29.01.2015 Views

Ontwerp en beheer MS-net met Vision - Phase to Phase

Ontwerp en beheer MS-net met Vision - Phase to Phase

Ontwerp en beheer MS-net met Vision - Phase to Phase

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Ontwerp</strong> <strong>en</strong> <strong>beheer</strong> <strong>MS</strong>-<strong>net</strong> <strong>met</strong> <strong>Vision</strong><br />

09-010 pmo<br />

21 januari 2009<br />

<strong>Phase</strong> <strong>to</strong> <strong>Phase</strong> BV<br />

Utrechtseweg 310<br />

Postbus 100<br />

6800 AC Arnhem<br />

T: 026 352 3700<br />

F: 026 352 3709<br />

www.phase<strong>to</strong>phase.nl


2 09-010 pmo<br />

© <strong>Phase</strong> <strong>to</strong> <strong>Phase</strong> BV, Arnhem, Nederland. Alle recht<strong>en</strong> voorbehoud<strong>en</strong>.<br />

Dit docum<strong>en</strong>t bevat vertrouwelijke informatie. Overdracht van de informatie aan derd<strong>en</strong> zonder schriftelijke <strong>to</strong>estemming van of nam<strong>en</strong>s <strong>Phase</strong><br />

<strong>to</strong> <strong>Phase</strong> BV is verbod<strong>en</strong>. Hetzelfde geldt voor het kopiër<strong>en</strong> van het docum<strong>en</strong>t of e<strong>en</strong> gedeelte daarvan.<br />

<strong>Phase</strong> <strong>to</strong> <strong>Phase</strong> BV is niet aansprakelijk voor <strong>en</strong>ige directe, indirecte, bijkomstige of gevolgschade ontstaan door of bij het gebruik van de<br />

informatie of gegev<strong>en</strong>s uit dit docum<strong>en</strong>t, of door de onmogelijkheid die informatie of gegev<strong>en</strong>s te gebruik<strong>en</strong>.


3 09-010 pmo<br />

INHOUD<br />

1 Inleiding ................................................................................................................................. 4<br />

2 Oploss<strong>en</strong> van de loadflow ..................................................................................................... 4<br />

3 Belastingsmodel .................................................................................................................... 4<br />

4 Converg<strong>en</strong>tie .......................................................................................................................... 6<br />

5 Transforma<strong>to</strong>rregeling<strong>en</strong> ....................................................................................................... 7<br />

5.1 Meester-slaafregeling bij parallelle transforma<strong>to</strong>r<strong>en</strong> ............................................................ 7<br />

5.2 Stroomcomp<strong>en</strong>satie .............................................................................................................. 8<br />

5.2.1 Invloed lokale belasting<strong>en</strong> <strong>en</strong> opwekkers .............................................................................. 9<br />

5.2.2 Keuze van de comp<strong>en</strong>satie-impedantie ............................................................................... 11<br />

6 G<strong>en</strong>era<strong>to</strong>rregeling<strong>en</strong> ............................................................................................................. 11<br />

7 Eilandbedrijf .......................................................................................................................... 13<br />

8 Geleiderweerstand van kabels .............................................................................................. 16<br />

9 Mo<strong>to</strong>rstart ............................................................................................................................. 17<br />

10 Patroon .................................................................................................................................. 17<br />

Bijlage A New<strong>to</strong>n-raphson loadflow<br />

Bijlage B Spanningshuishouding van e<strong>en</strong> distributi<strong>en</strong>et


4 09-010 pmo<br />

1 INLEIDING<br />

De <strong>met</strong>hode die in <strong>Vision</strong> wordt <strong>to</strong>egepast om de spanning<strong>en</strong> <strong>en</strong> strom<strong>en</strong> in e<strong>en</strong> elektriciteitsvoorzi<strong>en</strong>ingssysteem<br />

te berek<strong>en</strong><strong>en</strong> is de loadflow volg<strong>en</strong>s New<strong>to</strong>n-Raphson. De <strong>met</strong>hode is voor het eerst beschrev<strong>en</strong> in 1961 <strong>en</strong> 1967. De<br />

loadflow convergeert snel naar e<strong>en</strong> oplossing <strong>en</strong> vanaf de introductie van sparse matrixtechniek<strong>en</strong> <strong>en</strong> optimale<br />

ord<strong>en</strong>ing t<strong>en</strong> behoeve van het eliminatieproces war<strong>en</strong> geheug<strong>en</strong>ruimte <strong>en</strong> rek<strong>en</strong>tijd ge<strong>en</strong> probleem meer. De<br />

New<strong>to</strong>n-Raphson loadflow is <strong>met</strong> succes beproefd <strong>en</strong> is wereldwijd geaccepteerd.<br />

In het <strong>net</strong>werk kom<strong>en</strong> transforma<strong>to</strong>r<strong>en</strong> <strong>en</strong> synchrone g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> <strong>met</strong> spanningsregeling voor. De regelactie van<br />

deze compon<strong>en</strong>t<strong>en</strong> beïnvloedt de spanning<strong>en</strong> in het <strong>net</strong>werk <strong>en</strong> daarmee de strom<strong>en</strong> <strong>en</strong> de belastingstrom<strong>en</strong>.<br />

Tijd<strong>en</strong>s het oploss<strong>en</strong> van de <strong>net</strong>werkvergelijking<strong>en</strong> wordt ervan uitgegaan dat eerst de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> regel<strong>en</strong> <strong>en</strong> pas<br />

daarna de trapp<strong>en</strong>schakelaars van de transforma<strong>to</strong>r<strong>en</strong>.<br />

De meeste <strong>net</strong>t<strong>en</strong> zijn gekoppeld <strong>met</strong> e<strong>en</strong> extern <strong>net</strong>, waaruit het te bestuder<strong>en</strong> <strong>net</strong> gevoed wordt. Dat externe <strong>net</strong><br />

wordt verteg<strong>en</strong>woordigd <strong>met</strong> e<strong>en</strong> <strong>net</strong>voeding, ev<strong>en</strong>tueel <strong>met</strong> e<strong>en</strong> gereduceerd model (de belangrijkste<br />

transportverbinding<strong>en</strong>) van het externe <strong>net</strong>. Indi<strong>en</strong> e<strong>en</strong> <strong>net</strong>deel niet in verbinding staat <strong>met</strong> e<strong>en</strong> <strong>net</strong>voeding, is dat<br />

<strong>net</strong>deel e<strong>en</strong> eiland. In de standaard berek<strong>en</strong>ingsmodus wordt e<strong>en</strong> eiland<strong>net</strong> niet berek<strong>en</strong>d.<br />

In de berek<strong>en</strong>ingsinstelling<strong>en</strong> kan echter word<strong>en</strong> ingesteld dat e<strong>en</strong> <strong>net</strong> in eilandbedrijf wel moet word<strong>en</strong> berek<strong>en</strong>d.<br />

<strong>Vision</strong> regelt dan het vermog<strong>en</strong> van de aanwezige synchrone g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> zodanig, dat de opwekking in balans is<br />

<strong>met</strong> de belasting in het <strong>net</strong>.<br />

2 OPLOSSEN VAN DE LOADFLOW<br />

De berek<strong>en</strong>ing van de loadflow is gebaseerd op de wett<strong>en</strong> van Kirchhoff <strong>en</strong> Ohm <strong>en</strong> op het in orde mak<strong>en</strong> van de<br />

vermog<strong>en</strong>sbalans:<br />

S <strong>net</strong>voeding = S g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> – S belasting<strong>en</strong> - S verliez<strong>en</strong><br />

Hierin is S het complexe vermog<strong>en</strong>, bestaande uit actief vermog<strong>en</strong> <strong>en</strong> blindvermog<strong>en</strong>. Het door g<strong>en</strong>era<strong>to</strong>r<strong>en</strong><br />

opgewekte vermog<strong>en</strong> wordt opg<strong>en</strong>om<strong>en</strong> door de belasting<strong>en</strong>. De <strong>net</strong>verliez<strong>en</strong> zijn e<strong>en</strong> gevolg van het transport van<br />

de elektriciteit. Aangezi<strong>en</strong> dit niet au<strong>to</strong>matisch in balans is, is de <strong>net</strong>voeding (“swingbus”) geïntroduceerd om de<br />

vermog<strong>en</strong>sbalans klopp<strong>en</strong>d te mak<strong>en</strong>.<br />

E<strong>en</strong> <strong>net</strong> heeft doorgaans één <strong>net</strong>voeding. In <strong>Vision</strong> is het weliswaar mogelijk om meerdere <strong>net</strong>voeding<strong>en</strong> <strong>to</strong>e te<br />

pass<strong>en</strong>, maar hierbij is voorzichtigheid gebod<strong>en</strong>. E<strong>en</strong> <strong>net</strong>voeding heeft e<strong>en</strong> vaste spanning in grootte <strong>en</strong> hoek. Bij<br />

koppeling van meerdere <strong>net</strong>voeding<strong>en</strong> ontstaan verschilhoek<strong>en</strong> in het <strong>net</strong> die in de praktijk anders kunn<strong>en</strong> zijn. In<br />

gekoppeld verband kan het beste slechts één <strong>net</strong>voeding <strong>to</strong>egepast word<strong>en</strong>. Indi<strong>en</strong> het <strong>net</strong> op verschill<strong>en</strong>de plekk<strong>en</strong><br />

door e<strong>en</strong> "extern <strong>net</strong>" gevoed wordt, is het het beste om te werk<strong>en</strong> <strong>met</strong> e<strong>en</strong> equival<strong>en</strong>t voor het externe <strong>net</strong>, waarin<br />

één <strong>net</strong>voeding is opg<strong>en</strong>om<strong>en</strong>.<br />

3 BELASTINGSMODEL<br />

Voor zowel het reële als imaginaire deel van de belasting, kan e<strong>en</strong> onderverdeling word<strong>en</strong> gemaakt in constant<br />

vermog<strong>en</strong> (P <strong>en</strong> Q) <strong>en</strong> constante impedantie (R <strong>en</strong> X). Door nu e<strong>en</strong> bepaalde verhouding te kiez<strong>en</strong> tuss<strong>en</strong> constante<br />

P <strong>en</strong> constante R, resp. constante Q <strong>en</strong> constante X, kan de spanningsafhankelijkheid van de belasting variër<strong>en</strong><br />

tuss<strong>en</strong> 0 <strong>en</strong> kwadratisch. Voor de belasting geldt:


5 09-010 pmo<br />

Pbelasting = P * [ (const.P / 100) + (const.R / 100)(Umod / Unom)² ]<br />

Qbelasting = Q * [ (const.Q / 100) + (const.X / 100)(Umod / Unom)² ]<br />

waarin:<br />

P, Q : belasting bij nominale knooppuntspanning<br />

: actuele knooppuntspanning<br />

U mod<br />

U nom<br />

: nominale knooppuntspanning<br />

const.P : aandeel van constant reëel vermog<strong>en</strong> in %<br />

const.Q : aandeel van constant blindvermog<strong>en</strong> in %<br />

const.R : aandeel van constante impedantie (weerstand) in %<br />

const.X : aandeel van constante impedantie (reactantie) in %<br />

<strong>en</strong><br />

const.P + const.R = 100 %<br />

const.Q + const.X = 100 %<br />

Constant vermog<strong>en</strong><br />

Bij constant vermog<strong>en</strong> zal, onafhankelijk van de berek<strong>en</strong>de knooppuntspanning U mod<br />

, het opg<strong>en</strong>om<strong>en</strong> vermog<strong>en</strong><br />

altijd constant zal blijv<strong>en</strong>. Bij e<strong>en</strong> loadflowberek<strong>en</strong>ing geldt dan:<br />

Umod neem <strong>to</strong>e:<br />

Umod neemt af:<br />

Ibelasting neemt af<br />

Pbelasting blijft constant<br />

Qbelasting blijft constant<br />

Ibelasting neemt <strong>to</strong>e<br />

Pbelasting blijft constant<br />

Qbelasting blijft constant<br />

Constante impedantie<br />

Bij constante impedantie wordt aan de hand van P belasting<br />

<strong>en</strong> Q belasting<br />

, de Z belasting<br />

bepaald bij nominale<br />

knooppuntspanning. Bij e<strong>en</strong> loadflowberek<strong>en</strong>ing geldt dan:<br />

Umod neem <strong>to</strong>e:<br />

Umod neemt af:<br />

Zbelasting blijft constant<br />

Pbelasting neemt <strong>to</strong>e<br />

Qbelasting neemt <strong>to</strong>e<br />

Zbelasting blijft constant<br />

Pbelasting neemt af<br />

Qbelasting neemt af<br />

Toepassing<br />

Het modeller<strong>en</strong> van het belastingsgedrag is gecompliceerd omdat e<strong>en</strong> algem<strong>en</strong>e belasting bestaat uit e<strong>en</strong> groot<br />

aantal diverse apparat<strong>en</strong>, zoals: mo<strong>to</strong>r<strong>en</strong>, verlichting, klimaatbehandelingsinstallaties, huishoudelijke apparatuur,<br />

elektrochemische apparatuur, elektrische ov<strong>en</strong>s, <strong>en</strong>zovoorts. De exacte sam<strong>en</strong>stelling is moeilijk te schatt<strong>en</strong> <strong>en</strong> is<br />

bov<strong>en</strong>di<strong>en</strong> seizo<strong>en</strong>safhankelijk. Het door de apparat<strong>en</strong> opg<strong>en</strong>om<strong>en</strong> actieve vermog<strong>en</strong> <strong>en</strong> blindvermog<strong>en</strong> is<br />

afhankelijk van de aangebod<strong>en</strong> spanning. Enkele voorbeeld<strong>en</strong>:<br />

• Asynchrone mo<strong>to</strong>r<strong>en</strong>: het actieve vermog<strong>en</strong> is constant bij e<strong>en</strong> spanning die maximaal 10% afwijkt van de<br />

nominale waarde; het blindvermog<strong>en</strong> volgt bij b<strong>en</strong>adering het constantestroommodel.<br />

• Gloeilamp<strong>en</strong>: het actieve vermog<strong>en</strong> wijzigt <strong>met</strong> de afwijking van de nominale spanning, <strong>to</strong>t de macht 1,5.<br />

Dit wordt bereikt <strong>met</strong> 25% constant vermog<strong>en</strong> <strong>en</strong> 75% constante admittantie; er wordt praktisch ge<strong>en</strong><br />

blindvermog<strong>en</strong> opg<strong>en</strong>om<strong>en</strong>, zodat daarvoor het model niet uitmaakt.


