<strong>LE</strong>-<strong>System</strong><br />

DANSK<br />

Bemærk!<br />

Den ønskede funktion, undgåelse af dråbedannelse, kan<br />

kun opnås ved anvendelse af både <strong>LE</strong>-pumpe og <strong>LE</strong>-dyse<br />

eller <strong>LE</strong>-ventil.<br />

<strong>LE</strong>-pumper har en anden typebetegnelse end standard<br />

BFP 21 pumper, f.eks. BFP 21 L3 <strong>LE</strong>, og adskiller sig ved at<br />

have en indbygget nippel med returventil og en omstillingsskrue.<br />

Bemærk! Standard BFP 21 pumper kan ikke ombygges til<br />

BFP 21 <strong>LE</strong>-pumper!<br />

<strong>LE</strong>-funktion<br />

Drejes omstillingsskruen venstre om mod stop, er<br />

<strong>LE</strong>-funktionen indkoblet. Drejes omstillingsskruen højre<br />

om mod stop, er <strong>LE</strong>-funktionen udkoblet, og pumpen<br />

fungerer som en standard BFP 21 pumpe.<br />

<strong>LE</strong>-funktionen skal udkobles, hvis:<br />

- <strong>LE</strong>-dysen erstattes af en standard dyse<br />

- <strong>LE</strong>-ventilen fjernes<br />

Forfilter<br />

<strong>LE</strong>-systemer kræver et effektivt <strong>for</strong>filter:<br />

<strong>LE</strong>-1 system: Maks. 40 µm<br />

<strong>LE</strong>-2 system: Standard <strong>for</strong>filter<br />

Tekniske data<br />

Olietyper: Standard fyringsolie og fyringsolie iht.<br />

DIN V 51603-6 EL A Bio 10<br />

Viskositetsområde 1,8-12,0 mm 2 /s (cSt.)<br />

Omdrejningstal 2400-3450 min –1<br />

Trykområde 7-15 bar (kPa 10 2 )<br />

Fabriksindstilling 10 bar (kPa 10 2 )<br />

Spolespænding 220/240 V, 50/60 Hz<br />

Spolens kapsling IP 40<br />

Medietemperatur 0 til 70° C<br />

Ved <strong>LE</strong>-1 system er der et trykfald over <strong>LE</strong>-dysen på 1,6<br />

bar, som der skal korrigeres <strong>for</strong> ved indstilling af pumpetrykket.<br />

Eksempel:<br />

Ønsket dysetryk 10,0 bar (kPa 10 2 )<br />

Pumpetryk: 10,0 + 1,6 bar = 11,6 bar (kPa 10 2 )<br />

Ved <strong>LE</strong>-2 system er der et trykfald over <strong>LE</strong>-ventilen på<br />

maks. 0,1 bar.<br />

Pumpetrykket behøver der<strong>for</strong> ikke at blive korrigeret.<br />

Udluftning<br />

Udluftning af oliepumpen er kun nødvendig ved 1-strengs<br />

anlæg. Udluftning <strong>for</strong>etages gennem manometerstudsen<br />

P! Ved 2-strengs anlæg udlufter pumpen automatisk gennem<br />

returledningen.<br />

Filterskift (fig. 2)<br />

Filterproppen i dækslet skrues ud med en 4 mm nøgle og<br />

patronfilteret trækkes ud. Sæt evt. en skruetrækker imellem<br />

filter og prop og vrid <strong>for</strong>sigtigt filteret af. Filteret kasseres<br />

og erstattes med et nyt, som presses på proppen!<br />

Patronfilteret genmonteres og spændes let til.<br />

Husk udskiftning af O-ring.<br />

Omstilling fra 1- og 2-strengs drift (fig. 3)<br />

Sugeledningslængder i meter<br />

Tabellerne gælder <strong>for</strong> en standard fyringsgasolie (Heizöl-<br />

EL) normal handelskvalitet iht. gældende normer.<br />

Ved igangsætning af et anlæg med tomt rørsystem bør<br />

oliepumpen ikke køre uden olie i mere end 5 minutter.<br />

Henvisning!<br />

Oliepumperne er kun beregnet <strong>for</strong> anvendelse på oliebrændere.<br />

