22.11.2014 Views

Installationssystemer i metal - Viega

Installationssystemer i metal - Viega

Installationssystemer i metal - Viega

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Viega</strong> Anvendelsesteknik Bind I 2. udgave<br />

Anvendelsesteknik<br />

Bind I: <strong>Installationssystemer</strong> i <strong>metal</strong><br />

2. udgave<br />

DK 672 188-972.01 - 11/10<br />

<strong>Viega</strong> A/S<br />

Blokken 36<br />

3460 Birkerød<br />

Tel.: 45 94 29 50<br />

Fax: 45 94 29 69<br />

info@viega.dk<br />

www.viega.dk


Anvendelsesteknik<br />

<strong>Installationssystemer</strong> i <strong>metal</strong><br />

Sanpress, Sanpress Inox, Sanpress Inox G, Profipress, Profipress G, Prestabo<br />

DK 672 188-972.01-11/10<br />

Attendorn, November 2010<br />

© <strong>Viega</strong> GmbH & Co. KG, Attendorn<br />

Alle rettigheder – også mht. enhver form for mangfoldiggørelse – forbeholdes<br />

Udgiver<br />

<strong>Viega</strong> GmbH & Co. KG<br />

Plumbing and heating systems<br />

<strong>Viega</strong> Platz 1<br />

DE-57439 Attendorn<br />

Telefon +49 (0)2722 61-1297<br />

Telefax +49 (0)2722 61-941297<br />

Internet www.viega.com<br />

Indholdet af denne håndbog er uforbindende. Ret til ændringer baseret på ny viden og fremskridt forbeholdes.


<strong>Installationssystemer</strong> i<br />

<strong>metal</strong><br />

Sikkerhed og komfort i systemer<br />

1 Drikkevandsinstallation<br />

2 Varmeteknik<br />

3 Gasinstallation<br />

4 Anvendelse indenfor industri og håndværk<br />

5 Værktøjssystemer


Betjeningsvejledning<br />

De tekniske informationer i denne håndbog beskriver de grundliggende elementer af <strong>Viega</strong> anvendelsesteknologi<br />

inden for <strong>metal</strong>rør-installationssystemer. Derudover baserer informationerne om produkterne, deres egenskaber<br />

og anvendelsesteknik sig på de aktuelle standarder i Europa og/eller i Tyskland.<br />

Afsnit som er markeret med en stjerne (*) svarer til de tekniske regler i Europa/Tyskland. Disse skal forstås som<br />

anbefalinger hvis nationale krav ikke forefindes. Nationale love, standarder, regler, normer og andre tekniske regler<br />

har forrang for tyske/europæiske retningslinier i denne håndbog. De her anvendte informationer er uforbindende<br />

for andre landre og regioner og skal, som nævnt, ses som understøttende.<br />

Attendorn, november 2010


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

1 Drinking water installations<br />

Grundlag<br />

Besparelsespotentialer 15<br />

Projektering 16<br />

Bekendtgørelse vedrørende brugsvand.. . . . . . . . . . . . . . . . . . . . . . . 16<br />

Varmgalvaniserede jernmaterialer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16<br />

Blyrør. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17<br />

Kombination af forskellige materialer* .. . . . . . . . . . . . . . . . . . . . . . . . 17<br />

Forebyggelse/reduktion af kalkdannelse .. . . . . . . . . . . . . . . . . . . . . . 17<br />

Prøveudtagningssteder.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18<br />

<strong>Viega</strong>s rørsystemfilosofi. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19<br />

Visign for Care – hygiejnisk skyllefunktion 20<br />

Rørføring 22<br />

Brandsluknings- og sikringsenheder 22<br />

Rørnetberegning 22<br />

Installation 24<br />

Tæthedsprøvning* 25<br />

Tør tæthedsprøvning.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25<br />

Våd tæthedsprøvning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26<br />

Skylning 26<br />

Regler vedrørende hygiejne ved idriftsætning og<br />

aflevering (Udførendes ansvar) 26<br />

Desinficering 27<br />

Rørsystemers rentabilitet 28<br />

Oversigt over rørsystemer i <strong>metal</strong> 30<br />

Systembeskrivelse<br />

Sanpress Inox / Sanpress Inox XL 31<br />

Anvendelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31<br />

Tekniske data.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32<br />

Sanpress / Sanpress XL 33<br />

Anvendelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33<br />

Tekniske data.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34<br />

Profipress / Profipress XL 35<br />

Anvendelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35<br />

Tekniske data.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36<br />

6


Indholdsfortegnelse<br />

Anvendelsesteknik<br />

Komponenter<br />

Isolering* 37<br />

Isolering af drikkevandsledninger (kolde). . . . . . . . . . . . . . . . . . . . . . 37<br />

Isolering af drikkevandsledninger (varme).. . . . . . . . . . . . . . . . . . . . . 38<br />

Lydisolering 38<br />

Brandbeskyttelse* 39<br />

Længdeudvidelse 40<br />

Længdeudvidelseskompensatorer.. . . . . . . . . . . . . . . . . . . . . . . . . . . . 40<br />

Beregning af længden af kompensationssstykker til rør med<br />

Ø < 54 mm .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42<br />

Længdeudvidelse af rør med Ø > 54 mm.. . . . . . . . . . . . . . . . . . . . . . 44<br />

Axial-Kompensator.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46<br />

Rørfriktion 49<br />

Korrosion af rustfri stålrør forårsaget af klorider 50<br />

Easytop skråsædeventiler 51<br />

Anvendelse sammen med <strong>Viega</strong> presfittingssystemer.. . . . . . . . . 52<br />

Tekniske Data – Udførelser.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53<br />

Isoleringskappe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54<br />

Easytop XL-skråsædeventiler med flangetilslutning.. . . . . . . . . . . . 58<br />

Easytop prøveudtagningsventil* 60<br />

Ventilens konstruktion.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60<br />

Egenskaber.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61<br />

Aktiveringsenhed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61<br />

Særlige tekniske egenskaber.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61<br />

Easytop ligesædeventil til forsænket installation 63<br />

Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63<br />

Tilslutningsvarianter.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63<br />

Ventilens konstruktion.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63<br />

Easytop friløbsventiler til forsænket installation 64<br />

Tekniske data.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64<br />

Fastgøring/tætning.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66<br />

Fastgøring ved hjælp af fastgøringssættet .. . . . . . . . . . . . . . . . . . . . 66<br />

Udstyrssæt.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67<br />

Isoleringskappe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67<br />

Easytop kuglehaner 68<br />

Easytop cirkulationsreguleringsventil 69<br />

Funktion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69<br />

Udførelser.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70<br />

Tilbehør.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70<br />

7


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Smartloop-Inliner cirkulationsledning 71<br />

Anvendelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71<br />

Systembeskrivelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72<br />

Temperaturinddeling.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73<br />

Fordele.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74<br />

Komponenter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75<br />

Montering.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76<br />

Reparationsmuffe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79<br />

<strong>Viega</strong> tætningselementer 80<br />

Blandingsinstallation 81<br />

Isoleringsforskruning 81<br />

Tilslutning varmtvandsbeholder 82<br />

Potentialudligning 82<br />

<br />

Montering<br />

Opbevaring og transport 83<br />

Afkortning af rør 84<br />

Bukning af rør 84<br />

Rørføring og fastgøring 84<br />

Fastgøringsmetoder.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85<br />

Forsænket installation af varme rørledninger.. . . . . . . . . . . . . . . . . . 85<br />

Gevind- og flangetilslutninger 86<br />

Gevindtilslutninger.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86<br />

Flangetilslutninger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86<br />

Etablering af prestilslutningen 87<br />

Metalrør 12 – 54 mm.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87<br />

Sanpress XL 76,1 – 108,0 mm.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89<br />

Sanpress Inox XL og Profipress XL 64,0 – 108,0 mm .. . . . . . . . . . . . 91<br />

Pladsbehov ved presning 93<br />

Rørstørrelse 12 til 54 mm.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93<br />

Rørstørrelser 76,1 til 108,0 mm Presning med XL-kæde til<br />

Sanpress XL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95<br />

Grundregler for idriftsætningen 97<br />

SC-Contur .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97<br />

Desinficering - vejledende og gældende i Tyskland. I<br />

Danmark skal myndighederne altid kontakes. .. . . . . . . . . . . . . . . . . 97<br />

8<br />

Tillæg<br />

Tryktab: Koldt vand i rustfaste rør .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99<br />

Tryktab: Koldt vand i rustfaste rør .. . . . . . . . . . . . . . . . . . . . . . . . . . . . 100<br />

Tryktab: Varmt vand i rustfaste rør. . . . . . . . . . . . . . . . . . . . . . . . . . . . 101<br />

Tryktab: Varmt vand i rustfaste rør. . . . . . . . . . . . . . . . . . . . . . . . . . . . 102<br />

Protokol (eksempel): Skylning med vand.. . . . . . . . . . . . . . . . . . . . . 103


Indholdsfortegnelse<br />

Rapport: Tryktest for drikkevandsinstallationer.. . . . . . . . . . . . . . . 104<br />

Kombination af rør materialer i drikkevandsinstallationer.. . . . . 106<br />

2 Varmeteknik<br />

Rørsystemer af kobber<br />

Profipress – Systembeskrivelse 107<br />

Anvendelse .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107<br />

Tekniske data.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108<br />

Komponenter 109<br />

Rør.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109<br />

Presfittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109<br />

Easytop kuglehaner. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111<br />

Tætningselementer.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112<br />

Anvendelsesteknik 113<br />

Stigledninger 113<br />

Tilbageløbsforskruninger 114<br />

Radiatortilslutning 115<br />

Tilslutning via central gulvfordeler . . . . . . . . . . . . . . . . . . . . . . . . . . . 115<br />

Tilslutning med kryds-T-stykke.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117<br />

Tilslutning med T-stykke.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119<br />

Tilslutning med radiatortilslutningsblok.. . . . . . . . . . . . . . . . . . . . . . 119<br />

Tilslutning med sokkellistetilslutningssæt.. . . . . . . . . . . . . . . . . . . . 121<br />

Adaptersæt til radiatorer.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122<br />

Isolering og udlægning af rørledninger* 123<br />

Isolering mod varmetab* .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123<br />

Varmefordelingsledninger.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124<br />

Rørledninger i gulvet .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125<br />

Eksempler.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125<br />

Blandingsinstallationer 127<br />

Tryktest 127<br />

Tryktest med vand.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127<br />

Tryktest med luft .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127<br />

Fjernvarmeanlæg 128 >><br />

9


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Systembeskrivelse Profipress S-pres fitting 129<br />

Anvendelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129<br />

Solvarmeanlæg 130<br />

Rørføring.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130<br />

Rørmateriale. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130<br />

Skylning.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130<br />

Tryktest .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130<br />

Rørsystemer af stål<br />

Prestabo – Systembeskrivelse 132<br />

Anvendelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132<br />

Tekniske data .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133<br />

Komponenter 134<br />

Rør 134<br />

Mærkning.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135<br />

Opbevaring og transport .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135<br />

Presfittings 136<br />

SC-Contur .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136<br />

Særlige tekniske egenskaber.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136<br />

Tætningselementer 137<br />

EPDM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137<br />

FKM.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137<br />

Anvendelsesteknik 138<br />

Udvendig korrosionsbeskyttelse* 138<br />

Uddrag af DIN 50929 .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138<br />

Indvendig korrosionsbeskyttelse (trefasegrænsen) .. . . . . . . . . . . 138<br />

Isolering og udlægning af rørledninger 139<br />

Isolering mod varmetab 139<br />

Potentialeudligning* 142<br />

Blandingsinstallationer 142<br />

Rørføring og fastgøring 142<br />

Længdeudvidelse 143<br />

Længdeudvidelse af Prestabo rørledninger. . . . . . . . . . . . . . . . . . . 144<br />

Udligning af længdeudvidelser .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145<br />

10<br />

Montering 149<br />

Opbevaring og transport 149<br />

Forarbejdning 149<br />

Afkortning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149<br />

Afisolering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149


Indholdsfortegnelse<br />

Afgratning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150<br />

Bukning.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150<br />

Eksempler på montering 151<br />

Fastgøringsmetoder 152<br />

Forsænket installation 153<br />

Udlægning i støbt gulvbelægning 153<br />

Udlægning i støbeasfaltbelægning 154<br />

Pladsbehov ved presning 155<br />

Rørstørrelser 12 til 54 mm.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155<br />

Rørstørrelser 64,0 – 108,0 – Prestabo XL.. . . . . . . . . . . . . . . . . . . . . . 157<br />

Presning med presringe 12 - 54 mm .. . . . . . . . . . . . . . . . . . . . . . . . . . 158<br />

Udførelse af presforbindelse 12 til 54 mm 159<br />

Etablering af presforbindelse 64,0 til 108,0 mm 162<br />

Tryktest – i Danmark iflg. DS 469 – hér et eksempel jvf.<br />

tyske regler: 164<br />

3 Gasinstallation*<br />

Grundlag<br />

Nationalt forord 165<br />

<strong>Viega</strong>s systemfilosofi 166<br />

Krav til gasstikdåser 167<br />

Systembeskrivelse<br />

Profipress G / Profipress G XL 168<br />

Anvendelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168<br />

Tekniske data.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169<br />

Mærkning af presfittings 170<br />

HTB (højere termisk belastning)-krav 170<br />

Gasanlæg 171<br />

Sanpress Inox G / Sanpress Inox G XL 172<br />

Anvendelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172<br />

Tekniske data.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173<br />

Mærkning af presfittings 174<br />

Pressfittings med SC-Contur 174<br />

>><br />

11


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Montering<br />

Generelle regler for montering af gasledninger 175<br />

Forsænkede installationer 175<br />

Rørføring og fastgøring 176<br />

Udlægning i gulvkonstruktionen 177<br />

Korrosionsbeskyttelse 177<br />

4 Anvendelser inden for<br />

industri og håndværk<br />

Systembeskrivelse<br />

Profipress / Sanpress Inox / Profipress G / Sanpress Inox G / Prestabo 179<br />

Profipress / Profipress G 180<br />

Sanpress Inox / Sanpress Inox XL 182<br />

Prestabo 184<br />

Anvendelsesteknik<br />

SC-Contur – DVGW-kontrolleret sikkerhed 185<br />

Flangetilslutninger 187<br />

Anvendelsesområder<br />

Trykluftanlæg 187<br />

Kølevandsanlæg 189<br />

Procesvandsanlæg 190<br />

Anlæg til tekniske gasser 191<br />

Lavtryksdampanlæg 193<br />

Anvendelse i skibsbyggeri 193<br />

Profipress / Sanpress Labs-frei 194<br />

Easytop kuglehaner 195<br />

Oversigt over anvendelsesmuligheder 196<br />

Spørgeskema til materialebestandighed 197<br />

12


Indholdsfortegnelse<br />

5 Værktøjssystemer<br />

Systembeskrivelse<br />

Anvendelse.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199<br />

Pressguns 200<br />

Pressgun 4 E 230 V 200<br />

Pressgun 4 B 201<br />

Pressgun Picco 202<br />

Anvendelse af presværktøjer af andre mærker 202<br />

Tilbehør 203<br />

Presværktøj 204<br />

Presringe med led/kardan funktion 204<br />

Til <strong>Viega</strong> rørledningssystemer af <strong>metal</strong>.. . . . . . . . . . . . . . . . . . . . . . . 204<br />

Til XL presfittings.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204<br />

Preskæder / Presbakker 205<br />

Preskæde med trækbakke .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205<br />

Presbakker .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205<br />

Picco presbakker .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205<br />

Serviceanvisninger<br />

Presmaskiner 206<br />

Presringe / Presbakker 206<br />

Værktøjsservice 207<br />

Index 208<br />

13


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

1 Drikkevandsinstallation<br />

Grundlag<br />

Sundt drikkevand er en forudsætning for vores sundhed. Det indeholder nødvendige<br />

mineraler og er uundværligt ved tilberedning af fødevarer, til rengøring og til kropspleje.<br />

Konstruktører, installatører og leverandører har det fælles mål, at der skal være<br />

drikkevand til rådighed i tilstrækkelig mængde og kvalitet alle steder, hvor der tappes<br />

vand. Drikkevand er imidlertid også et let fordærveligt levnedsmiddel. Dets beskaffenhed<br />

ændrer sig i drikkevandsinstallationen, fx ved kontakt med materialer, ved<br />

opvarmning eller stilstandstider med deraf følgende bakterieformering.<br />

Drikkevand er et levnedsmiddel<br />

Fig. D–1<br />

Sammenligning af<br />

sygdomsraterne i<br />

forskellinge lande<br />

I Tyskland regner man nu med ca. 21,000 tilfælde af legionærsyge om året. Da der er en<br />

dødelighed på 10 %, svarer det til ca. 2,100 dødsfald. I andre lande er hyppigheden klart<br />

lavere med 34,1 (Spanien), 19,2 (Danmark) 17,9 (Holland) og 16,9 (Frankrig) pr. 1. million.<br />

For at undgå problemer findes der i alle lande regelsæt til sikring vand forsyningen og<br />

bevarelse af vandkvaliteten. Fra EU kommer der løbende nye regler til, som supplerer<br />

eller erstatter de nationale regler. Derfor er det nødvendigt, at man jævnligt beskæftiger<br />

sig med de tekniske regler og hurtigst muligt omsætter dem i praksis. For eksempel<br />

er den tørre tæthedsprøvning blevet standard i større installationer som hospitaler<br />

eller hoteller. Skylning af installationen foretages nu så sent som muligt.<br />

14


1 Drikkevandsinstallation – Grundlag<br />

Hvis man skulle sammenfatte alle forholdsregler til beskyttelse af drikkevandet i én<br />

sætning, ville det blive:<br />

»Undgå alt, hvad der medfører, at drikkevandet opholder sig for længe i installationen,<br />

både i byggefasen og under drift.«<br />

»En kontinuerlig driftstemperatur mellem 25 og 55 °C bør undgås.«<br />

Som allerede nævnt kræver drikkevandsinstallationer en omfattende faglig viden.<br />

EN 806 og EN 1717 er eksempler på bestræbelerne for at skabe ensartede normer for<br />

installationerne og beskyttelse af drikkevandet over hele Europa. Dette kapitel sammenfatter<br />

væsentlige tiltag til bevarelse af vandkvaliteten. Det giver et overblik over<br />

relevante aspekter af fagligt korrekt projektering, udførelse, idriftsættelse og drift af<br />

drikkevandsinstal lationer. De aktuelle krav i de forskellige lande har altid forrang for de<br />

her anførte. Herudover yder <strong>Viega</strong>s medarbejdere assistance til fagfolk i deres daglige<br />

arbejde.<br />

Besparelsespotentialer<br />

Rent vand er et stort gode. Det er ikke alle steder, det er til rådighed i tilstrækkelige<br />

mængder. Det gælder dog om at afveje, hvilken indflydelse besparingstiltagene har på<br />

drikkevandets kvalitet. Allerede i dag kræver eksperter i hygiejne, at der sker en fuldstændig<br />

udskiftning af vandet tre gange om ugen i bygninger, som benyttes til medicinske<br />

formål.<br />

Foruden vandbesparelser er også tiltag til reduktion af energiforbruget i fokus. Lave<br />

temperaturer øger imidlertid også legionella-risikoen, så der skal findes en gylden middelvej<br />

mellem sundhedshensyn og besparelsespotentialer.<br />

Vandbesparelse kontra<br />

Hygiejne<br />

Fig. D–2<br />

15


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Projektering<br />

1)<br />

Rådets direktiv 98/83/<br />

EF af 3 november 1998<br />

om kvaliteten af<br />

drikkevand<br />

Bekendtgørelse vedrørende brugsvand<br />

1998 1) trådte den nye europæiske drikkevandsdirektiv i kraft. I 2006 trådte miljøministeriets<br />

(nu By og landskabsstyrelsen) bekendtgørelse 1664 ikraft. Det fastsætter i bilagene,<br />

kvalitetskravene til vand fra vandforsyninger, som anvendes til drikkevand.<br />

Grænseværdierne skal overholdes alle steder, hvor der tappes drikkevand. I forbindelse<br />

med projektering af en drikkevandsinstallation bør følgende emner afstemmes med<br />

den stedlige vandleverandør.<br />

Hustilslutning<br />

QQHvem installerer?<br />

QQEjer?<br />

QQMateriale? Nominel diameter<br />

QQStikledninger – hvor?<br />

Målersystem<br />

QQHvem installerer?<br />

QQMålerstørrelse?<br />

QQTilbageløbsspærring?<br />

Tryk<br />

QQLaveste forsyningstryk/målt hvor?<br />

QQMaksimalt hviletryk?<br />

Drikkevandets beskaffenhed<br />

QQmulige materialerestriktioner, VA godkendelse<br />

Rørmaterialer<br />

De anvendte materialer og produkter skal overholde kravene i det pågældende land.<br />