6 09-010 pmo<br />

• Elektrische verwarming: het actieve vermog<strong>en</strong> is kwadratisch afhankelijk van de afwijking van de nominale<br />

spanning. Dit wordt bereikt <strong>met</strong> 100% constante admittantie; er wordt praktisch ge<strong>en</strong> blindvermog<strong>en</strong><br />

opg<strong>en</strong>om<strong>en</strong>.<br />

In de literatuur (Kundur, 1994) is het belastingsgedrag voor e<strong>en</strong> klein aantal typische belasting<strong>en</strong> gegev<strong>en</strong>.<br />

Onderstaande tabel is daaruit afgeleid.<br />

Belasting<br />

Arbeidsfac<strong>to</strong>r a = ∂P/∂V b = ∂Q/∂V<br />

cos(ϕ)<br />

Woning<strong>en</strong> 0,95 1,4 2,0<br />

Zakelijk 0,90 1,3 2,0<br />

Industrieel 0,85 0,2 2,0<br />

Elektriciteitsc<strong>en</strong>trale hulpsysteem 0,80 0,1 1,6<br />

De waard<strong>en</strong> uit de tabel word<strong>en</strong> als volgt omgerek<strong>en</strong>d:<br />

Const.P = ( 1 - a / 2 ) × 100%<br />

Const.Q = ( 1 - b / 2 ) × 100%<br />

In hoogspannings<strong>net</strong>t<strong>en</strong> wordt in het algeme<strong>en</strong> het constante vermog<strong>en</strong>smodel gebruikt voor alle belasting<strong>en</strong>,<br />

omdat die belasting<strong>en</strong> zich in werkelijkheid meestal achter geregelde transforma<strong>to</strong>r<strong>en</strong> bevind<strong>en</strong>, die ervoor zorg<strong>en</strong><br />

dat spanning binn<strong>en</strong> marges constant blijft.<br />

4 CONVERGENTIE<br />

Voor de berek<strong>en</strong>ing van de loadflow wordt gebruik gemaakt van de New<strong>to</strong>n-Raphson <strong>met</strong>hode. Deze <strong>met</strong>hode komt<br />

langs iteratieve weg <strong>to</strong>t e<strong>en</strong> oplossing, waar bij elke iteratie vanuit e<strong>en</strong> <strong>to</strong>estand van het <strong>net</strong> <strong>met</strong> behulp van de<br />

afgeleide de richting naar de volg<strong>en</strong>de <strong>to</strong>estand wordt bepaald. De New<strong>to</strong>n-Raphson <strong>met</strong>hode is algeme<strong>en</strong> gebruikt<br />

<strong>en</strong> staat bek<strong>en</strong>d om zijn hoge snelheid <strong>en</strong> goede converg<strong>en</strong>tie eig<strong>en</strong>schap.<br />

Toch kan het soms voorkom<strong>en</strong> dat er ge<strong>en</strong> oplossing gevond<strong>en</strong> wordt. Hierbij wordt de melding gegev<strong>en</strong>:<br />

"maximum aantal iteraties bereikt" of "oplossing divergeert". Netwerk<strong>en</strong> waarbij e<strong>en</strong> oplossing divergeert, bezitt<strong>en</strong><br />

vaak verbinding<strong>en</strong> <strong>met</strong> relatief hoge impedanties in combinatie <strong>met</strong> relatief grote belasting<strong>en</strong>. Bij gebruik van e<strong>en</strong><br />

constant vermog<strong>en</strong>model ontstaat daarbij het probleem van e<strong>en</strong> "Voltage Collapse". E<strong>en</strong> <strong>net</strong>werk kan daarop<br />

gecontroleerd word<strong>en</strong> door de belasting<strong>en</strong> te wijzig<strong>en</strong> in het constante admittantie model.<br />

Enkele manier<strong>en</strong> om dit op te loss<strong>en</strong> zijn:<br />

• Er is e<strong>en</strong> belastingsgedrag "0% Const.PQ" gedefinieerd, waarvoor de perc<strong>en</strong>tages voor Const.P <strong>en</strong> Const.Q<br />

gelijk aan nul zijn <strong>en</strong> dus de perc<strong>en</strong>tages Const.R <strong>en</strong> Const.X gelijk aan 100%. K<strong>en</strong> vervolg<strong>en</strong>s dit<br />

belastingsgedrag (constante admittantie) <strong>to</strong>e aan alle belasting<strong>en</strong> (via: Bewerk<strong>en</strong> | Collectief | Elem<strong>en</strong>t |<br />

Belasting) <strong>en</strong> kijk of na uitvoer<strong>en</strong> van de loadflow de spanning<strong>en</strong> bijzonder hoog of laag word<strong>en</strong>.<br />

Spanning<strong>en</strong> die meer dan 20% afwijk<strong>en</strong> van de nominale spanning gev<strong>en</strong> meestal problem<strong>en</strong> bij het<br />

oploss<strong>en</strong>. Vooral als van e<strong>en</strong> of meerdere verbinding<strong>en</strong> de impedantie in verhouding <strong>to</strong>t het te<br />

transporter<strong>en</strong> vermog<strong>en</strong> groot is, zal bij constante PQ ge<strong>en</strong> oplossing mogelijk zijn <strong>en</strong> de spanning<strong>en</strong><br />

bijzonder laag kunn<strong>en</strong> word<strong>en</strong>.<br />

• De waarde van Sbasis, in de Opties te wijzig<strong>en</strong>, moet aangepast zijn aan de vermog<strong>en</strong>s die in het <strong>net</strong><br />

voorkom<strong>en</strong>. E<strong>en</strong> exacte formule is niet te gev<strong>en</strong>, maar we moet<strong>en</strong> hierbij Sbasis ongeveer dezelfde ordegrootte<br />

mak<strong>en</strong> als de vermog<strong>en</strong>s die het meest voorkom<strong>en</strong> bij opwekking, belasting <strong>en</strong> transport door de


7 09-010 pmo<br />

verbinding<strong>en</strong> in het <strong>net</strong>model. Het volstaat hierbij Sbasis te kiez<strong>en</strong> uit bijvoorbeeld 10, 100 of 1000 MVA<br />

voor respectievelijk distributie-, <strong>MS</strong>-transport- <strong>en</strong> HS-transport<strong>net</strong>t<strong>en</strong>.<br />

5 TRANSFORMATORREGELINGEN<br />

Voor alle berek<strong>en</strong>ing<strong>en</strong> wordt de transforma<strong>to</strong>r gemodelleerd volg<strong>en</strong>s onderstaande figuur. Hierin wordt R<br />

voornamelijk bepaald door P k<br />

<strong>en</strong> X voornamelijk door u k<br />

. De trapschakelaar bevindt zich meestal aan de HS-zijde<br />

(w 1<br />

).<br />

De overzetverhouding wordt, afhankelijk van de trapzijde, bepaald volg<strong>en</strong>s:<br />

Trapzijde w1: (Unom,w1 + trapstand · trapgrootte) / Unom w2<br />

Trapzijde w2: Unom,w1 / ( Unom,w2 + trapstand · trapgrootte )<br />

De impedantie van de transforma<strong>to</strong>r wordt als volgt bepaald:<br />

Impedantie Weerstand Reactantie<br />

Z<br />

2<br />

2<br />

= U<br />

k<br />

U<br />

nom<br />

eq<br />

100 ⋅<br />

Pk<br />

/1000 U<br />

nom<br />

RT<br />

= ⋅<br />

S<br />

nom<br />

S<br />

nom<br />

S<br />

nom<br />

X<br />

T<br />

=<br />

Z<br />

2<br />

eq<br />

− R<br />

2<br />

T<br />

5.1 Meester-slaafregeling bij parallelle transforma<strong>to</strong>r<strong>en</strong><br />

Meesterregeling heeft te mak<strong>en</strong> <strong>met</strong> de mogelijkheid om twee parallelle transforma<strong>to</strong>r<strong>en</strong> volg<strong>en</strong>s het "Master-slave"<br />

principe te lat<strong>en</strong> regel<strong>en</strong>, dus zodanig dat de trapp<strong>en</strong>schakelaars van de transforma<strong>to</strong>r<strong>en</strong> altijd dezelfde regelstand<br />

hebb<strong>en</strong>. Hierbij wordt de trapstand van de regelaars door één transforma<strong>to</strong>r bepaald (de "Meester"). Bij e<strong>en</strong><br />

onafhankelijke regeling kan het wel e<strong>en</strong>s voorkom<strong>en</strong> dat dat niet zo is.<br />

• Bij e<strong>en</strong> <strong>en</strong>kele transforma<strong>to</strong>r: "Eig<strong>en</strong> regeling aanwezig" <strong>en</strong> "Eig<strong>en</strong> regeling aan".<br />

• Bij twee parallelle transforma<strong>to</strong>r<strong>en</strong> bestaat de keuze uit e<strong>en</strong> onafhankelijke regeling (beide transforma<strong>to</strong>r<strong>en</strong><br />

hebb<strong>en</strong> dan "Eig<strong>en</strong> regeling aan") of voor e<strong>en</strong> afhankelijke regeling. In het geval van e<strong>en</strong> afhankelijke<br />

meester-slaafregeling moet word<strong>en</strong> gespecificeerd:<br />

• voor de "Master"-trafo: "Eig<strong>en</strong> regeling aanwezig" <strong>en</strong> "Eig<strong>en</strong> regeling aan"<br />

• voor de "Slave"-trafo: "Meesterregeling bruikbaar"; de naam van de "Master"-trafo; "Meesterregeling<br />

volg<strong>en</strong>" (de trapp<strong>en</strong>schakelaar volgt die van de meesterregeling).


8 09-010 pmo<br />

Er is nog e<strong>en</strong> optie:<br />

"Meesterregeling volg<strong>en</strong>; eig<strong>en</strong> regeling standby". Dit houdt in dat de trapp<strong>en</strong>schakelaar die van de meesterregeling<br />

volgt. In het geval dat de meesterregeling uitgeschakeld is, werkt de eig<strong>en</strong> regeling.<br />

Bij het gebruik van de meester-slaaf-regeling <strong>met</strong> parallelle transforma<strong>to</strong>r<strong>en</strong>, wordt door de slav<strong>en</strong> de<br />

overzetverhouding van de meester gekoz<strong>en</strong> of b<strong>en</strong>aderd bij ongelijke typ<strong>en</strong>.<br />

5.2 Stroomcomp<strong>en</strong>satie<br />

Stroomcomp<strong>en</strong>satie in de spanningsregeling van e<strong>en</strong> voedingstransforma<strong>to</strong>r is bedoeld om het spanningsverlies<br />

over e<strong>en</strong> verbinding te comp<strong>en</strong>ser<strong>en</strong>. In dat geval wordt de regeling gestuurd <strong>met</strong> behulp van de secundaire<br />

spanning <strong>en</strong> de belastingsstroom. De regeling is zodanig dat behalve <strong>met</strong> de spanning op de secundaire klemm<strong>en</strong><br />

van de transforma<strong>to</strong>r ook rek<strong>en</strong>ing gehoud<strong>en</strong> wordt <strong>met</strong> spanningsverliez<strong>en</strong> voorbij dit punt. De regeling is dan dus<br />

in feite ingesteld op e<strong>en</strong> fictief punt in het distributiesysteem. Deze van de belastingsstroom afhankelijke regeling<br />

wordt "compounderingsregeling" of "stroomcomp<strong>en</strong>satieregeling" g<strong>en</strong>oemd.<br />

De werking van de stroomcomp<strong>en</strong>satie licht<strong>en</strong> we kort <strong>to</strong>e <strong>met</strong> behulp van onderstaand schema. E<strong>en</strong> 50 MVA<br />

transforma<strong>to</strong>r (kortsluitspanning 14%) voedt e<strong>en</strong> richting <strong>met</strong> 5 kabelstukk<strong>en</strong> van 2 km elk. De eerste twee<br />

kabelstukk<strong>en</strong> zijn 150 mm 2 AL. De volg<strong>en</strong>de kabelstukk<strong>en</strong> zijn 95 mm 2 AL. Op elk knooppunt is e<strong>en</strong> belasting van 40<br />

A (cosϕ=0,9) aangeslot<strong>en</strong>. De spanningsregelaar is ingesteld op e<strong>en</strong> spanning tuss<strong>en</strong> 10,3 <strong>en</strong> 10,5 kV.<br />

Regeling <strong>en</strong> stroomcomp<strong>en</strong>satie:<br />

Umin = 10,2 kV<br />

Umax = 10,6 kV<br />

Totale impedantie 5 kabels:<br />

R = 2,85 Ohm<br />

X = 0,81 Ohm<br />

V<br />

HS Voeding<br />

150 kV<br />

Uk: 14 %<br />

157 / 11.5 kV<br />

<strong>MS</strong> Rail<br />

10 kV <strong>MS</strong> 1<br />

10 kV<br />

2000 m 3*150 AL GPLK 10/10 2000 m 3*150 AL GPLK 10/10<br />

Inom = 40 A<br />

<strong>MS</strong> 2<br />

10 kV<br />

2000 m 3* 95 AL GPLK 10/10<br />

Inom = 40 A<br />

<strong>MS</strong> 3<br />

10 kV<br />

Inom = 40 A<br />

<strong>MS</strong> 5<br />

10 kV<br />

2000 m 3* 95 AL GPLK 10/10<br />

<strong>MS</strong> 4<br />

10 kV<br />

2000 m 3* 95 AL GPLK 10/10<br />

Inom = 40 A<br />

Inom = 40 A<br />

Figuur 1 <strong>MS</strong>-<strong>net</strong> <strong>met</strong> verdeelde belasting<strong>en</strong><br />

De knooppuntspanning<strong>en</strong> zijn weergegev<strong>en</strong> in figuur 2. De spanning aan het uiteinde van de richting is <strong>met</strong> 9,9 kV<br />

aan de lage kant.<br />

Door de stroomcomp<strong>en</strong>satie wordt de ge<strong>met</strong><strong>en</strong> spanning gecorrigeerd <strong>met</strong> het complexe product van de secundaire<br />

stroom <strong>en</strong> de comp<strong>en</strong>satie-impedantie Z c (=R c + j X c ) volg<strong>en</strong>s vergelijking (1):<br />

U U + I ⋅ Z ⋅ 3 (1)<br />

regelaar<br />

=<br />

secundair<br />

secundair<br />

c<br />

Hierdoor "ziet" de regelaar e<strong>en</strong> lagere spanning (het complexe product heeft door de tek<strong>en</strong>afspraak e<strong>en</strong> negatieve<br />

uitwerking). Door deze correctie zal de secundaire spanning doorgaans hoger word<strong>en</strong> dan <strong>met</strong> U min <strong>en</strong> U max is opgegev<strong>en</strong>.<br />

De stroomcomp<strong>en</strong>satie zorgt ervoor dat de spanningsdaling over e<strong>en</strong> lange lijn gecomp<strong>en</strong>seerd wordt.


9 09-010 pmo<br />

Stel dat we de spanning zodanig will<strong>en</strong> corriger<strong>en</strong> dat voor de <strong>to</strong>tale belasting van 200 A de spanning aan de<br />

klemm<strong>en</strong> van de transforma<strong>to</strong>r 500 V verbetert, dan moet de absolute waarde van de impedantie van de comp<strong>en</strong>satie<br />

gelijk zijn aan:<br />

500/ 3<br />

Z<br />

c<br />

= = 1, 44Ω<br />

(2)<br />

200<br />

Rek<strong>en</strong>ing houd<strong>en</strong>d <strong>met</strong> e<strong>en</strong> cosϕ gelijk aan 0,9 krijg<strong>en</strong> we e<strong>en</strong> comp<strong>en</strong>satie-impedantie van:<br />

Z c<br />

= 1,3<br />

+ j0,<br />

63Ω<br />

(3)<br />

De spanning voor de gehele richting verbetert op die manier inderdaad <strong>met</strong> ongeveer 500 V, namelijk 3 trapstand<strong>en</strong><br />

van 150 V, afhankelijk van de tapgrootte <strong>en</strong> het ingestelde spanningsinterval. Het spanningsprofiel is weergegev<strong>en</strong> in<br />

figuur 2.<br />

11.2<br />

Spanning (kV)<br />

11<br />

10.8<br />

10.6<br />

10.4<br />

10.2<br />

10<br />

9.8<br />

9.6<br />

9.4<br />

<strong>MS</strong><br />

Rail<br />

<strong>MS</strong> 1 <strong>MS</strong> 2 <strong>MS</strong> 3 <strong>MS</strong> 4 <strong>MS</strong> 5<br />

zonder comp<strong>en</strong>satie<br />

<strong>met</strong> comp<strong>en</strong>satie<br />

Knooppunt<br />

Figuur 2 Spanningsprofiel zonder <strong>en</strong> <strong>met</strong> stroomcomp<strong>en</strong>satie.<br />

De gehele richting heeft e<strong>en</strong> <strong>to</strong>tale impedantie van 2,85 + j0,81 Ω. Op e<strong>en</strong> zodanige afstand vanaf de transforma<strong>to</strong>r,<br />

waarvoor geldt dat de "elektrische afstand" ongeveer gelijk is aan deze impedantie, zou de spanning in het<br />

ingestelde spanningsinterval moet<strong>en</strong> ligg<strong>en</strong>. Deze red<strong>en</strong>ering gaat hier niet helemaal op omdat de kabelstroom<br />

weg<strong>en</strong>s de over de knooppunt<strong>en</strong> verdeelde belasting<strong>en</strong> naar het uiteinde van de <strong>MS</strong>-richting <strong>to</strong>e afneemt.<br />

5.2.1 INVLOED LOKALE BELASTINGEN EN OPWEKKERS<br />

Het komt nogal e<strong>en</strong>s voor dat e<strong>en</strong> bijzondere belasting of e<strong>en</strong> dec<strong>en</strong>trale opwekker direct op de midd<strong>en</strong>spanningsrail<br />

van e<strong>en</strong> voedingstransforma<strong>to</strong>r wordt aangeslot<strong>en</strong>. In dat geval moet de stroom van die klant word<strong>en</strong> afgetrokk<strong>en</strong><br />

van de te comp<strong>en</strong>ser<strong>en</strong> stroom. De invloed van e<strong>en</strong> grote lokale belasting wordt <strong>to</strong>egelicht <strong>met</strong> behulp van<br />

hetzelfde <strong>net</strong>schema als in het vorige hoofdstuk, maar nu uitgebreid <strong>met</strong> e<strong>en</strong> grote belasting (figuur 3). E<strong>en</strong> 50 MVA<br />

transforma<strong>to</strong>r voedt e<strong>en</strong> dichtbij geleg<strong>en</strong> belasting <strong>en</strong> e<strong>en</strong> <strong>MS</strong>-richting <strong>met</strong> belasting. De belasting in de <strong>MS</strong>-richting<br />

is ev<strong>en</strong>redig verdeeld over vijf knooppunt<strong>en</strong>. De gedachte is om het spanningsverlies over de kabel te comp<strong>en</strong>ser<strong>en</strong>.


