<strong>en</strong>ing<strong>en</strong> is vooral interessant voor het Asset<br />
Managem<strong>en</strong>t. In deze inleiding word<strong>en</strong> de mogelijkhed<strong>en</strong> van het gebruik van profiel<strong>en</strong> voor belasting <strong>en</strong> opwekking<br />
<strong>to</strong>egelicht. Deze pres<strong>en</strong>tatie geeft e<strong>en</strong> inleiding voor het invoer<strong>en</strong> van e<strong>en</strong> patroon, het koppel<strong>en</strong> aan belasting,<br />
opwekking <strong>en</strong> <strong>net</strong>voeding, het model van de belasting <strong>en</strong> het belastingsgedrag. In e<strong>en</strong> voorbeeld wordt de<br />
uitwerking op spanning, stroom <strong>en</strong> <strong>net</strong>verlies gedemonstreerd.<br />
E<strong>en</strong> profiel of patroon is e<strong>en</strong> getall<strong>en</strong>reeks die het gedrag van e<strong>en</strong> belasting of opwekking in de loop van de tijd<br />
beschrijft. Veel <strong>en</strong>ergiebedrijv<strong>en</strong> hebb<strong>en</strong> in het rec<strong>en</strong>te verled<strong>en</strong> deze reeks<strong>en</strong> verzameld voor typ<strong>en</strong> belasting<strong>en</strong> of<br />
voor specifieke knooppunt<strong>en</strong> in het <strong>net</strong>. De reeks<strong>en</strong> zijn meestal beschikbaar in spreadsheets.<br />
E<strong>en</strong> nieuwe patroon kan word<strong>en</strong> aangemaakt <strong>met</strong>: Nieuw | Patroon. E<strong>en</strong> bestaande patroon kan word<strong>en</strong> bekek<strong>en</strong> <strong>en</strong><br />
bewerkt <strong>met</strong>: Bewerk<strong>en</strong> | Patroon.<br />
Eig<strong>en</strong> patron<strong>en</strong> kunn<strong>en</strong> via Excel <strong>en</strong> het typ<strong>en</strong>bestand Types.XLS word<strong>en</strong> geïmporteerd.
18 09-010 pmo<br />
In het typ<strong>en</strong>bestand zijn vier voorbeeldpatron<strong>en</strong> opg<strong>en</strong>om<strong>en</strong>. Deze patron<strong>en</strong> kunn<strong>en</strong> als uitgangspunt di<strong>en</strong><strong>en</strong> om<br />
eig<strong>en</strong> patron<strong>en</strong> sam<strong>en</strong> te stell<strong>en</strong>. In het typ<strong>en</strong>bestand kunn<strong>en</strong> eig<strong>en</strong> typ<strong>en</strong> word<strong>en</strong> opg<strong>en</strong>om<strong>en</strong> voor bijvoorbeeld<br />
woonhuiz<strong>en</strong>, kan<strong>to</strong>r<strong>en</strong>, winkelc<strong>en</strong>tra, industrie.<br />
Bov<strong>en</strong>staand voorbeeld <strong>to</strong>ont de waarde voor tijdstip 9 van patroon “Voorbeeld 1”. In het volg<strong>en</strong>de diagram is deze<br />
waarde zichtbaar gemaakt.<br />
E<strong>en</strong> patroon bestaat uit 24 waard<strong>en</strong>. Dit zijn niet noodzakelijkerwijs 24 ur<strong>en</strong>. Bov<strong>en</strong>staand diagram <strong>to</strong>ont het<br />
verloop van patroon “Voorbeeld 1”, <strong>met</strong> de waarde voor tijdstip 9 omcirkeld. Alle waard<strong>en</strong> kunn<strong>en</strong> word<strong>en</strong><br />
aangepast om zodo<strong>en</strong>de de specifieke patron<strong>en</strong> voor de berek<strong>en</strong>ing<strong>en</strong> aan te mak<strong>en</strong>. Elk specifiek patroon krijgt e<strong>en</strong><br />
unieke naam, in dit voorbeeld “Demo 1”.
19 09-010 pmo<br />
Er zijn twee system<strong>en</strong> d<strong>en</strong>kbaar:<br />
• Patron<strong>en</strong> die g<strong>en</strong>ormeerd zijn op het maximum:<br />
de waarde komt niet bov<strong>en</strong> de 1 uit.<br />
• Patron<strong>en</strong> die g<strong>en</strong>ormeerd zijn op het gemiddelde:<br />
de waarde mag groter zijn dan 1.<br />
De keuze is geheel aan de gebruiker, maar heeft consequ<strong>en</strong>ties voor de belasting.<br />
E<strong>en</strong> bestaand patroon kan in het invulformulier voor belasting of opwekking word<strong>en</strong> gekoppeld.<br />
De keuze voor patron<strong>en</strong>, die g<strong>en</strong>ormeerd zijn op het maximum of op de gemiddelde waarde, heeft gevolg<strong>en</strong> voor de<br />
belasting die wordt ingevuld bij P <strong>en</strong> Q.
20 09-010 pmo<br />
Koppeling patroon aan e<strong>en</strong> <strong>net</strong>voeding<br />
Zoals e<strong>en</strong> patroon aan e<strong>en</strong> belasting of opwekking kan word<strong>en</strong> gekoppeld, kan e<strong>en</strong> patroon ook aan e<strong>en</strong> <strong>net</strong>voeding<br />
word<strong>en</strong> gekoppeld. Het patroon beïnvloed dan niet het vermog<strong>en</strong> maar de voedingsspanning, die immers ook<br />
volg<strong>en</strong>s e<strong>en</strong> patroon kan variër<strong>en</strong>.