Arbejder på husinstallationer må kun udføres af autoriseret fagpersonale, med undtagelser<br />

jf. lov 1382 af 1. januar 2006 (www.retsinfo.dk).<br />

I henhold til DS/EN 12502 skal der tages hensyn til bl.a. drikkevandets kvalitet allerede<br />

i projekteringsfasen. Der er grænser for anvendelsen af alle rørmaterialer, der ganske<br />

vist som regel ikke kan blive aktuelle ved normal drift, men udmærket kan forekomme<br />

i forbindelse med særlige tiltag som evt. desinfektion. Derfor er det tilrådeligt at henvende<br />

sig til komponenternes producenter i tvivlstilfælde.<br />

Varmgalvaniserede jernmaterialer<br />

Må kun anvendes iht. DIN 50930-6 og DS/EN 12502, når<br />

QQalkalikapaciteten er KB 8,2 0,5 mol / m 3 og samtidigt<br />

QQsyrekapaciteten er KS 4,3 1,0 mol / m 3 .<br />

De øgede krav i forbindelse med galvanisering skal opfyldes.<br />

16


1 Drikkevandsinstallation – Grundlag<br />

Blyrør<br />

Gamle systemer, som stadigvæk indeholder blyrør, skal renoveres hurtigst muligt. De<br />

strammere retningslinier, der er fastsat i EU’s drikkevandsdirektiv, for bly skal opfyldes<br />

senest i 2013. Det betyder som regel udskiftning af hele rørsystemet.<br />

Kombination af forskellige materialer*<br />

Anvendelse af forskellige materialer i drikkevandsinstallationer følger de gældende tekniske<br />

regler (DS/EN 12502). For eksempel kan rør af kobber, indvendigt fortinnet kobber,<br />

rustfast stål og PE-X uden videre kombineres indbyrdes.<br />

Når rør af galvaniserede jernmaterialer kombineres med andre rørmaterialer, skal<br />

DS/EN 12502 overholdes. Forenklet kan siges, at store komponenter og apparater af<br />

kobber, kobberlegeringer, fortinnet kobber og kobberlodninger ikke må anbringes i<br />

strømningsretningen foran komponenter af galvaniserede jernmaterialer. Som overgang<br />

mellem rustfrit stål og galvaniseret stål anbefales forbindelsesdele af kobberlegeringer<br />

af mindst samme længde som rørets diameter. Derved reduceres – afhængigt<br />

af vandets beskaffen hed - risikoen for galvanisk korrosion. Hvor vandet har stor<br />

ledeevne kan Sanpress isoleringsforskruning med fordel anvendes.<br />

Forebyggelse/reduktion af kalkdannelse<br />

Hårdt til meget hårdt drikkevand reducerer levetiden for drikkevands installationens<br />

apparater og komponenter. Desuden øges energibehovet betydeligt, fordi kalkaflejringer<br />

på varmelegemer hindrer varmeoverførslen. I sådanne tilfælde er tiltag til delvis<br />

blødgørelse af drikkevandet derfor relevante ud fra et økonomisk og miljømæssigt<br />

synspunkt. Afhængigt af metoden kan det være relevant at hæve pH-værdien til ca. 7,7,<br />

således at man samtidig opnår en korrosionsbeskyttende virkning. Hvor vandet er af<br />

en sådan beskaffenhed, at tiltag af denne art kan være relevante, skal de kommunale<br />

myndigheder kontaktes. Det er kun vandværkerne der må behandle drikkevand. For<br />

godkendelse og installation af vandbehandlingsanlæg henvises til miljøstyrelsens orientering<br />

nr. 6, 2004. Sådanne anlæg skal sikres overensstemmelse med de overordnede<br />

krav i bygningsreglementet. I praksis kan vejledningerne i DS 439 anvendes,<br />

omend de ikke er en del af byggelovgivningen.<br />

Anbefalede vandbehandlingstiltag til forebyggelse af kalkdannelse afhængigt af kalciummassekoncentration<br />

og temperatur<br />

Kalcium-massekoncentration [mg/l] Tiltag ved T ≤ 60 °C Tiltag ved T ≥ 60 °C<br />

< 80<br />

Svarer omtrent til hårdhedsklasse 1 og 2 1) Ingen Ingen<br />

80 til 120<br />

Svarer omtrent til hårdhedsklasse 3 1)<br />

120<br />

Svarer omtrent til hårdhedsklasse 4 1)<br />

Tab. D–1<br />

Ingen eller stabilisering<br />

eller blødgøring<br />

Stabilisering eller<br />

blødgøring anbefales<br />

Stabilisering eller blødgøring<br />

anbefales<br />

Stabilisering eller<br />

blødgøring<br />

1)<br />

Tysk lov ’Vask og renseprodukter’<br />

17


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Prøveudtagningssteder<br />

Kontrollen med vandets beskaffenhed i hospitaler, hoteller osv. forudsætter, at der<br />

forefindes egnede prøveudtagningssteder. Som regel vil det sige udtagningsarmaturer.<br />

Ved vidt forgrenede installationer er det dog praktisk at arrangere yderligere udtagningsssteder,<br />

fx i kælderfordelings- og stigstrengsområdet og i etagefordelingen. Det<br />

sidste, fordi det i tilfælde af mikrobiologiske problemer kun er udtagningsarmaturerne,<br />

der er involveret, og undersøgelsesresultatet derfor ville være misvisende.<br />

Derudover er det velkendt, at der forekommer betydeligt flere fejl ved prøveudtagningen<br />

end ved den efterfølgende undersøgelse. I offentlige bygninger er det er derfor<br />

praktisk at indlægge særlige prøveudtagningsventiler som dem, der tilbydes af <strong>Viega</strong>.<br />

Prøveudtagningsarmatur<br />

Anordning til orienterende<br />

og videregående<br />

undersøgelser<br />

C<br />

C<br />

Ved evt. samle og tømmeanordningerudtages<br />

ligeledes prøver<br />

C<br />

C<br />

C<br />

C<br />

C<br />

C<br />

C<br />

O =<br />

Orienterende prøveudtagning<br />

C =<br />

Regelmæssig prøveudtagning<br />

Fig. D–3<br />

C<br />

C<br />

18


1 Drikkevandsinstallation – Grundlag<br />

<strong>Viega</strong>s rørsystemfilosofi<br />

Anbefalede materialer<br />

Hustilslutning og underjordiske stikledninger af PE<br />

QQpresfittings af rødgods – korrosionsfri (Geopress)<br />

QQhurtig og sikker etablering af forbindelse uafhængigt af vejrforholdene<br />

Hustilslutningsledning<br />

Med Geopress<br />

Fig. D–4<br />

Kælderfordelings- og stigledninger af <strong>metal</strong><br />

QQGod formstabilitet med lave fastgøringsomkostninger<br />

QQLille udvendig diameter og derfor lille forbrug af isoleringsmateriale<br />

QQLille længdeudvidelse ved opvarmning<br />

QQForarbejdning med et presværktøj op til DN 100<br />

QQPladsbesparende<br />

Stigstreng Profipress<br />

med afgrening til PE-Xc<br />

rør<br />

Fig. D–5<br />

19


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Etagefordelingsledninger af PE-Xc<br />

QQFås eventuelt med indlagt, påsvejset aluminiumslag<br />

QQOgså med PE-beskyttelsesrør som kondensvandbeskyttelse<br />

QQI ruller til udlægning på rågulve og i standervægge samt til vægmonteringsteknik<br />

QQTil vægmontering og tørt elementbyggeri med lydisolerede armatur tilslutninger i<br />

enkelt-, række- eller ringledningssystemer, som er formonteret efter skabelon<br />

Stikledninger<br />

Med Geopress<br />

Fig. D–6<br />

Visign for Care – hygiejnisk skyllefunktion<br />

Til forhindring af stagnation, der kan medføre mikrobiel kontaminering, skal sjældent<br />

brugte dele af rørsystemet skylles grundigt med jævne mellemrum. Betjeningspladen<br />

”Visign for Care” er udstyret med en automatisk/programmerbar skyllefunktion, der<br />

registrerer tidsrummet, hvor vand ikke er blevet anvendt, og aktiverer en skylning iht.<br />

et individuelt programmerbart tidsrum.<br />

Installation og opgradering er mulig ved <strong>Viega</strong>s indbygningscisterner med dobbelt<br />

skylleteknik, når en 220-230 V tilslutning kan etableres.<br />

20


1 Drikkevandsinstallation – Grundlag<br />

Oversigt drikkevands- projektering og udførelse<br />

Ved projektering af drikkevandsinstallationer skal der tages hensyn til bl.a. følgende<br />

kriterier:<br />

QQMaterialevalg iht. DS/EN 12502<br />

QQBrug af produkter med anerkendte testmærkninger<br />

QQUdregning af minimalt vandvolumen.<br />

QQProjektering med den størst mulige afstand fra drikkevandsledninger (kolde) til varmekilder<br />

QQTilstrækkelig isolering af drikkevandsledninger (kolde og varme) i skakter og forsænkede<br />

lofter<br />

QQInstaller ikke koldtvands drikkeledninger i rum med temperaturer > 25 °C (f.eks.<br />

kedelrum)<br />

QQSikring af den nominelle temperatur ved opvarmning og fordeling af drikkevand<br />

QQSikring af tilsstækkelig vandstrøm i cirkulationssystemet<br />

QQEtablering af prøveudtagningsventiler i offentlige bygninger<br />

QQValg af individuelle sikringer<br />

QQUndgåelse af membranekspansionstanke i drikkevandsanlæg i videst muligt<br />

omfang<br />

QQMinimering af stagnation – fx skal bypass-længder og udtømningsledninger undgås,<br />

og reserver skal ikke indgå i projekteringen<br />

QQUndgå ledningsstrækninger med stillestående vand.<br />

QQAdskillelse af brandslukningsledninger fra drikkevandsanlæg<br />

QQTør tæthedsprøvning bør foretrækkes<br />

Stagnerende vand i kombination med kontinuerlig temperatur mellem 25 und 55 °C<br />

bør undgås<br />

Drikkevandsanlæg består af et stort antal enkeltkomponenter. Derudover skal der især<br />

lægges vægt på tilbageløbssikring ved hjælp af armaturer og andre dele iht. EN 1717.<br />

Kombinationsventil<br />

med skråsæde<br />

Med prøveudtagningsventil<br />

Fig. D–7<br />

21


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Rørføring<br />

Blandt de ting, der er vigtige for drikkevandshygiejnen, er en optimal ledningsføring til<br />

udtag, som sjældent benyttes. De skal indgå i installa tionen, således at regelmæssig<br />

udskiftning af vandet er sikret, selv om de for eksempel kun benyttes på bestemte årstider.<br />

Det kan gøres ved at inkorporere disse udtag i række- eller ringledningssystemer.<br />

Sjældent benyttede udtag er fx<br />

QQHave-/garageledninger<br />

QQGæstetoilet<br />

QQTekøkken<br />

QQRækkevaskeanlæg, fx sportsanlæg<br />

QQBidet<br />

QQTappesteder til vaskemaskiner<br />

QQTappesteder til slangetilslutninger i toiletanlæg<br />

QQUdslagsvask<br />

QQPåfyldnings- og tømningsledninger i varmeanlæg<br />

Række- og<br />

ringledning<br />

Fig. D–8 Fig. D–9<br />

Brandsluknings- og sikringsenheder<br />

Brandsluknings- og sikringsenheder er vigtige sikkerhedsinstallationer. Hvis disse enheder<br />

kombineres med drikkevandssystemet, kan det lede til problemer med drikkevandskvaliteten,<br />

hvis systemet ikke bruges jævnligt. Dette er næsten altid tilfældet.<br />

Derfor skal brandsluknings- og sikringsenheder separeres fra drikkevandssystemet i<br />

henhold til gældende lovgivning.<br />

Rørnetberegning<br />

Formålet med rørnetberegningen (fx iht. DS/EN 806-3) er fejlfri funktion med minimale<br />

rørdiametre og korte stikledninger som betyder, at drikkevandet kun opholder sig i<br />

installationen i kort tid. Det muliggør den nødvendige udskiftning af vandet med et<br />

minimalt vandforbrug.<br />

22


1 Drikkevandsinstallation – Grundlag<br />

Badinstallation<br />

Hygiejnisk stikledningsinstallation<br />

Fig. D–10<br />

I praksis er der ikke høj risiko for mikrobiel kontaminering på tappe og forbrugssteder<br />

som anvendes jævnligt. I ubeboede bygninger bør dette altid afgøres særskilt og for<br />

hvert enkelte tilfælde. I diagrammet ovenfor vises en typisk drikkevandsinstallation i en<br />

lejlighed. Enstrengsledninger findes på tappesteder som f.eks. håndvask eller bruser.<br />

Hvorimod badekarret (også indbygget med bruser) sjældnere anvendes og bør derfor<br />

videreføres/sluttes til et hyppigere anvendt tappested, f.eks. håndvask. Det samme<br />

gælder for et bidet og en vaskemaskinetilslutning. Sidstnævnte installeres ofte, men<br />

anvendes senere kun lidt i boligen.<br />

23


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Fordeling af tryktab<br />

En præcis beregning af tryktabet i systemet skaber forudsætning for optimal lydisolering.<br />

Med afspærringsarmaturer med minimalt tryktab som fx kugleventiler kan trykpotentialet<br />

udnyttes bedre. Mulighederne bliver desuden større, hvis der vælges gennemstrømningsvandvarmere<br />

med elektronisk i stedet for hydraulisk styring,<br />

udløbsarmaturer med lille strømningstryk osv. Producenternes tryktabsværdier er at<br />

foretrække for reglemen ternes vejledende værdier.<br />

Viptool Engineering er den professionelle løsning til beregning af rørdimensioner. På<br />

basis af tegninger beregner programmet alle rør, fitings og hydrauliske data samt udarbejder<br />

en materialeliste.<br />

Installation<br />

Fasen fra installationsarbejderne påbegyndes til idriftsætningen er af afgørende<br />

betydning for vandets kvalitet. Alle komponenter skal trans porteres og opbevares fagligt<br />

korrekt. Der må kun anvendes komponenter med ren overflade. Derfor skal presfittings<br />

først tages ud af emballagen, umiddelbart før de anvendes. Rør eller rørafsnit,<br />

som ikke eller ikke mere er lukket med propper, kan beskyttes mod tilsmudsning med<br />

hætter, som kan købes hos <strong>Viega</strong>.<br />

Det skal undgås, at vandet opholder sig for længe i installation eller komponenter<br />

(fx pumpestationer, magnetventiler) før idriftsætningen, da lange opholdstider kan<br />

resultere i øget bakterievækst i vandet.<br />

Rustfri stålrør<br />

Ved leveringen er rørene<br />

tilproppet<br />

Fig. D–11<br />

24


1 Drikkevandsinstallation – Grundlag<br />

Tæthedsprøvning*<br />

<strong>Viega</strong> SC-Contur garanterer detektering af upressede forbindelser i hele trykområdet<br />

fra 22 mbar til 3 bar (tørt) og fra 1 bar til 6,5 bar (vådt). Hvis tæthedsprøvningen falder<br />

i en frostperiode, anbefales tør prøvning også af mindre installationer. Der findes p.t.<br />

ingen standardiseret prøvningsmetode for installationer i bygninger. For prøvning af<br />

ledninger i jord henvises til DS 455. De følgende test/prøvninger er eksempler på hvordan<br />

det gøres i Tyskland.<br />

Tør tæthedsprøvning<br />

Af sundhedsmæssige årsager anbefales tør tæthedsprøvning af store installationer.<br />

Hertil anvendes tør, oliefri trykluft eller – hvor der stilles særlige krav til hygiejne – også<br />

inert gas. De relevante sikkerhedsforskrifter skal følges.<br />

I overensstemmelse hermed foretages tæthedsprøvningen med et prøvetryk på<br />

110 mbar før belastningsprøvningen. Varigheden af prøvningen ved 110 mbar er<br />

mindst 30 minutter for op til 100 liters ledningsvolumen; hertil lægges 10 minutter for<br />

hver 100 liter derudover. Allerede ved denne prøvning detekteres eventuelle upressede<br />

presfittings.<br />

Tør belastningsprøvning<br />

Belastningsprøvningen ved maks. 3 bar varer 10 minutter.<br />

Tæthedsprøvning<br />

Tør<br />

Fig. D–12 Fig. D–13<br />

25


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Våd tæthedsprøvning<br />

Den våde tæthedsprøvning anbefales kun ved anlæg, som idriftsættes kort efter, fx i<br />

enfamiliehuse.<br />

Anlægget fyldes med filtreret drikkevand. <strong>Viega</strong> presfittings, som eventuelt ikke er<br />

presset, detekteres som utætte ved et maksimalt tryk på 6,5 bar.<br />

Våd belastningsprøvning (Se evt. DS 439)<br />

QQPrøvetrykket skal være 1,5 gange det tilladte driftstryk. Prøvningstiden for <strong>metal</strong>rør<br />

er 10 minutter efter temperaturudligning.<br />

QQDetaljeret procedure kan fås hos <strong>Viega</strong>.<br />

Skylning<br />

Skylningen kan foretages, når vandleverandøren har skyllet og frigivet hovedtilslutningen.<br />

Skylningen skal foretages så sent som muligt, med mindre der er opstået<br />

grov tilsmudsning, fx på grund af oversvømmelse. Her er det relevant at skylle med en<br />

luft/vand-blanding. Ellers er det tilstrækkeligt at skylle med vand, hvor der er anvendt<br />

<strong>Viega</strong> pressystemer, og der er nogenlunde rent. I så fald – eller hvis idriftsætningen<br />

trækker ud – skal der indføres et skylleprogram for at sikre regelmæssig udskiftning af<br />

vandet.<br />

Regler vedrørende hygiejne ved idriftsætning og<br />

aflevering (Udførendes ansvar)<br />

QQPåfyldning af installationen foretages først, når idriftsætning er umiddelbart forestående.<br />

Hvis idriftsætningen forsinkes, skal et skylleprogram udarbejdes og dokumenteres.<br />

QQDokumentation af ledningsføringen udleveres til ejeren.<br />

QQBetjeningsvejledninger osv. udleveres.<br />

QQProtokol over tæthedsprøvning, skylning, idriftsætning samt instruktion udleveres.<br />

QQDer gøres opmærksom på, at regelmæssig og fuldstændig udskiftning af vandet er<br />

nødvendig – ca. tre gange om ugen for alle udtag i offentlige Bygninger.<br />

QQDer informeres om legionella-risikoen ved utilstrækkelige „koldt“- og „varmt“-temperaturer.<br />

QQDer tilbydes en vedligeholdelsesaftale.<br />

26


1 Drikkevandsinstallation – Grundlag<br />

Desinficering<br />

Hvis det ikke ved almindelig drift og vedligeholdelse er muligt at reducere evt. problemer<br />

med bakterievækst, kan det være nødvendigt at indføre bekæmpelsesmetoder.<br />

Der findes en lang række metoder til at desinficere vandinstallationer. Anvendelse af<br />

desinfektionsmetoder i vandsystemer kræver myndighedernes godkendelse. Termisk<br />

desinfektion kan dog direkte anvendes til bekæmpelse af vækst af legionella i varmtvandssystemer.<br />

Desuden er ultralydsbehandling godkendt som vandfiltreringsanlæg<br />

til varmt og koldt brugsvand for at sikre mod legionella bakterier samt forebyggelse af<br />

bakterieophobning i drikkevandsinstallationer. I det følgende er oplyst metoder og<br />

værdier som må anvendes i Tyskland. Disse understøtter at <strong>Viega</strong>s rør og fitting kan<br />

modstå evt. påvirkninger af disse metoder. Desinficeringstiltag virker kun, hvor vandstrømmen<br />

er tilstrækkelig. Desuden fjerner de aldrig årsagerne til problemerne, men<br />

er kun en hurtig, foreløbig løsning, indtil dekontamineringen er afsluttet. Principielt<br />

anbefales varmedesinficering, da den til i modsætning til andre metoder når til bunds<br />

i biofilmen. Af de kemiske metoder er brintoverilte (H2O2) og klordioxid at foretrække,<br />

fordi de tåles bedst af materialerne. Beskyttelsesforanstalt ningerne skal afpasses efter<br />

bygningens anvendelse, især hvis der færdes bøn eller demente. Efter kemisk desinficering<br />

skal der altid skylles, indtil koncentrationen af desinfektionsmiddel igen er nedbragt<br />

til det niveau, der er tilladt ved langtidsdesinficering.<br />

Til desinficering af legionella-inficerede ledningsanlæg er 50 mg/l klor i løbet af<br />

1–2 timer erfaringsmæssigt tilstrækkeligt. Til forebyggelse af legionella er kontinuerlig<br />

klorbehandling mindre egnet. Det er bedre at sørge for, at temperaturen af vandet<br />

holdes inden for det korrekte område.<br />

Pseudomonas<br />

Fig. D–14<br />

Vi anbefaler, at al desinficering udføres af kvalificeret fagpersonale og i samråd<br />

med den lokale tekniske forvaltning. Iøvrigt henvises til DS 439.<br />

27


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Rørsystemers rentabilitet<br />

Ved valg af rørmateriale til en drikkevandsinstallation skal der tages hensyn til både tekniske<br />

og økonomiske aspekter. Foruden langtidssikkerhed og drikkevandshygiejne er<br />

det meget vigtigt, at der tages hensyn til montagevenlighed og økonomi.<br />

Presteknikken er mest fordelagtig med hensyn til håndtering, montagetid og økonomi.<br />