Maks. tilladeligt tryk på suge- og returside: 1,5 bar<br />

Bemærk venligst at magnetventil og <strong>LE</strong>-ventil skal<br />

udskiftes efter 250.000 koblinger eller 10 år (godkendt<br />

<strong>for</strong>ventet levetid)<br />

<strong>LE</strong>-<strong>System</strong><br />

ENGLISH<br />

Note!<br />

The required function, avoiding drop <strong>for</strong>mation, can only<br />

be achieved by using the <strong>LE</strong> pump together with an <strong>LE</strong><br />

nozzle or an <strong>LE</strong> valve.<br />

<strong>LE</strong> pumps have been given a new type designation e.g. BFP<br />

21 L3 <strong>LE</strong> and differ from standard BFP 21 pumps by having<br />

a built-in return valve with changeover screw.<br />

Note! Standard BFP 21 pumps cannot be converted to<br />

BFP 21 <strong>LE</strong> pumps!<br />

<strong>LE</strong> function<br />

If the changeover screw is turned to the left towards stop,<br />

the <strong>LE</strong> function is engaged. If the change over screw is<br />

turned to the right to stop, the <strong>LE</strong> function is disengaged<br />

and the pump will function as a standard BFP 21 pump.<br />

The <strong>LE</strong> function must be disengaged if:<br />

- A standard nozzle is used instead of an <strong>LE</strong> nozzle.<br />

- The <strong>LE</strong> valve is removed.<br />

Prefilter<br />

The <strong>LE</strong>-1 system requires an effective prefilter:<br />

<strong>LE</strong>-1 system: Max. 40 μm<br />

<strong>LE</strong>-2 system: Standard prefilter<br />

Technical data<br />

Oil types: Standard fuel gas oil and fuel gas oil acc.<br />

to DIN V 51603-6 EL A Bio 10<br />

Viscosity range: 1,8-12,0 mm 2 /(cSt)<br />

Speed: 2400-3450 min –1<br />

Pressure range 7-15 bar (kPa 10 2 )<br />

Factory setting 10 bar (kPa 10 2 )<br />

Coil voltage: 220/240 V, 50/60 Hz<br />

Coil enclosure IP 40<br />

Temperature of medium: 0 to 70° C<br />

There is a pressure drop in the <strong>LE</strong> nozzle of 1.6 bar which<br />

needs to be compensated <strong>for</strong> by adjusting the pump<br />

pressure.<br />

Example:<br />

Required nozzle pressure 10.0 bar (kPa 10 2 )<br />

Pump pressure: 10.0 + 1.6 bar = 11.6 bar (kPa 10 2 )<br />

In the <strong>LE</strong>-2 system, there is a pressure drop of max. 0.1 bar<br />

across the <strong>LE</strong> valve.<br />

The pump pressure does not need to be adjusted.<br />

Bleeding of the oil pump may be necessary with 1-pipe<br />

systems. Use the pressure gauge connection P <strong>for</strong> bleeding!<br />

On 2-pipe systems the pump is automatically bleed<br />

through the return pipe.<br />

Filter replacement (fig. 2)<br />

Unscrew the filter plug in the cover with a 4 mm key and<br />

pull out the cartridge filter. Carefully twist the filter out (if<br />

necessary insert a screwdriver between filter and plug).<br />

Scrap the filter and press a new filter onto the plug!<br />

Reassemble the cartridge filter and tighten it lightly.<br />

Don’t <strong>for</strong>get to replace the O-ring.<br />

Conversion from 1 to 2-pipe operation (fig. 3)<br />

Suction line lengths in meters<br />

The table is applicable <strong>for</strong> a standard gas oil (Heizöl-EL) of<br />

normal commercial quality in accordance with applicable<br />

standards.<br />

When starting a system with an empty pipe, the oil pump<br />

should not operate without oil <strong>for</strong> more than 5 min. Assuming<br />

that the pump contains some oil be<strong>for</strong>e starting up.<br />

Attention<br />

The oil pumps are used only <strong>for</strong> oil burners.<br />

Max. permissible pres. on suction/return side: 1.5 bar<br />

Please note that the solenoid valve and the <strong>LE</strong>-valve<br />

must be replaced after 250.000 operations or 10 years<br />

(approved life expectancy).<br />

<strong>LE</strong>-<strong>System</strong><br />

DEUTSCH<br />

Achtung<br />

Der er<strong>for</strong>derliche Betrieb ohne Tropfenbildung wird nur<br />

durch kombinierten Einsatz der <strong>LE</strong>-Pumpe mit einer <strong>LE</strong>-<br />