10 09-010 pmo<br />

V<br />

HS Voeding<br />

150 kV<br />

Regeling <strong>en</strong> stroomcomp<strong>en</strong>satie:<br />

Umin = 10,2 kV<br />

Umax = 10,6 kV<br />

Rc = 1,3 Ohm<br />

Xc = 0,63 Ohm<br />

Uk: 14 %<br />

157 / 11.5 kV<br />

<strong>MS</strong> Rail<br />

10 kV <strong>MS</strong> 1<br />

10 kV<br />

2000 m 3*150 AL GPLK 10/10 2000 m 3*150 AL GPLK 10/10<br />

Inom = 200 A<br />

Totale impedantie 5 kabels:<br />

R = 2,85 Ohm<br />

X = 0,81 Ohm<br />

Inom = 40 A<br />

<strong>MS</strong> 5<br />

10 kV<br />

2000 m 3* 95 AL GPLK 10/10<br />

<strong>MS</strong> 2<br />

10 kV<br />

<strong>MS</strong> 4<br />

10 kV<br />

2000 m 3* 95 AL GPLK 10/10<br />

Inom = 40 A<br />

<strong>MS</strong> 3<br />

10 kV<br />

Inom = 40 A<br />

2000 m 3* 95 AL GPLK 10/10<br />

Inom = 40 A<br />

Inom = 40 A<br />

Figuur 3 <strong>MS</strong>-<strong>net</strong> <strong>met</strong> verdeelde belasting<strong>en</strong> <strong>en</strong> grote lokale belasting<br />

In het schema valt op dat e<strong>en</strong> stroomcomp<strong>en</strong>satie is aangebracht <strong>met</strong> als doel het spanningsverlies over de verbinding,<br />

bestaande uit vijf kabels in serie, te comp<strong>en</strong>ser<strong>en</strong>. Wat echter ook opvalt, is dat e<strong>en</strong> grote belasting direct op<br />

de secundaire rail van de transforma<strong>to</strong>r is aangebracht. In het <strong>net</strong>je wordt de comp<strong>en</strong>satie voor de afgaande richting<br />

als het ware misleid door de last van 200 A direct op de secundaire rail (waarvoor de comp<strong>en</strong>satie niet bedoeld is),<br />

naast de te comp<strong>en</strong>ser<strong>en</strong> belasting van 200 A in de <strong>MS</strong>-richting. De invloed van de lokale belasting op de regeling is<br />

zó groot, dat de spanning in de rest van het <strong>net</strong>, dus ook op de te comp<strong>en</strong>ser<strong>en</strong> <strong>MS</strong>-richting, wordt overgecomp<strong>en</strong>seerd,<br />

soms wel leid<strong>en</strong>d <strong>to</strong>t spanning<strong>en</strong> hoger dan 11 kV. Zelfs aan het uiteinde van de richting is de spanning<br />

hoger dan het ingestelde interval (zie figuur 4).<br />

HS Voeding<br />

150.000 kV<br />

Regeling <strong>en</strong> stroomcomp<strong>en</strong>satie: Totale impedantie 5 kabels:<br />

Umin = 10,2 kV<br />

R = 2,85 Ohm<br />

X = 0,81 Ohm<br />

Umax = 10,6 kV<br />

Rc = 1,3 Ohm<br />

<strong>MS</strong> Rail<br />

Xc = 0,63 Ohm 11.371 kV <strong>MS</strong> 1<br />

11.215 kV<br />

<strong>MS</strong> 2<br />

11.090 kV<br />

V<br />

tap: -3<br />

Inom = 40 A<br />

Inom = 40 A<br />

<strong>MS</strong> 3<br />

10.950 kV<br />

Inom = 40 A<br />

Inom = 200 A<br />

<strong>MS</strong> 5<br />

10.811 kV<br />

<strong>MS</strong> 4<br />

10.857 kV<br />

Inom = 40 A<br />

Inom = 40 A<br />

Figuur 4 Overcomp<strong>en</strong>satie door grote lokale belasting<br />

Figuur 5 geeft e<strong>en</strong> beeld van de invloed van e<strong>en</strong> dec<strong>en</strong>trale opwekker, die direct op de <strong>MS</strong>-rail is aangeslot<strong>en</strong>. De<br />

spanning wordt daardoor juist te weinig gecomp<strong>en</strong>seerd <strong>en</strong> ligt voor het eerste knooppunt in de richting al b<strong>en</strong>ed<strong>en</strong><br />

het ingestelde spanningsinterval.


11 09-010 pmo<br />

HS Voeding<br />

150.000 kV<br />

Regeling <strong>en</strong> stroomcomp<strong>en</strong>satie: Totale impedantie 5 kabels:<br />

Umin = 10,2 kV<br />

R = 2,85 Ohm<br />

X = 0,81 Ohm<br />

Umax = 10,6 kV<br />

Rc = 1,3 Ohm<br />

<strong>MS</strong> Rail<br />

Xc = 0,63 Ohm 10.409 kV <strong>MS</strong> 1<br />

10.253 kV<br />

<strong>MS</strong> 2<br />

10.128 kV<br />

V<br />

tap: 4<br />

C<br />

P = 3,1 MW<br />

cos=0,85<br />

Inom = 40 A<br />

<strong>MS</strong> 5<br />

9.850 kV<br />

Inom = 40 A<br />

<strong>MS</strong> 4<br />

9.897 kV<br />

<strong>MS</strong> 3<br />

9.989 kV<br />

Inom = 40 A<br />

Inom = 40 A<br />

Inom = 40 A<br />

Figuur 5 Te weinig comp<strong>en</strong>satie door lokale dec<strong>en</strong>trale opwekker<br />

Dec<strong>en</strong>trale opwekking levert vaak oorspronkelijk niet begrep<strong>en</strong> situaties op. Sommige apparat<strong>en</strong> werk<strong>en</strong> <strong>met</strong> absolute<br />

waard<strong>en</strong> voor stroom <strong>en</strong> spanning <strong>en</strong> is dus niet richtinggevoelig. In dat geval wordt de verwarring compleet, omdat de<br />

stroomcomp<strong>en</strong>satie bij <strong>net</strong><strong>to</strong> teruglevering via de transforma<strong>to</strong>r dan het teg<strong>en</strong>gestelde effect bewerkstelligt. In die<br />

gevall<strong>en</strong> kan de stroomcomp<strong>en</strong>satie beter word<strong>en</strong> uitgeschakeld.<br />

Zeker in het geval dat de dec<strong>en</strong>trale opwekking bestaat uit e<strong>en</strong> of meerdere windturbines is het spanningsgedrag<br />

onrustig <strong>en</strong> lijkt het onvoorspelbaar. De bijdrage van deze opwekkers mag dan ook ge<strong>en</strong> onderdeel uitmak<strong>en</strong> van de te<br />

comp<strong>en</strong>ser<strong>en</strong> stroom.<br />

5.2.2 KEUZE VAN DE COMPENSATIE-IMPEDANTIE<br />

Naast de <strong>met</strong>hode van formule (2) is het ook mogelijk Z c te schatt<strong>en</strong> <strong>met</strong> behulp van de impedantie van de<br />

afgaande richting. In het hierbov<strong>en</strong> geschetste voorbeeld zou de eerste schatting uitkom<strong>en</strong> op bijvoorbeeld de helft<br />

van de <strong>to</strong>tale impedantie (1,4 + j0,8 Ω). Dat deze waarde te groot blijkt te zijn, heeft te mak<strong>en</strong> <strong>met</strong> de verdeling van<br />

de belasting. Indi<strong>en</strong> alle belasting geconc<strong>en</strong>treerd zou zijn op één punt, zou deze b<strong>en</strong>adering stukk<strong>en</strong> e<strong>en</strong>voudiger<br />

zijn.<br />

Het kiez<strong>en</strong> van de juiste impedantie is vaak e<strong>en</strong> kwestie van prober<strong>en</strong> <strong>en</strong> simuler<strong>en</strong>. In de meeste gevall<strong>en</strong> is de<br />

belasting niet zo <strong>net</strong>jes verdeeld <strong>en</strong> bestaat de richting uit kabelstukk<strong>en</strong> van diverse l<strong>en</strong>gtes <strong>en</strong> impedanties <strong>en</strong> bevat<br />

de richting aftakking<strong>en</strong>. Van tevor<strong>en</strong> moet vastligg<strong>en</strong> hoeveel knooppunt<strong>en</strong> of welke knooppunt<strong>en</strong> zeker binn<strong>en</strong> het<br />

gekoz<strong>en</strong> spanningsinterval moet<strong>en</strong> ligg<strong>en</strong>. Aandachtspunt is de mogelijkheid dat meerdere transforma<strong>to</strong>rtrapstand<strong>en</strong><br />

e<strong>en</strong> oplossing kunn<strong>en</strong> lever<strong>en</strong>.<br />

6 GENERATORREGELINGEN<br />

Cos-phi geregelde synchrone g<strong>en</strong>era<strong>to</strong>r:<br />

Bij loadflowberek<strong>en</strong>ing<strong>en</strong> wordt e<strong>en</strong> synchrone g<strong>en</strong>era<strong>to</strong>r <strong>met</strong> cos(phi)-regeling voorgesteld als e<strong>en</strong> negatieve<br />

belasting van constant vermog<strong>en</strong>.


12 09-010 pmo<br />

P belasting = -Pref<br />

Q belasting = -Pref · √(1 - cos(phi) ²) / cos(phi)<br />

of<br />

Q belasting = +Pref · √ (1 - cos(phi) ²) / cos(phi)<br />

(instelling capacitief: Q lever<strong>en</strong>)<br />

(instelling inductief: Q opnem<strong>en</strong>)<br />

Spanning geregelde synchrone g<strong>en</strong>era<strong>to</strong>r:<br />

Met U ref wordt de spanning op het knooppunt aangegev<strong>en</strong> in pu <strong>en</strong> is e<strong>en</strong> fac<strong>to</strong>r van de in het form vermelde U nom<br />

van het knooppunt. Er geldt:<br />

U mod = U ref · U nom,knooppunt<br />

De spanningsregeling bepaalt het b<strong>en</strong>odigde blindvermog<strong>en</strong> (binn<strong>en</strong> de gr<strong>en</strong>z<strong>en</strong> Q min <strong>en</strong> Q max ) voor het verkrijg<strong>en</strong><br />

van de spanning U ref . Hierbij wordt rek<strong>en</strong>ing gehoud<strong>en</strong> <strong>met</strong> statiek.<br />

( Het verloop van de functie U = f(Q g<strong>en</strong>era<strong>to</strong>r ) <strong>met</strong> statiek <strong>en</strong> de gr<strong>en</strong>z<strong>en</strong> Q min <strong>en</strong> Q max , is weergegev<strong>en</strong> in de grafiek U<br />

= f(Q g<strong>en</strong>era<strong>to</strong>r ) in het form.)<br />

Voor e<strong>en</strong> loadflowberek<strong>en</strong>ing geldt:<br />

P g<strong>en</strong>era<strong>to</strong>r is gelijk aan P ref<br />

Q g<strong>en</strong>era<strong>to</strong>r is afhankelijk van U ref , Q min , Q max <strong>en</strong> de statiek <strong>en</strong> volgt uit de <strong>to</strong>estand van het <strong>net</strong>.<br />

Als Qg<strong>en</strong>era<strong>to</strong>r tuss<strong>en</strong> de gr<strong>en</strong>z<strong>en</strong> Q min <strong>en</strong> Q max ligt, dan ligt U g<strong>en</strong>era<strong>to</strong>r tuss<strong>en</strong> U min <strong>en</strong> U max . Het verband tuss<strong>en</strong> U <strong>en</strong><br />

Q is dan gegev<strong>en</strong> door de statiek.<br />

De spanning-blindvermog<strong>en</strong>statiek is gedefinieerd in %. De waarde repres<strong>en</strong>teert de spanningsvariatie als gevolg<br />

van e<strong>en</strong> variatie in blindvermog<strong>en</strong>.<br />

U<br />

UQStatiek =<br />

Q<br />

max<br />

max<br />

−U<br />

− Q<br />

min<br />

min<br />

Q<br />

⋅<br />

U<br />

nom<br />

nom<br />

⋅100%<br />

Het minimum <strong>en</strong> het maximum van het blindvermog<strong>en</strong> dat e<strong>en</strong> g<strong>en</strong>era<strong>to</strong>r kan opwekk<strong>en</strong> bepaalt, sam<strong>en</strong> <strong>met</strong> de<br />

statiek, de extrem<strong>en</strong> in de klemspanning van de g<strong>en</strong>era<strong>to</strong>r. Uitgangspunt is de ingestelde spanning U ref .<br />

U ref<br />

U min<br />

U max<br />

Q min<br />

Q max<br />

Q min<br />

Q min<br />

U ref<br />

U min<br />

U max<br />

: minimum opgewekt blindvermog<strong>en</strong><br />

: maximum opgewekt blindvermog<strong>en</strong><br />

: ingestelde spanning<br />

: minimum klemspanning op de schuine lijn<br />

: maximum klemspanning op de schuine lijn


13 09-010 pmo<br />

De hellingshoek van de schuine lijn wordt bepaald door de UQ-statiek.<br />

Berek<strong>en</strong>ing para<strong>met</strong>ers voor meerdere g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> op hetzelfde knooppunt <strong>met</strong> behulp van gewog<strong>en</strong> gemiddelde:<br />