Andre væsentlige faktorer er tilgængelighed, sortiment og omkostningerne til rørledningsføring<br />

og fastgøring. Til kælderfordelingsledninger og stigledninger er rørledninger<br />

af <strong>metal</strong> at foretrække for kunststofrør.<br />

Installation med<br />

Sanpress Inox<br />

Fig. D–15<br />

Fordele:<br />

QQMindre pladsbehov til længdeudvidelse<br />

QQMinimal udgift til kompensationsstykker og kompensatorer<br />

QQLave fastgørelsesomkostninger.<br />

QQLavere krav til forebyggende brandbeskyttelse<br />

QQMindre udgift til varmeisolering som følge af tyndere rørvægge (særligt ved rør<br />

med stor diameter)<br />

Ill. D-16 viser forskellen i udgifter til udligning af længdeudvidelser ved forskellige<br />

materialer. Her har rørledninger af <strong>metal</strong> klare fordele. Det samme gælder med hensyn<br />

til fastgøringsomkostninger, som for kælderfordelingsledningers og stigledningers<br />

vedkommende kun er 50 % eller derunder sammenlignet med kunststofrørene.<br />

28


1 Drikkevandsinstallation – Grundlag<br />

Derimod er der kun brug for mindre og kortere rør på etager og bag vægge. Længdeudvidelsen<br />

er derfor ringe og reducerer fastgøring af rørledninger i gulv og loft til et<br />

minimum.<br />

Ved at kombinere de to systemer – kælderfordelingsledninger og stigledninger af<br />

<strong>metal</strong> og etagedistributioner af kunststof – opnår man derfor de størst mulige fordele<br />

med hensyn til montering og økonomi.<br />

Længdeudvidelse<br />

af rørledninger<br />

Stål<br />

Kobber<br />

Polypropylen<br />

Fig. D–16<br />

Desuden har følgende forhold indflydelse på økonomien:<br />

QQIndkøbspriser på rør, fastgøringselementer og isolering<br />

QQMontageomkostninger (afhænger af materialerne) inkl. løn og indirekte lønomkostninger<br />

QQRørdiametre, udgifter til fastgøringer og udligning af længdeudvidelse ved opvarmning<br />

QQKontrol af produkternes sikkerhed og kvalitet – SC-Contur (upresset utæt)<br />

QQVærktøjsudgifter<br />

QQLagerbeholdning<br />

QQHurtig levering<br />

29


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Oversigt over rørsystemer i <strong>metal</strong><br />

Med SC-Contur<br />

Fig. D–17<br />

Sanpress Inox<br />

Rør:<br />

Rustfrit stål<br />

Presfittings: Rustfrit stål 15 – 108 mm<br />

Til alt drikkevand uden begrænsning<br />

Højeste materialekvalitet<br />

Fig. D–18<br />

Sanpress<br />

Rør:<br />

Rustfrit stål<br />

Presfittings: Rødgods 12 – 108 mm<br />

Til alt drikkevand uden begrænsning<br />

Høj kloridbestandighed<br />

Fig. D–19<br />

Profipress<br />

Rør:<br />

Kobber<br />

Presfittings: Kobber 12 – 108 mm<br />

Overhold reglerne om brug til drikkevand!<br />

30


1 Drikkevandsinstallation – Systembeskrivelse<br />

Systembeskrivelse<br />

Sanpress Inox / Sanpress Inox XL<br />

Anvendelse<br />

Systemet er beregnet til:<br />

QQDrikkevand uden begrænsning iht. vandforsyningsloven<br />

QQDriftstemperatur 85 °C; T maks. = 110 °C<br />

QQDriftstryk<br />

≤ 16 bar<br />

Systemkomponenterne skal beskyttes mod høje kloridkoncentra tioner, både fra<br />

mediet og påvirkninger udefra. For at undgå skader bør rør af rustfrit stål ikke<br />

opbevares på betongulve eller trækkes ud over ladkanter. Blandingsinstallationer<br />

er tilladt uafhængigt af strømningsretningen.<br />

Brug af Sanpress Inbox til andre end de beskrevne anvendelsesmåder skal afstemmes<br />

med vores fabrik i Attendorn.<br />

Rustfaste stålrør<br />

Med rustfaste press fittings<br />

Standard størrelse<br />

12 – 54 mm<br />

XL-størrelser<br />

64 – 108 mm<br />

med kompressionsring<br />

og EPDM tætningselement<br />

Fig. D–20 Fig. D–21<br />

Fig. D–22<br />

31


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Rørmateriale<br />

Identisk med Sanpress<br />

EN 10312<br />

Presfittingmateriale<br />

Tætningselement<br />

Leveringstilstand<br />

Godkendelser<br />

Rør<br />

Standardstørrelser<br />

[mm]<br />

Sanpress Inox<br />

Sanpress Inox XL<br />

Tekniske data<br />

Sanpress Inox- og Sanpress Inox XL-rør af rustfast stål er lasersvejsede ledningsrør af<br />

korrosionsfast stål.<br />

QQMaterialenr. 1.4401 (X5 CrNiMo 17-12-2), med 2,3 % Mo for længere holdbarhed;<br />

identificeret med gule propper<br />

QQMaterialenr. 1.4521 (X2 CrMoTi 18-2), PRE-værdi 24,1; identificeret med grønne<br />

propper<br />

Rustfast stål<br />

EPDM, sort (ethylen-propylen-dien-monomer gummi); op til 110 °C;<br />

ikke modstandsdygtigt over for opløsningsmidler med kulbrinte, klorerede kulbrintestoffer,<br />

terpentin og benzin<br />

QQStænger, 6 m lange, med blank ydre og indre overflade<br />

QQRørender med kunststofhætter<br />

QQAlle rør er kontrolleret for tæthed og kontrolmærket<br />

Rør materiale-nr. 1.4401:<br />

DVGW Godkendelse: DW 8501 BL 0551 (15 – 54 mm)<br />

DW 8511 BQ 0245 (64,0 – 108,0 mm)<br />

Rør materiale-nr. 1.4521: DVGW Godkendelse: DW 8501 BS 0376 (15 – 108,0 mm)<br />

15 / 18 / 22 / 28 / 35 / 42 / 54<br />

64,0 / 76,1 / 88,9 / 108,0<br />

Sanpress Inox-rør<br />

d x s<br />

[mm]<br />

Volumen pr.<br />

løbende<br />

meter rør<br />

[liter/m]<br />

Vægt pr.<br />

løbende<br />

meter rør<br />

[kg/m]<br />

Vægt<br />

pr. 6 m stang<br />

[kg]<br />

15 x 1,0 0,13 0,35 2,10<br />

18 x 1,0 0,20 0,43 2,55<br />

22 x 1,2 0,30 0,65 3,89<br />

28 x 1,2 0,51 0,84 5,02<br />

35 x 1,5 0,80 1,26 7,55<br />

42 x 1,5 1,19 1,52 9,13<br />

54 x 1,5 2,04 1,97 11,83<br />

Størrelse<br />

Standard<br />

Materiale,<br />

presfittings<br />

Rustfrit stål<br />

Sanpress Inox XL-rør<br />

64,0 x 2,0 2,83 3,04 18,24<br />

76,1 x 2,0 4,08 3,70 22,20<br />

88,9 x 2,0 5,66 4,34 26,00<br />

108,0 x 2,0 8,49 5,30 31,80<br />

Tab. D–2<br />

XL<br />

Rustfrit stål<br />

32


1 Drikkevandsinstallation – Systembeskrivelse<br />

Sanpress / Sanpress XL<br />

Anvendelse<br />

Systemet er beregnet til:<br />

QQDrikkevand uden begrænsning iht. vandforsyningsloven.<br />

QQDriftstemperatur 85 °C; T maks. = 110 °C<br />

QQDriftstryk<br />

≤ 16 bar<br />

Beskyttes mod høje kloridkoncentrationer både fra mediet og påvirkninger udefra.<br />

Blandingsinstallationer er tilladt uafhængigt af strømningsretningen. Brug af<br />

Sanpress XL til andre end de beskrevne anvendelsesmåder skal afstemmes med<br />

vores fabrik i Attendorn.<br />

Rustfri stålrør<br />

med presfittings<br />

af rødgods<br />

Standardstørrelse<br />

12 til 54 mm<br />

XL-størrelser<br />

76,1 til 108,0 mm<br />

med skærering<br />

og EPDMtætningselement<br />

Fig. D–23 Fig. D–24<br />

Sanpress<br />

Presfittingssystem<br />

med rustfri stålrør<br />

Presfittings af<br />

rødgods med<br />

EPDM-tætning,<br />

12 – 54 mm<br />

Alle størrelser med<br />

SC-Contur<br />

Fig. D–25<br />

33


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Rørmateriale<br />

Ref.-standard EN 10312<br />

Presfittingmateriale<br />

Tætningselement<br />

Leveringstilstand<br />

Godkendelser<br />

System<br />

Standardstørrelser<br />

[mm]<br />

Sanpress Inox<br />

Sanpress Inox XL<br />

Tekniske data<br />

Sanpress og Sanpress XL rustfast stålrør er tyndvæggede, lasersvejsede ledningsrør af<br />

korrosionsfast stål.<br />

QQMaterialenr. 1.4401 (X5 CrNiMo 17-12-2), med 2,3 % Mo for længere holdbarhed;<br />

identificeret med gule propper<br />

QQMaterialenr. 1.4521 (X2 CrMoTi 18-2), PRE-værdi 24,1; identificeret med grønne<br />

propper<br />

Rødgods<br />

EPDM, sort (ethylen-propylen-monomer gummi); op til 110 °C; ikke modstandsdygtigt over<br />

for opløsningsmidler med kulbrinte, klorerede kulbrintestoffer, terpentin og benzin<br />

QQStænger, 6 m lange, med <strong>metal</strong>lisk, blank ydre og indre overflade<br />

QQRørender med kunststofhætter<br />

QQAlle rør er tæthedsprøvet og kontrolmærket<br />

Konstant egenkontrol og kontrol ved materialetestinstituttet NRW.<br />

Rør materiale-nr. 1.4401: DVGW Godkendelse: DW 8501 AP 3032 (12 – 54 mm) /<br />

DW 8501 AT 2348 (76,1 – 108,0 mm)<br />

Rør materiale-nr. 1.4521 DVGW Godkendelse: DW 8501 BS 0377 (12 – 108,0 mm)<br />

EN 10088: Generelt krav til svejsede, cirkulære rør af ikke-rustende ståltyper<br />

Iht. DVGW-dokument W 541: Rør af ikke-rustende ståltyper til drikkevandsinstallationer<br />

12 / 15 / 18 / 22 / 28 / 35 / 42 / 54<br />

76,1 / 88,9 / 108,0<br />

Sanpress-rør<br />

d x s<br />

[mm]<br />

Volumen pr.<br />

løbende<br />

meter rør<br />

[liter/m]<br />

Vægt pr.<br />

løbende<br />

meter rør<br />

[kg / m]<br />

Vægt<br />

pr. 6 m stang<br />

[kg]<br />

12 x 1,0 0,08 0,27 1,60<br />

15 x 1,0 0,13 0,35 2,10<br />

18 x 1,0 0,20 0,43 2,55<br />

22 x 1,2 0,30 0,65 3,89<br />

28 x 1,2 0,51 0,84 5,02<br />

35 x 1,5 0,80 1,26 7,55<br />

42 x 1,5 1,19 1,52 9,13<br />

54 x 1,5 2,04 1,97 11,83<br />

Sanpress XL-rør<br />

76,1 x 2 4,08 3,70 22,20<br />

88,9 x 2,0 5,66 4,34 26,00<br />

108,0 x 2,0 8,49 5,30 31,80<br />

Tab. D–3<br />

Størrelse<br />

Standard<br />

XL<br />

Materiale,<br />

presfittings<br />

Rødgods<br />

Rødgods<br />

34


1 Drikkevandsinstallation – Systembeskrivelse<br />

Profipress / Profipress XL<br />

Anvendelse<br />

Rør og fittings af kobber kan kun anvendes til drikkevand uden begrænsning, når<br />

QQpH-værdien er 7,4 eller højere eller<br />

QQTOC-værdien ikke overskrider 1,5 g/l på pH-niveauer mellem 7,0 og 7,4<br />

Systemet er beregnet til:<br />

QQDriftstemperatur ≤ 85 °C; T maks. = 110 °C<br />

QQDriftstryk<br />

≤ 16 bar<br />

Komponenter af kobber må ikke indsættes foran galvaniserede jernmaterialer;<br />

anvisningerne på side 68 skal følges.<br />

Brug af Profipress til andre end de beskrevne anvendelser skal afstemmes med<br />

vores fabrik i Attendorn.<br />

Vandkvaliteten skal<br />

bevares!<br />

Strømningsreglerne<br />

skal overholdes<br />

Profipress fittings<br />

Standardstørrelser<br />

12 - 54 mm<br />

XL-størrelser<br />

64 – 108 mm<br />

med kompressionsring<br />

og EPDMtætningselement<br />

Fig. D–26 Fig. D–27<br />

Fitting<br />

Med pres- og<br />

gevindtilslutning<br />

Alle størrelser med<br />

SC-Contur<br />

Fig. D–28<br />

35


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Rørmateriale<br />

Presfittingmateriale<br />

Tætningselement<br />

Godkendelser<br />

System<br />

Størrelser [mm]<br />

Profipress<br />

Profipress XL<br />

Tekniske data<br />

Anvend kun kobberrør i overensstemmelse med EN 1057. Bemærk venligst minimums<br />

godstykkelse i henhold til Tab. D–4<br />

QQ12 – 108,0 mm<br />

Kobber<br />

QQPresfitting med gevindtilslutning<br />

12 – 54 mm rødgods<br />

64,0 – 108,0 mm Kobber<br />

EPDM, sort (ethylen-propylen-dien-monomer gummi); op til 110 °C;<br />

ikke modstandsdygtigt over for opløsningsmidler med kulbrinte, klorerede kulbrintestoffer,<br />

terpentin og benzin.<br />

Profipress med SC-Contur DVGW-reg.-nr. DW 8511 AP 3139<br />

Profipress XL DVGW reg.nr. DW 8511 AT 2347<br />

12 / 15 / 18 / 22 / 28 / 35 / 42 / 54<br />

64,0 / 76,1 / 88,9 / 108,0<br />

Godkendte kobberrør<br />

d x s<br />

[mm]<br />

Volumen pr.<br />

løbende meter<br />

rør<br />

[liter/m]<br />

Vægt pr.<br />

løbende meter<br />

rør<br />

[kg / m]<br />

Vægt<br />

pr. 5 m stang<br />

[kg]<br />

12 x 0,8 0,09 0,25 1,54<br />

12 x 1,0 0,13 0,39 1,54<br />

15 x 1,0 0,13 0,39 1,96<br />

18 x 1,0 0,20 0,48 2,38<br />

22 x 1,0 0,31 0,59 2,94<br />

28 x 1,0 0,53 0,76 4,54<br />

28 x 1,5 0,49 1,11 5,55<br />

35 x 1,2 0,84 1,13 6,80<br />

35 x 1,5 0,80 1,41 7,05<br />

42 x 1,2 1,23 1,37 8,21<br />

42 x 1,5 1,2 1,70 8,50<br />

54 x 1,5 2,04 2,20 13,21<br />

54 x 2,0 7,97 2,91 14,55<br />

XL-størrelser<br />

64,0 x 2,0 2,83 3,47 17,34<br />

76,1 x 2,0 4,08 4,14 20,72<br />

88,9 x 2,0 5,66 4,86 24,30<br />

108,0 x 2,5 8,33 7,37 36,87<br />

Tab. D–4<br />

Størrelse<br />

Standard<br />

XL<br />

Materiale,<br />

presfittings<br />

Kobber<br />

Kobber<br />

36


1 Drikkevandsinstallation – Anvendelsesteknik<br />

Anvendelsesteknik<br />

Isolering*<br />

Afhængigt af anvendelsesområde og rørmateriale kræves der af følgende grunde isolering,<br />

udlægning og fastgøring af rørledninger:<br />

QQBeskyttelse mod kondensdannelse<br />

QQForebyggelse af udvendig korrosion<br />

QQSikring af drikkevandskvalitet<br />

QQBegrænsning af varmetab<br />

QQForebyggelse af knæklyde på grund af længdeudvidelse<br />

QQDæmpning af trykstød som kunne forplante sig i bygningen<br />

QQMinimere overførsel af strømningsstøj<br />

Isolering af drikkevandsledninger (kolde)<br />

Drikkevandsledninger (kolde) skal isoleres som beskyttelse mod opvarmning og kondensdannelse.<br />

Ledningerne skal arrangeres således, at der er tilstrækkelig afstand til varmekilder som<br />

varme rørledninger, skorstene og varmeanlæg. Hvis dette ikke er muligt, skal koldtvandsledningerne<br />

isoleres således, at drikkevandskvaliteten ikke forringes på grund af<br />

opvarmning.<br />

Der henvises iøvringt til DS 452.<br />

Vejledende værdier for mindste isoleringstykkelse – koldt vand<br />

Montagesituation<br />

Isoleringens lagtykkelse ved<br />

l = 0,040 W/(mK) [mm] 1)<br />

Rørledninger frit udlagt, opvarmet rum 4<br />

Rørledninger frit udlagt, ikke opvarmet rum 9<br />

Rørledninger i kanal uden varme rørledninger 4<br />

Rørledninger i kanal ved siden af varme rørledninger 13<br />

Rørledninger i murspalte, stigledninger 4<br />

Rørledninger i murudsparing ved siden af varme rørledninger 13<br />

Rørledning på betondæk 4<br />

Tab. D–5<br />

1)<br />

Ved andre varmeledende<br />

egenskaber skal<br />

isoleringens tykkelse<br />

omregnes på basis<br />

af en diameter på<br />

20 mm.<br />

37


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Isolering af drikkevandsledninger (varme)<br />

Til minimering af varmeafgivelsen fra varmtvandsledningerne iht. den tyske energiforordning<br />

EnEV §12, kap. 5 gælder værdierne i nedenstående tabeller.<br />

For danske regler henvises til DS 452.<br />

Vejledende værdier for mindste isoleringstykkelse – varmt vand<br />

Linje<br />

Lednings-/armaturtype<br />

Mindste isoleringslagtykkelse<br />

ved en<br />

varmeledningsevne på<br />

0,035 W/mK<br />

1 Indvendig diameter op til 22 mm 20 mm<br />

2 Indvendig diameter fra 35 mm til 100 mm 30 mm<br />

3 Indvendig diameter fra 35 mm til 100 mm Same as internal diameter<br />

4 Invendig diameter fra 100 mm 100 mm<br />

Ledninger og armaturer iht. linje 1 til 4:<br />

– i mur- og dækgennemføringer<br />

5 – i rørkrydsningsområdet<br />

– ved rørsamlinger<br />

– ved centrale rørnetfordelere<br />

Tab. D–6<br />

50 % af kravene iht.<br />

Linje 1 – 4<br />

Dette gælder ikke for varmtvandsledninger i boliger med indvendig diameter indtil<br />

22 mm, hverken udstyret med elektrisk opvarmning eller integreret i cirkulationsledning.<br />

Lydisolering<br />

Støj i drikkevandsinstallationer stammer hovedsageligt fra armaturer og sanitetsgenstande.<br />

Støjen kan transmitteres gennem rørsystemet til bygningen, der så genererer<br />

luftbåren støj.<br />

Følgende forholdsregler kan forhindre dette:<br />

QQBrug af støjsvage armaturer<br />

QQReduktion af vandtrykket<br />

QQKorrekt fastgørelse af rørledningerne<br />

QQOverholde anbefalede minimumsafstande mellem rør mht. længdeudvidelse<br />

QQRørene udstyres med lydisolerende elementer, der forhindrer lydtransmission til<br />

bygningen forårsaget af trykstød<br />

38


1 Drikkevandsinstallation – Anvendelsesteknik<br />

Brandbeskyttelse*<br />

Hvis rørledninger føres igennem dæk og mure mellem forskellige brandceller, skal der<br />

træffes passende forholdsregler, som forhindrer overførsel af ild og røg i et nærmere<br />

defineret tidsrum. Her har fx rørbeklædninger af stenuld vist sig at være fremragende<br />

og yder en fagligt korrekt isolering af rørledningerne fra selve bygningen. Gældende<br />

regler i Danmark findes i de brandtekniske regler.<br />

Steptec<br />

installationsskakt<br />

Fig. D–29<br />

Sikring af at ild ikke<br />

breder sig<br />

Lukket dækkonstruktion<br />

med skakt fyldt med<br />

rockwool-isolerede rørledninger<br />

bag en gipskartonbeklædning<br />

Fig. D–30<br />

Selvom der ikke kræves afstand mellem ledningerne anbefales en mindsteafstand på<br />

ca. 20 mm.<br />

39


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Længdeudvidelse<br />

Varmeudvidelser i installationssystemer genererer store spændinger i rørledninger og<br />

tilslutninger til enheder. Ved meget lange rørstrækninger skal der derfor tages højde<br />

herfor, ved montering af udlignere.<br />

Længdeudvidelseskompensatorer er ledningsstrækninger med kompen sationsstykker i<br />

U- eller Z-form, som på grund af deres form og fastgøringsmåde kan kompensere for<br />

bevægelser.<br />

Længdeudvidelseskompensatorer<br />

Hvis montageforholdene tillader U- eller Z-kompensatorer, kan kompensationsstykkernes<br />

længde beregnes som følger:<br />

1. Fastlæggelse af den størst mulige temperaturforskel ΔT<br />

2. Bestemmelse af rørlængden l 0<br />

Ved hjælp af disse værdier beregnes det, hvor meget ledningsafsnittet forlænges i alt.<br />