21 09-010 pmo<br />
Demonstratie aan e<strong>en</strong> voorbeeld<strong>net</strong><br />
7...24 A<br />
MV node A1<br />
10.293...10.508 kV<br />
MV node A2<br />
10.285...10.506 kV<br />
MV node A3<br />
10.280...10.504 kV<br />
MV node A4<br />
10.276...10.503 kV<br />
V<br />
HV Rail<br />
150.000...150.000 kV<br />
1...14 A<br />
1...14 A 15...191 A<br />
Transformer A<br />
MV Rail<br />
10.405...10.557 kV<br />
1<br />
35...113 A<br />
14...47 A<br />
22...66 A 15...44 A 7...24 A<br />
7...22 A<br />
8...21 A<br />
17...59 A<br />
0...0 A<br />
Transformer B<br />
2<br />
7...89 A<br />
MV node B1<br />
10.301...10.572 kV<br />
3...77 A<br />
MV node B2<br />
10.292...10.576 kV<br />
22...51 A<br />
MV node B4<br />
10.284...10.589 kV<br />
G<br />
0...66 A<br />
8...21 A<br />
14...43 A<br />
7...24 A<br />
MV node B3<br />
10.289...10.574 kV<br />
7...24 A<br />
Spanning<strong>en</strong>:<br />
Knooppuntspanningsband<br />
HV Rail<br />
MV Rail<br />
MV node A1<br />
MV node A2<br />
MV node A3<br />
MV node A4<br />
MV node B1<br />
MV node B2<br />
MV node B3<br />
MV node B4<br />
1<br />
1.005<br />
1.01<br />
1.015<br />
1.02<br />
1.025 1.03 1.035<br />
Umin...Umax (pu)<br />
1.04<br />
1.045<br />
1.05<br />
1.055<br />
Strom<strong>en</strong>:<br />
Takbelastingsband<br />
1: MV Rail - MV node A1<br />
: MV node A1 - MV node A2<br />
: MV node A2 - MV node A3<br />
: MV node A3 - MV node A4<br />
2: MV Rail - MV node B1<br />
: MV node B1 - MV node B2<br />
: MV node B2 - MV node B3<br />
: MV node B2 - MV node B4<br />
: MV node A4 - MV node B4<br />
Transformer A: HV Rail - MV Rail<br />
2<br />
4<br />
6<br />
8 10 1214 16 18 20 22 24 2628 30 32 34 36 3840 42 44 46 48 5052 54 56 58 60 6264 66 68 70<br />
belasting min...max (%)
22 09-010 pmo<br />
Spanning als verloop van de tijd<br />
Knooppuntverloop<br />
U (kV)<br />
10.72<br />
10.7<br />
10.68<br />
10.66<br />
10.64<br />
10.62<br />
10.6<br />
10.58<br />
10.56<br />
10.54<br />
10.52<br />
10.5<br />
10.48<br />
10.46<br />
10.44<br />
10.42<br />
10.4<br />
10.38<br />
10.36<br />
10.34<br />
10.32<br />
10.3<br />
MV Rail<br />
MV node A1<br />
MV node A2<br />
MV node A3<br />
MV node A4<br />
MV node B1<br />
MV node B2<br />
MV node B3<br />
MV node B4<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12 13<br />
t<br />
14<br />
15<br />
16<br />
17<br />
18<br />
19<br />
20<br />
21<br />
22<br />
23<br />
24<br />
Stroom als verloop van de tijd<br />
70<br />
65<br />
60<br />
55<br />
50<br />
45<br />
Takverloop<br />
2<br />
Transformer A<br />
belasting (%)<br />
40<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12 13<br />
t<br />
14<br />
15<br />
16<br />
17<br />
18<br />
19<br />
20<br />
21<br />
22<br />
23<br />
24
23 09-010 pmo<br />
BIJLAGE A: NEWTON-RAPHSON LOADFLOW<br />
De <strong>met</strong>hode die in <strong>Vision</strong> wordt <strong>to</strong>egepast om de spanning<strong>en</strong> <strong>en</strong> strom<strong>en</strong> in e<strong>en</strong> elektriciteitsvoorzi<strong>en</strong>ingssysteem<br />
te berek<strong>en</strong><strong>en</strong> is de loadflow volg<strong>en</strong>s New<strong>to</strong>n-Raphson. De <strong>met</strong>hode is voor het eerst beschrev<strong>en</strong> in 1961 <strong>en</strong> 1967. De<br />
loadflow convergeert snel naar e<strong>en</strong> oplossing <strong>en</strong> vanaf de introductie van sparse matrixtechniek<strong>en</strong> <strong>en</strong> optimale<br />
ord<strong>en</strong>ing t<strong>en</strong> behoeve van het eliminatieproces war<strong>en</strong> geheug<strong>en</strong>ruimte <strong>en</strong> rek<strong>en</strong>tijd ge<strong>en</strong> probleem meer. De<br />
New<strong>to</strong>n-Raphson loadflow is <strong>met</strong> succes beproefd <strong>en</strong> is wereldwijd geaccepteerd. Dit docum<strong>en</strong>t geeft e<strong>en</strong> korte<br />
technische beschrijving.<br />
UITGANGSPUNTEN<br />
Het <strong>net</strong>werk kan word<strong>en</strong> beschrev<strong>en</strong> als e<strong>en</strong> systeem <strong>met</strong> n knooppunt<strong>en</strong> <strong>met</strong> stroominjecties I inj,i , zoals afgebeeld<br />
in onderstaande figuur.<br />
I inj,1<br />
I inj,i<br />
Y<br />
I inj,n<br />
Het systeem wordt beschrev<strong>en</strong> door n complexe vergelijking<strong>en</strong>. In matrixnotatie:<br />
I inj = [ Y ] U<br />
Voor het systeem zijn 3 soort<strong>en</strong> knooppunt<strong>en</strong> gedefinieerd. Voor elk knooppunt is e<strong>en</strong> andere set bek<strong>en</strong>de <strong>en</strong><br />
onbek<strong>en</strong>de gegev<strong>en</strong>s. Onderstaande tabel geeft e<strong>en</strong> overzicht.<br />
Knooppunt Type Bek<strong>en</strong>de para<strong>met</strong>ers Onbek<strong>en</strong>de variabel<strong>en</strong><br />
Swingbus UT |U i |<br />
arg(U i )<br />
P i<br />
Q i<br />
Spanningsgeregelde<br />
synchrone g<strong>en</strong>era<strong>to</strong>r<br />
PU |U i |<br />
P i<br />
arg(U i )<br />
Q i<br />
Belasting PQ P i<br />
Q i<br />
|U i |<br />
arg(U i )<br />
Op het knooppunt "Swingbus" is e<strong>en</strong> <strong>net</strong>voeding aanwezig. Modulus <strong>en</strong> hoek van de spanning zijn gegev<strong>en</strong>.<br />
Voor e<strong>en</strong> "G<strong>en</strong>era<strong>to</strong>r" knooppunt is het van belang of er e<strong>en</strong> spanningsgeregelde g<strong>en</strong>era<strong>to</strong>r is aangeslot<strong>en</strong>. Elk<br />
ander type g<strong>en</strong>era<strong>to</strong>r maakt van het knooppunt ge<strong>en</strong> "G<strong>en</strong>era<strong>to</strong>r" knooppunt, maar e<strong>en</strong> belastingsknooppunt,<br />
omdat die elem<strong>en</strong>t<strong>en</strong> als negatieve belasting word<strong>en</strong> behandeld.<br />
Elk ander type knooppunt is e<strong>en</strong> belastingsknooppunt. Alle<strong>en</strong> het gedeelte "Constante P <strong>en</strong> Q" komt in aanmerking<br />
voor de set "Bek<strong>en</strong>de para<strong>met</strong>ers". Het "Constante admittantie" gedeelte van de belasting wordt niet als stroom<br />
geïnjecteerd, maar komt in de systeemmatrix [Y].