∑<br />

∑<br />

Snom<br />

,<br />

pu<br />

= S nom i<br />

U<br />

nom,<br />

i<br />

⋅ S<br />

nom,<br />

i<br />

Unom =<br />

Snom<br />

∑ 0.01⋅UQStatieki<br />

⋅ S<br />

statiek = ,<br />

Snom<br />

qmin =<br />

qmax =<br />

∑<br />

Q<br />

min,<br />

i<br />

Sbase<br />

∑<br />

Q<br />

max,<br />

i<br />

Sbase<br />

nom i<br />

Unom<br />

⋅ ⋅<br />

Ubase<br />

Sbase<br />

Snom<br />

De extrem<strong>en</strong> van de spanning<strong>en</strong> waartuss<strong>en</strong> de synchrone machine kan regel<strong>en</strong> volg<strong>en</strong> uit de statiek <strong>en</strong> de overige<br />

para<strong>met</strong>ers van de equival<strong>en</strong>te machine:<br />

u = | u | −statiek<br />

⋅ qmin<br />

pu<br />

u<br />

max<br />

min<br />

ref<br />

= | u | −statiek<br />

⋅ qmax<br />

pu<br />

ref<br />

pu<br />

pu<br />

pu<br />

pu<br />

Het blindvermog<strong>en</strong> van de g<strong>en</strong>era<strong>to</strong>r is dan, afhankelijk van de berek<strong>en</strong>de spanning:<br />

Q<br />

g<strong>en</strong><br />

= Q min<br />

MVA, voor u actueel ≥ u max<br />

Q<br />

g<strong>en</strong><br />

uref<br />

− uactueel<br />

= ⋅ Sbase MVA, voor u min < u actueel < u max<br />

statiek<br />

Q<br />

g<strong>en</strong><br />

= Q max<br />

MVA, voor u actueel ≤ u min<br />

7 EILANDBEDRIJF<br />

<strong>Vision</strong> kan rek<strong>en</strong><strong>en</strong> aan <strong>net</strong>t<strong>en</strong> in eilandbedrijf, zoals op schep<strong>en</strong> <strong>en</strong> boorplatforms <strong>en</strong> zoals dat kan voorkom<strong>en</strong> bij<br />

industriële <strong>net</strong>t<strong>en</strong> die soms los van het externe <strong>net</strong> kom<strong>en</strong> te staan. E<strong>en</strong> loadflowberek<strong>en</strong>ing vereist echter altijd e<strong>en</strong><br />

<strong>net</strong>voeding, waarin e<strong>en</strong> "Swingbus" is opg<strong>en</strong>om<strong>en</strong>. E<strong>en</strong> loadflow zonder swingbus werkt in principe niet, zodat er<br />

e<strong>en</strong> creatieve oplossing gevond<strong>en</strong> moet word<strong>en</strong>. In de oplossing is <strong>met</strong> name aandacht besteed aan de<br />

vermog<strong>en</strong>sverdeling over de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong>.<br />

De techniek van e<strong>en</strong> traditionele loadflow is gebaseerd op het zoek<strong>en</strong> van de knooppuntspanning<strong>en</strong> <strong>met</strong> behulp van<br />

e<strong>en</strong> systeem van <strong>net</strong>werkvergelijking<strong>en</strong>. Het <strong>net</strong>werk is gemodelleerd <strong>met</strong> ev<strong>en</strong>veel vergelijking<strong>en</strong> als er<br />

knooppunt<strong>en</strong> zijn. Op elk knooppunt kan e<strong>en</strong> vermog<strong>en</strong> word<strong>en</strong> geïnjecteerd. Dit stelsel vergelijking<strong>en</strong> kan niet<br />

word<strong>en</strong> opgelost als niet één van de onbek<strong>en</strong>d<strong>en</strong> als refer<strong>en</strong>tie g<strong>en</strong>om<strong>en</strong> wordt. Het knooppunt, waarvan de<br />

spanning als refer<strong>en</strong>tie g<strong>en</strong>om<strong>en</strong> wordt, wordt de “Swingbus” g<strong>en</strong>oemd. Van dat knooppunt ligg<strong>en</strong> de grootte <strong>en</strong> de<br />

hoek van de spanning vast. In e<strong>en</strong> traditionele loadflowberek<strong>en</strong>ing wordt de swingbus in de <strong>net</strong>voeding opg<strong>en</strong>om<strong>en</strong>.<br />

De spanning van de <strong>net</strong>voeding is daarbij e<strong>en</strong> door de gebruiker ingevoerde waarde (U ref ) maal de nominale<br />

spanning. De hoek van de spanning is meestal nul, maar kan door de gebruiker ingevoerd word<strong>en</strong>.<br />

Doordat de spanning van de <strong>net</strong>voeding vastligt, moet het complexe vermog<strong>en</strong> (P+jQ) “losgelat<strong>en</strong>” word<strong>en</strong>. Dat<br />

betek<strong>en</strong>t dat het verschil tuss<strong>en</strong> opwekking <strong>en</strong> belasting in het <strong>net</strong> altijd door de <strong>net</strong>voeding wordt aangezuiverd. De


14 09-010 pmo<br />

traditionele loadflow is dus altijd gebaseerd op vermog<strong>en</strong>suitwisseling <strong>met</strong> e<strong>en</strong> extern <strong>net</strong>, waarbij de swingbus<br />

onmisbaar is.<br />

Aangezi<strong>en</strong> er in eilandbedrijf ge<strong>en</strong> externe <strong>net</strong>voeding aanwezig is, moet er e<strong>en</strong> onzichtbare swingbus word<strong>en</strong><br />

aangebracht, <strong>en</strong> wel op zo’n manier dat die ge<strong>en</strong> merkbare invloed heeft op de <strong>to</strong>estand van het eiland<strong>net</strong>.<br />

Het vermog<strong>en</strong> dat alle belasting<strong>en</strong> in het eiland<strong>net</strong> vrag<strong>en</strong>, moet door de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> tezam<strong>en</strong> word<strong>en</strong> opgebracht.<br />

Er moet dus e<strong>en</strong> algoritme zijn ingebouwd, dat ervoor zorgt dat de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> zodanig zijn ingesteld dat de<br />

vermog<strong>en</strong>suitwisseling <strong>met</strong> de swingbus nul is. Ook moet de refer<strong>en</strong>tiespanning van de swingbus op de in het<br />

eiland<strong>net</strong> aanwezige spanning<strong>en</strong> zijn afgestemd.<br />

De kortsluitberek<strong>en</strong>ing<strong>en</strong> volg<strong>en</strong>s de <strong>met</strong>hode van de Sequ<strong>en</strong>tiële S<strong>to</strong>ringsanalyse gaat uit van de loadflowsituatie,<br />

zodat ook daar e<strong>en</strong> swingbus nodig is.<br />

Voor de kortsluitberek<strong>en</strong>ing volg<strong>en</strong>s IEC 60909 is ge<strong>en</strong> swingbus nodig.<br />

Voor de verdeling van de vermog<strong>en</strong>s over alle g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> is e<strong>en</strong> frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling aanwezig. Bij elke<br />

verandering van de belasting zal de frequ<strong>en</strong>tie iets wijzig<strong>en</strong>. De opwekkers zull<strong>en</strong> <strong>met</strong>e<strong>en</strong> reager<strong>en</strong> door meer of<br />

minder vermog<strong>en</strong> te lever<strong>en</strong>, zodat in de nieuwe <strong>to</strong>estand weer e<strong>en</strong> ev<strong>en</strong>wicht tuss<strong>en</strong> belasting <strong>en</strong> opwekking<br />

aanwezig is.<br />

E<strong>en</strong> opweke<strong>en</strong>heid <strong>met</strong> frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling gaat door de frequ<strong>en</strong>tiedaling meer vermog<strong>en</strong> lever<strong>en</strong>.<br />

Hoeveel vermog<strong>en</strong> de e<strong>en</strong>heid bijregelt, ligt vast in de statiek. De statiek is gedefinieerd als het quotiënt van de<br />

frequ<strong>en</strong>tieverandering <strong>en</strong> de vermog<strong>en</strong>sverandering.<br />

Δf<br />

/ fnom<br />

S = − ⋅100%<br />

ΔP<br />

/ P<br />

nom<br />

Hoe groter de statiek, des te minder draagt de e<strong>en</strong>heid bij aan de vermog<strong>en</strong>sverandering.<br />

De regelcoëffici<strong>en</strong>t is e<strong>en</strong> afgeleide grootheid, die aangeeft hoeveel de e<strong>en</strong>heid bijdraagt aan e<strong>en</strong> vermog<strong>en</strong>stekort.<br />

Het uiteindelijk bijgeregelde vermog<strong>en</strong> is aldus afhankelijk van de frequ<strong>en</strong>tiedaling <strong>en</strong> de regelcoëffici<strong>en</strong>t van de<br />

e<strong>en</strong>heid.<br />

P 100<br />

K<br />

T<br />

=<br />

f<br />

nom<br />

nom<br />

S<br />

⇒<br />

ΔP<br />

= −Δf<br />

⋅ K<br />

T<br />

De som van de regelconstantes van alle e<strong>en</strong>hed<strong>en</strong> wordt de Netconstante (K N ) g<strong>en</strong>oemd.<br />

Met de <strong>net</strong>constante is het mogelijk om de frequ<strong>en</strong>tieverandering in e<strong>en</strong> <strong>net</strong> als gevolg van e<strong>en</strong><br />

belastingsverandering in e<strong>en</strong> eiland<strong>net</strong> uit te rek<strong>en</strong><strong>en</strong>. Deze is gelijk aan het quotiënt van de belastingsverandering<br />

<strong>en</strong> de <strong>net</strong>constante.<br />

Δf<br />

= −<br />

n<br />

∑<br />

i=<br />

1<br />

n<br />

∑<br />

i=<br />

1<br />

ΔPi<br />

= −<br />

K<br />

i<br />

ΔP<br />

n<br />

∑<br />

i=<br />

1<br />

L<br />

K<br />

i<br />

ΔP<br />

= −<br />

K<br />

L<br />

N<br />

Ook het grote gekoppelde HS-<strong>net</strong> is e<strong>en</strong> eiland<strong>net</strong>. Elke belastingsverandering leidt <strong>to</strong>t e<strong>en</strong> frequ<strong>en</strong>tieverandering.<br />

Alle gekoppelde c<strong>en</strong>trales zijn voorzi<strong>en</strong> van e<strong>en</strong> frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling volg<strong>en</strong>s dit principe.<br />

De bijdrage van e<strong>en</strong> <strong>en</strong>kele e<strong>en</strong>heid m volgt uit de eig<strong>en</strong> regelconstante (K m ).<br />

K<br />

m<br />

Δ Pm<br />

= −Δf<br />

⋅ Km<br />

= ΔPL<br />

K<br />

N<br />

In <strong>Vision</strong> is gekoz<strong>en</strong> voor e<strong>en</strong> g<strong>en</strong>erieke aanpak. Dat houdt in dat we niet gebond<strong>en</strong> zijn aan één eiland. Elk<br />

losstaand <strong>net</strong>deel kan in eilandbedrijf word<strong>en</strong> opgelost. Daarbij word<strong>en</strong> de volg<strong>en</strong>de voorwaard<strong>en</strong> gesteld:


15 09-010 pmo<br />

• Er moet<strong>en</strong> synchrone g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> aanwezig zijn, die voorzi<strong>en</strong> zijn van e<strong>en</strong> ingeschakelde<br />

spanningsregeling <strong>en</strong> de statiek van de frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling moet zijn ingevuld.<br />

• Het in het eiland<strong>net</strong> opgestelde <strong>en</strong> ingeschakelde vermog<strong>en</strong> moet voldo<strong>en</strong>de zijn om de belasting te<br />

voed<strong>en</strong>.<br />

G<strong>en</strong>era<strong>to</strong>r<strong>en</strong>, waarvan de f/P-statiek niet is ingevuld, do<strong>en</strong> niet mee aan de regeling. Ook g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> <strong>met</strong> e<strong>en</strong> vaste<br />

cos-phi do<strong>en</strong> niet mee aan de regeling.<br />

E<strong>en</strong> gevolg voor de gekoz<strong>en</strong> aanpak is dat de keuze voor S basis belangrijker is voor het oplossingsproces. E<strong>en</strong><br />

algem<strong>en</strong>e formule voor deze waarde is niet te gev<strong>en</strong>. Indi<strong>en</strong> het oplossingsproces niet convergeert of het maximaal<br />

aantal iteraties bereikt is, kan e<strong>en</strong> andere keuze voor S basis <strong>to</strong>t betere resultat<strong>en</strong> leid<strong>en</strong>.<br />

Voorbeeld<br />

Voor de demonstratie gaan we uit van e<strong>en</strong> standaard industri<strong>en</strong>et <strong>met</strong> veel mo<strong>to</strong>rbelasting<strong>en</strong>. De nominale<br />

spanning<strong>en</strong> zijn 10 kV <strong>en</strong> 400 V. De g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> G1 <strong>en</strong> G2 hebb<strong>en</strong> e<strong>en</strong> nominaal vermog<strong>en</strong> van 10 MVA. De<br />

g<strong>en</strong>era<strong>to</strong>r G3 heeft e<strong>en</strong> nominaal vermog<strong>en</strong> van 20 MVA. Dit <strong>net</strong> kan ev<strong>en</strong>goed het <strong>net</strong> aan boord van e<strong>en</strong> schip of<br />

boorplatform zijn.<br />

Het <strong>net</strong> is gekoppeld <strong>met</strong> e<strong>en</strong> voed<strong>en</strong>d HS-<strong>net</strong>. De <strong>net</strong>voeding is gekoppeld via e<strong>en</strong> 150/10 kV transforma<strong>to</strong>r.<br />

HS-<strong>net</strong><br />

150.000 kV<br />

Inkooppunt<br />

9.980 kV<br />

-3.994 MW<br />

-1.999 Mvar<br />

-3.994 MW<br />

-1.999 Mvar<br />

4.000 MW<br />

2.001 Mvar<br />

4.000 MW<br />

2.001 Mvar<br />

Opwekking 1<br />

10.000 kV<br />

Opwekking 2<br />

10.000 kV<br />

G<br />

G1<br />

2.000 MW<br />

1.000 Mvar<br />

G G2<br />

2.000 MW<br />

1.000 Mvar<br />

G G3<br />

4.000 MW<br />

2.001 Mvar<br />

Industri<strong>en</strong>et<br />

V<br />

1.542 MW<br />

1.972 Mvar<br />

1.542 MW<br />

1.972 Mvar<br />

-1.542 MW<br />

-1.966 Mvar<br />

4.946 MW<br />

3.300 Mvar<br />

4.583 MW<br />

2.664 Mvar<br />

-4.574 MW<br />

-2.659 Mvar<br />

Fabriek 1<br />

9.956 kV<br />

-4.935 MW<br />

-3.293 Mvar<br />

0.363 MW<br />

0.632 Mvar<br />

M M1<br />

2.105 MW<br />

1.013 Mvar<br />

M M2<br />

2.105 MW<br />

1.013 Mvar<br />

-0.363 MW<br />

-0.637 Mvar<br />

Fabriek 2<br />

9.953 kV<br />

3.193 MW<br />

2.917 Mvar<br />

M3<br />

2.105 MW<br />

1.013 Mvar<br />

M<br />

LV<br />

0.386 kV<br />

-3.191 MW<br />

-2.728 Mvar<br />

M M11<br />

0.532 MW<br />

0.455 Mvar<br />

M<br />

M M13<br />

0.532 MW<br />

0.455 Mvar<br />

M<br />

M M15<br />

0.532 MW<br />

0.455 Mvar<br />

M<br />

M12<br />

0.532 MW<br />

0.455 Mvar<br />

M14<br />

0.532 MW<br />

0.455 Mvar<br />

M16<br />

0.532 MW<br />

0.455 Mvar<br />

De g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> voed<strong>en</strong> het eig<strong>en</strong> <strong>net</strong> <strong>en</strong> de onbalans wordt uit het HS-<strong>net</strong> gevoed.<br />

De <strong>to</strong>tale belasting in dit <strong>net</strong> is:<br />

P = 1,542 + 2 + 2 + 4 MW = 9,542 MW<br />

Q = 1,972 + 1 + 1 + 2,001 = 5,973 Mvar<br />

Op<strong>en</strong><strong>en</strong> van de verbinding <strong>met</strong> het voed<strong>en</strong>de HS-<strong>net</strong> leidt <strong>to</strong>t afschakeling van het achterligg<strong>en</strong>de <strong>net</strong>. In de<br />

traditionele loadflow zou dit <strong>net</strong> niet berek<strong>en</strong>d kunn<strong>en</strong> word<strong>en</strong>.<br />