På grundlag heraf kan det aflæses, hvor lange kompensationsstykkerne – hhv L BZ og<br />

L BU – skal være til de aktuelle rørstørrelser.<br />

Eksempel (se følgende sider)<br />

1. Driftstemperaturen ligger mellem 10 og 60 °C. Altså er: ΔT = 50 K.<br />

2. Ledningsafsnittet har en længde på: l 0 = 20 m.<br />

3. Længdeudvidelseskoefficienten for rustfast stålrør: α = 0,0165 [mm / mK].<br />

4. Værdierne indsættes i formlen: Δl = α [mm / mK]· L[m] · ΔT [K]<br />

hvoraf følger<br />

Længdeudvidelsen: Δl = 0,0165 [mm / mK] · 20 [m] · 50 [K] = 16,5 mm<br />

5. Valg af U- eller Z-form alt efter pladsforhold.<br />

6. Den nødvendige længde på kompensationsstykket L BZ aflæses i U- eller eller Z-diagrammet.<br />

I dette eksempel for Z-kompenationsstykker:<br />

Gå til 16,5 mm på den lodrette akse og derfra vandret til linjen med den aktuelle<br />

rørstørrelse. Den nødvendige længde på kompensationsstykket kan nu aflæses forneden<br />

på den vandrette akse.<br />

Hvis den valgte nominelle rørdiameter er 28 mm, er længden på kompensationsstykket<br />

L BZ = 1,3 m.<br />

40


1 Drikkevandsinstallation – Anvendelsesteknik<br />

Forskellige materialers længdeudvidelse<br />

Rustfast stål 1.4401<br />

Rustfast stål 1.4521<br />

Galvaniseret stål<br />

Kobber<br />

Kunststoff<br />

Tab. D–7<br />

Varmeudvidelseskoefficient<br />

α<br />

[mm / mK]<br />

0,0165<br />

0,0108<br />

0,0120<br />

0,0166<br />

0,08 – 0,18<br />

Længdeudvidelse ved<br />

rørlængde = 20 m<br />

og ΔT = 50 K<br />

[mm]<br />

16,5<br />

10,8<br />

12,0<br />

16,6<br />

80,0 – 180,0<br />

Længdeudvidelse<br />

Forskellige materialer<br />

Forlængelse af ledninger i rustfast stål<br />

Længdeudvidelse Δl [mm]<br />

Rørlængde Δl 0 [m]<br />

Temperaturdifference<br />

ΔT [K]<br />

Fig. D–31<br />

41


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Beregning af længden af kompensationssstykker til rør med Ø < 54 mm<br />

Kompensationsstykker<br />

I Z-form med kompensationsstykke<br />

L BZ<br />

og som T-tilslutning<br />

Fig. D–32 Fig. D–33<br />

Længdeberegning<br />

For kompensationsstykker<br />

i Z- og T-form<br />

Ekspansionskompensation Δl [mm]<br />

Fig. D–34<br />

Længde på kompensationsstykke<br />

L BZ [m]<br />

42


1 Drikkevandsinstallation – Anvendelsesteknik<br />

Kompensationsstykker<br />

U-form med kompensationsstykke<br />

L BU<br />

Fig. D–35<br />

Ekspansionskompensation Δl [mm]<br />

Længdeberegning<br />

For kompensationsstykker<br />

i U-form<br />

Fig. D–36<br />

Længde på kompensationsstykke<br />

L BU [m]<br />

43


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Længdeudvidelse af rør med Ø > 54 mm<br />

Kompensationsstykker<br />

I Z-form med kompensationsstykke<br />

L BZ<br />

og som T-tilslutning<br />

Fig. D–37<br />

Z-ekspansionskompensator<br />

med XL-fittings<br />

Fig. D–38<br />

Længdeudvidelse, T-stykke<br />

Længdeberegning<br />

For kompensationsstykker<br />

i Z- og T-form<br />

Længde på kompensationsstykke Δl [mm]<br />

Ekspansionskompensation<br />

L BZ [m]<br />

Fig. D–39<br />

44


1 Drikkevandsinstallation – Anvendelsesteknik<br />

Kompensationsstykker<br />

I U-form med kompensationsstykke<br />

L BU<br />

Fig. D–40<br />

Længdeberegning<br />

For kompensationsstykker<br />

i U-form<br />

Længde på kompensationsstykke Δl [mm]<br />

Ekspansionskompensation L BU [m]<br />

Fig. D–41<br />

45


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Kompensatorer<br />

Alternativet til længdeudvidelseskompensatorer (se forrige kapitel) er Aksialkompensatorer.<br />

De er egnede til at kompensere for aksiale bevægelser i rørinstallationer ved driftstemperaturer<br />

på 20 – 120 °C men bør ikke anvendes ved radiale belastninger.<br />

Axial-Kompensator<br />

Størrelse 15 til 54 mm<br />

Fig. D–42<br />

QQSom pladsbesparende alternativ til udvidelseskompensatorer<br />

QQForspænding ikke nødvendig<br />

QQStøjreducerende<br />

QQLang levetid, korrosions bestandige<br />

QQEgnede til blandingsinstallationer<br />

46


1 Drikkevandsinstallation – Anvendelsesteknik<br />

Dimensions<br />

Ø d i 15 til 54 mm<br />

Fig. D–43<br />

Tekniske data aksial kompensator<br />

Nominel<br />

diameter<br />

Længdeudvidelseskomp.<br />

i alt<br />

Artikelnr.<br />

Vægt<br />

Presfittings – Mål<br />

Længde<br />

Fjederkonstant<br />

Indstiksdybde<br />

Udvendig<br />

ø<br />

Bælg<br />

effektivt<br />

tværsnit<br />

Byggelængde<br />

d i<br />

[mm]<br />

δ N<br />

[mm]<br />

–<br />

Lo<br />

[mm]<br />

G<br />

[kg]<br />

e<br />

[mm]<br />

y<br />

[mm]<br />

D<br />

[mm]<br />

A<br />

[cm 2 ]<br />

Cδ<br />

[N / mm]<br />

15<br />

18<br />

22<br />

28<br />

35<br />

42<br />

54<br />

-20<br />

-20<br />

-22<br />

-24<br />

-24<br />

-24<br />

-30<br />

329 945<br />

329 952<br />

329 969<br />

329 976<br />

329 983<br />

329 990<br />

330 002<br />

116<br />

120<br />

121<br />

140<br />

150<br />

175<br />

195<br />

0,10<br />

0,15<br />

0,19<br />

0,28<br />

0,44<br />

0,62<br />

0,98<br />

24<br />

24<br />

24<br />

24<br />

26<br />

40<br />

45<br />

29<br />

29<br />

31<br />

34<br />

39<br />

49<br />

54<br />

24<br />

28<br />

34<br />

41<br />

50<br />

60<br />

72<br />

3,39<br />

4,55<br />

6,41<br />

9,46<br />

14,40<br />

21,40<br />

31,80<br />

21<br />

43<br />

30<br />

37<br />

54<br />

53<br />

48<br />

Tab. D–8<br />

47


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Funktionen af faste punkter/glidepunkter<br />

Faste punkter fastholder rørledningerne med bygningen / den bærende konstruktion<br />

og sikrer udvidelsesbevægelsen i den ønskede retning.<br />

En rørledning, som ikke afbrydes på grund af et retningsskift, eller som ikke indeholder<br />

et ekspansionsstykke har kun brug for ét fast punkt. I tilfælde af lange rørledninger<br />

anbefales det at placere disse faste punkter i segmentets midte, således at udvidelsen<br />

styres i to retninger.<br />

Indespændt<br />

fastgøring<br />

Fig. D–44<br />

Glidende<br />

fastgøring<br />

Glidepunkter for aksiale<br />

bevægelser<br />

Fig. D–45<br />

48


1 Drikkevandsinstallation – Anvendelsesteknik<br />

Rørfriktion<br />

Ved hjælp af nedenstående diagram kan tryktabet ved rørfriktion for kobberrør og<br />

rustfri stålrør skønnes tilstrækkelig præcist.<br />

Til beregning af mere komplekse rørsystemer anbefales, at anvende dedikeret beregningssoftware<br />

f. eks. Viptool Engineering.<br />

Maksimal gennemstrømning V S [l / s]<br />

.<br />

Rørfriktionstrykdifference R [mbar / m]<br />

Fig. D–46<br />

·<br />

V S = maksimal gennemstrømning; v = strømningshastighed; R = rørfriktionstrykdifference<br />

49


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Korrosion af rustfri stålrør forårsaget af klorider<br />

Undgå altid kontakt<br />

med klorider<br />

på ydersiden<br />

Kloridkoncentration<br />

i drikkevand<br />

For højt kloridindhold resulterer i korrosion af rustfri stålrør i drikkevand. Vær derfor<br />

venligst opmærksom på<br />

QQat isoleringsmaterialer ikke må overskride en masseandel af vandopløselige kloridioner<br />

på 0,05 %.<br />

QQRørbøjlernes lydisolerende indlæg må ikke indeholde klorider, som kan udvaskes.<br />

QQRustfri stålrør må ikke komme i kontakt med kloridholdige byggematerialer.<br />

QQRustfri stålrør, der er udsat for kloridholdige gasser eller dampe (i malerværksteder<br />

eller galvaniseringsanstalter), skal forsynes med tilstrækkelig korrosionsbeskyttelse,<br />

se DS 439<br />

I Tyskland anses allerede et kloridindhold på 150 mg/l i drikkevandet for at være over<br />

gennemsnittet. Drikkevandsdirektivet foreskriver en grænseværdi på 250 mg/l for klorid.<br />

Ved dette ‚klorid‘ drejer det sig ikke om et desinfektionsmiddel men om en<br />

bestanddel af hav- og kogesalt (natriumklorid). Ved et kloridindhold på op til 250 mg/l<br />

kan Sanpress og Sanpress Inox anvendes i alt drikkevand. Vores fabrik i Attendorn giver<br />

oplysninger i særtilfælde.<br />

50


1 Drikkevandsinstallation – Komponenter<br />

Komponenter<br />

Easytop skråsædeventiler<br />

Easytop ventiler af rødgods eller rustfrit stål med skråsæde giver mulighed for direkte<br />

prestilslutning – uden overgangsstykker – til <strong>Viega</strong> rørsystemerne Sanpress Inox,<br />

Sanpress, Profipress til drikkevandsinstallationer. Som fristrømsventiler forhindrer de<br />

trykstød ved aktivering og skåner dermed de tilsluttede armaturer, enheder og rørinstallationer.<br />

Alle Easytop ventiltyper er godkendt iht. EN 1213 (armaturgruppe I). For yderligere godkendelser<br />

se også www.etadanmark.dk<br />

QQfristrømsventil<br />

QQfristrømsventil med tilbageløbsspærring<br />

QQtilbageløbsspærring<br />

8<br />

1<br />

Easytop skråsædeventil<br />

Med SC-Contur<br />

7<br />

2<br />

3<br />

6<br />

5<br />

4<br />

Fig. D–47<br />

1 Mediemærkning<br />

2 Spindeltætning, EPDM<br />

3 Ventilhoved af rødgods med EPDM-ventilpakning<br />

4 Prestilslutning med SC-Contur<br />

5 Ventilhus og -legeme i rødgods<br />

6 Rustfast stålventilsæde<br />

7 Ventilhus<br />

8 Stillingsindikator<br />

51


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Anvendelse sammen med <strong>Viega</strong> presfittingssystemer<br />

Easytop skråsædeventiler anvendes – afhængigt af materiale – sammen med følgende<br />

presfittingssystemer:<br />

Anvendelsesområder<br />

Ventilmateriale Materiale Presfittingssystem<br />

Easytop Inox skråsædeventiler Rustfrit stål Sanpress Inox<br />

Easytop skråsædeventiler Rødgods Sanpress / Profipress<br />

Tab. D–9<br />

Easytop<br />

skråsædeventiler<br />

Til systemerne<br />

– Sanpress Inox<br />

– Sanpress<br />

– Profipress<br />

Fig. D–48<br />

Easytop<br />

skråsædeventiltyper<br />

– Skråsædeventil<br />

– Kombineret<br />

Skråsæde/kontra<br />

– Tilbageløbsspærring<br />

(kontraventil)<br />

Fig. D–49<br />

52


1 Drikkevandsinstallation – Komponenter<br />

Tekniske Data – Udførelser<br />

QQEgnet til alle former for drikkevand<br />

QQI overensstemmelse med de tyske DVGW-AB-W270 og KTW (Kunststof i drikkevand)<br />

- anbefaling<br />

QQStørrelser – <strong>metal</strong>systemer: 15 – 54 mm<br />

QQPressetilslutninger med SC-Contur<br />

QQUdvendigt gevind iht. EN ISO 228-1; størrelser: DN 15 til DN 50<br />

QQLydisolering L ap ≤ 20 dB (A)<br />

QQDriftstemperatur T maks. = 90 °C<br />

QQDriftstryk<br />

p maks. = 16 bar<br />

Fordele<br />

QQSpindeltætning vedligeholdelsesfri<br />

QQPladsbesparende konstruktion uden spindelstigning<br />

QQKorrosionssikkert ventilsæde af rustfrit stål<br />

QQVentiltop med reduceret dødvolumen (stagnation)<br />

QQEnkel lagring, da tilbehøret leveres separat<br />

QQPræcis aktivering med servoteknik<br />

QQHus med nøgleflader for enkel montering<br />

QQLille tryktab<br />

Tilbehør<br />

Til Easytop skråsædeventiler fås følgende tilbehør:<br />

QQEasytop isoleringskappe<br />

QQEasytop tømme/aftapningsventil (rustfrit stål og rødgods)<br />

QQEasytop forlængerstykke (rustfrit stål og rødgods)<br />

Easytoptømme/aftapningsventil<br />

Easytopforlængerstykke<br />

Fig. D–50 Fig. D–51<br />

53


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Isoleringskappe<br />

De selvsiddende isoleringskapper i EPP (Ekspanderet Polypopylen) fås i alle størrelser<br />

og passer til alle skråsædeventiler i alle varianter.*<br />

Easytop skråsædeventiler med tømmeventil kan også forsynes med isoleringskappe. I<br />

så fald indsættes der forlængelsesstykker af rødgods eller rustfrit stål i forbindelse med<br />

monteringen. Isoleringskapperne er udstyret med brudpunkter, som gør det let at tilpasse<br />

dem til forholdene på montagestedet. Rørledningens isolering slutter fuldstændig<br />

tæt til isoleringskapperne.<br />

Easytop<br />

skråsædeventil<br />

Tilbehør:<br />

Isoleringskappe<br />

med brudpunkt<br />

til tømmeventil<br />

Isoleringskappe<br />

og isoleret rørledning<br />

Fig. D–52 Fig. D–53<br />

54


1 Drikkevandsinstallation – Komponenter<br />

Easytop Inox<br />

skråsædeventil<br />

Installation i en<br />

koldtvandsledning<br />

Fig. D–54<br />

Easytop<br />

skråsædeventil<br />

Stikledning til<br />

drikkevand med Easytop<br />

tilslutningsplade for<br />

vandmåler<br />

Fig. D–55<br />

55


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Easytop<br />

skråsædeventil<br />

Varmtvandsfordeling<br />

med Easytop skråsædeventiler<br />

og cirkulationsreguleringsventiler<br />

uden<br />

isoleringskapper<br />

Fig. D–56<br />

56


1 Drikkevandsinstallation – Komponenter<br />

Tryktab for Easytop<br />

skråsædeventiler<br />

Tryktab for KVR-ventiler/tilbageløbsspærringer<br />

Tryktab Δp [mbar]<br />

Tryktab Δp [mbar]<br />

Volumenstrøm<br />

.<br />

V [l / min]<br />

Fig. D–57<br />

Volumenstrøm<br />

.<br />

V [l / min]<br />

Fig. D–58<br />

57


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Easytop XL-skråsædeventiler med flangetilslutning<br />

Easytop XL-skråsædeventiler med flangetilslutning iht. EN 1092-1 anvendes hovedsageligt<br />

i fordelingssystemer eller som afspærringsventiler i koldt- og varmtvandsinstallationer.<br />

En overgangsflange muliggør overførsel til <strong>Viega</strong> presfittingssystemer i <strong>metal</strong> Sanpress<br />

Inox XL, Sanpress XL og Profipress XL.<br />

Easytop XL–<br />

skråsædeventiler<br />

Iht. EN 558-2<br />

Fig. D–59<br />

Tekniske data<br />

QQDN 50, 65, 80, 100<br />

QQLydisoleringsværdier<br />

L ap ≤ 20 dB (A)<br />

QQDriftstemperatur T max = 90 °C<br />

QQDriftstryk p max = 16 bar (PN 16)<br />

QQInstallation i indikeret strømningsretning<br />

Egenskaber<br />

QQVarme og kolde drikkevandsinstallationer<br />

QQHus i rødgods<br />

QQFast flange iht. EN 1092-1<br />

QQVentilsæde i rustfast stål<br />

QQTømmeprop og prøveudtagningssted<br />

QQSpindel og tætning af EPDM, vedligeholdelsesfri<br />

QQVentiltop uden dødvolumen (stagnation)<br />

QQUden spindelstigning<br />

QQStillingsindikator for åben/lukket<br />

QQMedieindikator på aktiveringsgrebet (grøn/rød)<br />

QQPræcis aktivering med servoteknik<br />

Tilbehør<br />

QQTømmeventil G 1/4 (≤ DN 50), G 3/8 (≥ DN 65)<br />

58


1 Drikkevandsinstallation – Komponenter<br />

Eksempler på anvendelse<br />

Sanpress Inoxfordelingsledninger<br />

Tilførselsrør med<br />

Easytop XLskråsædeventil<br />

DN 100<br />

Fordelerafgange med<br />

Easytop XL-skråsædeventiler<br />

DN 80 og DN 50<br />

med Sanpress Inox XLovergangsflanger<br />

Fig. D–60<br />

Profipressfordeler<br />

Fordelerafgange 54 /<br />

64,0 og 76,1 mm med<br />

Easytop XL-skråsædeventiler<br />

med<br />

Profipress XL- og<br />

Sanpress XL-flangeadaptere<br />

Fig. D–61<br />

Flangeadaptere<br />

Sanpress XL<br />

Profipress XL<br />

Sanpress Inox XL<br />

Fig. D–62<br />

59


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Easytop prøveudtagningsventil*<br />

Kvalitetskontrol jf. miljøministeriets bekendtgørelse om vandkvalitet og tilsyn med<br />

vandforsyningsanlæg, underkastes kemisk og mikrobiologisk kontrol med regelmæssige<br />

mellemrum. Prøveudtagningsventilen er udviklet, for at denne kontrol kan finde<br />

sted under laboratorielignende forhold uden ydre påvirkning af parametrene. Den<br />

består af en fast installeret udtagningsventil uden dødvolumen og en aftagelig aktiveringsenhed,<br />

som kan steriliseres, og som kun anvendes til udtagningen.<br />

Alle dele af aktiveringsenheden, som kommer i berøring med vandet, er af rødgods og<br />

kan derfor f.eks flammesteriliseres på stedet.<br />

Ventilens konstruktion<br />

2<br />

3 4<br />

1<br />

6<br />

5<br />

7<br />

Fig. D–63<br />

1 Håndventil<br />

2 Aktiveringsenhed<br />

3 Fjederbøjle<br />

4 Udtagningsventil G 3/8<br />

5 Udtagningsventil G 1/4<br />

6 Beskyttelseshætte<br />

7 Udtagsbøjning<br />

60


1 Drikkevandsinstallation – Komponenter<br />

Håndtering<br />

Aktiveringsenheden or monteres med fjederbøjlen på den fastmonterede<br />

(i rørledning eller f.eks. en spærreventil) udtagningsventil . Udtagningen foretages<br />

ved at aktivere ventilen ved hjælp af håndhjulet.<br />

Efter prøveudtagningen afmonteres aktiveringsenheden, steriliseres og opbevares<br />

under laboratorieforhold, til den skal bruges igen. Udtagnings ventilen bliver siddende<br />

i installationen og beskyttes med en kunststofhætte (se ill. T-62 til T-64).<br />

Aktiveringsenhed<br />

Aktiveringsenheden monteres på prøveudtagningsventilen og holdes på plads af en<br />

fjederbøjle, så prøveudtagningen kan gennemføres. Positionen kan drejes 360° i trin<br />

på 45°. Da udtagsbøjningen også kan drejes 360°; kan prøveudtagningsventilen monteres<br />

næsten overalt i systemet.<br />

Prøveudtagningsventil<br />

Aktiveringsenhed<br />

og udløbsbøjning<br />

kan drejes 360°<br />

Fig. D–64<br />

Særlige tekniske egenskaber<br />

QQPrøveudtagning under de sikrest mulige forhold<br />

QQFlammesteriliserbar og uden dødvolumen<br />

QQBåde aktiveringsenhed og udløbsbøjning kan drejes 360°<br />

QQDele med mediekontakt er af rødgods og kan let steriliseres<br />

QQUdtagningsenheden monteres uden værktøj<br />

QQBestår af to dele – udtagningsventilen bliver siddende i anlægget<br />

61


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Prøveudtagningsventil<br />

Sikret<br />

– Ventilen kan åbnes<br />

Usikret<br />

– Aktiveringsenheden<br />

kan tages af<br />

Fig. D–65 Fig. D–66<br />

Easytop XL–<br />

skråsædeventiler<br />

Med overgangsflanger<br />

Med presforbindelse<br />

Fig. D–67 Fig. D–68<br />

62


1 Drikkevandsinstallation – Komponenter<br />

Easytop ligesædeventil til forsænket installation<br />

Til afspærring af etager eller etageenheder.<br />

Idet der i Danmark er krav om udskiftelighed og at en evt. utæthed skal kunne konstateres<br />

vil ventiltyperne i det følgende, måske kunne monteres lovligt i Danmark – Ventiler<br />

kan problemfrit monteres i f.eks. Tyskland.<br />

Egenskaber<br />

QQVelegnet til alle typer drikkevand – ventilhus af rødgods, rustfrit stålventilsæde<br />

