19.12.2013 Views

Multi Split Inverter Modular VRF Set Free Eco Flex Série ... - Hitachi

Multi Split Inverter Modular VRF Set Free Eco Flex Série ... - Hitachi

Multi Split Inverter Modular VRF Set Free Eco Flex Série ... - Hitachi

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

16<br />

PROCEDIMENTO PARA VERIFICAÇÃO DAS INFORMAÇÕES, ATRAVÉS DO<br />

DISPLAY DE 7 SEGMENTOS DA UNDADE EXTERNA<br />

1) ACESSO AOS PARÂMETROS DA CONEXÃO<br />

(CP, 0AA, ICP, IAA, GA, OP, HT, UJ)<br />

3) ACESSO AOS PARÂMETROS DAS UNID. EXTERNAS<br />

LEMBRE-SE QUE A NUMERAÇÃO DAS UNIDADES EXTERNAS SÃO 0d00 (CD00),<br />

OBJETIVO: NAVEGAR ATÉ SER EXIBIDO NO DISPLAY "OCP"<br />

0d02 (CD02), 0d03 (CD03)<br />

1 PRESSIONE PSW1(POR MAIS DE 3 SEGUNDOS)<br />

OBJETIVO: NAVEGAR ATÉ SER EXIBIDO NO DISPLAY "0d00"<br />

2 APARECE NO DISPLAY "CHEC"<br />

1 PRESSIONE PSW1 (POR MAIS DE 3 SEGUNDOS)<br />

3 PRESSIONE PSW1 NOVAMENTE<br />

2 APARECE NO DISPLAY "CHEC"<br />

4 APARECE NO DISPLAY "Prto"<br />

3 PRESSIONE PSW1 NOVAMENTE<br />

5 PRESSIONE PSW4<br />

4 APARECE NO DISPLAY "Prto"<br />

6 APARECE NO DISPLAY "CAPA"<br />

5 PRESSIONE PSW4<br />

7 PRESSIONE PSW3<br />

6 APARECE NO DISPLAY "CAPA"<br />

8 APARECE O PRIMEIRO DADO A SER LIDO "0CP"<br />

7 PRESSIONE PSW4<br />

9 PRESSIONE PSW4 PARA OBTER VALOR "0CP"<br />

8 APARECE NO DISPLAY "0dUT"<br />

10<br />

CONTINUE PRESSIONANDO PSW4 PARA REALIZAR AS<br />

9 PRESSIONE PSW3<br />

LEITURAS DOS DEMAIS PARÂMETROS<br />

10 APARECE NO DISPLAY "0d00" (CD00)<br />

11 PRESSIONE PSW3<br />

2) ACESSO AOS PARÂMETROS DAS UNID. INTERNAS<br />

(CA, ie, TL , TG, Ti, To, di)<br />

12<br />

13<br />

APARECE NO DISPLAY "CA0"<br />

PRESSIONE PSW4 PARA OBTER VALOR "CA0"<br />

CONTINUE PRESSIONANDO PSW4 PARA OBTER OS<br />

LEMBRE-SE QUE A PORTA DE ENTRADA PARA LEITURA DAS UNIDADES 14<br />

INTERNAS PARA OS DADOS ACIMA É O ITEM id0---, id01(UI01), id02(UI02), id03<br />

DEMAIS DADOS DA UNIDADE EXTERNA "CA00"<br />

(UI03), Id04 (UI04) .....<br />

QUANDO "id00" ESTIVER SENDO EXIBIDO NO DISPLAY<br />

15<br />

OBJETIVO: NAVEGAR ATÉ SER EXIBIDO NO DISPLAY "id01"<br />

NOVAMENTE PRESSIONE PSW4<br />

1 PRESSIONE PSW1 (POR MAIS DE 3 SEGUNDOS)<br />

16 APARECE NO DISPLAY "0d02" (CD02)<br />

2 APARECE NO DISPLAY "CHEC"<br />

PRESSIONE PSW3 E COMEÇE A REALIZAR AS LEITURAS<br />

17<br />

3 PRESSIONE PSW1 NOVAMENTE<br />

DOS DADOS DA UNIDADE EXTERNA "CD02"<br />

4 APARECE NO DISPLAY "Prto"<br />

ADOTE O MESMO PROCEDIMENTO PARA OBTER OS<br />

18<br />

5 PRESSIONE PSW4<br />

DADOS DA UNIDADE EXTERNA "CD03"<br />

6<br />

7<br />

8<br />

9<br />

APARECE NO DISPLAY "CAPA"<br />

PRESSIONE PSW4<br />

APARECE NO DISPLAY "0dUT"<br />

PRESSIONE PSW4<br />

4) ACESSO AO HISTÓRICO DE ALARMES EXIBIDOS<br />