24 09-010 pmo<br />
OPLOSMETHODE<br />
De oplos<strong>met</strong>hode in het algeme<strong>en</strong> is redelijk goed beschrev<strong>en</strong> in het boek "Computer Analysis of Power Systems"<br />
van Arrilaga <strong>en</strong> Arnold. De <strong>met</strong>hode volg<strong>en</strong>s New<strong>to</strong>n-Raphson zoekt het nulpunt van de functie: f k (x m ) = 0, voor alle<br />
k <strong>en</strong> alle m. Bij elke iteratie wordt het niet-lineaire vraagstuk b<strong>en</strong>aderd door e<strong>en</strong> lineaire matrixvergelijking. De<br />
b<strong>en</strong>adering wordt geïllustreerd <strong>met</strong> e<strong>en</strong> vergelijking <strong>met</strong> één variabele. In onderstaande figuur is x (p) e<strong>en</strong> b<strong>en</strong>adering<br />
van de oplossing, <strong>met</strong> fout Δx (p) bij iteratie p.<br />
raaklijn van f(x)<br />
Δx (p) f(x)<br />
x (p+1) x (p)<br />
Oplossing<br />
In dat geval is:<br />
( p)<br />
( p)<br />
f ( x + Δx<br />
) = 0 (1)<br />
Deze vergelijking kan word<strong>en</strong> beschrev<strong>en</strong> in e<strong>en</strong> Taylor reeksontwikkeling:<br />
( p)<br />
2<br />
( p)<br />
( p)<br />
( p)<br />
( p)<br />
( p)<br />
( Δx<br />
) ( p)<br />
f ( x + Δx<br />
) = f ( x ) + Δx<br />
f '( x ) + f ''( x ) + ... (2)<br />
2!<br />
Indi<strong>en</strong> de initiële schatting van de variabele x (p) zich in de buurt van de oplossing bevindt, is Δx (p) relatief klein <strong>en</strong><br />
kunn<strong>en</strong> alle hogere term<strong>en</strong> van de Taylor reeksontwikkeling word<strong>en</strong> verwaarloosd. We krijg<strong>en</strong> dan:<br />
( p)<br />
( p)<br />
( p)<br />
f ( x ) + Δx<br />
f '( x ) = 0 (3)<br />
of:<br />
( p)<br />
( p)<br />
f ( x )<br />
Δ x = −<br />
(4)<br />
( p)<br />
f '( x )<br />
De nieuwe waarde van de variabele voor de volg<strong>en</strong>de iteratie (p+1) wordt dan verkreg<strong>en</strong> via:<br />
x<br />
= x<br />
+ Δx<br />
( p+<br />
1) ( p)<br />
( p)<br />
(5)<br />
Vergelijking (3) kan ook geschrev<strong>en</strong> word<strong>en</strong> als:<br />
f ( x<br />
( p)<br />
)<br />
( p)<br />
= −JΔx<br />
(6)<br />
Waarin J de vierkante Jacobiaan is van eerste orde partiële differ<strong>en</strong>tiaalvergelijking<strong>en</strong> van de functies f k (x m ). De<br />
elem<strong>en</strong>t<strong>en</strong> van J zijn gedefinieerd door:<br />
∂fk<br />
J<br />
km<br />
= (7)<br />
∂x<br />
m
25 09-010 pmo<br />
En repres<strong>en</strong>ter<strong>en</strong> de helling<strong>en</strong> van de rak<strong>en</strong>de hyperoppervlaktes, die de functies f k (x m ) b<strong>en</strong>ader<strong>en</strong> in elk iteratiepunt.<br />
In formulevorm e<strong>en</strong> stelsel van 2n vergelijking<strong>en</strong> <strong>en</strong> 2n onbek<strong>en</strong>d<strong>en</strong>:<br />
⎡ΔP⎤<br />
⎡J<br />
⎡ Δ<br />
1<br />
J ⎤ ⎤<br />
⎥ = ⎢ ⎥ ⋅ θ<br />
2<br />
⎢<br />
⎢ ⎥ (8)<br />
⎣<br />
ΔQ<br />
⎦ ⎣J<br />
⎦ ⎣Δ<br />
| U |<br />
3<br />
J<br />
4 ⎦<br />
De New<strong>to</strong>n-Raphson <strong>met</strong>hode convergeert kwadratisch indi<strong>en</strong>:<br />
− de functies continue eerste afgeleid<strong>en</strong> hebb<strong>en</strong> in de buurt van de oplossing,<br />
− de Jacobiaan niet-singulier is <strong>en</strong><br />
− de initiële schatting<strong>en</strong> van x zich dicht bij de actuele oplossing<strong>en</strong> bevind<strong>en</strong>.<br />
Echter, de <strong>met</strong>hode is gevoelig voor het gedrag van de functies f k (x m ) <strong>en</strong> voor hun formulering. Hoe lineairder ze<br />
zijn, deste sneller <strong>en</strong> betrouwbaarder de <strong>met</strong>hode convergeert. Discontinuïteit<strong>en</strong> in de functies in de buurt van de<br />
oplossing zijn oorzaak van converg<strong>en</strong>tieproblem<strong>en</strong>, <strong>to</strong>tale onoplosbaarheid of e<strong>en</strong> niet bruikbare oplossing.<br />
Het oplosalgoritme komt in het kort neer op het onderstaande schema:<br />
Reset aantal iteraties op 0<br />
Initialiseer RHSMax op 1+Eps<br />
Zolang RHSMax > Eps & aantal iteraties niet te groot, doe:<br />
Berek<strong>en</strong> sparse Jacobiaan<br />
Berek<strong>en</strong> Mismatches<br />
Indi<strong>en</strong> de Mismatch plotseling veel groter wordt, is er sprake van diverg<strong>en</strong>tie<br />
Indi<strong>en</strong> de oplossing nog niet gevond<strong>en</strong> is:<br />
Maak de hoofddiagonaal elem<strong>en</strong>t<strong>en</strong> van Swing <strong>en</strong> G<strong>en</strong>era<strong>to</strong>rknooppunt<strong>en</strong> groot<br />
Fac<strong>to</strong>riseer de Jacobiaan t.b.v. de LU-decompositie: Jacobiaan wordt [L][U]<br />
Los het systeem op uit <strong>met</strong> behulp van y = [L][U] x<br />
Berek<strong>en</strong> de knooppuntspanning<strong>en</strong><br />
Het volg<strong>en</strong>de hoofdstuk gaat kort in op de onderdel<strong>en</strong> van het algoritme.