QQDriftstemperatur T maks. = 95 °C<br />

QQDriftstryk<br />

p maks. = 10 bar<br />

QQOverdel uden dødvolumen<br />

QQMontagedybden kan varieres med op til 129 mm<br />

QQStøjsvag<br />

QQModstandsdygtig over for tilkalkning<br />

QQLet at betjene<br />

QQÈn overdel til alle størrelser<br />

Tilslutningsvarianter<br />

Tilslutningsvarianter<br />

Med<br />

– Indvendigt gevind iht.<br />

EN 10226<br />

– Sanpress<br />

Fig. D–69<br />

Ventilens konstruktion<br />

Ventilkomponenter<br />

1<br />

3<br />

2<br />

4<br />

Fig. D–70<br />

1 Ventillegeme<br />

2 Aktiveringsaksel<br />

3 Beskyttelseskappe<br />

4 Beskyttelseshætte<br />

63


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Easytop friløbsventiler til forsænket installation<br />

Isolering<br />

Montering<br />

Easytop friløbsventiler til forsænket installation anvendes til afspærring af etage- og<br />

gulvenheder. De egner sig til drikkevandsinstallationer (varmt / koldt) iht. TrinkwV<br />

(Tyskland) og DIN 50930-6. På grund af deres konstruktion har friløbsventiler en lille<br />

vandring. Som kuglehanen kan de åbnes eller lukkes helt med en kvart omgang.<br />

Til rørledninger, der kræver isolering, skal der anvendes enheder med isolerende muffer<br />

af byggemateriale klasse B1, som opfylder kravene i EnEv (Tyskland) og DIN 4102-4.<br />

Installation kan foretages i murværk (våd konstruktion) og i tørre konstruktioner<br />

(træ/gipsvægs- / kanalinstallationer).<br />

Easytop friløbsventil<br />

til forsænket installation<br />

Fremstillet af rødgods,<br />

med presforbindelse<br />

Med<br />

gevindforbindelse Rp<br />

Fig. D–71 Fig. D–72<br />

Tekniske data<br />

QQForbindelser: Presforbindelse 15, 18 og 22 mm, gevind Rp 1/2 og Rp 3/4<br />

QQDriftstryk 10 bar (PN 10)<br />

QQDriftstemperatur 90 °C<br />

QQInstallation er mulig uafhængigt af strømningsretning<br />

Egenskaber<br />

QQTil alle typer drikkevand iht. TrinkwV (Tyskland) og DIN 50930-6<br />

QQÅbnes/lukkes med en kvart omgang<br />

QQVentilhus og -top af rødgods iht. DIN 50930-6<br />

QQVentiltop uden dødvolumen (stagnation) - med vedligeholdelsesfri spindeltætning<br />

QQKan anvendes i byggefasen ved brug af beskyttelseshætter<br />

QQKan kombineres med udstyrssættene 2236 og 2236,10<br />

QQAfspærringskomponenten kan udskiftes – en type til alle slags ventiler<br />

QQOpfylder de tyske DVGW-AB W270 og KTW-anbefaling<br />

64


1 Drikkevandsinstallation – Komponenter<br />

Montagemål<br />

Montagedybde<br />

≥ 43 (A)<br />

≤ 130 mm (B)<br />

Fastgøringssæt<br />

”Forside”<br />

Model 2235.90<br />

Fig. D–73 Fig. D–74<br />

Ventilkomponenter<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

Fig. D–75<br />

1 Ventilhus<br />

2 Ventilsæde<br />

3 Ventiltop<br />

4 Beskyttelseskappe<br />

5 Aktiveringsaksel<br />

6 Beskyttelseshætte<br />

65


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Fastgøring/tætning<br />

Til fastgøring af ventilen har systemet forskellige løsninger og sæt.<br />

Fastgøringssæt for<br />

Til forvæg,<br />

sandwichmontage<br />

Fig. D–76 Fig. D–77<br />

Fastgøring over væggennemføring<br />

De to omløbermøtrikker og underlagsskiver klemmer beskyttelseskappen fast i væggen<br />

(fx gipsplade) i mørtelfri elementvæg.<br />

Tætning gennem muren sikres ved hjælp af en selvklæbende tætningsflange på forsiden<br />

af væggen. Beskyttelseshætten giver til enhver tid adgang til ventilen for betjening.<br />

Fastgøringssæt bag<br />

På normal vis<br />

i stolpebyggeri<br />

Fig. D–78 Fig. D–79<br />

Fastgøring ved hjælp af fastgøringssættet<br />

Den lydisolerende fastgøringsplade skrues sammen med ventillegemet og monteres<br />

på en montageskinne (fx en profilskinne).<br />

Tætning gennem muren sikres ved hjælp af en selvklæbende tætningsflange på forsiden<br />

af væggen. Beskyttelseshætten giver til enhver tid adgang til ventilen for betjening.<br />

66


1 Drikkevandsinstallation – Komponenter<br />

Udstyrssæt<br />

Til Easytop ligesædeventil til forsænket montering.<br />

Fig. D–80<br />

Fig. D–81<br />

Isoleringskappe<br />

Den selvsiddende isoleringskappe af EPP-isoleringsmateriale opfylder kravene i Tyskland<br />

(EnEV) med hensyn til reduktion af varmeafgivelse.<br />

Én udførelse passer til alle tilslutnlingstyper.<br />

Fig. D–82<br />

67


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Easytop kuglehaner<br />

Maksimalt tilladte<br />

værdier<br />

Godkendt af DVGW med prestilslutninger til rørsystemerne, for aktuelle godkendelser<br />

i Danmark henvises til www.etadanmark.dk<br />

QQSanpress Inox<br />

QQSanpress<br />

QQProfipress<br />

Egenskaber<br />

QQVelegnet til alle typer drikkevand – ventilhus af rødgods<br />

QQMed prestilslutning, indvendigt gevind iht. EN 10226-1 eller udvendigt gevind iht.<br />

EN ISO 228-1<br />

QQDriftstemperatur T maks. = 110 °C<br />

QQDriftstryk<br />

p maks. = 16 bar<br />

QQVedligeholdelsesfri spindel, dog anbefales 2 x årlig motionering.<br />

QQMediemærkning på aktiveringsgrebet kan udskiftes<br />

QQYderligere anvendelsesmuligheder: Varme-, trykluft-, regnvandsanlæg, industrianlæg<br />

osv.<br />

QQIsoleringskapper som tilbehør<br />

Prestilslutning<br />

Fig. D–83 Fig. D–84<br />

Pres-/<br />

gevindtilslutning<br />

Gevindtilslutning<br />

iht. EN ISO 228-1<br />

Fig. D–85 Fig. D–86<br />

Gevindtilslutning<br />

iht. EN 10226-1<br />

Pumpekuglehane<br />

68<br />

Fig. D–87 Fig. D–88


1 Drikkevandsinstallation – Komponenter<br />

Easytop cirkulationsreguleringsventil<br />

Til styring af varmedesinficeringsprocessen med temperaturer fra 70 °C til 75 °C i alle<br />

strenge. Installeres mellem varmtvandsbeholderens udløb og cirkulationstanken. Indløb<br />

svarende DVGW-Arbeitsblatt W 553.<br />

Funktion<br />

Cirkulationsreguleringsventilen regulerer strømningsvolumenet i cirkulationsstrengen,<br />

og sikrer den ønskede temperatur ved tappestedet. Endvidere giver den mulighed for<br />

varmedesinficering fra 70 °C.<br />

Desinficeringsprocessen kan udløses manuelt (kedelstyring) eller via processtyring. Derved<br />

åbnes reguleringsmodulet som regulerer den hydrauliske justering, mens alle<br />

strenge kortvarigt varmedesinficeres ved 70–75 °C.<br />

Easytop cirkulationsreguleringsventil model 2281<br />

6<br />

1<br />

5<br />

2<br />

4<br />

3<br />

Fig. D–89<br />

1 Temperaturindstilling<br />

2 Cirkulationsreguleringsmodul<br />

3 Presfitting med SC-Contur<br />

4 Ventilhus af rødgods<br />

5 Plads til termometer eller temperaturføler<br />

6 Desinficeringsmodul<br />

69


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Udførelser<br />

Cirkulationsventilerne fås med enten prestilslutning – til kobberrør eller Sanpress-rør –<br />

eller gevindtilslutning iht. EN ISO 228-1. De kan således anvendes til alle rørledningssystemer.<br />

Begge varianter kan leveres med følgende tilbehør:<br />

QQKuglehane<br />

QQTømmeventil, også med forlængerstykke til isolerede ledninger<br />

Tilbehør<br />

Easytop cirkulationsreguleringsventilens funktionssikkerhed kan forøges ved hjælp af<br />

et bredt sortiment af tilbehør<br />

Fig. D–90<br />

Aktiveringsenhed<br />

Elektronisk aktivering af desinfektion via styreboks,<br />

model 1465.5<br />

Fig. D–91<br />

Kuglehane<br />

Til afspærring af cirkulationsstigrøret, med<br />

tømmepropper.<br />

Fig. D–92<br />

Termometer<br />

Temperaturviser, mekanisk.<br />

Fig. D–93<br />

Temperaturføler<br />

70


1 Drikkevandsinstallation – Komponenter<br />

Smartloop-Inliner cirkulationsledning<br />

Anvendelse<br />

Systemet anvendes med en intern cirkulationsledning i varmtvandsinstallationer,<br />

i varmtvandsstigrør fra 28 mm, med <strong>Viega</strong> presfittingssystemerne.<br />

Til etablering af en varmtvandsinstallation med Smartloop-Inliner teknik, anbefaler<br />

vi at bruge <strong>Viega</strong> Viptool projekteringssoftwaren.<br />

Installationen må kun udføres af kvalificeret fagpersonale og kun med brug af<br />

<strong>Viega</strong> komponenter. Anvendelse til andet end de her beskrevne skal afstemmes<br />

med vores fabrik i Attendorn.<br />

Systemet består af følgende dele:<br />

QQTilslutningssæt med endefittingog Smartloop-rørforbindelser<br />

QQSmartloop-rør, fleksibelt<br />

Tilslutningssæt til<br />

Smartloop-Inliner<br />

Fig. D–94 Fig. D–95<br />

Smartloop-rør<br />

Hygiejnisk indpakket indtil<br />

monteringen<br />

Fig. D–96<br />

71


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Systembeskrivelse<br />

Varmtvandscirkulationen i røret opnås ved kontinuerligt at lede vand tilbage til varmtvandsanlægget<br />

fra stigrørets T-stykke. Dette sikrer, at der er tilstrækkeligt varmt vand i<br />

hver etageafgang.<br />

Cirkulationsrør<br />

Smartloop-Inliner<br />

7<br />

1<br />

1<br />

6<br />

5<br />

2<br />

Fig. D–97<br />

4<br />

3<br />

1 Etageafgang varmt vand<br />

2 Varmtvandsfordelingsrør<br />

3 Cirkulationssamlerør<br />

4 Forbindelser<br />

5 Indvendigt liggende cirkulationsrør<br />

6 Varmtvandsstigrør<br />

7 Endefitting<br />

72


1 Drikkevandsinstallation – Komponenter<br />

Temperaturinddeling<br />

Sammenlignet med konventionelle kredsløb falder temperaturen i stigrørsområdet<br />

ikke kontinuerligt i strømningsretning ved Smartloop-Inliner kredsløbet.<br />

Den laveste temperatur på stigledningsstrækningen er dermed heller ikke<br />

udgangstemperaturen fra stigledningssystemet, men temperaturen i det område 2 ,<br />

hvor vandet ledes fra blænden i 1 til cirkulations-inlineren. I større systemer med flere<br />

ledninger fører dette til en forøgelse af temperaturen i cirkulationssamlerøret. Det<br />

resulterer i, at returvandets temperatur er højere end ved konventionelle cirkulationssystemer,<br />

hvilke igen har fordele hvad angår energi.<br />

1 1<br />

1 1<br />

1 1<br />

2<br />

60<br />

°C<br />

55<br />

Fig. D–98<br />

1 Etageafgang varmt vand<br />

2 Varmtvandsfordelingsrør<br />

73


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Fordele<br />

QQ20 til 30 % mindre varmefordelingstab<br />

QQSikring af vandskvaliteten på grund af temperaturopretholdelse og cirkulation<br />

QQMindre varmeafgivelse i skakten reducerer opvarmningen af koldtvandsledningen<br />

QQCa. 20 % færre omkostninger til kerneboringer, brandbeskyttelse, rørisolering og<br />

fastgøring<br />

QQLavere monteringsomkostninger, da der ikke er behov for et separat udlagt cirkulationsledningssystem<br />

QQMere plads i boligen på grund af mindre installationskakte<br />

QQFleksibelt Smartloop-rør tillader parallel forskydning/spring i stigrøret<br />

Forskudt stigrør<br />

Fig. D–99<br />

74


1 Drikkevandsinstallation – Komponenter<br />

Komponenter<br />

Tilslutningssæt<br />

Model 2276.1<br />

1<br />

4<br />

2<br />

4<br />

3<br />

1 Lukkeprop<br />

2 Adapter<br />

3 Forbindelsesstykke<br />

4 Presmuffe<br />

Fig. D–100<br />

2<br />

’Trække’ fitting<br />

Model 2276.9<br />

1<br />

Fig. D–101<br />

1 Støttebøsning<br />

2 Hoved<br />

1<br />

Samlenippel<br />

Model 2276.8<br />

Fig. D–102<br />

2<br />

2<br />

1 Samlenippel<br />

2 Presmuffe<br />

Smartloop-rør<br />

Model 2007.3<br />

Fig. D–103<br />

75


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Forberedelser<br />

Montering<br />

De nødvendige komponenter og værktøjer til monteringen af en Smartloop-Inliner i<br />

Sanpress, Sanpress Inox eller Profipress stigrør er vist to sider tilbage. Smartloop-rørets<br />

presforbindelse kan udføres med manuelt presværktøj (model 2782) eller prestangen<br />

(model 2799.7) og en egnet presmaskine – vi anbefaler at anvende <strong>Viega</strong> presmaskinerne<br />

PT2, PT3H, PT3-AH, PT3-EH eller Pressgun 4E og 4B.<br />

Montering med parallel forskydning<br />

Det fleksible Smartloop-rør muliggør også montering i stigrør med forskydning. Murfremspring<br />

og spring i skakter, er ingen hindring for professionel montering.<br />

Materialprüfungsamt NRW (materialeprøvningsinstitut i Nordrhein-Westfalen, Tyskland)<br />

har inspiceret og undersøgt monteringen i parallel forskydning af stigrøret, således<br />

at de nødvendige krav overholdes.<br />

Lodret forskydning af stigrøret i en position har hverken indflydelse på Inlinerens funktion<br />

eller montering. Andre installationssituationer end de beskrevne skal afstemmes<br />

med vores fabrik i Attendorn.<br />

Til montering af Smartloop-røret anbefaler vi at anvende ’trække fitting’ eller, til større<br />

forskydninger/spring, én af de viste metoder.<br />

Maksimal forskydning – monteringsforslag<br />

mindste<br />

Spring<br />

45 ° 90 °<br />

forskydning<br />

Forskydning<br />

L [mm]<br />

Anvendte<br />

komponenter<br />

Tab. D–10<br />

≥ 40 – 45 ≥ 45 – 500 ≥ 150 – 500<br />

1 stk. 45° bøjning<br />

muffe/muffe<br />

1 stk. 45° bøjning<br />

muffe/nippel<br />

2 stk 45° bøjninger<br />

muffe/muffe<br />

2 stk. 45° bøjning muffe/muffe<br />

2 stk. 45° bøjning muffe/nippel<br />

76


1 Drikkevandsinstallation – Komponenter<br />

Montering med lille eller ingen forskydning<br />

Montering af stigrøret med efterfølgende montering af Smartloop-røret.<br />

1<br />

– Stigrøret bygges op og et T-stykke<br />

presses på foroven og forneden.<br />

− Til etageafgang anvendes min. Ø 22,<br />

som umiddelbart derefter kan mindskes.<br />

2<br />

Ved en lille forskydning,<br />

kombineres to 45 ° bøjninger: den<br />

øverste med muffe/nippel, den<br />

nederste med fitting med to<br />

pressmuffer.<br />

3<br />

Træk fitting (hjælpeværktøj),<br />

model 2276.9), kan lette monteringen<br />

af Smartloop-røret.<br />

Fig. D–104<br />

Fig. D–105<br />

Fig. D–106<br />

4<br />

Smartloop-røret føres oppefra ind i<br />

varmtvandsstigrøret, indtil røret stikker<br />

ca. 30 cm ud af stigrørets nederste<br />

ende.<br />

5<br />

Smartloop-røret afkortes<br />

tilsvarende.<br />

6<br />

− Presmuffen skubbes på den<br />

øverste rørende.<br />

– Endeforbindelsen skubbes ind i<br />

røret, og indstiksdybden<br />

kontrolleres vha. skuehullet.<br />

Fig. D–107<br />

Fig. D–108<br />

Fig. D–109<br />

7<br />

− Den manuelle pressetang sættes på<br />

i en ret vinkel.<br />

– Pressetangen trykkes helt sammen,<br />

indtil den kan åbnes igen.<br />

Smartloop-røret skal tilpasses.<br />

8<br />

Endeforbindelsen sættes ind i varmtvandsstigrørets<br />

øverste T-stykke.<br />

9<br />

Forbindelsen presses sammen med<br />

et passende presværktøj.<br />

Fig. D–110<br />

Fig. D–111<br />

Fig. D–112<br />

77


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Fig. D–113<br />

Fig. D–114<br />

Fig. D–115<br />

10<br />

− Smartloop-røret på den<br />

nederste ende spændes med en<br />

monteringstang og afkortes vinkelret<br />

til en længde på 40 mm under<br />

T-stykket.<br />

− Smartloop-røret gøres fast.<br />

11<br />

− Presmuffen skubbes på den<br />

nederste Smartloop-rørende.<br />

− Forbindelsens overgangsstykke<br />

skubbes ind i Smartloop-røret, og<br />

indstiksdybden kontrolleres vha.<br />

skuehullet.<br />

12<br />

Den manuelle prestang sættes vinkelret<br />

på og presses sammen, indtil<br />

tangen igen kan åbnes.<br />

Fig. D–116<br />

Fig. D–117<br />

13<br />

Fig. D–118<br />

Forbindelsen skubbes til overgangsstykkets<br />

ende og presses fast.<br />

14<br />

− Monteringsværktøjet fjernes.<br />

− Forbindelsen skubbes til<br />

det nederste T-stykkes ende på<br />

varmtvandsstigrøret og presses<br />

sammen.<br />

15<br />

− Varmtvands- og cirkulationsrøret<br />

forbindes til ledningerne i kælder.<br />

− Hele rørsystemet lækprøves.<br />

I Tyskland i henhold til ZVSHK<br />

databladet.<br />

78


1 Drikkevandsinstallation – Komponenter<br />

Reparationsmuffe<br />

I tilfælde af et beskadiget stigrør eller længdeudvidelse af installationen repareres<br />

Smartloop-røret med samleniplen model 2276.8 og stigrøret med glidebøsningen<br />

model 2215.4 og 2215.5.<br />

1 2 3<br />

Både installationsrøret og Smartloop-røret<br />

skæres over.<br />

Med en fintandet sav eller rørskærer<br />

skæres rørstykket – glidebøsningens<br />

længde – ud af stigrøret.<br />

Glidemuffen model 2215.5 skubbes<br />

på det nederste rør.<br />

Fig. D–119<br />

Fig. D–120<br />

Fig. D–121<br />

4 5 6<br />

Glidemuffen med indstiksdelen<br />

model 2215.4 skubbes på<br />

det øverste rør.<br />

Samleniplen model 2276.9 sættes på<br />

Smartloop-røret. (cirkulationsrøret).<br />

– Samleniplen presses sammen.<br />

– Den manuelle pressetang sættes<br />

vinkelret på, og den presses sammen,<br />

indtil tangen igen kan åbnes.<br />

Fig. D–122<br />

Fig. D–123<br />

Fig. D–124<br />

7 8 9<br />

Glidemufferne sættes sammen.<br />

Glidemufferne skal placeres i en sådan<br />

position, at indstiksdybden i presmuffen<br />

er sikret.<br />

Presforbindelsen presses sammen<br />

med en egnet presmaskine.<br />

Fig. D–125<br />

Fig. D–126<br />

Fig. D–127<br />

79


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

<strong>Viega</strong> tætningselementer<br />

Elastomere tætninger<br />

Anvendt i <strong>metal</strong> rørsystemer<br />

Fig. D–128<br />

I <strong>Viega</strong> rørledningssystemer anvendes 4 elastomere. Hver type har en individuel karakteristik<br />

og er afhængig af hvilket medie de anvendes i. NBR anvendes kun i koldt vand<br />

som f.eks. køleanlæg og jordlagte forsyningsledninger. HNBR tætningselementer har<br />

en god ‚kulde’ elasticitet, hvilket har stor betydning i forbindelse med udendørs liggende<br />

gasinstallationer. EPDM kvaliteten af <strong>Viega</strong>s tætningselementer byder på fremragende<br />

egenskaber for alle øvrige vand og varmeanvendelser også over 70 °C. Netop<br />

<strong>metal</strong> rørsystemer anvendes ofte, også ved saneringer og udvidelser i industrianlæg<br />

og industrien hvor der optræder høje driftstemperaturer. Af disse årsager kan Presfitting<br />

med EPDM tætningselementer anvendes bredt i varme og drikkevands systemer.<br />

EPDM (Ethylen-Propylen-Dien-Monomer gummi) er en peroxid vulkaniseret syntetisk<br />

gummitype. Den er meget modstandsdygtig overfor ældning, Ozon, sollys, vejr og<br />

miljøpåvirkninger samt alkaliske stoffer og kemikalier. Derfor kan brugerne regne med,<br />

at <strong>Viega</strong> presfitting er tætte, når de definerede driftsbetingelser overholdes.<br />