De voedingstransforma<strong>to</strong>r wordt uitgeschakeld <strong>en</strong> het <strong>net</strong> gaat over in eilandbedrijf. De vermog<strong>en</strong>sverandering die<br />

de g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> “zi<strong>en</strong>” is gelijk aan het weggevall<strong>en</strong> vermog<strong>en</strong> dat de <strong>net</strong>voeding leverde. De g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> voed<strong>en</strong> het<br />

eig<strong>en</strong> <strong>net</strong> <strong>en</strong> de onbalans wordt via de frequ<strong>en</strong>tie-vermog<strong>en</strong>sregeling opgevang<strong>en</strong>.<br />

De <strong>to</strong>tale opwekking in dit <strong>net</strong> is:<br />

P = 2,387 + 2,387 + 4,774 MW = 9,548 MW<br />

Q = 1,486 + 1,486 + 2,972 = 5,944 Mvar


16 09-010 pmo<br />

Deze vermog<strong>en</strong>s zijn nag<strong>en</strong>oeg gelijk aan de vermog<strong>en</strong>s in de situatie van het gekoppelde <strong>net</strong>, dus de regeling heeft<br />

goed gewerkt.<br />

De f/P-statiek van alle g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> is gelijk. Het nominale vermog<strong>en</strong> van g<strong>en</strong>era<strong>to</strong>r G3 is twee maal zo groot als dat<br />

van g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> G1 <strong>en</strong> G2.<br />

Duidelijk is te zi<strong>en</strong> dat g<strong>en</strong>era<strong>to</strong>r G3 twee keer zoveel bijdraagt aan de vermog<strong>en</strong>sverandering als g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> G1 of<br />

G2.<br />

G<strong>en</strong>era<strong>to</strong>r 1 <strong>en</strong> 2: P van 2 naar 2.387 MW<br />

G<strong>en</strong>era<strong>to</strong>r 3: P van 4 naar 4.774 MW<br />

Voor de verhouding van de bijdrag<strong>en</strong> geldt:<br />

To<strong>en</strong>ame G3 / To<strong>en</strong>ame G1 = 0.774 / 0.387 = 2<br />

HS-<strong>net</strong><br />

150.000 kV<br />

Inkooppunt<br />

9.926 kV<br />

-4.764 MW<br />

-2.966 Mvar<br />

-4.764 MW<br />

-2.967 Mvar<br />

4.774 MW<br />

2.972 Mvar<br />

4.774 MW<br />

2.973 Mvar<br />

Opwekking 1<br />

9.951 kV<br />

Opwekking 2<br />

9.951 kV<br />

G<br />

G1<br />

2.387 MW<br />

1.486 Mvar<br />

G G2<br />

2.387 MW<br />

1.486 Mvar<br />

G G3<br />

4.774 MW<br />

2.972 Mvar<br />

Industri<strong>en</strong>et<br />

V<br />

0.000 MW<br />

0.000 Mvar<br />

4.946 MW<br />

3.281 Mvar<br />

4.583 MW<br />

2.651 Mvar<br />

-4.574 MW<br />

-2.646 Mvar<br />

Fabriek 1<br />

9.902 kV<br />

-4.935 MW<br />

-3.274 Mvar<br />

0.363 MW<br />

0.626 Mvar<br />

M M1<br />

2.105 MW<br />

1.010 Mvar<br />

M M2<br />

2.105 MW<br />

1.010 Mvar<br />

-0.363 MW<br />

-0.631 Mvar<br />

Fabriek 2<br />

9.898 kV<br />

3.193 MW<br />

2.895 Mvar<br />

M3<br />

2.105 MW<br />

1.010 Mvar<br />

M<br />

LV<br />

0.384 kV<br />

-3.191 MW<br />

-2.705 Mvar<br />

M M11<br />

0.532 MW<br />

0.451 Mvar<br />

M<br />

M M13<br />

0.532 MW<br />

0.451 Mvar<br />

M<br />

M M15<br />

0.532 MW<br />

0.451 Mvar<br />

M<br />

M12<br />

0.532 MW<br />

0.451 Mvar<br />

M14<br />

0.532 MW<br />

0.451 Mvar<br />

M16<br />

0.532 MW<br />

0.451 Mvar<br />

8 GELEIDERWEERSTAND VAN KABELS<br />

De laagspanningskabels, die standaard in de kabeldatabase word<strong>en</strong> meegeleverd, hebb<strong>en</strong> e<strong>en</strong> geleiderweerstand die<br />

overe<strong>en</strong>komt <strong>met</strong> e<strong>en</strong> gespecificeerde geleidertemperatuur. De meeste kabels zijn niet continu vol belast, waardoor<br />

de temperatuur niet de maximum waarde zal bereik<strong>en</strong>. E<strong>en</strong> bedrijfspecifieke waarde kan door de gebruiker zelf<br />

word<strong>en</strong> vastgesteld. De geleiderweerstand wordt dan berek<strong>en</strong>d <strong>met</strong> onderstaande formule.<br />

R ' = R0[1<br />

+ α<br />

20<br />

( θ − 20)]<br />

waarin:<br />

R 0 : geleider gelijkstroomweerstand bij 20 grad<strong>en</strong> Celcius (opgave fabrikant)<br />

α 20 : temperatuurcoëfficiënt (0,00403 K -1 )<br />

θ: geleidertemperatuur (grad<strong>en</strong> Celsius)<br />

De berek<strong>en</strong>de waarde voor R' is de voor de temperatuur gecorrigeerde gelijkstroomweerstand. Formeel moet deze<br />

berek<strong>en</strong>de waarde nog gecorrigeerd word<strong>en</strong> <strong>met</strong> de skin effect <strong>en</strong> proximity effect fac<strong>to</strong>r<strong>en</strong> om de<br />

wisselstroomweerstand te krijg<strong>en</strong>. Deze fac<strong>to</strong>r<strong>en</strong> hebb<strong>en</strong> zo e<strong>en</strong> kleine bijdrage, dat we deze invloed<strong>en</strong> verwaarloz<strong>en</strong><br />

<strong>en</strong> de gezochte wisselstroomweerstand R gelijk stell<strong>en</strong> aan R'.


17 09-010 pmo<br />

Invloed geleiderweerstand op <strong>net</strong>spanning<br />

De spanningsval over e<strong>en</strong> kabelverbinding wordt volg<strong>en</strong>s de wet van Ohm bepaald door de stroomsterkte door <strong>en</strong><br />

door de impedantie van de kabel. De impedantie wordt bepaald door de geleiderweerstand <strong>en</strong> de zelfinductie. In<br />

laagspannings<strong>net</strong>t<strong>en</strong> <strong>met</strong> kabels heeft de geleiderweerstand de grootste invloed <strong>en</strong> speelt de zelfinductie e<strong>en</strong> veel<br />

kleinere rol. Daarom is de invloed van de temperatuur op de spanning<strong>en</strong> voornamelijk beperkt <strong>to</strong>t de laagspannings<strong>net</strong>t<strong>en</strong>.<br />

De temperatuurcoëfficiënt α 20 leidt ongeveer <strong>to</strong>t e<strong>en</strong> afwijking van 0,4 % van de geleiderweerstand per graad <strong>en</strong> <strong>to</strong>t<br />

e<strong>en</strong> ev<strong>en</strong> zo grote afwijking van de spanningsval over de betreff<strong>en</strong>de kabel.<br />

9 MOTORSTART<br />

Het aanlop<strong>en</strong> van e<strong>en</strong> mo<strong>to</strong>r gaat gepaard <strong>met</strong> e<strong>en</strong> grote aanloopstroom, waardoor spanningsdips in het <strong>net</strong><br />

ontstaan. Met e<strong>en</strong> statische berek<strong>en</strong>ing kan de dip als gevolg e<strong>en</strong> aanlop<strong>en</strong>de mo<strong>to</strong>r redelijk word<strong>en</strong> berek<strong>en</strong>d.<br />

Hierbij wordt de aanlop<strong>en</strong>de mo<strong>to</strong>r <strong>met</strong> zijn aanloopimpedantie (kortsluitimpedantie) gemodelleerd. De<br />

<strong>net</strong>voeding<strong>en</strong> <strong>en</strong> synchrone g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> word<strong>en</strong> gemodelleerd als e<strong>en</strong> equival<strong>en</strong>te spanningsbron achter hun<br />

subtransiënte impedanties.<br />

Na selecter<strong>en</strong> van mo<strong>to</strong>rstart kunn<strong>en</strong> bij de gelijknamige tab de te start<strong>en</strong> asynchrone <strong>en</strong> synchrone mo<strong>to</strong>r<strong>en</strong><br />

word<strong>en</strong> geselecteerd. Er word<strong>en</strong> 3 berek<strong>en</strong>ing<strong>en</strong> uitgevoerd waarvan de resultat<strong>en</strong> word<strong>en</strong> weergegev<strong>en</strong>:<br />

• situatie zonder de geselecteerde mo<strong>to</strong>r<strong>en</strong><br />

• situatie bij inschakeling van geselecteerde mo<strong>to</strong>r<strong>en</strong><br />

• situatie na de mo<strong>to</strong>rstart (<strong>met</strong> gestarte mo<strong>to</strong>r<strong>en</strong>).<br />

10 PATROON<br />

De functionaliteit die patron<strong>en</strong> combineert in de loadflowberek<strong>en</strong>ing<strong>en</strong> is vooral interessant voor het Asset<br />

Managem<strong>en</strong>t. In deze inleiding word<strong>en</strong> de mogelijkhed<strong>en</strong> van het gebruik van profiel<strong>en</strong> voor belasting <strong>en</strong> opwekking<br />

<strong>to</strong>egelicht. Deze pres<strong>en</strong>tatie geeft e<strong>en</strong> inleiding voor het invoer<strong>en</strong> van e<strong>en</strong> patroon, het koppel<strong>en</strong> aan belasting,<br />

opwekking <strong>en</strong> <strong>net</strong>voeding, het model van de belasting <strong>en</strong> het belastingsgedrag. In e<strong>en</strong> voorbeeld wordt de<br />

uitwerking op spanning, stroom <strong>en</strong> <strong>net</strong>verlies gedemonstreerd.<br />

E<strong>en</strong> profiel of patroon is e<strong>en</strong> getall<strong>en</strong>reeks die het gedrag van e<strong>en</strong> belasting of opwekking in de loop van de tijd<br />

beschrijft. Veel <strong>en</strong>ergiebedrijv<strong>en</strong> hebb<strong>en</strong> in het rec<strong>en</strong>te verled<strong>en</strong> deze reeks<strong>en</strong> verzameld voor typ<strong>en</strong> belasting<strong>en</strong> of<br />

voor specifieke knooppunt<strong>en</strong> in het <strong>net</strong>. De reeks<strong>en</strong> zijn meestal beschikbaar in spreadsheets.<br />

E<strong>en</strong> nieuwe patroon kan word<strong>en</strong> aangemaakt <strong>met</strong>: Nieuw | Patroon. E<strong>en</strong> bestaande patroon kan word<strong>en</strong> bekek<strong>en</strong> <strong>en</strong><br />

bewerkt <strong>met</strong>: Bewerk<strong>en</strong> | Patroon.<br />

Eig<strong>en</strong> patron<strong>en</strong> kunn<strong>en</strong> via Excel <strong>en</strong> het typ<strong>en</strong>bestand Types.XLS word<strong>en</strong> geïmporteerd.


18 09-010 pmo<br />

In het typ<strong>en</strong>bestand zijn vier voorbeeldpatron<strong>en</strong> opg<strong>en</strong>om<strong>en</strong>. Deze patron<strong>en</strong> kunn<strong>en</strong> als uitgangspunt di<strong>en</strong><strong>en</strong> om<br />

eig<strong>en</strong> patron<strong>en</strong> sam<strong>en</strong> te stell<strong>en</strong>. In het typ<strong>en</strong>bestand kunn<strong>en</strong> eig<strong>en</strong> typ<strong>en</strong> word<strong>en</strong> opg<strong>en</strong>om<strong>en</strong> voor bijvoorbeeld<br />

woonhuiz<strong>en</strong>, kan<strong>to</strong>r<strong>en</strong>, winkelc<strong>en</strong>tra, industrie.<br />

Bov<strong>en</strong>staand voorbeeld <strong>to</strong>ont de waarde voor tijdstip 9 van patroon “Voorbeeld 1”. In het volg<strong>en</strong>de diagram is deze<br />

waarde zichtbaar gemaakt.<br />

E<strong>en</strong> patroon bestaat uit 24 waard<strong>en</strong>. Dit zijn niet noodzakelijkerwijs 24 ur<strong>en</strong>. Bov<strong>en</strong>staand diagram <strong>to</strong>ont het<br />

verloop van patroon “Voorbeeld 1”, <strong>met</strong> de waarde voor tijdstip 9 omcirkeld. Alle waard<strong>en</strong> kunn<strong>en</strong> word<strong>en</strong><br />

aangepast om zodo<strong>en</strong>de de specifieke patron<strong>en</strong> voor de berek<strong>en</strong>ing<strong>en</strong> aan te mak<strong>en</strong>. Elk specifiek patroon krijgt e<strong>en</strong><br />

unieke naam, in dit voorbeeld “Demo 1”.


19 09-010 pmo<br />

Er zijn twee system<strong>en</strong> d<strong>en</strong>kbaar:<br />

• Patron<strong>en</strong> die g<strong>en</strong>ormeerd zijn op het maximum:<br />

de waarde komt niet bov<strong>en</strong> de 1 uit.<br />

• Patron<strong>en</strong> die g<strong>en</strong>ormeerd zijn op het gemiddelde:<br />

de waarde mag groter zijn dan 1.<br />

De keuze is geheel aan de gebruiker, maar heeft consequ<strong>en</strong>ties voor de belasting.<br />

E<strong>en</strong> bestaand patroon kan in het invulformulier voor belasting of opwekking word<strong>en</strong> gekoppeld.<br />

De keuze voor patron<strong>en</strong>, die g<strong>en</strong>ormeerd zijn op het maximum of op de gemiddelde waarde, heeft gevolg<strong>en</strong> voor de<br />

belasting die wordt ingevuld bij P <strong>en</strong> Q.


20 09-010 pmo<br />

Koppeling patroon aan e<strong>en</strong> <strong>net</strong>voeding<br />

Zoals e<strong>en</strong> patroon aan e<strong>en</strong> belasting of opwekking kan word<strong>en</strong> gekoppeld, kan e<strong>en</strong> patroon ook aan e<strong>en</strong> <strong>net</strong>voeding<br />

word<strong>en</strong> gekoppeld. Het patroon beïnvloed dan niet het vermog<strong>en</strong> maar de voedingsspanning, die immers ook<br />

volg<strong>en</strong>s e<strong>en</strong> patroon kan variër<strong>en</strong>.


