Руководство пользователя D-500 User Manual Rev_05

Программное обеспечение Firmware V-5.4

0: no e-mail on engine run/stop

1: e-mail sent on engine run/stop

Trend Sample Interval Sec 1 3600 1

WARNING: Available only in color screen models.

This is the pixel period in trend graphics. A short

interval will slide the graphic faster, while a long

interval will slow it down.

Fuel Pulses from MPU input - 0 1 0

0: MPU input is used for engine speed detection

1: MPU input is used for reading the flowmeter pulses

during fuel filling.

Fuel Pulses per Volume - 0 65000 1000

This is the number of pulses produced by the

flowmeter for the unit volume. This parameter is

characteristic of the flowmeter used and should be set

according to the flowmeter data.

Fuel Counter Unit Lt/gal - - liters This is the unit for the fuel counter

SMS on Engine Run/Stop - 0 1 0

This parameter controls SMS sending when the engine

runs or stops. No warnings generated.

0: no SMS on engine run/stop

1: SMS sent on engine run/stop

E-mail on Engine Run/Stop - 0 1 0

This parameter controls e-mail sending when the

engine runs or stops. No warnings generated.

0: no e-mail on engine run/stop

1: e-mail sent on engine run/stop