<strong>Mounting</strong> <strong>Instruction</strong><br />
MIC 60 1+1<br />
1. Mount the valve unit (1) as shown in the diagram.<br />
2. Install the high pressure hoses according to the instruction packed together with the high pressure hoses.<br />
IMPORTANT!<br />
Do not assemble without the gaskets. All washers are included when you order a complete manifold.<br />
Tighten all connections. Check all connections with TL4 leak detection spray.<br />
NOTICE!<br />
Use screws and bolts of stainless steel when mounting valve unit, connecting pipes, and cylinder brackets.<br />
MIC 60 2+2<br />
1. Mount the valve unit (1) as shown in the diagram.<br />
2. Fit the coupling pipe (2) to the high pressure filter (3).<br />
3. Fit the shut-off valves (5) to the connecting pipes (4). Remove the high pressure filter (A) from valve (B), this<br />
provides access to the upper hole of the bracket (G). Note! Use the spanner on the upper hexagon. Fit the adaptor<br />
(D) to the inlet connection (E) on the connecting pipe (6). Fit the shut-off valve (B) to the connecting pipe<br />
with the help of the coupling nut (F). To ensure correct location of the gasket between adaptor (D) and shut-off<br />
valve (B), turn the connecting pipe with the adaptor faced upwards and place the gasket on to the adaptor. Attach<br />
the coupling nut (F) and turn it 1-2 turns. Assemble the valve with the coupling nut and tighten the valve<br />
until it meets the gasket. Do not assemble without the gasket!<br />
4. Fit the assembled connecting pipe to the coupling pipe (2) and mark for the mounting holes. Dismount<br />
the connecting pipe and drill the holes. Assemble the connecting pipe to the coupling pipe, and mount to<br />
the wall using the connecting pipe brackets.<br />
5. Mount the high pressure filters (A) to the shut-off valves (B). Note! Use the spanner on the upper hexagon face<br />
only.<br />
6. Install the blind plugs (6) on the ends of the connecting pipes.<br />
7. Install the high pressure hoses according to the instruction packed together with the high pressure hoses.<br />
IMPORTANT!<br />
Do not assemble without the gaskets. All washers are included when you order a complete manifold.<br />
Tighten all connections. Check all connections with TL4 leak detection spray.<br />
NOTICE!<br />
Use screws and bolts of stainless steel when mounting valve unit, connecting pipes, and cylinder brackets.<br />