21 09-010 pmo<br />

Demonstratie aan e<strong>en</strong> voorbeeld<strong>net</strong><br />

7...24 A<br />

MV node A1<br />

10.293...10.508 kV<br />

MV node A2<br />

10.285...10.506 kV<br />

MV node A3<br />

10.280...10.504 kV<br />

MV node A4<br />

10.276...10.503 kV<br />

V<br />

HV Rail<br />

150.000...150.000 kV<br />

1...14 A<br />

1...14 A 15...191 A<br />

Transformer A<br />

MV Rail<br />

10.405...10.557 kV<br />

1<br />

35...113 A<br />

14...47 A<br />

22...66 A 15...44 A 7...24 A<br />

7...22 A<br />

8...21 A<br />

17...59 A<br />

0...0 A<br />

Transformer B<br />

2<br />

7...89 A<br />

MV node B1<br />

10.301...10.572 kV<br />

3...77 A<br />

MV node B2<br />

10.292...10.576 kV<br />

22...51 A<br />

MV node B4<br />

10.284...10.589 kV<br />

G<br />

0...66 A<br />

8...21 A<br />

14...43 A<br />

7...24 A<br />

MV node B3<br />

10.289...10.574 kV<br />

7...24 A<br />

Spanning<strong>en</strong>:<br />

Knooppuntspanningsband<br />

HV Rail<br />

MV Rail<br />

MV node A1<br />

MV node A2<br />

MV node A3<br />

MV node A4<br />

MV node B1<br />

MV node B2<br />

MV node B3<br />

MV node B4<br />

1<br />

1.005<br />

1.01<br />

1.015<br />

1.02<br />

1.025 1.03 1.035<br />

Umin...Umax (pu)<br />

1.04<br />

1.045<br />

1.05<br />

1.055<br />

Strom<strong>en</strong>:<br />

Takbelastingsband<br />

1: MV Rail - MV node A1<br />

: MV node A1 - MV node A2<br />

: MV node A2 - MV node A3<br />

: MV node A3 - MV node A4<br />

2: MV Rail - MV node B1<br />

: MV node B1 - MV node B2<br />

: MV node B2 - MV node B3<br />

: MV node B2 - MV node B4<br />

: MV node A4 - MV node B4<br />

Transformer A: HV Rail - MV Rail<br />

2<br />

4<br />

6<br />

8 10 1214 16 18 20 22 24 2628 30 32 34 36 3840 42 44 46 48 5052 54 56 58 60 6264 66 68 70<br />

belasting min...max (%)


22 09-010 pmo<br />

Spanning als verloop van de tijd<br />

Knooppuntverloop<br />

U (kV)<br />

10.72<br />

10.7<br />

10.68<br />

10.66<br />

10.64<br />

10.62<br />

10.6<br />

10.58<br />

10.56<br />

10.54<br />

10.52<br />

10.5<br />

10.48<br />

10.46<br />

10.44<br />

10.42<br />

10.4<br />

10.38<br />

10.36<br />

10.34<br />

10.32<br />

10.3<br />

MV Rail<br />

MV node A1<br />

MV node A2<br />

MV node A3<br />

MV node A4<br />

MV node B1<br />

MV node B2<br />

MV node B3<br />

MV node B4<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12 13<br />

t<br />

14<br />

15<br />

16<br />

17<br />

18<br />

19<br />

20<br />

21<br />

22<br />

23<br />

24<br />

Stroom als verloop van de tijd<br />

70<br />

65<br />

60<br />

55<br />

50<br />

45<br />

Takverloop<br />

2<br />

Transformer A<br />

belasting (%)<br />

40<br />

35<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12 13<br />

t<br />

14<br />

15<br />

16<br />

17<br />

18<br />

19<br />

20<br />

21<br />

22<br />

23<br />

24


23 09-010 pmo<br />

BIJLAGE A: NEWTON-RAPHSON LOADFLOW<br />

De <strong>met</strong>hode die in <strong>Vision</strong> wordt <strong>to</strong>egepast om de spanning<strong>en</strong> <strong>en</strong> strom<strong>en</strong> in e<strong>en</strong> elektriciteitsvoorzi<strong>en</strong>ingssysteem<br />

te berek<strong>en</strong><strong>en</strong> is de loadflow volg<strong>en</strong>s New<strong>to</strong>n-Raphson. De <strong>met</strong>hode is voor het eerst beschrev<strong>en</strong> in 1961 <strong>en</strong> 1967. De<br />

loadflow convergeert snel naar e<strong>en</strong> oplossing <strong>en</strong> vanaf de introductie van sparse matrixtechniek<strong>en</strong> <strong>en</strong> optimale<br />

ord<strong>en</strong>ing t<strong>en</strong> behoeve van het eliminatieproces war<strong>en</strong> geheug<strong>en</strong>ruimte <strong>en</strong> rek<strong>en</strong>tijd ge<strong>en</strong> probleem meer. De<br />

New<strong>to</strong>n-Raphson loadflow is <strong>met</strong> succes beproefd <strong>en</strong> is wereldwijd geaccepteerd. Dit docum<strong>en</strong>t geeft e<strong>en</strong> korte<br />

technische beschrijving.<br />

UITGANGSPUNTEN<br />

Het <strong>net</strong>werk kan word<strong>en</strong> beschrev<strong>en</strong> als e<strong>en</strong> systeem <strong>met</strong> n knooppunt<strong>en</strong> <strong>met</strong> stroominjecties I inj,i , zoals afgebeeld<br />

in onderstaande figuur.<br />

I inj,1<br />

I inj,i<br />

Y<br />

I inj,n<br />

Het systeem wordt beschrev<strong>en</strong> door n complexe vergelijking<strong>en</strong>. In matrixnotatie:<br />

I inj = [ Y ] U<br />

Voor het systeem zijn 3 soort<strong>en</strong> knooppunt<strong>en</strong> gedefinieerd. Voor elk knooppunt is e<strong>en</strong> andere set bek<strong>en</strong>de <strong>en</strong><br />

onbek<strong>en</strong>de gegev<strong>en</strong>s. Onderstaande tabel geeft e<strong>en</strong> overzicht.<br />

Knooppunt Type Bek<strong>en</strong>de para<strong>met</strong>ers Onbek<strong>en</strong>de variabel<strong>en</strong><br />

Swingbus UT |U i |<br />

arg(U i )<br />

P i<br />

Q i<br />

Spanningsgeregelde<br />

synchrone g<strong>en</strong>era<strong>to</strong>r<br />

PU |U i |<br />

P i<br />

arg(U i )<br />

Q i<br />

Belasting PQ P i<br />

Q i<br />

|U i |<br />

arg(U i )<br />

Op het knooppunt "Swingbus" is e<strong>en</strong> <strong>net</strong>voeding aanwezig. Modulus <strong>en</strong> hoek van de spanning zijn gegev<strong>en</strong>.<br />

Voor e<strong>en</strong> "G<strong>en</strong>era<strong>to</strong>r" knooppunt is het van belang of er e<strong>en</strong> spanningsgeregelde g<strong>en</strong>era<strong>to</strong>r is aangeslot<strong>en</strong>. Elk<br />

ander type g<strong>en</strong>era<strong>to</strong>r maakt van het knooppunt ge<strong>en</strong> "G<strong>en</strong>era<strong>to</strong>r" knooppunt, maar e<strong>en</strong> belastingsknooppunt,<br />

omdat die elem<strong>en</strong>t<strong>en</strong> als negatieve belasting word<strong>en</strong> behandeld.<br />

Elk ander type knooppunt is e<strong>en</strong> belastingsknooppunt. Alle<strong>en</strong> het gedeelte "Constante P <strong>en</strong> Q" komt in aanmerking<br />

voor de set "Bek<strong>en</strong>de para<strong>met</strong>ers". Het "Constante admittantie" gedeelte van de belasting wordt niet als stroom<br />

geïnjecteerd, maar komt in de systeemmatrix [Y].


24 09-010 pmo<br />

OPLOSMETHODE<br />

De oplos<strong>met</strong>hode in het algeme<strong>en</strong> is redelijk goed beschrev<strong>en</strong> in het boek "Computer Analysis of Power Systems"<br />

van Arrilaga <strong>en</strong> Arnold. De <strong>met</strong>hode volg<strong>en</strong>s New<strong>to</strong>n-Raphson zoekt het nulpunt van de functie: f k (x m ) = 0, voor alle<br />

k <strong>en</strong> alle m. Bij elke iteratie wordt het niet-lineaire vraagstuk b<strong>en</strong>aderd door e<strong>en</strong> lineaire matrixvergelijking. De<br />

b<strong>en</strong>adering wordt geïllustreerd <strong>met</strong> e<strong>en</strong> vergelijking <strong>met</strong> één variabele. In onderstaande figuur is x (p) e<strong>en</strong> b<strong>en</strong>adering<br />

van de oplossing, <strong>met</strong> fout Δx (p) bij iteratie p.<br />

raaklijn van f(x)<br />

Δx (p) f(x)<br />

x (p+1) x (p)<br />

Oplossing<br />

In dat geval is:<br />

( p)<br />

( p)<br />

f ( x + Δx<br />

) = 0 (1)<br />

Deze vergelijking kan word<strong>en</strong> beschrev<strong>en</strong> in e<strong>en</strong> Taylor reeksontwikkeling:<br />

( p)<br />

2<br />

( p)<br />

( p)<br />

( p)<br />

( p)<br />

( p)<br />

( Δx<br />

) ( p)<br />

f ( x + Δx<br />

) = f ( x ) + Δx<br />

f '( x ) + f ''( x ) + ... (2)<br />

2!<br />

Indi<strong>en</strong> de initiële schatting van de variabele x (p) zich in de buurt van de oplossing bevindt, is Δx (p) relatief klein <strong>en</strong><br />

kunn<strong>en</strong> alle hogere term<strong>en</strong> van de Taylor reeksontwikkeling word<strong>en</strong> verwaarloosd. We krijg<strong>en</strong> dan:<br />

( p)<br />

( p)<br />

( p)<br />

f ( x ) + Δx<br />

f '( x ) = 0 (3)<br />

of:<br />

( p)<br />

( p)<br />

f ( x )<br />

Δ x = −<br />

(4)<br />

( p)<br />

f '( x )<br />

De nieuwe waarde van de variabele voor de volg<strong>en</strong>de iteratie (p+1) wordt dan verkreg<strong>en</strong> via:<br />

x<br />

= x<br />

+ Δx<br />

( p+<br />

1) ( p)<br />

( p)<br />

(5)<br />

Vergelijking (3) kan ook geschrev<strong>en</strong> word<strong>en</strong> als:<br />

f ( x<br />

( p)<br />

)<br />

( p)<br />

= −JΔx<br />

(6)<br />

Waarin J de vierkante Jacobiaan is van eerste orde partiële differ<strong>en</strong>tiaalvergelijking<strong>en</strong> van de functies f k (x m ). De<br />

elem<strong>en</strong>t<strong>en</strong> van J zijn gedefinieerd door:<br />

∂fk<br />

J<br />

km<br />

= (7)<br />

∂x<br />

m


25 09-010 pmo<br />

En repres<strong>en</strong>ter<strong>en</strong> de helling<strong>en</strong> van de rak<strong>en</strong>de hyperoppervlaktes, die de functies f k (x m ) b<strong>en</strong>ader<strong>en</strong> in elk iteratiepunt.<br />

In formulevorm e<strong>en</strong> stelsel van 2n vergelijking<strong>en</strong> <strong>en</strong> 2n onbek<strong>en</strong>d<strong>en</strong>:<br />

⎡ΔP⎤<br />

⎡J<br />

⎡ Δ<br />

1<br />

J ⎤ ⎤<br />

⎥ = ⎢ ⎥ ⋅ θ<br />

2<br />

⎢<br />

⎢ ⎥ (8)<br />

⎣<br />

ΔQ<br />

⎦ ⎣J<br />

⎦ ⎣Δ<br />

| U |<br />

3<br />

J<br />

4 ⎦<br />

De New<strong>to</strong>n-Raphson <strong>met</strong>hode convergeert kwadratisch indi<strong>en</strong>:<br />

− de functies continue eerste afgeleid<strong>en</strong> hebb<strong>en</strong> in de buurt van de oplossing,<br />

− de Jacobiaan niet-singulier is <strong>en</strong><br />

− de initiële schatting<strong>en</strong> van x zich dicht bij de actuele oplossing<strong>en</strong> bevind<strong>en</strong>.<br />

Echter, de <strong>met</strong>hode is gevoelig voor het gedrag van de functies f k (x m ) <strong>en</strong> voor hun formulering. Hoe lineairder ze<br />

zijn, deste sneller <strong>en</strong> betrouwbaarder de <strong>met</strong>hode convergeert. Discontinuïteit<strong>en</strong> in de functies in de buurt van de<br />

oplossing zijn oorzaak van converg<strong>en</strong>tieproblem<strong>en</strong>, <strong>to</strong>tale onoplosbaarheid of e<strong>en</strong> niet bruikbare oplossing.<br />

Het oplosalgoritme komt in het kort neer op het onderstaande schema:<br />

Reset aantal iteraties op 0<br />

Initialiseer RHSMax op 1+Eps<br />

Zolang RHSMax > Eps & aantal iteraties niet te groot, doe:<br />

Berek<strong>en</strong> sparse Jacobiaan<br />

Berek<strong>en</strong> Mismatches<br />

Indi<strong>en</strong> de Mismatch plotseling veel groter wordt, is er sprake van diverg<strong>en</strong>tie<br />

Indi<strong>en</strong> de oplossing nog niet gevond<strong>en</strong> is:<br />

Maak de hoofddiagonaal elem<strong>en</strong>t<strong>en</strong> van Swing <strong>en</strong> G<strong>en</strong>era<strong>to</strong>rknooppunt<strong>en</strong> groot<br />

Fac<strong>to</strong>riseer de Jacobiaan t.b.v. de LU-decompositie: Jacobiaan wordt [L][U]<br />

Los het systeem op uit <strong>met</strong> behulp van y = [L][U] x<br />

Berek<strong>en</strong> de knooppuntspanning<strong>en</strong><br />

Het volg<strong>en</strong>de hoofdstuk gaat kort in op de onderdel<strong>en</strong> van het algoritme.


26 09-010 pmo<br />

DE VERGELIJKINGEN IN RELATIE TOT HET SYSTEEM<br />

De vermog<strong>en</strong>sinjectie op e<strong>en</strong> knooppunt i is beschrev<strong>en</strong> als:<br />

N<br />

u<br />

y<br />

i<br />

ij<br />

i<br />

<strong>met</strong> :<br />

ij<br />

= u ⋅i<br />

i<br />

i<br />

i<br />

= | u | e<br />

= | y<br />

ij<br />

∗<br />

inj,<br />

i<br />

jθi<br />

θ = θ −θ<br />

| e<br />

j<br />

jγ<br />

ij<br />

⎡<br />

= ui<br />

⎢<br />

⎣<br />

n<br />

∑<br />

j=<br />

1<br />

y<br />

ij<br />

u<br />

j<br />

⎤<br />

⎥<br />

⎦<br />

∗<br />

(9)<br />

Berek<strong>en</strong>ing van de Jacobiaan<br />

Voor het bepal<strong>en</strong> van de afgeleid<strong>en</strong> wordt bov<strong>en</strong>staande uitdrukking omgezet:<br />

N<br />

i<br />

=<br />

n<br />

∑<br />

j = 1<br />

| u || y<br />

i<br />

ij<br />

|| u<br />

j<br />

| e<br />

j(<br />

θ i −θ<br />

j −γ<br />

ij )<br />

= | u<br />

i<br />

2<br />

| | y<br />

ii<br />

| e<br />

j(<br />

−γ<br />

ij )<br />

+<br />

n<br />

∑<br />

i<br />

j = 1, j ≠i<br />

| u || y<br />

ij<br />

|| u<br />

j<br />

| e<br />

j(<br />

θ i −θ<br />

j −γ<br />

ij )<br />

(10)<br />

Bov<strong>en</strong>staande vergelijking wordt eerst afgeleid naar θ i <strong>en</strong> |u i | voor de (sub)diagonaal elem<strong>en</strong>t<strong>en</strong>:<br />