26 09-010 pmo<br />
DE VERGELIJKINGEN IN RELATIE TOT HET SYSTEEM<br />
De vermog<strong>en</strong>sinjectie op e<strong>en</strong> knooppunt i is beschrev<strong>en</strong> als:<br />
N<br />
u<br />
y<br />
i<br />
ij<br />
i<br />
<strong>met</strong> :<br />
ij<br />
= u ⋅i<br />
i<br />
i<br />
i<br />
= | u | e<br />
= | y<br />
ij<br />
∗<br />
inj,<br />
i<br />
jθi<br />
θ = θ −θ<br />
| e<br />
j<br />
jγ<br />
ij<br />
⎡<br />
= ui<br />
⎢<br />
⎣<br />
n<br />
∑<br />
j=<br />
1<br />
y<br />
ij<br />
u<br />
j<br />
⎤<br />
⎥<br />
⎦<br />
∗<br />
(9)<br />
Berek<strong>en</strong>ing van de Jacobiaan<br />
Voor het bepal<strong>en</strong> van de afgeleid<strong>en</strong> wordt bov<strong>en</strong>staande uitdrukking omgezet:<br />
N<br />
i<br />
=<br />
n<br />
∑<br />
j = 1<br />
| u || y<br />
i<br />
ij<br />
|| u<br />
j<br />
| e<br />
j(<br />
θ i −θ<br />
j −γ<br />
ij )<br />
= | u<br />
i<br />
2<br />
| | y<br />
ii<br />
| e<br />
j(<br />
−γ<br />
ij )<br />
+<br />
n<br />
∑<br />
i<br />
j = 1, j ≠i<br />
| u || y<br />
ij<br />
|| u<br />
j<br />
| e<br />
j(<br />
θ i −θ<br />
j −γ<br />
ij )<br />
(10)<br />
Bov<strong>en</strong>staande vergelijking wordt eerst afgeleid naar θ i <strong>en</strong> |u i | voor de (sub)diagonaal elem<strong>en</strong>t<strong>en</strong>:<br />
∂Ni<br />
= j<br />
∂θ<br />
i<br />
∂Ni<br />
∂ | u<br />
i<br />
n<br />
∑<br />
i<br />
j = 1, j ≠i<br />
| u || y<br />
= 2 | ui<br />
|| y<br />
|<br />
ij<br />
ij<br />
| e<br />
|| u<br />
j<br />
| e<br />
j(<br />
−γ<br />
ij )<br />
j(<br />
θ i −θ<br />
j −γ<br />
ij )<br />
+<br />
n<br />
∑<br />
| y<br />
ij<br />
j = 1, j ≠i<br />
=<br />
|| u<br />
j<br />
j<br />
n<br />
∑<br />
i<br />
j = 1, j ≠i<br />
| e<br />
u ( y u )<br />
ij<br />
j(<br />
θ i −θ<br />
j −γ<br />
ij )<br />
j<br />
∗<br />
= 2 | u<br />
i<br />
| y<br />
∗<br />
ij<br />
1<br />
+<br />
| u |<br />
i<br />
n<br />
∑<br />
i<br />
j = 1, j ≠i<br />
u ( y u )<br />
ij<br />
j<br />
∗<br />
(11)<br />
En vervolg<strong>en</strong>s naar θ j <strong>en</strong> |u j | voor de niet-(sub)diagonaal elem<strong>en</strong>t<strong>en</strong>:<br />
∂Ni<br />
j(<br />
θ i −θ<br />
j −γ<br />
ij )<br />
∗<br />
= − j | ui<br />
|| yij<br />
|| u<br />
j<br />
| e = − j ⋅ui(<br />
yiju<br />
j<br />
)<br />
∂θ<br />
j<br />
(12)<br />
∂Ni<br />
j(<br />
θ − − ) 1<br />
i θ j γ ij<br />
∗<br />
= | ui<br />
|| yij<br />
| e = ui(<br />
yiju<br />
j<br />
)<br />
∂ | u |<br />
| u |<br />
j<br />
j<br />
De resultat<strong>en</strong> van vergelijking<strong>en</strong> (11) word<strong>en</strong> op de hoofddiagonal<strong>en</strong> van de sub-matrices J 1 , J 2 , J 3 <strong>en</strong> J 4 ingevuld. Het<br />
reële deel van de eerste vergelijking van (11) in J 1 , het reële deel van de tweede vergelijking van (11) in J 2 , het<br />
imaginaire deel van de eerste vergelijking van (11) in J 3 <strong>en</strong> het imaginaire deel van de tweede vergelijking van (11) in<br />
J 4 .<br />
Berek<strong>en</strong>ing van de Mismatches<br />
Aan de hand van de Mismatches wordt bekek<strong>en</strong> of e<strong>en</strong> oplossing gevond<strong>en</strong> is. Indi<strong>en</strong> de <strong>met</strong>hode e<strong>en</strong> correct<br />
startpunt had, is de oplossing vrijwel zeker de juiste. De vec<strong>to</strong>r Δx bevat de hoek<strong>en</strong> <strong>en</strong> de moduli van de spanning<strong>en</strong><br />
in het <strong>net</strong>werk.<br />
⎡ Δθ<br />
⎤<br />
Δx<br />
= ⎢ ⎥ (20)<br />
⎣Δ<br />
|U | ⎦
27 09-010 pmo<br />
Voor alle knooppunt<strong>en</strong> wordt het maximum van de absolute waard<strong>en</strong> van de hoek<strong>en</strong> bepaald <strong>en</strong> voor alle<br />
belastingsknooppunt<strong>en</strong> wordt het maximum van de moduli van de spanning<strong>en</strong> bepaald. Indi<strong>en</strong> beide maxima<br />
kleiner zijn dan de <strong>to</strong>lerantie (Eps), verandert de oplossingsvec<strong>to</strong>r Δx niet meer <strong>en</strong> is e<strong>en</strong> oplossing gevond<strong>en</strong>.<br />
Berek<strong>en</strong>ing van de knooppuntspanning<strong>en</strong><br />
De knooppuntspanning<strong>en</strong> word<strong>en</strong> berek<strong>en</strong>d uit de elem<strong>en</strong>t<strong>en</strong> van de oplossingsvec<strong>to</strong>r, door de bestaande<br />
spanningsvec<strong>to</strong>r te verm<strong>en</strong>igvuldig<strong>en</strong> <strong>met</strong> de elem<strong>en</strong>t<strong>en</strong> uit vec<strong>to</strong>r Δx.<br />
Δui<br />
jΔθi<br />
ui<br />
: = ui<br />
⋅(1<br />
+ ) ⋅e<br />
(21)<br />
u<br />
|<br />
i<br />
|<br />
Voor g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> wordt dan de spanning bijgesteld in verband <strong>met</strong> de gew<strong>en</strong>ste maximale <strong>en</strong> minimale spanning,<br />
die volgt uit de spanningsstatiek.<br />
U<br />
max, i<br />
= U<br />
ref , i<br />
− statiek ⋅Qmin,<br />
i<br />
(22)<br />
U = U − statiek ⋅Q<br />
min, i<br />
ref , i<br />
max, i<br />
Als de spanning buit<strong>en</strong> de gr<strong>en</strong>z<strong>en</strong> dreigt te ligg<strong>en</strong>, wordt de nieuwe spanning:<br />
U<br />
max, i<br />
ui<br />
: = ui<br />
u<br />
U<br />
ui<br />
: = ui<br />
| u |<br />
|<br />
of<br />
(23)<br />
i<br />
|<br />
min, i<br />
i<br />
Voor e<strong>en</strong> Swingknooppunt blijft de spanning gelijk aan de gegev<strong>en</strong> waarde.