Sluttelig kan nævnes FKM tætningselement som opfylder de højeste krav med hensyn<br />

til driftstemperatur, som f.eks. ved solfangeranlæg med rørkollektorer.<br />

<strong>Viega</strong> presfitting til drikkevandsanlæg leveres som standard, fabriksmonteret med<br />

EPDM. På grund af den høje modstandsdygtighed overfor hedt vand og damp, kan<br />

EPDM også anvendes som tætning i varmeanlæg, i armaturer og husholdningsapparater<br />

(vaskemaskiner, pumper, opvaskemaskiner etc.) til driftstemperatur på T max = 110 °C.<br />

80


1 Drikkevandsinstallation – Komponenter<br />

Blandingsinstallation<br />

Installation i strømningsretningen<br />

System Foran galvaniseret stål Efter galvaniseret stål<br />

Sanpress Inox<br />

Sanpress<br />

Profipress –<br />

Tab. D–11<br />

Isoleringsforskruning<br />

I vandssystemer med høj hårdhed, bør der installeres Sanpress-isolerings forskruninger<br />

for at undgå galvanisk korrosion.<br />

Sanpress isoleringsforskruning<br />

1 2 3 4 5<br />

Fig. D–129<br />

1 Gevindstuds i rødgods med indvendigt cylindrisk gevind Rp iht. DS/EN 10226<br />

2 EPDM-fladringspakning, ikke elektrisk ledende<br />

3 Sanpress / Profipress presstuds af rødgods med SC-Contur<br />

4 Isolieringsring ikke elektrisk ledende (til adskillelse)<br />

5 Omløber<br />

81


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Tilslutning varmtvandsbeholder<br />

Hvis der anvendes isoleringsforskruninger til beholdertilslutningen, må selve beholderen ikke<br />

indgå i potentialudligningen.<br />

Potentialeudligning<br />

Ved beholdertilslutningen<br />

<br />

Brugsvand, varmt<br />

<br />

Cirkulation<br />

<br />

Opvarmning, fremløb<br />

Tilbageløb<br />

<br />

Drikkevand, koldt<br />

Fig. D–130<br />

<br />

Potential-jord<br />

Potentialudligning<br />

Efter en evt. sanering af dele af rørnettet, skal potentialeudligningen genoprettes, når arbejdet<br />

er afsluttet. Når der anvendes isoleringsforskruninger, skal der slås bro over delstrækningen<br />

med en NYM-J 1 x 6 mm 2 jordledning.<br />

Isoleringsforskruning<br />

Fig. D–131<br />

Den indsatte delstrækning mellem isoleringsforskruningerne indgår ikke i potentialudligningen.<br />

Naionale regler skal overholdes.<br />

82


1 Drikkevandsinstallation – Montering<br />

Montering<br />

Rørstørrelser og fastgøringsintervaller for rør [m]<br />

Standard<br />

Størrelser<br />

[mm]<br />

Sanpress<br />

Sanpress<br />

Inox<br />

Profipress<br />

Fastgøringsafstand<br />

[m]<br />

12 – 1,25<br />

15 1,25<br />

18 1,50<br />

22 2,00<br />

28 2,25<br />

35 2,75<br />

42 3,00<br />

54 3,50<br />

XL<br />

Tab. D–12<br />

64,0 – 4,00<br />

76,1 4,25<br />

88,9 4,75<br />

108,0 5,00<br />

Opbevaring og transport<br />

Sanpress-rør af rustfrit stål er tyndvæggede, svejsede ledningsrør i materiale (Werkstoff)<br />

1.4401 eller 1.4521 i overensstemmelse med EN 10088.<br />

For ikke at forringe de hygiejniske egenskaber ved beskadigelser, skal der tages højde<br />

for følgende henvisninger vedrørende transport og opbevaring af rørene.<br />

QQFjern først beskyttelsesfolier og beskyttelseshætter umiddelbart før anvendelse.<br />

QQMå ikke opbevares ubeskyttet på hårde gulve. Anvend strøer.<br />

QQDer må ikke påklæbes beskyttelsesfolie el.lign.<br />

QQMå ikke trækkes ud over ladkanter.<br />

QQRengøring af overfladen må kun foretages med rengøringsmiddel til rustfrit stål.<br />

Kobberrør opfylder kravene gevind iht. DS/EN 1057. Ved opbevaring og transport skal<br />

der tages højde for producentens angivelser.<br />

Rustfri stålrør<br />

Kobberrør<br />

83


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Afkortning af rør<br />

Kobberrør og rustfri stålrør kan afkortes med en rørskærer, en fintandet <strong>metal</strong>sav eller med<br />

en elektrisk sav.<br />

Ved afkortning skal man være opmærksom på følgende:<br />

QQDer må ikke anvendes vinkelsliber eller skærebrænder.<br />

QQDer må kun anvendes værktøj, der er egnet til det pågældende rørmateriale.<br />

QQBløde kobberrør (ringmateriale) og kobberrør, der leveres med isolering, må kun<br />

afkortes med en dertil egnet sav.<br />

QQDer sluttes af med at afgrate rørene indvendigt og udvendigt.<br />

Bukning af rør<br />

Sanpress-rør i rustfrit stål eller kobberrør skal bukkes med en dertil egnet maskine. Bukkeradius<br />

findes i rørproducenternes produktinformation. For Sanpress rustfri stålrør og<br />

kobberrør gælder: R ≥ 3,5 x d. Generelt gælder følgende:<br />

QQKorrekt påsætning af presmufferne kræver, at kompensationsstykkerne skal være<br />

lige og mindst 50 mm lange.<br />

QQSpændinger mellem bøjninger og presfittings skal undgås.<br />

QQFør der anvendes bukkespray, skal det kontrolleres, at den er kompatibel med rørmaterialet.<br />

QQRustfri stålrør må kun koldbøjes. Varmebehandling kan resultere i korrosion.<br />

QQVed kobberrør skal producentens anvisninger overholdes.<br />

Rørføring og fastgøring<br />

Til fastgøring af rørene anvendes gængse rørbøjler med kloridfri lydisolerende indlæg.<br />

De generelle regler for fastgøringsteknik er gældende:<br />

QQAnvend kun plugs, som er godkendt af Byggetilsynet.<br />

QQFastgjorte rørledninger må ikke benyttes som holdere for andre rørledninger og<br />

byggekomponenter.<br />

QQRørkroge må ikke anvendes.<br />

For at sikre en fejlfri rørsystemfunktion skal fastgøringsafstandene i Tabel D-12. overholdes.<br />

84


1 Drikkevandsinstallation – Montering<br />

Fastgøringsmetoder<br />

Der kan anvendes fast eller glidende fastgøring af rørledningerne.<br />

Faste fastgøringspunkter forbinder røret med bygningsdelen, så det ikke kan give efter,<br />

mens glidepunkter muliggør aksiale udvidelsesbevægelser.<br />

Fastpunkter skal arrangeres således, at<br />

QQspændinger som følge af længdeændringer så vidt muligt udelukkes, og<br />

QQlige rørledninger kun er fikseret i ét punkt.<br />

Glidepunkter skal være anbragt i tilstrækkelig afstand fra fittings. Der skal tages hensyn<br />

til den forventede udvidelse.<br />

Faste punkter<br />

Glidepunkter<br />

Faste punkter<br />

Hold afstand til fittings<br />

Glidepunkter<br />

Tag højde for<br />

udvidelsesretningen<br />

Fig. D–132 Fig. D–133<br />

Forsænket installation af varme rørledninger<br />

Udvidelsesbevægelser giver knæk- og strømningsstøj. Den samlede ledningsinstallation<br />

skal derfor holdes helt fri af selve bygningen ved hjælp af isolering.<br />

Ved isolering skal følgende overholdes:<br />

QQAnvend kun egnede isoleringsmaterialer.<br />

QQRør må ikke dækkes af fast puds.<br />

QQT-stykker og bøjninger skal isoleres særlig omhyggeligt.<br />

Generelle<br />

anvisninger<br />

85


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Gevind- og flangetilslutninger<br />

Gevind iht.<br />

DS/EN 10226-01<br />

Gevindtilslutninger<br />

Til tætning af gevind ved overgangsstykker til <strong>Viega</strong>-presssystemer må der kun anvendes<br />

gængse hamp- og kloridfri tætningsmaterialer. Teflonbånd kan ikke anbefales, da<br />

det erfaringsmæssigt trækker sig ud af fittings, når der skrues.<br />

Rørforbindelser har koniske udvendige gevind (fx R 3/4) og cylindriske indvendige<br />

gevind (fx Rp 3/4).<br />

Ved montering etableres først gevindforbindelsen og derefter presforbindelsen.<br />

Flangetilslutninger<br />

I <strong>Viega</strong> pressystemer af <strong>metal</strong> fås flangeforbindelser i størrelserne 15,0 til 108,0 mm.<br />

Følgende tilbehør kan leveres:<br />

QQSkruesæt i rustfrit stål og galvaniseret.<br />

QQPakninger af EPDM eller asbestfrit materiale til flangeforbindelser.<br />

Ved monteringen etableres først flangeforbindelsen og derefter presforbindelsen.<br />

Fig. D–134<br />

Fig. D–135<br />

Sanpress Inox<br />

Fast flange<br />

Af rustfrit stål 1.4401 (presmuffe)<br />

15 til 54 mm Model 2359<br />

64,0 til 108,0 mm Model 2359XL<br />

Sanpress<br />

Løs flange, bevægelig<br />

Af stål, pulverlakeret,<br />

med prestilslutning af rødgods<br />

28 til 54 mm Model 2259.5<br />

64 mm (kobber) Model 2459.5XL<br />

76,1 til 108,0 mm Model 2259.5XL<br />

86


1 Drikkevandsinstallation – Montering<br />

Etablering af prestilslutningen<br />

Metalrør 12 – 54 mm<br />

Rustfri stålrør og kobberrør forbindes enkelt og sikkert med en prestilslutning.<br />

Følgende skal bruges:<br />

QQRørskærer eller fintandet stålsav<br />

QQAfgrater og farvestift til afmærkning af indstiksdybden<br />

QQ<strong>Viega</strong> presmaskine med en bakke, der passer til rørdiameteren<br />

Sanpress Inox<br />

Sanpress<br />

Profipress<br />

Nødvendigt<br />

værktøj<br />

Arbejdstrin<br />

1 2<br />

Røret afkortes vinkelret.<br />

Røret afgrates indvendigt og udvendigt.<br />

Fig. D–136<br />

Fig. D–137<br />

3 4<br />

Det kontrolleres, at tætningselementet<br />

er placeret korrekt.<br />

Presfittingen skubbes ind over røret, til<br />

den støder imod.<br />

Fig. D–138<br />

Fig. D–139<br />

QQDer skal anvendes rørskærer eller fintandet stålsav.<br />

QQHvis der anvendes vinkelsliber, udglødes materialet og der opstår risiko for korrosion!<br />

QQDer må ikke anvendes olie eller fedt!<br />

87


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Fig. D–140<br />

Fig. D–141<br />

5 6<br />

Marker indstiksdybden.<br />

Sæt presbakken på presmaskinen. Skub<br />

holdebolten ind, til den går i indgreb.<br />

Fig. D–142<br />

Fig. D–143<br />

7 8<br />

Åbn presbakken, og sæt den vinkelret<br />

på fittingen; kontroller samtidig indstiksdybden.<br />

Start presningen.<br />

Efter afsluttet presning åbnes presbakken.<br />

88


1 Drikkevandsinstallation – Montering<br />

Sanpress XL 76,1 – 108,0 mm<br />

Rustfri stålrør og kobberrør forbindes enkelt og sikkert med en prestilslutning.<br />

QQRørskærer eller fintandet stålsav<br />

QQAfgrater og farvestift til afmærkning<br />

QQ<strong>Viega</strong> presmaskine med en bakke, der passer til rørdiameteren<br />

QQPreskæde i passende størrelse<br />

Sæt trækbakken på <strong>Viega</strong> presmaskinen, og skub holdebolten ind, til den går i indgreb.<br />

Nødvendigt værktøj<br />

Forberedelse<br />

Arbejdstrin<br />

1 2<br />

Røret afkortes vinkelret.<br />

Vær forsigtig ved fastspændingen!<br />

Rørenderne skal absolut være runde.<br />

Fig. D–144<br />

Fig. D–145<br />

3 4<br />

Røret afgrates udvendigt og indvendigt.<br />

Marker indstiksdybden.<br />

ø 76,1 mm = 50 mm<br />

ø 88,9 mm = 50 mm<br />

ø 108,0 mm = 60 mm<br />

Fig. D–146<br />

Fig. D–147<br />

89


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Fig. D–148<br />

Fig. D–149<br />

5 6<br />

Kontroller, at tætningselementet og<br />

skæreringen sidder korrekt.<br />

Skub presfittingen hen til den markerede<br />

indstiksdybde på røret.<br />

Fig. D–150<br />

Fig. D–151<br />

7 8<br />

Sæt preskæden på fittingen, og kontroller,<br />

at positionen er korrekt.<br />

Prestangen åbnes og klikkes ind i preskædens<br />

holdere.<br />

Fig. D–152<br />

Fig. D–153<br />

9 10<br />

Start presmaskinen, og udfør presningen.<br />

Fjern kontrolmærket. Det viser, at forbindelsen<br />

nu er „sammenpresset“.<br />

90


1 Drikkevandsinstallation – Montering<br />

Sanpress Inox XL og Profipress XL 64,0 – 108,0 mm<br />

Rør af rustfrit stål forbindes enkelt og sikkert med en prestilslutning.<br />

QQRørskærer eller fintandet stålsav<br />

QQAfgrater og farvestift til afmærkning<br />

QQ<strong>Viega</strong> presmaskine med en bakke, der passer til rørdiameteren<br />

Sæt ledtrækbakken på <strong>Viega</strong> presmaskinen, og skub holdebolten ind, til den går i indgreb.<br />

Nødvendigt<br />

værktøj<br />

Forberedelse<br />

Arbejdstrin<br />

1 2<br />

Røret afkortes vinkelret.<br />

Pas på ved tilspændingen! Rørenderne<br />

skal absolut være runde.<br />

Fig. D–154<br />

Fig. D–155<br />

3 4<br />

Røret afgrates udvendigt og indvendigt.<br />

Marker indstiksdybden.<br />

ø 64,0 mm = 43 mm<br />

ø 76,1 mm = 50 mm<br />

ø 88,9 mm = 50 mm<br />

ø 108,0 mm = 60 mm<br />

Fig. D–156<br />

Fig. D–157<br />

91


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Fig. D–158<br />

Fig. D–159<br />

5 6<br />

Kontroller, at tætningselementet og skæreringen<br />

sidder korrekt.<br />

Skub presfittingen hen til den markerede<br />

indstiksdybde på røret.<br />

Fig. D–160<br />

Fig. D–161<br />

7 8<br />

Sæt presringen på fittingen, og kontroller,<br />

at positionen er korrekt.<br />

Prestangen åbnes og klikkes på plads<br />

over presringen.<br />

Fig. D–162<br />

Fig. D–163<br />

9 10<br />

Start presmaskinen, og udfør presningen.<br />

Fjern kontrolmærket. Det viser, at forbindelsen<br />

nu er „sammenpresset“.<br />

92


1 Drikkevandsinstallation – Montering<br />

Pladsbehov ved presning<br />

Rørstørrelse 12 til 54 mm<br />

En fejlfri presning kræver, at der er plads til presmaskine og værktøj. Tabellerne nedenfor<br />

indeholder oplysninger om mindste pladsbehov i forskellige montagesituationer.<br />

Bemærk pladskrav er ikke ens for alle presmaskiner.<br />

Presning mellem rør og væg<br />

Vulst på presfittingen<br />

Pladsbehov<br />

Fig. D–164 Fig. D–165<br />

Rør-ød a<br />

[mm]<br />

Tab. D–13<br />

Lysnettilslutning<br />

Pressgun 4 E<br />

PT2<br />

PT3-EH<br />

Akku<br />

Pressgun 4 B<br />

PT3-AH<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

12 20 50<br />

15 20 50<br />

18 20 55<br />

22 25 60<br />

28 25 70<br />

35 30 85<br />

42 45 100<br />

54 50 115<br />

Rør-ød a<br />

[mm]<br />

Tab. D–14<br />

Akku<br />

Picco<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

12 25 55<br />

15 25 60<br />

18 25 60<br />

22 25 65<br />

28 25 65<br />

Presværktøjer<br />

Med forskelligt<br />

pladsbehov<br />

93


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Presning mellem rør og væg<br />

Mindste<br />

pladsbehov<br />

Pressgun 4 B / 4 E, PT2, PT3-AH, PT3-EH<br />

Vulst på presfittingen<br />

Picco<br />

Fig. D–166 Fig. D–167<br />

Rør-ø d a<br />

[mm]<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

c<br />

[mm]<br />

12 25 40 65<br />

15 25 40 65<br />

18 25 40 75<br />

22 30 40 80<br />

28 30 50 85<br />

35 50 50 95<br />

42 50 70 115<br />

54 55 80 140<br />

Rør-ø d a<br />

[mm]<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

c<br />

[mm]<br />

12 30 40 65<br />

15 30 40 70<br />

18 30 40 70<br />

22 30 40 75<br />

28 30 40 80<br />

Tab. D–15 Tab. D–16<br />

Pladsbehov ved bygningsdele<br />

Vægafstand<br />

Ved anvendelse af kardan<br />

trækbakke<br />

kan a min reduceres<br />

Pladsbehov minimum a min [mm]<br />

Rør-ø d a<br />

[mm]<br />

PT2<br />

PT3-AH<br />

PT3-EH<br />

Pressgun Picco<br />

Picco<br />

Pressgun<br />

4B / 4E<br />

Afstand mellem<br />

presningerne<br />

Kantning undgås – tætningsfunktionen<br />

er sikret<br />

94<br />

Tab. D–17<br />

Tab. D–18<br />

12 – 54 45 50 35 50<br />

Rør-ø d a<br />

[mm]<br />

Mindste afstand a<br />

[mm]<br />

12 0<br />

15 0<br />

18 0<br />

22 0<br />

28 0<br />

35 10<br />

42 15<br />

54 25


1 Drikkevandsinstallation – Montering<br />

Pladsbehov ved presning<br />

Rørstørrelser 76,1 til 108,0 mm<br />

Presning med XL-kæde til Sanpress XL<br />

Mindste pladsbehov, fremgår af tabellerne nedenfor.<br />

Mellem rørledninger<br />

Mellem rør og væg<br />

Fig. D–168<br />

Rør-ø<br />

d a [mm]<br />

Tab. D–19<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

76,1 90 185<br />

88,9 100 200<br />

108,0 110 215<br />

Fig. D–169<br />

Rør-ø<br />

d a [mm]<br />

Tab. D–20<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

c<br />

[mm]<br />

76,1 90 185 130<br />

88,9 100 200 140<br />

108,0 110 215 155<br />

Pladsbehov ved bygningsdele<br />

Rør-ød a<br />

[mm]<br />

76,1<br />

88,9<br />

108,0<br />

Mindste afstand a<br />

[mm]<br />

ikke påkrævet!<br />

Afstand mellem presningerne<br />

Kantning undgås,<br />

og tætningsfunk tionen<br />

er sikret<br />

Tab. D–21<br />

Tab. D–22<br />

Rør-ø d a<br />

[mm]<br />

76,1<br />

88,9<br />

108,0<br />

Pladsbehov minimum a min [mm]<br />

PT2<br />

PT3-AH<br />

Pressgun<br />

4B / 4E<br />

45 50 50<br />

Vægafstand<br />

Gælder også for<br />

Sanpress Inox Xl og<br />

Profipress 64,0 mm<br />

95


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Presning med presværktøj til Sanpress Inox XL og Profipress 64,0 mm<br />