∂Ni<br />

= j<br />

∂θ<br />

i<br />

∂Ni<br />

∂ | u<br />

i<br />

n<br />

∑<br />

i<br />

j = 1, j ≠i<br />

| u || y<br />

= 2 | ui<br />

|| y<br />

|<br />

ij<br />

ij<br />

| e<br />

|| u<br />

j<br />

| e<br />

j(<br />

−γ<br />

ij )<br />

j(<br />

θ i −θ<br />

j −γ<br />

ij )<br />

+<br />

n<br />

∑<br />

| y<br />

ij<br />

j = 1, j ≠i<br />

=<br />

|| u<br />

j<br />

j<br />

n<br />

∑<br />

i<br />

j = 1, j ≠i<br />

| e<br />

u ( y u )<br />

ij<br />

j(<br />

θ i −θ<br />

j −γ<br />

ij )<br />

j<br />

∗<br />

= 2 | u<br />

i<br />

| y<br />

∗<br />

ij<br />

1<br />

+<br />

| u |<br />

i<br />

n<br />

∑<br />

i<br />

j = 1, j ≠i<br />

u ( y u )<br />

ij<br />

j<br />

∗<br />

(11)<br />

En vervolg<strong>en</strong>s naar θ j <strong>en</strong> |u j | voor de niet-(sub)diagonaal elem<strong>en</strong>t<strong>en</strong>:<br />

∂Ni<br />

j(<br />

θ i −θ<br />

j −γ<br />

ij )<br />

∗<br />

= − j | ui<br />

|| yij<br />

|| u<br />

j<br />

| e = − j ⋅ui(<br />

yiju<br />

j<br />

)<br />

∂θ<br />

j<br />

(12)<br />

∂Ni<br />

j(<br />

θ − − ) 1<br />

i θ j γ ij<br />

∗<br />

= | ui<br />

|| yij<br />

| e = ui(<br />

yiju<br />

j<br />

)<br />

∂ | u |<br />

| u |<br />

j<br />

j<br />

De resultat<strong>en</strong> van vergelijking<strong>en</strong> (11) word<strong>en</strong> op de hoofddiagonal<strong>en</strong> van de sub-matrices J 1 , J 2 , J 3 <strong>en</strong> J 4 ingevuld. Het<br />

reële deel van de eerste vergelijking van (11) in J 1 , het reële deel van de tweede vergelijking van (11) in J 2 , het<br />

imaginaire deel van de eerste vergelijking van (11) in J 3 <strong>en</strong> het imaginaire deel van de tweede vergelijking van (11) in<br />

J 4 .<br />

Berek<strong>en</strong>ing van de Mismatches<br />

Aan de hand van de Mismatches wordt bekek<strong>en</strong> of e<strong>en</strong> oplossing gevond<strong>en</strong> is. Indi<strong>en</strong> de <strong>met</strong>hode e<strong>en</strong> correct<br />

startpunt had, is de oplossing vrijwel zeker de juiste. De vec<strong>to</strong>r Δx bevat de hoek<strong>en</strong> <strong>en</strong> de moduli van de spanning<strong>en</strong><br />

in het <strong>net</strong>werk.<br />

⎡ Δθ<br />

⎤<br />

Δx<br />

= ⎢ ⎥ (20)<br />

⎣Δ<br />

|U | ⎦


27 09-010 pmo<br />

Voor alle knooppunt<strong>en</strong> wordt het maximum van de absolute waard<strong>en</strong> van de hoek<strong>en</strong> bepaald <strong>en</strong> voor alle<br />

belastingsknooppunt<strong>en</strong> wordt het maximum van de moduli van de spanning<strong>en</strong> bepaald. Indi<strong>en</strong> beide maxima<br />

kleiner zijn dan de <strong>to</strong>lerantie (Eps), verandert de oplossingsvec<strong>to</strong>r Δx niet meer <strong>en</strong> is e<strong>en</strong> oplossing gevond<strong>en</strong>.<br />

Berek<strong>en</strong>ing van de knooppuntspanning<strong>en</strong><br />

De knooppuntspanning<strong>en</strong> word<strong>en</strong> berek<strong>en</strong>d uit de elem<strong>en</strong>t<strong>en</strong> van de oplossingsvec<strong>to</strong>r, door de bestaande<br />

spanningsvec<strong>to</strong>r te verm<strong>en</strong>igvuldig<strong>en</strong> <strong>met</strong> de elem<strong>en</strong>t<strong>en</strong> uit vec<strong>to</strong>r Δx.<br />

Δui<br />

jΔθi<br />

ui<br />

: = ui<br />

⋅(1<br />

+ ) ⋅e<br />

(21)<br />

u<br />

|<br />

i<br />

|<br />

Voor g<strong>en</strong>era<strong>to</strong>r<strong>en</strong> wordt dan de spanning bijgesteld in verband <strong>met</strong> de gew<strong>en</strong>ste maximale <strong>en</strong> minimale spanning,<br />

die volgt uit de spanningsstatiek.<br />

U<br />

max, i<br />

= U<br />

ref , i<br />

− statiek ⋅Qmin,<br />

i<br />

(22)<br />

U = U − statiek ⋅Q<br />

min, i<br />

ref , i<br />

max, i<br />

Als de spanning buit<strong>en</strong> de gr<strong>en</strong>z<strong>en</strong> dreigt te ligg<strong>en</strong>, wordt de nieuwe spanning:<br />

U<br />

max, i<br />

ui<br />

: = ui<br />

u<br />

U<br />

ui<br />

: = ui<br />

| u |<br />

|<br />

of<br />

(23)<br />

i<br />

|<br />

min, i<br />

i<br />

Voor e<strong>en</strong> Swingknooppunt blijft de spanning gelijk aan de gegev<strong>en</strong> waarde.


28 09-010 pmo<br />

BIJLAGE B SPANNINGSHUISHOUDING VAN EEN DISTRIBUTIENET IN NEDERLAND<br />

Met de spanningshuishouding van e<strong>en</strong> distributi<strong>en</strong>et wordt bedoeld de grootte <strong>en</strong> variatie van de <strong>net</strong>spanning van<br />

alle knooppunt<strong>en</strong> van het onderstation <strong>to</strong>t <strong>en</strong> <strong>met</strong> de <strong>met</strong>erkast van de aangeslot<strong>en</strong><strong>en</strong>. De <strong>net</strong><strong>beheer</strong>der is er<br />

verantwoordelijk voor dat de <strong>net</strong>spanning binn<strong>en</strong> de gestelde gr<strong>en</strong>z<strong>en</strong> blijft.<br />

Bepaling <strong>to</strong>elaatbare spanningsvariatie in het 10 kV-<strong>net</strong><br />

Voor e<strong>en</strong> goed <strong>MS</strong>-<strong>net</strong>ontwerp qua spanningshuishouding moet<strong>en</strong> we e<strong>en</strong> beeld hebb<strong>en</strong> van de spanningsvariatie<br />

van de voedingszijde van het 10 kV-<strong>net</strong> <strong>to</strong>t <strong>en</strong> <strong>met</strong> de <strong>met</strong>erkast van de LS-aangeslot<strong>en</strong><strong>en</strong>. De spanningsvariatie<br />

wordt behalve door de variatie aan de voedingszijde van het 10 kV-<strong>net</strong>, in belangrijke mate bepaald door het<br />

spanningsverlies in het <strong>MS</strong>-transport- <strong>en</strong> distributi<strong>en</strong>et, de 10 kV-LS transforma<strong>to</strong>r<strong>en</strong> <strong>en</strong> het LS-distributie- <strong>en</strong><br />

aansluit<strong>net</strong>. Ev<strong>en</strong>tueel aanwezige dec<strong>en</strong>trale opwek vergroot de spanningsvariatie.<br />

Er zijn drie belangrijke ijkpunt<strong>en</strong> aan te wijz<strong>en</strong>.<br />

• Het eerste ijkpunt is de spanningsvariatie aan de voedingszijde. Zoals eerder vermeld bedraagt de<br />

setwaarde van de <strong>net</strong>spanning van de10 kV-rail op het onderstation 10,55 kV. Deze waarde stell<strong>en</strong> we op<br />

100 %. De maximale <strong>net</strong>spanning is 10,65 kV (100,95 %) <strong>en</strong> de minimale 10,45 kV (99,05%).<br />

• Het tweede ijkpunt betreft de maximaal <strong>to</strong>elaatbare spanning in het 10 kV-<strong>net</strong>. Met het oog op het isoler<strong>en</strong>d<br />

vermog<strong>en</strong> mag de gr<strong>en</strong>swaarde van de <strong>net</strong>spanning 11 kV bedrag<strong>en</strong>. Kritische compon<strong>en</strong>t<strong>en</strong> hierbij zijn de<br />

GPL-kabels, de oudere 10 kV-schakelinstallaties (COQ <strong>en</strong> Conel). De oudere distributietransforma<strong>to</strong>r<strong>en</strong>,<br />

<strong>met</strong> name de N 60-g<strong>en</strong>eratie, ver<strong>to</strong>n<strong>en</strong> ook aanzi<strong>en</strong>lijk meer ijzerverliez<strong>en</strong> bij e<strong>en</strong> hogere <strong>net</strong>spanning.<br />

• Het derde ijkpunt is de fasespanning bij de LS-aangeslot<strong>en</strong>e. De afspraak is bijvoorbeeld dat de maximale<br />

fasespanning bij de LS-aangeslot<strong>en</strong>e 230 V + 6% is 243,8 V mag bedrag<strong>en</strong>. Volg<strong>en</strong>s de Netcode mag de<br />

maximale fasespanning 230 V + 10% is 253 V bedrag<strong>en</strong> (gr<strong>en</strong>swaarde). De “ruimte” bedraagt 4% ofwel<br />

9,2 V. Deze ruimte zou in de <strong>to</strong>ekomst kunn<strong>en</strong> word<strong>en</strong> b<strong>en</strong>ut voor dec<strong>en</strong>trale opwek (DCO).<br />

De laagste fasespanning bij de LS-aangeslot<strong>en</strong>e bedraagt 230 V -10% is 207 V. Dit is in overe<strong>en</strong>stemming <strong>met</strong> de<br />

Netcode.<br />

Bij de bepaling van de spanningsvariatie gaan we behalve van de bov<strong>en</strong>g<strong>en</strong>oemde ijkpunt<strong>en</strong>, uit van de volg<strong>en</strong>de<br />

richtlijn<strong>en</strong> <strong>en</strong> praktijkwaard<strong>en</strong>:<br />

1. De fasespanning op de aftakmof van de huisaansluiting bedraagt minimaal 212 V ofwel 92,2%, t<strong>en</strong> tijde van<br />

maximale belasting;<br />

2. Het spanningsverlies van het LS-rek <strong>to</strong>t de aftakmof van de huisaansluiting bedraagt t<strong>en</strong> tijde van de<br />

maximale belasting 4%;<br />

3. Het spanningsverlies in de distributietransforma<strong>to</strong>r bedraagt t<strong>en</strong> tijde van de maximale belasting 2%. Dit<br />

komt overe<strong>en</strong> <strong>met</strong> e<strong>en</strong> belastingsperc<strong>en</strong>tage van 66%. Verderop wordt dit verklaard;<br />

4. De laagste <strong>net</strong>spanning in het 10 kV-<strong>net</strong> bedraagt t<strong>en</strong> tijde van de maximale belasting 9,78 kV ofwel 92,7 %<br />

van de setwaarde. De waarde van de laagste <strong>net</strong>spanning wordt mede bepaald door het regelbereik van de<br />

oudere distributietransforma<strong>to</strong>r<strong>en</strong> (N 60). Verderop wordt dit verklaard;<br />

5. De laagste belasting in het LS-distributi<strong>en</strong>et <strong>en</strong> de distributietransforma<strong>to</strong>r<strong>en</strong> bedraagt 20% van de<br />

maximale belasting;<br />

6. De laagste belasting in het 10 kV-<strong>net</strong> bedraagt 30% van de maximale belasting.<br />

Voornoemde ijkpunt<strong>en</strong>, richtlijn<strong>en</strong> <strong>en</strong> praktijkwaard<strong>en</strong> leid<strong>en</strong> <strong>to</strong>t de spanningsvariatie welke in figuur 21 is<br />

weergegev<strong>en</strong>. Deze is gerelateerd aan de opbouw van het distributi<strong>en</strong>et.


Figuur 21<br />

Spanningsvariatie in het 10 kV-<strong>net</strong> <strong>en</strong> LS-<strong>net</strong><br />

gr<strong>en</strong>swaarde = 253 V (110%)<br />

bov<strong>en</strong>gr<strong>en</strong>swaarde<br />

11 kV (104,27%)<br />

“normaal” max. <strong>net</strong>spanning bedrijf<br />

243,8 V (106%)<br />

10,65 kV (100,95%)<br />

U SET = 10,55 kV (100%)<br />

10,45 kV (99,05%)<br />

“normaal” max. <strong>net</strong>spanning<br />

“normaal” min. <strong>net</strong>spanning<br />

gem.<br />

10,51 kV (99,67%)<br />

10,26 kV (97,25%)<br />

10,00 kV (94,79%)<br />

221,26 V (96,2%)<br />

230 V (100%)<br />

ondergr<strong>en</strong>swaarde i.v.m. regelbereik trafo’s<br />

9,78 kV (92,7%)<br />

212 V (92,2%)<br />

ondergr<strong>en</strong>swaarde i.v.m<br />

eis<strong>en</strong> Netcode<br />

207 V (90%)<br />

110 kV-<strong>net</strong> 10 kV-rail verdeelstation RMU LS-rek aftakmof <strong>met</strong>erkast


10.1 Bepaling laagste <strong>to</strong>elaatbare <strong>net</strong>spanning in 10 kV- <strong>net</strong><br />

In tabel 1 is de transformatieverhouding van alle gangbare typ<strong>en</strong> distributietransforma<strong>to</strong>r<strong>en</strong> vermeld.<br />

Transformatieverhouding “n” distributietransforma<strong>to</strong>r<strong>en</strong><br />

Type Tapstand Ums Uls n<br />

1 10500 380 27,632<br />

2 10250 380 26,974<br />

N 60 3 10000 380 26,316<br />

4 9750 380 25,658<br />

5 9500 380 25,000<br />

1 10750 400 26,875<br />

2 10500 400 26,250<br />

N 83 3 10250 400 25,625<br />

4 10000 400 25,000<br />

5 9750 400 24,375<br />

1 11000 420 26,190<br />

2 10750 420 25,595<br />

N 91 3 10500 420 25,000<br />

4 10250 420 24,405<br />

5 10000 420 23,810<br />

1 11250 420 26,786<br />

2 11000 420 26,190<br />

N 95 3 10750 420 25,595<br />

4 10500 420 25,000<br />

5 10250 420 24,405<br />

Tabel 1<br />

Zoals gezegd wordt de laagste <strong>to</strong>elaatbare <strong>net</strong>spanning in het 10 kV-<strong>net</strong> bepaald door de<br />

transformatieverhouding van de oude N 60 transforma<strong>to</strong>r<strong>en</strong>. Het <strong>net</strong> is maximaal belast.<br />

Uit de figuur 21 <strong>met</strong> de spanningsvariatie is te zi<strong>en</strong> dat bij de maximale belasting de spanning op het<br />

LS-rek 221,26 V (96,2%) bedraagt. De secundaire fasespanning in onbelaste <strong>to</strong>estand is 2% hoger <strong>en</strong><br />

bedraagt 225,86 V (98,2%).<br />

Als de spanningsregelaar van de N 60-types op maximaal staat (tapstand 5), is de<br />

transformatieverhouding minimaal, namelijk 25. De primaire <strong>net</strong>spanning moet dan minimaal<br />

bedrag<strong>en</strong> :<br />

U NET = Uf 0 x √3 x n = 225,86 x √3 x 25 = 9870 V<br />

Gelet op het grot<strong>en</strong>deels stedelijke voorzi<strong>en</strong>ingsgebied van dit voorbeeldbedrijf zal onder normale<br />

omstandighed<strong>en</strong> de <strong>net</strong>spanning nooit lager zijn dan 10.000 V.