28 09-010 pmo<br />
BIJLAGE B SPANNINGSHUISHOUDING VAN EEN DISTRIBUTIENET IN NEDERLAND<br />
Met de spanningshuishouding van e<strong>en</strong> distributi<strong>en</strong>et wordt bedoeld de grootte <strong>en</strong> variatie van de <strong>net</strong>spanning van<br />
alle knooppunt<strong>en</strong> van het onderstation <strong>to</strong>t <strong>en</strong> <strong>met</strong> de <strong>met</strong>erkast van de aangeslot<strong>en</strong><strong>en</strong>. De <strong>net</strong><strong>beheer</strong>der is er<br />
verantwoordelijk voor dat de <strong>net</strong>spanning binn<strong>en</strong> de gestelde gr<strong>en</strong>z<strong>en</strong> blijft.<br />
Bepaling <strong>to</strong>elaatbare spanningsvariatie in het 10 kV-<strong>net</strong><br />
Voor e<strong>en</strong> goed <strong>MS</strong>-<strong>net</strong>ontwerp qua spanningshuishouding moet<strong>en</strong> we e<strong>en</strong> beeld hebb<strong>en</strong> van de spanningsvariatie<br />
van de voedingszijde van het 10 kV-<strong>net</strong> <strong>to</strong>t <strong>en</strong> <strong>met</strong> de <strong>met</strong>erkast van de LS-aangeslot<strong>en</strong><strong>en</strong>. De spanningsvariatie<br />
wordt behalve door de variatie aan de voedingszijde van het 10 kV-<strong>net</strong>, in belangrijke mate bepaald door het<br />
spanningsverlies in het <strong>MS</strong>-transport- <strong>en</strong> distributi<strong>en</strong>et, de 10 kV-LS transforma<strong>to</strong>r<strong>en</strong> <strong>en</strong> het LS-distributie- <strong>en</strong><br />
aansluit<strong>net</strong>. Ev<strong>en</strong>tueel aanwezige dec<strong>en</strong>trale opwek vergroot de spanningsvariatie.<br />
Er zijn drie belangrijke ijkpunt<strong>en</strong> aan te wijz<strong>en</strong>.<br />
• Het eerste ijkpunt is de spanningsvariatie aan de voedingszijde. Zoals eerder vermeld bedraagt de<br />
setwaarde van de <strong>net</strong>spanning van de10 kV-rail op het onderstation 10,55 kV. Deze waarde stell<strong>en</strong> we op<br />
100 %. De maximale <strong>net</strong>spanning is 10,65 kV (100,95 %) <strong>en</strong> de minimale 10,45 kV (99,05%).<br />
• Het tweede ijkpunt betreft de maximaal <strong>to</strong>elaatbare spanning in het 10 kV-<strong>net</strong>. Met het oog op het isoler<strong>en</strong>d<br />
vermog<strong>en</strong> mag de gr<strong>en</strong>swaarde van de <strong>net</strong>spanning 11 kV bedrag<strong>en</strong>. Kritische compon<strong>en</strong>t<strong>en</strong> hierbij zijn de<br />
GPL-kabels, de oudere 10 kV-schakelinstallaties (COQ <strong>en</strong> Conel). De oudere distributietransforma<strong>to</strong>r<strong>en</strong>,<br />
<strong>met</strong> name de N 60-g<strong>en</strong>eratie, ver<strong>to</strong>n<strong>en</strong> ook aanzi<strong>en</strong>lijk meer ijzerverliez<strong>en</strong> bij e<strong>en</strong> hogere <strong>net</strong>spanning.<br />
• Het derde ijkpunt is de fasespanning bij de LS-aangeslot<strong>en</strong>e. De afspraak is bijvoorbeeld dat de maximale<br />
fasespanning bij de LS-aangeslot<strong>en</strong>e 230 V + 6% is 243,8 V mag bedrag<strong>en</strong>. Volg<strong>en</strong>s de Netcode mag de<br />
maximale fasespanning 230 V + 10% is 253 V bedrag<strong>en</strong> (gr<strong>en</strong>swaarde). De “ruimte” bedraagt 4% ofwel<br />
9,2 V. Deze ruimte zou in de <strong>to</strong>ekomst kunn<strong>en</strong> word<strong>en</strong> b<strong>en</strong>ut voor dec<strong>en</strong>trale opwek (DCO).<br />
De laagste fasespanning bij de LS-aangeslot<strong>en</strong>e bedraagt 230 V -10% is 207 V. Dit is in overe<strong>en</strong>stemming <strong>met</strong> de<br />
Netcode.<br />
Bij de bepaling van de spanningsvariatie gaan we behalve van de bov<strong>en</strong>g<strong>en</strong>oemde ijkpunt<strong>en</strong>, uit van de volg<strong>en</strong>de<br />
richtlijn<strong>en</strong> <strong>en</strong> praktijkwaard<strong>en</strong>:<br />
1. De fasespanning op de aftakmof van de huisaansluiting bedraagt minimaal 212 V ofwel 92,2%, t<strong>en</strong> tijde van<br />
maximale belasting;<br />
2. Het spanningsverlies van het LS-rek <strong>to</strong>t de aftakmof van de huisaansluiting bedraagt t<strong>en</strong> tijde van de<br />
maximale belasting 4%;<br />
3. Het spanningsverlies in de distributietransforma<strong>to</strong>r bedraagt t<strong>en</strong> tijde van de maximale belasting 2%. Dit<br />
komt overe<strong>en</strong> <strong>met</strong> e<strong>en</strong> belastingsperc<strong>en</strong>tage van 66%. Verderop wordt dit verklaard;<br />
4. De laagste <strong>net</strong>spanning in het 10 kV-<strong>net</strong> bedraagt t<strong>en</strong> tijde van de maximale belasting 9,78 kV ofwel 92,7 %<br />
van de setwaarde. De waarde van de laagste <strong>net</strong>spanning wordt mede bepaald door het regelbereik van de<br />
oudere distributietransforma<strong>to</strong>r<strong>en</strong> (N 60). Verderop wordt dit verklaard;<br />
5. De laagste belasting in het LS-distributi<strong>en</strong>et <strong>en</strong> de distributietransforma<strong>to</strong>r<strong>en</strong> bedraagt 20% van de<br />
maximale belasting;<br />
6. De laagste belasting in het 10 kV-<strong>net</strong> bedraagt 30% van de maximale belasting.<br />
Voornoemde ijkpunt<strong>en</strong>, richtlijn<strong>en</strong> <strong>en</strong> praktijkwaard<strong>en</strong> leid<strong>en</strong> <strong>to</strong>t de spanningsvariatie welke in figuur 21 is<br />
weergegev<strong>en</strong>. Deze is gerelateerd aan de opbouw van het distributi<strong>en</strong>et.