Düse oder einem <strong>LE</strong>-Ventil erreicht.<br />

<strong>LE</strong>-Pumpen verfügen über eine neue Typenkennzeichnung<br />

z. B. „BFP 21 L3 <strong>LE</strong>“ und unterscheiden sich von Standard-<br />

BFP-21-Pumpen durch ein eingebautes Rückschlagventil<br />

mit Umstellungsschraube.<br />

Hinweis! Standard-BFP-21-Pumpen können nicht in BFP-<br />

21-<strong>LE</strong>-Pumpen umgerüstet werden.<br />

<strong>LE</strong>-Funktion<br />

Wenn die Umstellungsschraube bis zum Anschlag nach<br />

links gedreht wird, wird die <strong>LE</strong>-Funktion aktiviert. Wenn<br />

die Umstellungsschraube bis zum Anschlag nach rechts<br />

gedreht wird, wird die <strong>LE</strong>-Funktion deaktiviert, und die<br />

Pumpe arbeitet als Standard-BFP-21-Pumpe.<br />

In folgenden Fällen muss die <strong>LE</strong>-Funktion deaktiviert<br />

werden:<br />

- Anstelle einer <strong>LE</strong>-Düse wird eine Standarddüse<br />

verwendet.<br />

- Das <strong>LE</strong> Ventil im Ölvorwärmer wurde entfernt.<br />

Vorfilter<br />

Für das <strong>LE</strong>-1-<strong>System</strong> ist ein effektiver Vorfilter<br />

er<strong>for</strong>derlich:<br />

<strong>LE</strong>-1-<strong>System</strong>: Max. 40 μm<br />

<strong>LE</strong>-2-<strong>System</strong>: Standard-Vorfilter<br />

Technische Daten<br />

Öltypen: Standard Heizöl und Heizöl gemäβ<br />

DIN V 51603-6 EL A Bio 10<br />

Viskositätsbereich 1,8-12,0 mm 2 /(cSt)<br />

Drehzahl 2400-3500 min –1<br />

Druckbereich 7-15 bar (kPa 10 2 )<br />

Werkseinstellung 10 bar (kPa 10 2 )<br />

Spulenspannung 220/240 V, 50/60 Hz<br />

Schutzart der Spule IP 40<br />

Medientemperatur 0 bis 70° C<br />

In der <strong>LE</strong>-Düse fällt der Druck um 1,6 bar ab. Dieser<br />

Druckabfall muss durch Anpassung des Pumpendrucks<br />

ausgeglichen werden.<br />

Beispiel:<br />

Er<strong>for</strong>derlicher Düsendruck: 10,0 bar (kPa 10 2 )<br />

Pumpendruck: 10,0 + 1,6 bar = 11,6 bar (kPa 10 2 )<br />

Im <strong>LE</strong>-2-<strong>System</strong> fällt der Druck im <strong>LE</strong>-Ventil um maximal<br />

0,1 bar ab.<br />

Eine Anpassung des Pumpendrucks ist nicht er<strong>for</strong>derlich.<br />

Entlüftung<br />

Die Entlüftung der Ölpumpe ist nur bei Einstranganlagen<br />

notwendig. Die Entlüftung wird durch den<br />

Manometerstutzen P vorgenommen. In Zweistranganlagen<br />

entlüftet die Pumpe automatisch über die<br />

Rücklaufleitung.<br />

Filterwechsel (Abb.2)<br />

Filterschraube im Deckel mit einem 4 mm Inbus-<br />

Schlüssel lösen und Patronenfilter heraus ziehen.<br />

Evtl. einen Schraubendreher zwischen Filter und<br />

Schraube zum Lösen des Filters stecken. Einen<br />

neuen Filter auf die Schraube pressen! Patronenfilter<br />

montieren und leicht anziehen.<br />

Wechseln des O-Ringes nicht vergessen.<br />

Umstellung von Ein- auf Zweistrangbetrieb<br />

(Abb.3).<br />

Saugrohrlängen in Meter<br />

Die Tabellen sind für Qualitätsheizöl (Heizöl-EL)<br />

einer normalen Handelsqualität nach geltenden<br />

Normen gültig.<br />

Bei der Inbetriebnahme einer Anlage mit leerem<br />

Rohrsystem sollte die Ölpumpe nicht länger als 5<br />

Minuten ohne Öl betrieben werden, vorausgesetzt,<br />

dass vor der Inbetriebnahme Öl in der Pumpe ist.<br />

Hinweis!<br />

Die Ölpumpen sind ausschließlich für Ölbrenner<br />

vorgesehen!<br />

Max. zul. Druck auf Saug-u.Rucklaufseite:1,5 bar<br />

Achtung: Das NC-Magnetventil und das <strong>LE</strong> Ventil im<br />

Ölvorwärmer müssen nach 250.000 Schaltungen oder<br />

10 Jahren ausgetauscht werden (geprüfte Lebensdauererwartung).