<strong>EcoZenith</strong> <strong>–</strong> <strong>Parameterlista</strong> <strong>Modbus</strong><br />

Adress: 604 <strong>–</strong> Larmregister 4<br />

Bit Funktion Nr R/W Interv. Variabelnamn i EcoLogic<br />

0 VP2, Pressostat högtryck R A bAlarm_vp2pressHP @ LarmBIT[3].0<br />

1 VP2, Pressostat lågtryck R A bAlarm_vp2pressLP @ LarmBIT[3].1<br />

2 VP2, Motorskydd R A bAlarm_vp2_MS @ LarmBIT[3].2<br />

3 VP2,Givare retur R A bAlarm_vp2_retur @ LarmBIT[3].3<br />

4 VP2, Givare framledning R A bAlarm_vp2_framl @ LarmBIT[3].4<br />

5 VP2, Givare ute R A bAlarm_vp2_ute @ LarmBIT[3].5<br />

6 VP2, Givare brine ut R A bAlarm_vp2_brineut @ LarmBIT[3].6<br />

7 VP2, Givare brine in R A bAlarm_vp2_brinein @ LarmBIT[3].7<br />

8 VP2, Givare hetgas R A bAlarm_vp2_hetgas @ LarmBIT[3].8<br />

9 VP2, Hög hetgastemperatur R A bAlarm_vp2_highHG @ LarmBIT[3].9<br />

10 VP2, Fel fasföljd R A bAlarm_vp2_fasfel @ LarmBIT[3].10<br />

11 VP2, Låg brinetemperatur R A bAlarm_vp2_lowBr @ LarmBIT[3].11<br />

12 VP2, Hög brinetemperatur R A bAlarm_vp2_highBr @ LarmBIT[3].12<br />

13 VP2, Hög diff brine R A bAlarm_vp2_diffBr @ LarmBIT[3].13<br />

14 VP2, Givare avfrostning 1 R A bAlarm_vp2_giv115 @ LarmBIT[3].14<br />

15 VP2, Givare avfrostning 2 R A bAlarm_vp2_giv116 @ LarmBIT[3].15<br />