Figuur 21<br />
Spanningsvariatie in het 10 kV-<strong>net</strong> <strong>en</strong> LS-<strong>net</strong><br />
gr<strong>en</strong>swaarde = 253 V (110%)<br />
bov<strong>en</strong>gr<strong>en</strong>swaarde<br />
11 kV (104,27%)<br />
“normaal” max. <strong>net</strong>spanning bedrijf<br />
243,8 V (106%)<br />
10,65 kV (100,95%)<br />
U SET = 10,55 kV (100%)<br />
10,45 kV (99,05%)<br />
“normaal” max. <strong>net</strong>spanning<br />
“normaal” min. <strong>net</strong>spanning<br />
gem.<br />
10,51 kV (99,67%)<br />
10,26 kV (97,25%)<br />
10,00 kV (94,79%)<br />
221,26 V (96,2%)<br />
230 V (100%)<br />
ondergr<strong>en</strong>swaarde i.v.m. regelbereik trafo’s<br />
9,78 kV (92,7%)<br />
212 V (92,2%)<br />
ondergr<strong>en</strong>swaarde i.v.m<br />
eis<strong>en</strong> Netcode<br />
207 V (90%)<br />
110 kV-<strong>net</strong> 10 kV-rail verdeelstation RMU LS-rek aftakmof <strong>met</strong>erkast
10.1 Bepaling laagste <strong>to</strong>elaatbare <strong>net</strong>spanning in 10 kV- <strong>net</strong><br />
In tabel 1 is de transformatieverhouding van alle gangbare typ<strong>en</strong> distributietransforma<strong>to</strong>r<strong>en</strong> vermeld.<br />
Transformatieverhouding “n” distributietransforma<strong>to</strong>r<strong>en</strong><br />
Type Tapstand Ums Uls n<br />
1 10500 380 27,632<br />
2 10250 380 26,974<br />
N 60 3 10000 380 26,316<br />
4 9750 380 25,658<br />
5 9500 380 25,000<br />
1 10750 400 26,875<br />
2 10500 400 26,250<br />
N 83 3 10250 400 25,625<br />
4 10000 400 25,000<br />
5 9750 400 24,375<br />
1 11000 420 26,190<br />
2 10750 420 25,595<br />
N 91 3 10500 420 25,000<br />
4 10250 420 24,405<br />
5 10000 420 23,810<br />
1 11250 420 26,786<br />
2 11000 420 26,190<br />
N 95 3 10750 420 25,595<br />
4 10500 420 25,000<br />
5 10250 420 24,405<br />
Tabel 1<br />
Zoals gezegd wordt de laagste <strong>to</strong>elaatbare <strong>net</strong>spanning in het 10 kV-<strong>net</strong> bepaald door de<br />
transformatieverhouding van de oude N 60 transforma<strong>to</strong>r<strong>en</strong>. Het <strong>net</strong> is maximaal belast.<br />
Uit de figuur 21 <strong>met</strong> de spanningsvariatie is te zi<strong>en</strong> dat bij de maximale belasting de spanning op het<br />
LS-rek 221,26 V (96,2%) bedraagt. De secundaire fasespanning in onbelaste <strong>to</strong>estand is 2% hoger <strong>en</strong><br />
bedraagt 225,86 V (98,2%).<br />
Als de spanningsregelaar van de N 60-types op maximaal staat (tapstand 5), is de<br />
transformatieverhouding minimaal, namelijk 25. De primaire <strong>net</strong>spanning moet dan minimaal<br />
bedrag<strong>en</strong> :<br />
U NET = Uf 0 x √3 x n = 225,86 x √3 x 25 = 9870 V<br />
Gelet op het grot<strong>en</strong>deels stedelijke voorzi<strong>en</strong>ingsgebied van dit voorbeeldbedrijf zal onder normale<br />
omstandighed<strong>en</strong> de <strong>net</strong>spanning nooit lager zijn dan 10.000 V.
31 09-011 pmo<br />
10.2 Instelling spanningsregelaar distributietransforma<strong>to</strong>r<strong>en</strong><br />
De instelling van de spanningsregelaar van distributietransforma<strong>to</strong>r<strong>en</strong> wordt niet alle<strong>en</strong> bepaald door<br />
het type transforma<strong>to</strong>r, maar ook door de <strong>net</strong>locatie. In figuur figuur 21 “Spanningsvariatie 10 kV-<strong>net</strong><br />
<strong>en</strong> LS-<strong>net</strong>” is te zi<strong>en</strong> dat nabij de invoeding van het 10 kV-<strong>net</strong> onder normale omstandighed<strong>en</strong> e<strong>en</strong><br />
gemiddelde <strong>net</strong>spanning heerst van 10,55 kV <strong>met</strong> e<strong>en</strong> variatie +/- 0,95 %. Bij de elektrisch verst<br />
geleg<strong>en</strong> RMU’s heerst onder normale omstandighed<strong>en</strong> e<strong>en</strong> gemiddelde <strong>net</strong>spanning van 10,26 kV <strong>met</strong><br />
e<strong>en</strong> variatie +/- 2,44 %. Bij de instelling van de spanningsregelaar houd<strong>en</strong> we ge<strong>en</strong> rek<strong>en</strong>ing <strong>met</strong> de<br />
extreme <strong>net</strong>situaties, e<strong>en</strong> bov<strong>en</strong>gr<strong>en</strong>swaarde van 11 kV of de ondergr<strong>en</strong>swaarde van 9,78 kV.<br />
Gegev<strong>en</strong> de normale <strong>net</strong>spanningsvariaties moet de fasespanning bij de LS-aangeslot<strong>en</strong><strong>en</strong> binn<strong>en</strong> de<br />
vastgestelde gr<strong>en</strong>z<strong>en</strong> blijv<strong>en</strong>; U MAX = 244 V <strong>en</strong> U MIN = 207 V.<br />
In tabel 2 zijn de berek<strong>en</strong>de tapstand<strong>en</strong> vermeld.<br />
<strong>net</strong>locatie<br />
fasespanning LS-rek (normale <strong>MS</strong>-variatie)<br />