Mellem rørledninger<br />

Mellem rør og væg<br />

Fig. D–170<br />

Rør-ø d a<br />

[mm]<br />

64,0<br />

76,1<br />

Tab. D–23<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

110 185<br />

88,9 120 200<br />

108,0 135 215<br />

Fig. D–171<br />

Rør-ø d a<br />

[mm]<br />

64,0<br />

76,1<br />

Tab. D–24<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

c<br />

[mm]<br />

110 185 130<br />

88,9 120 200 140<br />

108,0 135 215 155<br />

Afstand mellem presningerne<br />

Kantning undgås – tætningsfunktionen<br />

er sikret<br />

Pladsbehov ved bygningsdele<br />

Tab. D–25<br />

Rør-ø d a<br />

[mm]<br />

64,0<br />

76,1<br />

88,9<br />

108,0<br />

Mindste afstand a<br />

[mm]<br />

15<br />

Tab. D–26<br />

Rør-ø d a<br />

[mm]<br />

64,0<br />

76,1<br />

88,9<br />

108,0<br />

Mindste afstand a<br />

[mm]<br />

20<br />

96


1 Drikkevandsinstallation – Montering<br />

Grundregler for idriftsætningen<br />

QQPåfyldning af installationen foretages først, når idriftsætning er umiddelbart forestående.<br />

Forsinkes idriftsætningen, skal et skylleprogram oprettes og dokumenteres.<br />

QQTæthedstest, skylning, idriftsætning og instruktioner indføres i en protokol, der<br />

udleveres til brugeren som dokumentation.<br />

QQFordelene ved en vedligeholdelseskontrakt forklares for kunden.<br />

QQOplys om nødvendigheden af regelmæssig og fuldstændig udskiftning af vandet<br />

– ca. tre gange pr. uge på alle tappesteder.<br />

SC-Contur<br />

<strong>Viega</strong> SC-Contur sikrer at upressede samlinger straks kan konstateres i trykområdet<br />

22 mbar til 3 bar (tør) og fra 1 til 6,5 bar (våd). Hvis der trykprøves i en frostperiode<br />

anbefales en tør test. Upressede presfittings konstateres med sikkerhed i trykområdet<br />

1–6 bar ved lækage fra SC-Conturen, og fitting kan presses straks.<br />

SC-Contur<br />

<strong>Viega</strong> presfittings er<br />

udstyret med denne sikkerhedsanordning.<br />

Den<br />

kan kendes på den<br />

grønne prik.<br />

Fig. D–172<br />

Desinficering - vejledende og gældende i Tyskland. I Danmark<br />

skal myndighederne altid kontakes.<br />

Hvis vandets mikrobiologiske kvalitet ikke er tilstrækkeligt god, kan det desinficeres i<br />

<strong>Viega</strong> pressystemer med anvendelse af de desinfektionsmetoder, der er godkendt<br />

ifølge drikkevandsforordningen, i de angivne tidsrum (grund- eller støddesinficering).<br />

Efterfølgende skal der altid foretages en skylning, indtil koncentrationen af desinfektionsmiddel<br />

igen er inden for de tilladte koncentrationer for langtidsdesinficering.<br />

Vi anbefaler, at al desinficering udføres af kvalificeret og erfarent fagpersonale.<br />

Brint overilte (H 2 O 2 ) og klordioxid foretrækkes på grund af deres højere materialekompabilitet.<br />

Problematik<br />

i forbindelse med<br />

langtidskloring<br />

97


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Til desinficering af legionella-kontaminerede ledningsanlæg er 50 mg/l klor i løbet af<br />

12 timer tilstrækkeligt iht. DVGW-dokument W 551. Yderligere information om desinficering<br />

findes i ZVSHK-cirkulæret „Skylning, desinficering og idriftsætning af drikkevandsinstallationer“.<br />

Langtidsklorering er ifølge DVGW-dokument W 551 ikke egnet til forebyggelse af legionella.<br />

Citat: „En kontinuerlig desinficering med kemikalier er derfor ikke formålstjenlig. Med<br />

denne metode udryddes legionella ikke tilstrækkeligt.“ Hvis en kontinuerlig desinficering<br />

alligevel midlertidigt er nødvendig under en dekontaminering, skal denne udføres<br />

i overensstemmelse med drikkevandsforordningen.<br />

Forbrugeren skal informeres herom (TrinkwV § 16 og 20).<br />

Iht. det eruropæiske drikkevandsdirektiv skal 0,1 til 0,3 mg/l frit klor – eller i undtagelsestilfælde,<br />

som er godkendt af sundhedsmyndighederne, også op til 0,6 mg/l – overholdes.<br />

Ved decentrale desinficeringsanlæg (klordioxid undtaget) i bygninger kræver de tyske miljømyndigheder,<br />

at grænseværdien for trihalogenmetaner (THM – fx kloroform) hos forbrugeren<br />

overholdes – hvilket indebærer en krævende og kostbar dokumentationsproces.<br />

Yderligere information om desinficering af installationer i US-bygninger kan fås hos<br />

<strong>Viega</strong>.<br />

98


1 Drikkevandsinstallation – Tillæg<br />

99<br />

Tillæg<br />

Tryktab: Koldt vand i rustfaste rør<br />

Rørfriktionstrykdifference R og strømningshastighed v afhængigt af den maksimale gennemstrømning Vs ved en<br />

temperatur på 10 °C for rør af rustfast stål iht. DVGW-dokument W 541.<br />

Størrelser: 15 til 54 mm<br />

di (mm)<br />

V (l/m)<br />

15 x 1,0 mm<br />

13,0<br />

0,13<br />

18 x 1,0 mm<br />

16,0<br />

0,20<br />

22 x 1,2 mm<br />

19,6<br />

0,30<br />

28 x 1,2 mm<br />

25,6<br />

0,51<br />

35 x 1,5 mm<br />

32,0<br />

0,80<br />

Vs<br />

l/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

0,05<br />

0,08<br />

0,10<br />

0,15<br />

0,20<br />

0,25<br />

0,30<br />

0,35<br />

0,40<br />

0,45<br />

0,50<br />

0,55<br />

0,60<br />

0,65<br />

0,70<br />

0,75<br />

0,80<br />

0,85<br />

0,90<br />

0,95<br />

1,00<br />

1,05<br />

1,10<br />

1,15<br />

1,20<br />

1,25<br />

1,30<br />

1,35<br />

1,40<br />

1,45<br />

1,50<br />

1,55<br />

1,60<br />

1,65<br />

1,70<br />

1,75<br />

1,80<br />

1,85<br />

1,90<br />

1,95<br />

2,00<br />

2,10<br />

2,20<br />

2,30<br />

2,40<br />

2,50<br />

2,60<br />

2,70<br />

2,80<br />

2,90<br />

3,00<br />

3,25<br />

3,50<br />

3,75<br />

4,00<br />

2,2<br />

5,0<br />

7,3<br />

14,8<br />

24,5<br />

36,2<br />

49,9<br />

65,6<br />

83,1<br />

102,4<br />

123,6<br />

146,5<br />

171,1<br />

197,5<br />

0,4<br />

0,6<br />

0,8<br />

1,1<br />

1,5<br />

1,9<br />

2,3<br />

2,6<br />

3,0<br />

3,4<br />

3,8<br />

4,1<br />

4,5<br />

4,9<br />

0,8<br />

1,9<br />

2,7<br />

5,5<br />

9,1<br />

13,5<br />

18,5<br />

24,3<br />

30,8<br />

37,9<br />

45,7<br />

54,1<br />

63,2<br />

72,9<br />

83,2<br />

94,1<br />

105,6<br />

117,6<br />

130,3<br />

143,6<br />

157,4<br />

0,2<br />

0,4<br />

0,5<br />

0,7<br />

1,0<br />

1,2<br />

1,5<br />

1,7<br />

2,0<br />

2,2<br />

2,5<br />

2,7<br />

3,0<br />

3,2<br />

3,5<br />

3,7<br />

4,0<br />

4,2<br />

4,5<br />

4,7<br />

5,0<br />

0,3<br />

0,7<br />

1,0<br />

1,9<br />

3,3<br />

5,1<br />

7,1<br />

9,3<br />

11,7<br />

14,4<br />

17,4<br />

20,6<br />

24,0<br />

27,6<br />

31,5<br />

35,6<br />

40,0<br />

44,5<br />

49,3<br />

54,3<br />

59,5<br />

64,9<br />

70,6<br />

76,4<br />

82,5<br />

88,7<br />

95,2<br />

101,9<br />

108,8<br />

115,8<br />

123,1<br />

130,6<br />

138,3<br />

0,2<br />

0,3<br />

0,3<br />

0,5<br />

0,6<br />

0,8<br />

1,0<br />

1,2<br />

1,3<br />

1,5<br />

1,7<br />

1,8<br />

1,9<br />

2,2<br />

2,3<br />

2,5<br />

2,7<br />

2,8<br />

3,0<br />

3,1<br />

3,3<br />

3,5<br />

3,6<br />

3,8<br />

4,0<br />

4,1<br />

4,3<br />

4,5<br />

4,6<br />

4,8<br />

5,0<br />

5,1<br />

5,3<br />

0,1<br />

0,2<br />

0,3<br />

0,7<br />

1,1<br />

1,6<br />

2,1<br />

2,8<br />

3,6<br />

4,0<br />

4,9<br />

5,8<br />

6,7<br />

7,7<br />

8,8<br />

9,9<br />

11,1<br />

12,4<br />

13,7<br />

15,1<br />

16,6<br />

18,1<br />

19,6<br />

21,2<br />

22,9<br />

24,6<br />

26,4<br />

28,3<br />

30,1<br />

32,1<br />

34,1<br />

36,2<br />

38,3<br />

40,4<br />

42,7<br />

44,9<br />

47,3<br />

49,6<br />

52,1<br />

54,6<br />

57,1<br />

62,3<br />

67,8<br />

73,4<br />

79,3<br />

85,3<br />

0,1<br />

0,3<br />

0,2<br />

0,3<br />

0,4<br />

0,5<br />

0,6<br />

0,7<br />

0,8<br />

0,9<br />

1,0<br />

1,1<br />

1,2<br />

1,3<br />

1,4<br />

1,5<br />

1,6<br />

1,7<br />

1,7<br />

1,8<br />

1,9<br />

2,0<br />

2,1<br />

2,2<br />

2,3<br />

2,4<br />

2,5<br />

2,6<br />

2,7<br />

2,8<br />

2,9<br />

3,0<br />

3,1<br />

3,2<br />

3,3<br />

3,4<br />

3,5<br />

3,6<br />

3,7<br />

3,8<br />

3,9<br />

4,1<br />

4,3<br />

4,5<br />

4,7<br />

4,9<br />

–<br />

–<br />

0,1<br />

0,2<br />

0,3<br />

0,5<br />

0,7<br />

0,9<br />

1,1<br />

1,5<br />

1,7<br />

2,0<br />

2,3<br />

2,7<br />

3,0<br />

3,4<br />

3,8<br />

4,2<br />

4,7<br />

5,2<br />

5,7<br />

6,2<br />

6,7<br />

7,3<br />

7,9<br />

8,5<br />

9,1<br />

9,7<br />

10,3<br />

11,0<br />

11,7<br />

12,4<br />

13,1<br />

13,8<br />

14,6<br />

15,4<br />

16,2<br />

17,0<br />

17,8<br />

18,7<br />

19,5<br />

21,3<br />

23,1<br />

25,1<br />

27,1<br />

29,1<br />

31,2<br />

33,4<br />

35,7<br />

38,0<br />

40,4<br />

46,9<br />

53,3<br />

60,4<br />

67,9<br />

–<br />

–<br />

0,1<br />

0,2<br />

0,2<br />

0,3<br />

0,4<br />

0,4<br />

0,5<br />

0,6<br />

0,6<br />

0,7<br />

0,7<br />

0,8<br />

0,9<br />

0,9<br />

1,0<br />

1,0<br />

1,1<br />

1,2<br />

1,2<br />

1,3<br />

1,4<br />

1,4<br />

1,5<br />

1,5<br />

1,6<br />

1,7<br />

1,7<br />

1,8<br />

1,9<br />

1,9<br />

2,0<br />

2,1<br />

2,1<br />

2,2<br />

2,2<br />

2,3<br />

2,4<br />

2,4<br />

2,5<br />

2,6<br />

2,7<br />

2,9<br />

3,0<br />

3,1<br />

3,2<br />

3,4<br />

3,5<br />

3,6<br />

3,7<br />

4,0<br />

4,4<br />

4,7<br />

5,0<br />

di (mm)<br />

V (l/m)<br />

42 x 1,5 mm<br />

39,0<br />

1,19<br />

54 x 1,5 mm<br />

51,0<br />

2,04<br />

Vs<br />

l/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

0,25<br />

0,50<br />

0,60<br />

0,70<br />

0,80<br />

0,90<br />

1,00<br />

1,10<br />

1,20<br />

1,30<br />

1,40<br />

1,50<br />

1,60<br />

1,70<br />

1,80<br />

1,90<br />

2,00<br />

2,10<br />

2,20<br />

2,30<br />

2,40<br />

2,50<br />

2,60<br />

2,70<br />

2,80<br />

2,90<br />

3,00<br />

3,50<br />

4,00<br />

4,50<br />

5,00<br />

5,50<br />

6,00<br />

6,50<br />

7,00<br />

7,50<br />

8,00<br />

8,50<br />

9,00<br />

9,50<br />

10,00<br />

0,2<br />

0,7<br />

1,0<br />

1,2<br />

1,5<br />

1,8<br />

2,2<br />

2,6<br />

3,1<br />

3,5<br />

4,0<br />

4,5<br />

5,1<br />

5,7<br />

6,3<br />

6,9<br />

7,6<br />

8,2<br />

9,0<br />

9,7<br />

10,5<br />

11,3<br />

12,1<br />

12,9<br />

13,8<br />

14,7<br />

15,6<br />

20,6<br />

26,2<br />

32,4<br />

39,1<br />

46,5<br />

53,8<br />

0,2<br />

0,4<br />

0,5<br />

0,6<br />

0,7<br />

0,8<br />

0,8<br />

0,9<br />

1,0<br />

1,1<br />

1,2<br />

1,3<br />

1,3<br />

1,4<br />

1,5<br />

1,6<br />

1,7<br />

1,8<br />

1,8<br />

1,9<br />

2,0<br />

2,1<br />

2,2<br />

2,3<br />

2,3<br />

2,4<br />

2,5<br />

2,9<br />

3,4<br />

3,7<br />

4,2<br />

4,6<br />

5,0<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,5<br />

0,6<br />

0,8<br />

1,0<br />

1,1<br />

1,3<br />

1,4<br />

1,6<br />

1,7<br />

1,9<br />

2,1<br />

2,3<br />

2,5<br />

2,7<br />

2,9<br />

3,1<br />

3,3<br />

3,6<br />

3,8<br />

4,1<br />

4,3<br />

5,7<br />

7,2<br />

9,0<br />

10,8<br />

12,8<br />

14,9<br />

17,3<br />

19,7<br />

22,3<br />

25,1<br />

28,0<br />

31,3<br />

34,3<br />

37,6<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,5<br />

0,5<br />

0,6<br />

0,6<br />

0,7<br />

0,7<br />

0,8<br />

0,8<br />

0,9<br />

0,9<br />

1,0<br />

1,0<br />

1,1<br />

1,1<br />

1,2<br />

1,2<br />

1,3<br />

1,3<br />

1,4<br />

1,4<br />

1,5<br />

1,7<br />

2,0<br />

2,2<br />

2,5<br />

2,7<br />

2,9<br />

3,2<br />

3,4<br />

3,7<br />

3,9<br />

4,2<br />

4,4<br />

4,7<br />

4,9<br />

Tab. D–27


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

100<br />

Tryktab: Koldt vand i rustfaste rør<br />

XL-størrelser: 64,0 til 108,0 mm<br />

di (mm)<br />

V (l/m)<br />

64 x 2,0 mm<br />

60,0<br />

2,83<br />

76,1 x 2,0 mm<br />

72,1<br />

4,08<br />

88,9 x 2,0 mm<br />

84,9<br />

5,66<br />

108 x 2,0 mm<br />

104,0<br />

8,49<br />

Vs<br />

l/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

0,60<br />

0,80<br />

1,00<br />

1,20<br />

1,40<br />

1,50<br />

1,60<br />

1,80<br />

2,00<br />

2,20<br />

2,40<br />

2,50<br />

2,60<br />

2,80<br />

3,00<br />

3,20<br />

3,40<br />

3,50<br />

3,60<br />

3,80<br />

4,00<br />

4,20<br />

4,40<br />

4,50<br />

4,60<br />

4,80<br />

5,00<br />

5,20<br />

5,40<br />

5,50<br />

5,60<br />

5,80<br />

6,00<br />

6,50<br />

7,00<br />

7,50<br />

8,00<br />

8,50<br />

9,00<br />

9,50<br />

10,00<br />

11,00<br />

12,00<br />

13,00<br />

14,00<br />

15,00<br />

16,00<br />

17,00<br />

18,00<br />

19,00<br />

20,00<br />

21,00<br />

22,00<br />

23,00<br />

24,00<br />

25,00<br />

30,00<br />

35,00<br />

40,00<br />

45,00<br />

0,1<br />

0,2<br />

0,3<br />

0,4<br />

0,5<br />

–<br />

0,6<br />

0,8<br />

1,0<br />

1,1<br />

1,3<br />

–<br />

1,5<br />

1,8<br />

2,0<br />

2,2<br />

2,5<br />

–<br />

2,7<br />

3,0<br />

3,3<br />

3,6<br />

3,9<br />

–<br />

4,2<br />

4,6<br />

4,9<br />

5,3<br />

5,7<br />

–<br />

6,0<br />

6,4<br />

6,8<br />

7,9<br />

9,0<br />

10,6<br />

11,5<br />

12,8<br />

14,2<br />

15,7<br />

17,2<br />

20,4<br />

23,9<br />

27,6<br />

31,6<br />

0,2<br />

0,3<br />

0,4<br />

0,4<br />

0,5<br />

–<br />

0,6<br />

0,6<br />

0,7<br />

0,8<br />

0,8<br />

–<br />

0,9<br />

1,0<br />

1,1<br />

1,1<br />

1,2<br />

-<br />

1,3<br />

1,3<br />

1,4<br />

1,5<br />

1,6<br />

–<br />

1,6<br />

1,7<br />

1,8<br />

1,8<br />

1,9<br />

–<br />

2,0<br />

2,1<br />

2,1<br />

2,3<br />

2,5<br />

2,7<br />

2,8<br />

3,0<br />

3,2<br />

3,4<br />

3,5<br />

3,9<br />

4,2<br />

4,6<br />

5,0<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

0,8<br />

–<br />

–<br />

1,1<br />

–<br />

–<br />

1,4<br />

–<br />

–<br />

1,7<br />

–<br />

–<br />

2,0<br />

–<br />

–<br />

2,4<br />

–<br />

–<br />

2,8<br />

3,3<br />

3,7<br />

4,2<br />

4,7<br />

5,3<br />

5,9<br />

6,5<br />

7,1<br />

8,4<br />

9,9<br />

11,4<br />

13,0<br />

14,8<br />

16,6<br />

18,5<br />

20,5<br />

22,7<br />

24,9<br />

27,2<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

0,7<br />

–<br />

–<br />

0,9<br />

–<br />

–<br />

1,0<br />

–<br />

–<br />

1,1<br />

–<br />

–<br />

1,2<br />

–<br />

–<br />

1,3<br />

–<br />

–<br />

1,5<br />

1,6<br />

1,7<br />

1,9<br />

2,0<br />

2,1<br />

2,2<br />

2,3<br />

2,4<br />

2,7<br />

2,9<br />

3,2<br />

3,4<br />

3,7<br />

3,9<br />

4,2<br />

4,4<br />

4,7<br />

4,9<br />

5,1<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,2<br />

–<br />

0,3<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

0,8<br />

–<br />

–<br />

0,9<br />

–<br />

–<br />

1,1<br />

–<br />

–<br />

1,3<br />

–<br />

1,7<br />

–<br />

2,2<br />

–<br />

2,7<br />

–<br />

3,2<br />

3,8<br />

4,5<br />

5,2<br />

5,9<br />

6,7<br />

7,5<br />

8,4<br />

9,3<br />

10,3<br />

11,3<br />

12,3<br />

13,4<br />

14,6<br />

15,7<br />

17,0<br />

23,4<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,3<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

0,7<br />

–<br />

–<br />

0,8<br />

–<br />

–<br />

0,9<br />

–<br />

–<br />

1,0<br />

–<br />

–<br />

1,1<br />

–<br />

1,2<br />

–<br />

1,4<br />

–<br />

1,6<br />

–<br />

1,8<br />

1,9<br />

2,1<br />

2,3<br />

2,5<br />

2,6<br />

2,8<br />

3,0<br />

3,2<br />

3,4<br />

3,5<br />

3,7<br />

3,9<br />

4,1<br />

4,2<br />

4,4<br />

5,3<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,3<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,5<br />

–<br />

0,7<br />

–<br />

0,9<br />

–<br />

1,1<br />

–<br />

1,2<br />

1,5<br />

1,8<br />

2,0<br />

2,3<br />

2,5<br />

2,8<br />

3,2<br />

3,5<br />

3,9<br />

4,3<br />

4,7<br />

5,1<br />

5,5<br />

5,9<br />

6,4<br />

9,0<br />

11,8<br />

15,0<br />

18,6<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,3<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,7<br />

