Konfigurasjon<br />

• Hafslund nett trafo 1600 kVA<br />

• Egen generator 325 kVA<br />

• Online UPS anlegg 2 x 200 kVA<br />

• ”Enkel” omkoblingsautomatikk mellom nett<br />

og generator<br />

• Aktive harmoniske filtre<br />

AFHFL2<br />

Phase A Voltage<br />

SS Wave<br />

Volts<br />

% Fund<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

0<br />

Hovedtavle<br />

May 05, 1999 at 16:02:46 Local<br />

-100<br />

-200<br />

-300<br />

-400<br />

0 2.5 5 7.5 10 12.5 15 17.5 20<br />

0<br />

400<br />

300<br />

Fund 229.9<br />

200<br />

100<br />

RMS 230.3<br />

CF 1.369<br />

Min -315.3<br />

Max 313.1<br />

THD 6.017<br />

Time (mSeconds)<br />

HRMS13.83<br />

TIF/IT 14.34<br />

0 20 40 60 80 100 120 140<br />

Harmonic<br />

Electrotek<br />

20