Type nabij onderstation verst geleg<strong>en</strong> RMU nabij onderstation verst geleg<strong>en</strong> RMU<br />
trafo tapstand tr.verh. tapstand tr.verh. hoogst laagst hoogst laagst<br />
N 60 4 25,658 5 25 238,72 230,54 242,03 226,34<br />
N 83 3 25,625 4 25 239,03 230,85 242,03 226,34<br />
N 91 2 25,595 3 25 239,31 231,12 242,03 226,34<br />
N 95 3 25,595 4 25 239,31 231,12 242,03 226,34<br />
Tabel 2<br />
Berek<strong>en</strong>de tapstand<strong>en</strong><br />
Toelichting tabel 2<br />
Bij de berek<strong>en</strong>ing van de tapstand gaan we uit van de gemiddelde spanning op de <strong>net</strong>locatie.<br />
Nabij het onderstation is de gemiddelde <strong>net</strong>spanning 10,55 kV. De spanning op het LS-rek mag<br />
minimaal 221,26 V zijn bij maximale belasting <strong>en</strong> 244 V bij minimale belasting. De “op<strong>en</strong>” spanning<br />
van de transforma<strong>to</strong>r is dan respectievelijk 225,72 V <strong>en</strong> 244,92 V. De gemiddelde “op<strong>en</strong>” spanning van<br />
de transforma<strong>to</strong>r is 235,39 V.<br />
De transformatieverhouding bij de gemiddelde <strong>MS</strong>- <strong>en</strong> op<strong>en</strong> LS-spanning is: 10550 / 235,39 √3 =<br />
25,876.<br />
Uit tabel 1 van de transformatieverhouding<strong>en</strong> van de verschill<strong>en</strong>de typ<strong>en</strong> transforma<strong>to</strong>r<strong>en</strong> kunn<strong>en</strong> we<br />
dan de transformatieverhouding kiez<strong>en</strong> die het dichts in de buurt zit.<br />
Nabij de verst geleg<strong>en</strong> RMU is de gemiddelde <strong>net</strong>spanning 10,26 kV. De gemiddelde “op<strong>en</strong>” spanning<br />
van de transforma<strong>to</strong>r bedraagt zoals hiervoor vermeld 235,39 V.<br />
De transformatieverhouding bij de gemiddelde <strong>MS</strong>- <strong>en</strong> op<strong>en</strong> LS-spanning is: 10260 / 235,39 √3 =<br />
25,165.<br />
Voor alle typ<strong>en</strong> transforma<strong>to</strong>r<strong>en</strong> kiez<strong>en</strong> we de transformatieverhouding 25. Per type geeft dit wel<br />
verschill<strong>en</strong>de tapstand<strong>en</strong>.<br />
Uit de berek<strong>en</strong>ing<strong>en</strong> blijkt dat bij normale spanningsvariaties aan de gestelde eis<strong>en</strong> kan word<strong>en</strong><br />
voldaan.<br />
Het blijkt niet mogelijk om per type transforma<strong>to</strong>r één tapstand aan te houd<strong>en</strong>.
32 09-011 pmo<br />
Als we kijk<strong>en</strong> wat bij de gegev<strong>en</strong> tapstand<strong>en</strong> de gevolg<strong>en</strong> zijn in extreme situaties, krijg<strong>en</strong> we het<br />
volg<strong>en</strong>de beeld.<br />
Type<br />
tapstand<strong>en</strong><br />
op<br />
<strong>net</strong>locatie<br />
fasespanning LS-rek (gr<strong>en</strong>swaard<strong>en</strong> <strong>MS</strong>)<br />
trafo nabij onderstation verst geleg<strong>en</strong> RMU nabij onderstation verst geleg<strong>en</strong> RMU<br />
tapstand tr.verh. tapstand tr.verh. hoogst laagst hoogst laagst<br />
N 60 4 25,658 5 25 246,60 230,54 253,11 221,26<br />
N 83 3 25,625 4 25 246,92 230,85 253,11 221,26<br />
N 91 2 25,595 3 25 247,21 231,12 253,11 221,26<br />
N 95 3 25,595 4 25 247,21 231,12 253,11 221,26<br />
Tabel 3<br />
Het blijkt dat nabij het onderstation niet aan de bedrijfs-eis van maximaal 244 V wordt voldaan.<br />
Voorts dat bij de verst geleg<strong>en</strong> RMU niet aan de eis<strong>en</strong> van de Netcode wordt voldaan.<br />
Zie ook de <strong>Vision</strong>-berek<strong>en</strong>ing<strong>en</strong> van de figur<strong>en</strong> 22 <strong>en</strong> 23.<br />
V<br />
72 kW<br />
45 kvar<br />
4 A<br />
10 kV-<strong>net</strong><br />
11,000 kV<br />
0,000 °<br />
72 kW<br />
45 kvar<br />
4 A<br />
Type N 95<br />
Verst geleg<strong>en</strong> RMU<br />
400 10750/420 5j<br />
trap: 4<br />
21 %<br />
-71 kW<br />
-44 kvar<br />
110 A<br />
LS-rek<br />
0,438 kV<br />
-0,310 °<br />
71 kW<br />
44 kvar<br />
110 A<br />
Figuur 22<br />
<strong>Vision</strong>-berek<strong>en</strong>ing<br />
V<br />
210 kW<br />
136 kvar<br />
15 A<br />
10 kV-<strong>net</strong><br />
9,780 kV<br />
0,000 °<br />
210 kW<br />
136 kvar<br />
15 A<br />
Type N 95<br />
Verst geleg<strong>en</strong> RMU<br />
400 10750/420 5j<br />
trap: 4<br />
62 %<br />
-208 kW<br />
-129 kvar<br />
368 A<br />
LS-rek<br />
0,383 kV<br />
-1,160 °<br />
208 kW<br />
129 kvar<br />
368 A<br />
Figuur 23<br />
<strong>Vision</strong>-berek<strong>en</strong>ing<br />
De berek<strong>en</strong>de lijnspanning<strong>en</strong> zijn 438 V <strong>en</strong> 383 V, overe<strong>en</strong>kom<strong>en</strong>d <strong>met</strong> e<strong>en</strong> fasespanning van<br />
respectievelijk <strong>en</strong> 252,88 V <strong>en</strong> 221,13 V.
