1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
Capacity kW 162.881
Mean temp.diff. K 15.220
Coefficient kW/K 10.702
Coolant IN ºC 7.000
Coolant OUT ºC 12.000
Capacity partition 1 % 22.576
Capacity partition 2 % 19.796
Capacity partition 3 % 17.358
Capacity partition 4 % 15.221
Capacity partition 5 % 13.346
Capacity partition 6 % 11.703
Air IN
Air OUT
Temperature ºC 34.000 17.000
Rel. Humidity % 33.000 77.547
Abs. Humidity g/kg 12.270 10.494
Density humid kg/m³ 1.018 1.079
Enthalpy humid kJ/kg 65.678 43.677
Volumeflow humid m³/h 26500.000 24963.271
Massflow dry kg/h 26651.917 26651.917
Condensed water kg/h 47.334
Surface temperature ºC 9.600
2) Heating of air
Capacity kW 321.769
Air IN
Air OUT
Temperature ºC -12.000 24.000
Rel. Humidity % 90.000 6.517
Abs. Humidity g/kg 1.337 1.337
Density humid kg/m³ 1.205 1.059
Enthalpy humid kJ/kg -8.759 27.558
Volumeflow humid m³/h 26500.000 30152.945
Massflow dry kg/h 31895.897 31895.897