Jordfeilautomat Type B<br />

Jordfeilautomat Type B NK - 3 + N , C-Kar<br />

El.nr. Varenavn Art.Nr Feilstrøm Type Ant.Pol Ant. mod Strøm Pakning<br />

16 048 28 FIC JFB/AUT 16A 3+N 30 mA B NK 09958224 30 mA B 3 + N 6 16 A 1/1<br />

16 062 50 FIC4 JFB/AUT 32A 3+N 30 mA B NK 09958227 30 mA B 3 + N 6 32 A 1/1<br />

16 048 29 FIC4 JFB/AUT 32A 3+N/300mA B NK 09958237 300 mA B 3 + N 6 32 A 1/1<br />

Tilkoplingsklemmer<br />

Kabeltverrsnitt 1 x 1 - 25 mm² Tiltrekking 2 Nm - 2.4 Nm<br />

Tekniske data<br />

Kortslutningsstrøm<br />

6 kA<br />

Utløsetid<br />

1 x I∆n ≤ 300 ms; 5 x I∆n ≤ 40 ms<br />

Forsinket utløsning<br />

10ms<br />

<strong>No</strong>minell spenning Un 230 V ~ Un + / - 10%<br />

<strong>No</strong>minell Frekvens<br />

50 Hz<br />

Utløserkaratristikk<br />

C<br />

Utløserfrekvense<br />

0 Hz ... 100000 Hz<br />

Støtstrømsstyrke<br />

3 kA<br />

Omgivelsestempratur<br />

- 25° C til + 40° C<br />

Beskyttelsesart<br />

IP20 (front: IP40)<br />

<strong>No</strong>rmer VDE 0664, EN 62423, EN 61009<br />

Jordfeilautomat Type B NK - 2 pol, C-Kar<br />

El.nr. Varenavn Art.Nr Feilstrøm Type Ant.Pol Ant. mod Strøm Pakning<br />

16 062 59 DRCBO JFB/AUT 10A 2P 30mA B SK 09959422 30 mA B 2 5 10 A 1/1<br />

16 062 51 DRCBO JFB/AUT 16A 2P 30mA B SK 09959424 30 mA B 2 5 16 A 1/1<br />

16 062 52 DRCBO JFB/AUT 32A 2P 30mA B SK 09959427 30 mA B 2 5 32 A 1/1<br />

Type B SK<br />

10000<br />

Tilkoblingsklemmer<br />

Kabeltverrsnitt 1 x 1 - 25 mm² Tiltrekning 2 Nm ... 2.4 Nm<br />

Frequency band I<br />

Frequency band II<br />

Frequency band III<br />

(b) Fire protection limit<br />

(limit for Protection level 2)<br />

Tripping current (mA)<br />

1000<br />

I 500 mA<br />

I 300 mA<br />

100<br />

(c) Danger limit for currents passing<br />

through the human body<br />

(limit for Protection Level 3)<br />

ID 30 mA<br />

10<br />

0,1 1 10 100 1000 10000 100000<br />

Frequency (Hz)<br />

Type B NK<br />

1000<br />

Frequency band I<br />

Frequency band II<br />

Frequency band III<br />

(b) Fire protection limit<br />

(limit for Protection level 2)<br />

I 500 mA<br />

1 3<br />

I 300 mA<br />

87,5<br />

Tripping current (mA)<br />

100<br />

(c) Danger limit for currents passing<br />

through the human body<br />

(limit for Protection Level 3)<br />

I 30 mA<br />

10<br />

0,1 1 10 100 1000 10000 100000<br />

Frequency (Hz)<br />

2 4<br />

LAREL - Borgeskogen 8 - 3160 Stokke<br />

Telefon 33 38 19 00 - Epost: post@larel.no - www.larel.no<br />

Side 3