33 09-011 pmo<br />
10.3 Invloed dec<strong>en</strong>trale opwek (DCO) op de spanningshuishouding<br />
Invoeding door dec<strong>en</strong>trale opwek leidt <strong>to</strong>t verhoging van de <strong>net</strong>spanning. De spanningsverhoging<br />
hangt af van de grootte van het DCO-vermog<strong>en</strong> <strong>en</strong> grootte van het kortsluitvermog<strong>en</strong> S K ter plaatse.<br />
Voor de berek<strong>en</strong>ing van het DCO-vermog<strong>en</strong> pass<strong>en</strong> we de formule uit paragraaf 1.2 <strong>to</strong>e van de<br />
berek<strong>en</strong>ing van het spanningsverlies.<br />
ΔU<br />
= I<br />
G<br />
• ( R • cosΦ + X • sin Φ)<br />
N<br />
N<br />
Waarin:<br />
∆ U<br />
I G<br />
R N<br />
X N<br />
Ф<br />
= <strong>to</strong>elaatbare spanningsverhoging [V]<br />
= g<strong>en</strong>era<strong>to</strong>rstroom [A}<br />
= de kortsluitweerstand van het distributi<strong>en</strong>et ter plaatse van de DCO<br />
= de kortsluitreactantie van het distributi<strong>en</strong>et ter plaatse van de DCO<br />
= de ingestelde fasehoek van de DCO<br />
De maximale g<strong>en</strong>era<strong>to</strong>rstroom I G volgt uit:<br />
I<br />
G<br />
=<br />
R<br />
N<br />
ΔU<br />
• cosΦ + X<br />
N<br />
• sin Φ<br />
Het schijnbare vermog<strong>en</strong> S G van de g<strong>en</strong>era<strong>to</strong>r volgt dan uit:<br />
S<br />
G<br />
= I<br />
G G<br />
• U • 3<br />
Als rek<strong>en</strong>voorbeeld nem<strong>en</strong> we RMU “Tammingaborg 16”. De vraag is hoeveel DCO-vermog<strong>en</strong> op die<br />
locatie zou kunn<strong>en</strong> word<strong>en</strong> aangeslot<strong>en</strong>.<br />
We berek<strong>en</strong> eerst de hoogste <strong>net</strong>spanning op het knooppunt, zie figuur 24 (10495 V ). De hoogste<br />
<strong>net</strong>spanning wordt verkreg<strong>en</strong> bij de hoogste spanning op de 10 kV-rail (10,65 kV) in combinatie <strong>met</strong> de<br />
laagste <strong>net</strong>belasting (gelijktijdigheid knooppunt<strong>en</strong> 0,2) <strong>en</strong> de maximale opwekking van de overige<br />
DCO. Zie figuur 24.<br />
10,496 kV<br />
10,509 kV<br />
Tammingaborg 16<br />
10 kV<br />
U: 10,495 kV<br />
U: 1,050 pu<br />
hoek: -0,229 °<br />
P: 51 kW<br />
Q: 24 kvar<br />
I: 3 A<br />
P: 51 kW<br />
Q: 27 kvar<br />
I: 3 A<br />
trafo 1<br />
P: 0 kW<br />
Q: 3 kvar<br />
I: 0 A<br />
U: 398 V<br />
Figuur 24<br />
De “spanningsruimte” t<strong>en</strong> behoeve van DCO bedraagt: 11000 – 10495 = 505 V.
34 09-011 pmo<br />
Dan berek<strong>en</strong><strong>en</strong> we de kortsluitweerstand- <strong>en</strong> reactantie <strong>met</strong> <strong>Vision</strong> <strong>met</strong> behulp van het subm<strong>en</strong>u<br />
“Berek<strong>en</strong><strong>en</strong>-IEC 60909” het minimale kortsluitvermog<strong>en</strong> via “IEC 60909”. Zie figuur 25.<br />
Tammingaborg 16<br />
10 kV<br />
Ik": 1,93 kA<br />
R/X: 2,205<br />
Sk": 33,3 MVA<br />
Ri: 2731 mOhm<br />
Xi: 1239 mOhm<br />
tmax: 0,000 s<br />
1925 A 0 A<br />
0 A<br />
trafo 1<br />
Ik: 1,92 kA<br />
Figuur 25<br />
Uit figuur 25 blijkt dat de kortsluitweerstand R N = 2,731 Ω <strong>en</strong> de kortsluitreactantie X N = 1,239 Ω.<br />
Verder is gegev<strong>en</strong> dat de nominale cos Ф 0,8 bedraagt, dus sin Ф = 0,6. U G = 10,5 kV.<br />
De maximale g<strong>en</strong>era<strong>to</strong>rstroom I G volgt uit:<br />
I<br />
ΔU<br />
• cosΦ + X<br />
505<br />
=<br />
=<br />
= 172,<br />
G<br />
R<br />
5<br />
N<br />
N<br />
• sin Φ 2,731•<br />
0,8 + 1,239 • 0,6<br />
Het schijnbare vermog<strong>en</strong> S G van de g<strong>en</strong>era<strong>to</strong>r volgt dan uit:<br />
A<br />
SG = I<br />
G<br />
• U<br />
G<br />
• 3 = 172,5 • 10,5 • 3 = 3137kVA<br />
Het tabblad “G<strong>en</strong>era<strong>to</strong>r” van de synchrone g<strong>en</strong>era<strong>to</strong>r is in figuur 26 weergegev<strong>en</strong>.<br />
Figuur 26<br />
Tabblad g<strong>en</strong>era<strong>to</strong>r
35 09-011 pmo<br />
Voor Q MAX geldt: Q MAX = S G x sinФ = 3137 x 0,6 = 1882 kvar (lever<strong>en</strong> blindvermog<strong>en</strong>).<br />
Voor Q MIN geldt: Q MIN = -Q MAX = -1882 kvar (capacitief)<br />
Op het tabblad “Algeme<strong>en</strong>” (niet afgebeeld) wordt voor P REF ingevuld:<br />
P REF = S G x cosФ = 3137 x 0,8 = 2510 kW<br />
De loadflowberek<strong>en</strong>ing levert het volg<strong>en</strong>de resultaat op voor het knooppunt Tammingaborg 16, zie<br />
figuur 27.<br />
10,996 kV<br />
10,775 kV<br />
Tammingaborg 16<br />
10 kV<br />
U: 11,038 kV<br />
U: 1,104 pu<br />
hoek: -0,894 °<br />
P: 2455 kW<br />
Q: 1857 kvar<br />
I: 161 A<br />
P: 2510 kW<br />
Q: 1882 kvar<br />
I: 164 A<br />
P: 0 kW<br />
Q: 3 kvar<br />
I: 0 A<br />
P: 55 kW<br />
Q: 28 kvar<br />
I: 3 A<br />
trafo 1<br />
G<br />
U: 419 V<br />
Figuur 27<br />
Loadflowberek<strong>en</strong>ing bij maximale DCO<br />
De berek<strong>en</strong>de <strong>net</strong>spanning bedraagt iets meer dan 11 kV. Dit wordt veroorzaakt door e<strong>en</strong> kleine<br />
verwaarlozing in de formule voor de <strong>to</strong>elaatbare spanningsverhoging, namelijk de kleine<br />
faseverschuiving tuss<strong>en</strong> fase- <strong>en</strong> g<strong>en</strong>era<strong>to</strong>rspanning. Zie ook paragraaf 1.3 figuur 8. Ook is e<strong>en</strong> kleine<br />
belasting (3 A) aanwezig op het betreff<strong>en</strong>de knooppunt.<br />
Door middel van de “try & error” - <strong>met</strong>hode <strong>met</strong> <strong>Vision</strong> kan het g<strong>en</strong>era<strong>to</strong>rvermog<strong>en</strong> word<strong>en</strong> bepaald<br />
waarbij de <strong>net</strong>spanning exact 11 kV is; in dit voorbeeld 2900 kVA.