31 09-011 pmo<br />

10.2 Instelling spanningsregelaar distributietransforma<strong>to</strong>r<strong>en</strong><br />

De instelling van de spanningsregelaar van distributietransforma<strong>to</strong>r<strong>en</strong> wordt niet alle<strong>en</strong> bepaald door<br />

het type transforma<strong>to</strong>r, maar ook door de <strong>net</strong>locatie. In figuur figuur 21 “Spanningsvariatie 10 kV-<strong>net</strong><br />

<strong>en</strong> LS-<strong>net</strong>” is te zi<strong>en</strong> dat nabij de invoeding van het 10 kV-<strong>net</strong> onder normale omstandighed<strong>en</strong> e<strong>en</strong><br />

gemiddelde <strong>net</strong>spanning heerst van 10,55 kV <strong>met</strong> e<strong>en</strong> variatie +/- 0,95 %. Bij de elektrisch verst<br />

geleg<strong>en</strong> RMU’s heerst onder normale omstandighed<strong>en</strong> e<strong>en</strong> gemiddelde <strong>net</strong>spanning van 10,26 kV <strong>met</strong><br />

e<strong>en</strong> variatie +/- 2,44 %. Bij de instelling van de spanningsregelaar houd<strong>en</strong> we ge<strong>en</strong> rek<strong>en</strong>ing <strong>met</strong> de<br />

extreme <strong>net</strong>situaties, e<strong>en</strong> bov<strong>en</strong>gr<strong>en</strong>swaarde van 11 kV of de ondergr<strong>en</strong>swaarde van 9,78 kV.<br />

Gegev<strong>en</strong> de normale <strong>net</strong>spanningsvariaties moet de fasespanning bij de LS-aangeslot<strong>en</strong><strong>en</strong> binn<strong>en</strong> de<br />

vastgestelde gr<strong>en</strong>z<strong>en</strong> blijv<strong>en</strong>; U MAX = 244 V <strong>en</strong> U MIN = 207 V.<br />

In tabel 2 zijn de berek<strong>en</strong>de tapstand<strong>en</strong> vermeld.<br />

<strong>net</strong>locatie<br />

fasespanning LS-rek (normale <strong>MS</strong>-variatie)<br />

Type nabij onderstation verst geleg<strong>en</strong> RMU nabij onderstation verst geleg<strong>en</strong> RMU<br />

trafo tapstand tr.verh. tapstand tr.verh. hoogst laagst hoogst laagst<br />

N 60 4 25,658 5 25 238,72 230,54 242,03 226,34<br />

N 83 3 25,625 4 25 239,03 230,85 242,03 226,34<br />

N 91 2 25,595 3 25 239,31 231,12 242,03 226,34<br />

N 95 3 25,595 4 25 239,31 231,12 242,03 226,34<br />

Tabel 2<br />

Berek<strong>en</strong>de tapstand<strong>en</strong><br />

Toelichting tabel 2<br />

Bij de berek<strong>en</strong>ing van de tapstand gaan we uit van de gemiddelde spanning op de <strong>net</strong>locatie.<br />

Nabij het onderstation is de gemiddelde <strong>net</strong>spanning 10,55 kV. De spanning op het LS-rek mag<br />

minimaal 221,26 V zijn bij maximale belasting <strong>en</strong> 244 V bij minimale belasting. De “op<strong>en</strong>” spanning<br />

van de transforma<strong>to</strong>r is dan respectievelijk 225,72 V <strong>en</strong> 244,92 V. De gemiddelde “op<strong>en</strong>” spanning van<br />

de transforma<strong>to</strong>r is 235,39 V.<br />

De transformatieverhouding bij de gemiddelde <strong>MS</strong>- <strong>en</strong> op<strong>en</strong> LS-spanning is: 10550 / 235,39 √3 =<br />

25,876.<br />

Uit tabel 1 van de transformatieverhouding<strong>en</strong> van de verschill<strong>en</strong>de typ<strong>en</strong> transforma<strong>to</strong>r<strong>en</strong> kunn<strong>en</strong> we<br />

dan de transformatieverhouding kiez<strong>en</strong> die het dichts in de buurt zit.<br />

Nabij de verst geleg<strong>en</strong> RMU is de gemiddelde <strong>net</strong>spanning 10,26 kV. De gemiddelde “op<strong>en</strong>” spanning<br />

van de transforma<strong>to</strong>r bedraagt zoals hiervoor vermeld 235,39 V.<br />

De transformatieverhouding bij de gemiddelde <strong>MS</strong>- <strong>en</strong> op<strong>en</strong> LS-spanning is: 10260 / 235,39 √3 =<br />

25,165.<br />

Voor alle typ<strong>en</strong> transforma<strong>to</strong>r<strong>en</strong> kiez<strong>en</strong> we de transformatieverhouding 25. Per type geeft dit wel<br />

verschill<strong>en</strong>de tapstand<strong>en</strong>.<br />

Uit de berek<strong>en</strong>ing<strong>en</strong> blijkt dat bij normale spanningsvariaties aan de gestelde eis<strong>en</strong> kan word<strong>en</strong><br />

voldaan.<br />

Het blijkt niet mogelijk om per type transforma<strong>to</strong>r één tapstand aan te houd<strong>en</strong>.


32 09-011 pmo<br />

Als we kijk<strong>en</strong> wat bij de gegev<strong>en</strong> tapstand<strong>en</strong> de gevolg<strong>en</strong> zijn in extreme situaties, krijg<strong>en</strong> we het<br />

volg<strong>en</strong>de beeld.<br />

Type<br />

tapstand<strong>en</strong><br />

op<br />

<strong>net</strong>locatie<br />

fasespanning LS-rek (gr<strong>en</strong>swaard<strong>en</strong> <strong>MS</strong>)<br />

trafo nabij onderstation verst geleg<strong>en</strong> RMU nabij onderstation verst geleg<strong>en</strong> RMU<br />

tapstand tr.verh. tapstand tr.verh. hoogst laagst hoogst laagst<br />

N 60 4 25,658 5 25 246,60 230,54 253,11 221,26<br />

N 83 3 25,625 4 25 246,92 230,85 253,11 221,26<br />

N 91 2 25,595 3 25 247,21 231,12 253,11 221,26<br />

N 95 3 25,595 4 25 247,21 231,12 253,11 221,26<br />

Tabel 3<br />

Het blijkt dat nabij het onderstation niet aan de bedrijfs-eis van maximaal 244 V wordt voldaan.<br />

Voorts dat bij de verst geleg<strong>en</strong> RMU niet aan de eis<strong>en</strong> van de Netcode wordt voldaan.<br />

Zie ook de <strong>Vision</strong>-berek<strong>en</strong>ing<strong>en</strong> van de figur<strong>en</strong> 22 <strong>en</strong> 23.<br />

V<br />

72 kW<br />

45 kvar<br />

4 A<br />

10 kV-<strong>net</strong><br />

11,000 kV<br />

0,000 °<br />

72 kW<br />

45 kvar<br />

4 A<br />

Type N 95<br />

Verst geleg<strong>en</strong> RMU<br />

400 10750/420 5j<br />

trap: 4<br />

21 %<br />

-71 kW<br />

-44 kvar<br />

110 A<br />

LS-rek<br />

0,438 kV<br />

-0,310 °<br />

71 kW<br />

44 kvar<br />

110 A<br />

Figuur 22<br />

<strong>Vision</strong>-berek<strong>en</strong>ing<br />

V<br />

210 kW<br />

136 kvar<br />

15 A<br />

10 kV-<strong>net</strong><br />

9,780 kV<br />

0,000 °<br />

210 kW<br />

136 kvar<br />

15 A<br />

Type N 95<br />

Verst geleg<strong>en</strong> RMU<br />

400 10750/420 5j<br />

trap: 4<br />

62 %<br />

-208 kW<br />

-129 kvar<br />

368 A<br />

LS-rek<br />

0,383 kV<br />

-1,160 °<br />

208 kW<br />

129 kvar<br />

368 A<br />

Figuur 23<br />

<strong>Vision</strong>-berek<strong>en</strong>ing<br />

De berek<strong>en</strong>de lijnspanning<strong>en</strong> zijn 438 V <strong>en</strong> 383 V, overe<strong>en</strong>kom<strong>en</strong>d <strong>met</strong> e<strong>en</strong> fasespanning van<br />

respectievelijk <strong>en</strong> 252,88 V <strong>en</strong> 221,13 V.


33 09-011 pmo<br />

10.3 Invloed dec<strong>en</strong>trale opwek (DCO) op de spanningshuishouding<br />

Invoeding door dec<strong>en</strong>trale opwek leidt <strong>to</strong>t verhoging van de <strong>net</strong>spanning. De spanningsverhoging<br />

hangt af van de grootte van het DCO-vermog<strong>en</strong> <strong>en</strong> grootte van het kortsluitvermog<strong>en</strong> S K ter plaatse.<br />

Voor de berek<strong>en</strong>ing van het DCO-vermog<strong>en</strong> pass<strong>en</strong> we de formule uit paragraaf 1.2 <strong>to</strong>e van de<br />

berek<strong>en</strong>ing van het spanningsverlies.<br />

ΔU<br />

= I<br />

G<br />

• ( R • cosΦ + X • sin Φ)<br />

N<br />

N<br />

Waarin:<br />

∆ U<br />

I G<br />

R N<br />

X N<br />

Ф<br />

= <strong>to</strong>elaatbare spanningsverhoging [V]<br />

= g<strong>en</strong>era<strong>to</strong>rstroom [A}<br />

= de kortsluitweerstand van het distributi<strong>en</strong>et ter plaatse van de DCO<br />

= de kortsluitreactantie van het distributi<strong>en</strong>et ter plaatse van de DCO<br />

= de ingestelde fasehoek van de DCO<br />

De maximale g<strong>en</strong>era<strong>to</strong>rstroom I G volgt uit:<br />

I<br />

G<br />

=<br />

R<br />

N<br />

ΔU<br />

• cosΦ + X<br />

N<br />

• sin Φ<br />

Het schijnbare vermog<strong>en</strong> S G van de g<strong>en</strong>era<strong>to</strong>r volgt dan uit:<br />

S<br />

G<br />

= I<br />

G G<br />

• U • 3<br />

Als rek<strong>en</strong>voorbeeld nem<strong>en</strong> we RMU “Tammingaborg 16”. De vraag is hoeveel DCO-vermog<strong>en</strong> op die<br />

locatie zou kunn<strong>en</strong> word<strong>en</strong> aangeslot<strong>en</strong>.<br />

We berek<strong>en</strong> eerst de hoogste <strong>net</strong>spanning op het knooppunt, zie figuur 24 (10495 V ). De hoogste<br />

<strong>net</strong>spanning wordt verkreg<strong>en</strong> bij de hoogste spanning op de 10 kV-rail (10,65 kV) in combinatie <strong>met</strong> de<br />

laagste <strong>net</strong>belasting (gelijktijdigheid knooppunt<strong>en</strong> 0,2) <strong>en</strong> de maximale opwekking van de overige<br />

DCO. Zie figuur 24.<br />

10,496 kV<br />

10,509 kV<br />

Tammingaborg 16<br />

10 kV<br />

U: 10,495 kV<br />

U: 1,050 pu<br />

hoek: -0,229 °<br />

P: 51 kW<br />

Q: 24 kvar<br />

I: 3 A<br />

P: 51 kW<br />

Q: 27 kvar<br />

I: 3 A<br />

trafo 1<br />

P: 0 kW<br />

Q: 3 kvar<br />

I: 0 A<br />

U: 398 V<br />

Figuur 24<br />

De “spanningsruimte” t<strong>en</strong> behoeve van DCO bedraagt: 11000 – 10495 = 505 V.


34 09-011 pmo<br />

Dan berek<strong>en</strong><strong>en</strong> we de kortsluitweerstand- <strong>en</strong> reactantie <strong>met</strong> <strong>Vision</strong> <strong>met</strong> behulp van het subm<strong>en</strong>u<br />

“Berek<strong>en</strong><strong>en</strong>-IEC 60909” het minimale kortsluitvermog<strong>en</strong> via “IEC 60909”. Zie figuur 25.<br />

Tammingaborg 16<br />

10 kV<br />

Ik": 1,93 kA<br />

R/X: 2,205<br />

Sk": 33,3 MVA<br />

Ri: 2731 mOhm<br />

Xi: 1239 mOhm<br />

tmax: 0,000 s<br />

1925 A 0 A<br />

0 A<br />

trafo 1<br />

Ik: 1,92 kA<br />

Figuur 25<br />

Uit figuur 25 blijkt dat de kortsluitweerstand R N = 2,731 Ω <strong>en</strong> de kortsluitreactantie X N = 1,239 Ω.<br />

Verder is gegev<strong>en</strong> dat de nominale cos Ф 0,8 bedraagt, dus sin Ф = 0,6. U G = 10,5 kV.<br />

De maximale g<strong>en</strong>era<strong>to</strong>rstroom I G volgt uit:<br />

I<br />

ΔU<br />

• cosΦ + X<br />

505<br />

=<br />

=<br />

= 172,<br />

G<br />

R<br />

5<br />

N<br />

N<br />

• sin Φ 2,731•<br />

0,8 + 1,239 • 0,6<br />

Het schijnbare vermog<strong>en</strong> S G van de g<strong>en</strong>era<strong>to</strong>r volgt dan uit:<br />

A<br />

SG = I<br />

G<br />

• U<br />

G<br />

• 3 = 172,5 • 10,5 • 3 = 3137kVA<br />

Het tabblad “G<strong>en</strong>era<strong>to</strong>r” van de synchrone g<strong>en</strong>era<strong>to</strong>r is in figuur 26 weergegev<strong>en</strong>.<br />

Figuur 26<br />

Tabblad g<strong>en</strong>era<strong>to</strong>r


35 09-011 pmo<br />

Voor Q MAX geldt: Q MAX = S G x sinФ = 3137 x 0,6 = 1882 kvar (lever<strong>en</strong> blindvermog<strong>en</strong>).<br />

Voor Q MIN geldt: Q MIN = -Q MAX = -1882 kvar (capacitief)<br />

Op het tabblad “Algeme<strong>en</strong>” (niet afgebeeld) wordt voor P REF ingevuld:<br />

P REF = S G x cosФ = 3137 x 0,8 = 2510 kW<br />

De loadflowberek<strong>en</strong>ing levert het volg<strong>en</strong>de resultaat op voor het knooppunt Tammingaborg 16, zie<br />

figuur 27.<br />

10,996 kV<br />

10,775 kV<br />

Tammingaborg 16<br />

10 kV<br />

U: 11,038 kV<br />

U: 1,104 pu<br />

hoek: -0,894 °<br />

P: 2455 kW<br />

Q: 1857 kvar<br />

I: 161 A<br />

P: 2510 kW<br />

Q: 1882 kvar<br />

I: 164 A<br />

P: 0 kW<br />

Q: 3 kvar<br />

I: 0 A<br />

P: 55 kW<br />

Q: 28 kvar<br />

I: 3 A<br />

trafo 1<br />

G<br />

U: 419 V<br />

Figuur 27<br />

Loadflowberek<strong>en</strong>ing bij maximale DCO<br />

De berek<strong>en</strong>de <strong>net</strong>spanning bedraagt iets meer dan 11 kV. Dit wordt veroorzaakt door e<strong>en</strong> kleine<br />

verwaarlozing in de formule voor de <strong>to</strong>elaatbare spanningsverhoging, namelijk de kleine<br />

faseverschuiving tuss<strong>en</strong> fase- <strong>en</strong> g<strong>en</strong>era<strong>to</strong>rspanning. Zie ook paragraaf 1.3 figuur 8. Ook is e<strong>en</strong> kleine<br />

belasting (3 A) aanwezig op het betreff<strong>en</strong>de knooppunt.<br />

Door middel van de “try & error” - <strong>met</strong>hode <strong>met</strong> <strong>Vision</strong> kan het g<strong>en</strong>era<strong>to</strong>rvermog<strong>en</strong> word<strong>en</strong> bepaald<br />

waarbij de <strong>net</strong>spanning exact 11 kV is; in dit voorbeeld 2900 kVA.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!