NA UNIDADE EXTERNA<br />

LEMBRE-SEALARME 01 SERÁ O MAIS RECENTE<br />

10 APARECE NO DISPLAY "idUT"<br />

(MÁXIMO 15 ÚLTIMAS OCORRÊNCIAS)<br />

11 PRESSIONE PSW3<br />

12 APARECE NO DISPLAY "id01"<br />

OBJETIVO: NAVEGAR ATÉ SER EXIBIDO NO DISPLAY "ACHi"<br />

13<br />

14<br />

15<br />

16<br />

17<br />

18<br />

19<br />

20<br />

21<br />

PRESSIONE PSW3<br />

APARECE NO DISPLAY "CA01"<br />

PRESSIONE PSW4<br />

APARECE NO DISPLAY O VALOR DO "CA01"<br />

PRESSIONE PSW4<br />

APARECE NO DISPLAY "ie01"<br />

PRESSIONE PSW4<br />

APARECE NO DISPLAY O VALOR DO "ie01"<br />

REPITA O PROCEDIMENTO NESTES PARÂMETROS ATÉ<br />

QUE SEJA EXIBIDO O ÚLTIMO PARÂMETRO DA UNIDADE<br />

INTERNA 01<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

PRESSIONE PSW1 (POR MAIS DE 3 SEGUNDOS)<br />

APARECE NO DISPLAY "CHEC"<br />

PRESSIONE PSW1 NOVAMENTE<br />

APARECE NO DISPLAY "Prto"<br />

PRESSIONE PSW4<br />

APARECE NO DISPLAY "CAPA"<br />

PRESSIONE PSW4<br />

APARECE NO DISPLAY "0duT"<br />

PRESSIONE PSW4<br />

APARECE NO DISPLAY "iduT"<br />

PRESSIONE PSW4<br />

22<br />

QUANDO TERMINAR A COLETA DE TODOS OS DADOS DA<br />

12 APARECE NO DISPLAY "Accd"<br />

UNIDADE INTERNA 01 O ITEM "id01" VOLTARÁ A SER<br />

EXIBIDO NO DISPLAY<br />

13 PRESSIONE PSW4<br />

23<br />

24<br />

25<br />

26<br />

PRESSIONE PSW5 PARA NAVEGAR ATÉ O "id02" (UI02)<br />

APARECE NO DISPLAY "id02"<br />

PRESSIONE PSW3<br />

APARECE NO DISPLAY "CA02"<br />

14<br />

15<br />

16<br />

17<br />

APARECE NO DISPLAY "ACHi"<br />

PRESSIONE PSW3<br />

APARECERÁ NO DISPLAY " Nº01" (Alarme 01)<br />

PRESSIONE PSW3 E OBTENHA CÓDIGO DO ALARME "Nº01"<br />

27 PRESSIONE PSW4<br />

QUANDO O CÓDIGO DO ALARME ESTIVER EXIBIDO NO<br />

18<br />

DISPLAY PRESSIONE PSW5<br />

28 APARECE NO VISOR O VALOR DE "CA02"<br />

QUANDO TERMINAR A COLETA DE TODOS OS DADOS DA<br />

19 APARECERÁ NO DISPLAY " Nº01" (Alarme 01) NOVAMENTE<br />

29 UNIDADE INTERNA 02 O ITEM "id02" VOLTARÁ A SER<br />

PRESSIONE PSW4 PARA QUE SEJA EXIBIDO NO<br />

20<br />

EXIBIDO NO DISPLAY<br />

DISPLAY "Nº02"<br />

30 PRESSIONE PSW5 PARA NAVEGAR ATÉ O "id03" (UI03)<br />

31 APARECE NO DISPLAY "id03"<br />

21 PRESSIONE PSW3 E OBTENHA CÓDIGO DO ALARME "Nº02"<br />

32 PRESSIONE PSW3<br />

ADOTE O MESMO PROCEDIMENTO PARA OBTER OS<br />

22<br />

33 APARECE NO DISPLAY "CA03"<br />

DEMAIS ALARMES<br />

34<br />

35<br />

PRESSIONE PSW4<br />

APARECE NO VISOR O VALOR DE "CA03"<br />

QUANDO TERMINAR A COLETA DE TODOS OS DADOS<br />

36 DA UNIDADE INTERNA 03 O ITEM "id03" VOLTARÁ A SER<br />

EXIBIDO NO DISPLAY<br />

37<br />

ADOTE O MESMO PROCEDIMENTO PARA OBTER OS<br />

DADOS DAS DEMAIS UNIDADES INTERNAS (0 a 63 )<br />

84

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!