–<br />

0,8<br />

–<br />

1,0<br />

–<br />

1,1<br />

–<br />

1,2<br />

1,3<br />

1,4<br />

1,6<br />

1,7<br />

1,8<br />

1,9<br />

2,0<br />

2,2<br />

2,3<br />

2,4<br />

2,5<br />

2,6<br />

2,7<br />

2,8<br />

2,9<br />

3,5<br />

4,1<br />

4,7<br />

5,3<br />

Tab. D–28


1 Drikkevandsinstallation – Tillæg<br />

101<br />

Tryktab: Varmt vand i rustfaste rør<br />

Rørfriktionstrykdifference R og strømningshastighed v afhængigt af den maksimale gennemstrømning Vs ved en<br />

temperatur på 60 °C for rør af rustfast stål iht. DVGW-dokument W 541.<br />

Størrelser: 15 til 54 mm<br />

di (mm)<br />

V (l/m)<br />

15 x 1,0 mm<br />

13,0<br />

0,13<br />

18 x 1,0 mm<br />

16,0<br />

0,20<br />

22 x 1,2 mm<br />

19,6<br />

0,30<br />

28 x 1,2 mm<br />

25,6<br />

0,51<br />

35 x 1,5 mm<br />

32,0<br />

0,80<br />

Vs<br />

l/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

0,05<br />

0,08<br />

0,10<br />

0,15<br />

0,20<br />

0,25<br />

0,30<br />

0,35<br />

0,40<br />

0,45<br />

0,50<br />

0,55<br />

0,60<br />

0,65<br />

0,70<br />

0,75<br />

0,80<br />

0,85<br />

0,90<br />

0,95<br />

1,00<br />

1,05<br />

1,10<br />

1,15<br />

1,20<br />

1,25<br />

1,30<br />

1,35<br />

1,40<br />

1,45<br />

1,50<br />

1,55<br />

1,60<br />

1,65<br />

1,70<br />

1,75<br />

1,80<br />

1,85<br />

1,90<br />

1,95<br />

2,00<br />

2,10<br />

2,20<br />

2,30<br />

2,40<br />

2,50<br />

2,60<br />

2,70<br />

2,80<br />

2,90<br />

3,00<br />

3,25<br />

3,50<br />

3,75<br />

4,00<br />

1,7<br />

3,8<br />

5,6<br />

11,4<br />

19,1<br />

28,4<br />

39,4<br />

52,1<br />

66,3<br />

82,0<br />

99,3<br />

118,1<br />

138,4<br />

160,2<br />

183,4<br />

0,4<br />

0,6<br />

0,8<br />

1,1<br />

1,5<br />

1,9<br />

2,5<br />

2,6<br />

3,0<br />

3,4<br />

3,8<br />

4,1<br />

4,5<br />

4,9<br />

5,3<br />

0,6<br />

1,4<br />

2,1<br />

4,2<br />

7,0<br />

10,5<br />

14,5<br />

19,1<br />

24,3<br />

30,1<br />

36,4<br />

43,2<br />

50,6<br />

58,5<br />

66,9<br />

75,9<br />

85,3<br />

95,3<br />

105,8<br />

116,7<br />

128,2<br />

140,2<br />

152,7<br />

0,3<br />

0,4<br />

0,5<br />

0,8<br />

1,0<br />

1,2<br />

1,5<br />

1,7<br />

2,0<br />

2,2<br />

2,5<br />

2,7<br />

3,0<br />

3,2<br />

3,5<br />

3,7<br />

4,0<br />

4,2<br />

4,5<br />

4,7<br />

5,0<br />

5,2<br />

5,5<br />

0,2<br />

0,5<br />

0,8<br />

1,6<br />

2,7<br />

4,0<br />

5,5<br />

7,2<br />

9,2<br />

11,3<br />

13,7<br />

16,2<br />

19,0<br />

21,9<br />

25,1<br />

28,4<br />

31,9<br />

35,6<br />

39,5<br />

43,6<br />

47,9<br />

52,3<br />

56,9<br />

61,7<br />

66,7<br />

71,9<br />

77,2<br />

82,7<br />

88,4<br />

94,3<br />

100,3<br />

106,6<br />

112,9<br />

119,5<br />

126,3<br />

0,2<br />

0,3<br />

0,3<br />

0,5<br />

0,7<br />

0,8<br />

1,0<br />

1,2<br />

1,3<br />

1,5<br />

1,7<br />

1,8<br />

2,0<br />

2,2<br />

2,3<br />

2,5<br />

2,7<br />

2,8<br />

3,0<br />

3,2<br />

3,3<br />

3,5<br />

3,7<br />

3,8<br />

4,0<br />

4,1<br />

4,3<br />

4,5<br />

4,6<br />

4,8<br />

5,0<br />

5,1<br />

5,3<br />

5,5<br />

5,6<br />

0,1<br />

0,2<br />

0,2<br />

0,5<br />

0,8<br />

1,1<br />

1,5<br />

2,0<br />

2,6<br />

3,1<br />

3,8<br />

4,5<br />

5,3<br />

6,1<br />

6,9<br />

7,8<br />

8,8<br />

9,8<br />

10,9<br />

12,0<br />

13,2<br />

14,4<br />

15,6<br />

17,0<br />

18,3<br />

19,7<br />

21,2<br />

22,7<br />

24,2<br />

25,8<br />

27,4<br />

29,1<br />

30,9<br />

32,6<br />

34,5<br />

36,3<br />

38,3<br />

40,2<br />

42,2<br />

44,3<br />

46,4<br />

50,7<br />

55,2<br />

59,9<br />

64,7<br />

69,8<br />

75,0<br />

80,4<br />

85,9<br />

91,7<br />

0,1<br />

0,2<br />

0,2<br />

0,3<br />

0,4<br />

0,5<br />

0,6<br />

0,7<br />

0,8<br />

0,9<br />

1,0<br />

1,1<br />

1,2<br />

1,3<br />

1,4<br />

1,5<br />

1,6<br />

1,7<br />

1,8<br />

1,9<br />

1,9<br />

2,0<br />

2,1<br />

2,2<br />

2,3<br />

2,4<br />

2,5<br />

2,6<br />

2,7<br />

2,8<br />

2,9<br />

3,0<br />

3,1<br />

3,2<br />

3,3<br />

3,4<br />

3,5<br />

3,6<br />

3,7<br />

3,8<br />

3,9<br />

4,1<br />

4,3<br />

4,5<br />

4,7<br />

4,9<br />

5,1<br />

5,2<br />

5,4<br />

5,6<br />

–<br />

–<br />

0,1<br />

0,2<br />

0,3<br />

0,4<br />

0,5<br />

0,7<br />

0,9<br />

1,1<br />

1,3<br />

1,5<br />

1,8<br />

2,1<br />

2,4<br />

2,7<br />

3,0<br />

3,4<br />

3,7<br />

4,1<br />

4,5<br />

4,9<br />

5,3<br />

5,8<br />

6,2<br />

6,7<br />

7,2<br />

7,7<br />

8,2<br />

8,8<br />

9,3<br />

9,9<br />

10,5<br />

11,1<br />

11,7<br />

12,3<br />

13,0<br />

13,6<br />

14,3<br />

15,0<br />

15,7<br />

17,2<br />

18,7<br />

20,3<br />

21,9<br />

23,6<br />

25,4<br />

27,2<br />

29,0<br />

31,0<br />

32,9<br />

38,1<br />

43,7<br />

49,6<br />

55,8<br />

–<br />

–<br />

0,1<br />

0,2<br />

0,3<br />

0,3<br />

0,4<br />

0,4<br />

0,5<br />

0,6<br />

0,6<br />

0,7<br />

0,8<br />

0,8<br />

0,9<br />

0,9<br />

1,0<br />

1,1<br />

1,1<br />

1,2<br />

1,2<br />

1,3<br />

1,4<br />

1,4<br />

1,5<br />

1,6<br />

1,6<br />

1,7<br />

1,7<br />

1,8<br />

1,9<br />

1,9<br />

2,0<br />

2,1<br />

2,1<br />

2,2<br />

2,2<br />

2,3<br />

2,4<br />

2,4<br />

2,5<br />

2,6<br />

2,7<br />

2,9<br />

3,0<br />

3,1<br />

3,2<br />

3,4<br />

3,5<br />

3,6<br />

3,7<br />

4,0<br />

4,4<br />

4,7<br />

5,0<br />

di (mm)<br />

V (l/m)<br />

42 x 1,5 mm<br />

39,0<br />

1,19<br />

54 x 1,5 mm<br />

51,0<br />

2,04<br />

Vs<br />

l/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

0,25<br />

0,50<br />

0,60<br />

0,70<br />

0,80<br />

0,90<br />

1,00<br />

1,10<br />

1,20<br />

1,30<br />

1,40<br />

1,50<br />

1,60<br />

1,70<br />

1,80<br />

1,90<br />

2,00<br />

2,10<br />

2,20<br />

2,30<br />

2,40<br />

2,50<br />

2,60<br />

2,70<br />

2,80<br />

2,90<br />

3,00<br />

3,50<br />

4,00<br />

4,50<br />

5,00<br />

5,50<br />

6,00<br />

6,50<br />

7,00<br />

7,50<br />

8,00<br />

8,50<br />

9,00<br />

9,50<br />

10,00<br />

0,1<br />

0,5<br />

0,7<br />

0,9<br />

1,2<br />

1,4<br />

1,7<br />

2,1<br />

2,4<br />

2,8<br />

3,2<br />

3,6<br />

4,0<br />

4,5<br />

5,0<br />

5,5<br />

6,0<br />

6,6<br />

7,2<br />

7,8<br />

8,4<br />

9,1<br />

9,7<br />

10,4<br />

11,1<br />

11,9<br />

12,6<br />

16,7<br />

21,3<br />

26,5<br />

32,1<br />

38,3<br />

44,9<br />

0,2<br />

0,4<br />

0,5<br />

0,6<br />

0,7<br />

0,8<br />

0,8<br />

0,9<br />

1,0<br />

1,1<br />

1,2<br />

1,3<br />

1,3<br />

1,4<br />

1,5<br />

1,6<br />

1,7<br />

1,8<br />

1,8<br />

1,9<br />

2,0<br />

2,1<br />

2,2<br />

2,3<br />

2,3<br />

2,4<br />

2,5<br />

2,9<br />

3,4<br />

3,7<br />

4,2<br />

4,6<br />

5,0<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,5<br />

0,6<br />

0,7<br />

0,8<br />

0,9<br />

1,0<br />

1,1<br />

1,2<br />

1,4<br />

1,5<br />

1,7<br />

1,8<br />

2,0<br />

2,1<br />

2,3<br />

2,5<br />

2,7<br />

2,9<br />

3,0<br />

3,2<br />

3,5<br />

4,6<br />

5,8<br />

7,2<br />

8,7<br />

10,4<br />

12,2<br />

14,1<br />

16,2<br />

18,3<br />

20,6<br />

23,1<br />

25,6<br />

28,3<br />

31,1<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,5<br />

0,5<br />

0,6<br />

0,6<br />

0,7<br />

0,7<br />

0,8<br />

0,8<br />

0,9<br />

0,9<br />

1,0<br />

1,0<br />

1,1<br />

1,1<br />

1,2<br />

1,2<br />

1,3<br />

1,3<br />

1,4<br />

1,4<br />

1,5<br />

1,7<br />

2,0<br />

2,2<br />

2,5<br />

2,7<br />

2,9<br />

3,2<br />

3,4<br />

3,7<br />

3,9<br />

4,2<br />

4,4<br />

4,7<br />

4,9<br />

Tab. D–29


102<br />

<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Tryktab: Varmt vand i rustfaste rør<br />

XL-størrelser: 64,0 til 108,0 mm<br />

di (mm)<br />

V (l/m)<br />

64 x 2,0 mm<br />

60,0<br />

2,83 mm<br />

76,1 x 2,0 mm<br />

72,1<br />

4,08<br />

88,9 x 2,0 mm<br />

84,9<br />

5,66<br />

108 x 2,0 mm<br />

104,0<br />

8,49<br />

Vs<br />

l/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

R<br />

mbar/m<br />

V<br />

m/s<br />

0,60<br />

0,80<br />

1,00<br />

1,20<br />

1,40<br />

1,50<br />

1,60<br />

1,80<br />

2,00<br />

2,20<br />

2,40<br />

2,50<br />

2,60<br />

2,80<br />

3,00<br />

3,20<br />

3,40<br />

3,50<br />

3,60<br />

3,80<br />

4,00<br />

4,20<br />

4,40<br />

4,50<br />

4,60<br />

4,80<br />

5,00<br />

5,20<br />

5,40<br />

5,50<br />

5,60<br />

5,80<br />

6,00<br />

6,50<br />

7,00<br />

7,50<br />

8,00<br />

8,50<br />

9,00<br />

9,50<br />

10,00<br />

11,00<br />

12,00<br />

13,00<br />

14,00<br />

15,00<br />

16,00<br />

17,00<br />

18,00<br />

19,00<br />

20,00<br />

21,00<br />

22,00<br />

23,00<br />

24,00<br />

25,00<br />

30,00<br />

35,00<br />

40,00<br />

45,00<br />

0,1<br />

0,8<br />

0,2<br />

0,3<br />

1,4<br />

–<br />

0,5<br />

0,6<br />

0,8<br />

0,9<br />

1,1<br />

–<br />

1,2<br />

1,4<br />

1,6<br />

1,8<br />

2,0<br />

–<br />

2,2<br />

3,8<br />

2,7<br />

2,9<br />

3,2<br />

–<br />

3,4<br />

3,7<br />

4,0<br />

4,3<br />

5,4<br />

–<br />

4,9<br />

5,2<br />

5,5<br />

6,4<br />

7,3<br />

8,3<br />

9,4<br />

10,5<br />

11,6<br />

12,8<br />

14,1<br />

16,8<br />

19,7<br />

22,9<br />

26,2<br />

29,8<br />

0,2<br />

0,3<br />

0,4<br />

0,4<br />

0,5<br />

–<br />

0,6<br />

0,6<br />

0,7<br />

0,8<br />

0,8<br />

–<br />

0,9<br />

1,0<br />

1,1<br />

1,1<br />

1,2<br />

-<br />

1,3<br />

1,3<br />

1,4<br />

1,5<br />

1,6<br />

–<br />

1,6<br />

1,7<br />

1,8<br />

1,8<br />

1,9<br />

–<br />

2,0<br />

2,1<br />

2,1<br />

2,3<br />

2,5<br />

2,7<br />

2,8<br />

3,0<br />

3,2<br />

3,4<br />

3,5<br />

3,9<br />

4,2<br />

4,6<br />

5,0<br />

5,3<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,3<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,7<br />

–<br />

–<br />

0,9<br />

–<br />

–<br />

1,1<br />

–<br />

–<br />

1,4<br />

–<br />

–<br />

1,6<br />

–<br />

–<br />

2,0<br />

–<br />

–<br />

2,3<br />

2,6<br />

3,0<br />

3,4<br />

3,9<br />

4,3<br />

4,8<br />

5,3<br />

5,8<br />

6,9<br />

8,1<br />

9,4<br />

10,7<br />

12,2<br />

13,7<br />

15,3<br />

17,0<br />

18,8<br />

20,7<br />

22,6<br />

24,7<br />

–<br />

0,2<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

0,7<br />

–<br />

–<br />

0,9<br />

–<br />

–<br />

1,0<br />

–<br />

–<br />

1,1<br />

–<br />

–<br />

1,2<br />

–<br />

–<br />

1,3<br />

–<br />

–<br />

1,5<br />

1,6<br />

1,7<br />

1,8<br />

2,0<br />

2,1<br />

2,2<br />

2,3<br />

2,4<br />

2,7<br />

2,9<br />

3,2<br />

3,4<br />

3,7<br />

3,9<br />

4,2<br />

4,4<br />

4,7<br />

4,9<br />

5,1<br />

5,4<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,1<br />

–<br />

0,2<br />

–<br />

–<br />

0,3<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

0,7<br />

–<br />

–<br />

0,9<br />

–<br />

–<br />

1,0<br />

1,2<br />

1,4<br />

1,6<br />

1,7<br />

2,0<br />

2,2<br />

2,4<br />

2,6<br />

3,1<br />

3,7<br />

4,2<br />

4,9<br />

5,5<br />

6,2<br />

6,9<br />

7,7<br />

8,5<br />

9,3<br />

10,2<br />

11,1<br />

12,1<br />

13,1<br />

14,1<br />

19,7<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,3<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

0,7<br />

–<br />

–<br />

0,8<br />

–<br />

–<br />

0,9<br />

–<br />

–<br />

1,0<br />

–<br />

–<br />

1,1<br />

1,1<br />

1,2<br />

1,3<br />

1,4<br />

1,5<br />

1,6<br />

1,7<br />

1,8<br />

1,9<br />

2,1<br />

2,3<br />

2,5<br />

2,6<br />

2,8<br />

3,0<br />

3,2<br />

3,4<br />

3,5<br />

3,7<br />

3,9<br />

4,1<br />

4,2<br />

4,4<br />

5,3<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,1<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,3<br />

–<br />

–<br />

0,3<br />

–<br />

–<br />

0,4<br />

0,5<br />

0,5<br />

0,6<br />

0,7<br />

0,7<br />

0,8<br />

0,9<br />

1,0<br />

1,2<br />

1,4<br />

1,6<br />

1,8<br />

2,1<br />

2,3<br />

2,6<br />

2,9<br />

3,2<br />

3,5<br />

3,8<br />

4,2<br />

4,5<br />

4,9<br />

5,3<br />

7,3<br />

9,8<br />

12,5<br />

15,5<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0,2<br />

–<br />

–<br />

0,3<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,4<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,5<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

0,6<br />

–<br />

–<br />

0,7<br />

0,8<br />

0,8<br />

0,9<br />

0,9<br />

1,0<br />

1,1<br />

1,1<br />

1,2<br />

1,3<br />

1,4<br />

1,5<br />

1,6<br />

1,8<br />

1,9<br />

2,0<br />

2,1<br />

2,2<br />

2,4<br />

2,5<br />

2,6<br />

2,7<br />

2,8<br />

2,9<br />

3,5<br />

4,1<br />

4,7<br />

5,3<br />

Tab. D–30


Protokol (eksempel): Skylning med vand<br />

Byggeri<br />

______________________________________________<br />

Ordregiver repræsenteret ved<br />

______________________________________________<br />

1. Trykprøven har fundet sted den ______________________________________________<br />

2. Rørledningssystemets materiale ______________________________________________<br />

3. Tabeller: Vejledende værdier for det antal udtagssteder, der som minimum skal være, på grundlag af fordelingsledningens<br />

største nominelle diameter<br />

Største nominelle diameter<br />

i fordelingsledningen<br />

DN i det aktuelle skylleafsnit<br />

Mindste antal udtagssteder, der<br />

skal være DN 15<br />

25 32 40 50 65 80 100<br />

2 4 6 8 12 18 28<br />

4. Inden for en etage lukkes der helt op på de udtagssteder, som sidder længst fra stigstrengen.<br />

Efter en skylning af 5 minutters varighed ved det sidst åbnede skyllested lukkes skyllestederne efter tur.<br />

5. Det drikkevand, der anvendes til skylning, er filtreret. Stilstandstryk P W = _______ bar.<br />

6. Vedligeholdelsesarmaturer (etageafspærring, forafspærring) er fuldt åbnet.<br />

7. Følsomme armaturer og apparater er afmonteret og erstattet af hhv. passtykker og fleksible ledninger.<br />

8. Luftblandere, perlatorer og gennemstrømningsbegrænsere er afmonteret.<br />

9. monterede smudsfangersier og smudsfangere foran armaturer skal renses efter skylningen med vand.<br />

10. Der skylles et afsnit ad gangen, og skylningen begynder ved hovedafspærringsarmaturet og slutter ved<br />

det fjerneste tappested.<br />

Skylning af drikkevandsanlægget er udført korrekt<br />

Sted ________________________________________<br />

____________________________________________<br />

Underskrift / Ordregiver / Repræsentant<br />

Dato ________________________________<br />

____________________________________<br />

Underskrift / Ordremodtager / Repræsentant


Rapport: Tryktest for drikkevandsinstallationer<br />

Systemer:Sanpress, Sanpress Inox, Profipress<br />

Kontrolmedie: Trykluft eller inert gas<br />

Byggeri<br />

Byggeafsnit<br />

Ordregiver repræsenteret ved<br />

Ordremodtager repræsenteret ved<br />

Rørsystemets materiale<br />

______________________________________________<br />

______________________________________________<br />

______________________________________________<br />

______________________________________________<br />

______________________________________________<br />

______________________________________________<br />

Tilslutningssted<br />

______________________________________________<br />

Anlæggets tryk<br />

______ bar<br />

Omgivende temperatur ______ ______ °C<br />

Testmedie ______ ______ °C<br />

Testmedie Oliefri trykluft Kvælstof Kuldioxid<br />

Drikkevandsanlægget er kontrolleret som samlet anlæg i ______ delafsnit<br />

Alle ledninger er lukket med <strong>metal</strong>propper, hætter, blændplader eller blindflanger.<br />

Apparater, hydroforer eller drikkevandsvarmere er adskilt fra ledningerne.<br />

Der er gennemført en visuel kontrol af, at alle rørtilslutninger er udført fagligt korrekt.<br />

1. Tæthedsprøvning<br />

Kontroltryk 110 mbar<br />

Op til 100 liter ledningsvolumen, mindst 30 minutters testtid, for hver yderligere 100 liter skal testtiden forlænges<br />

med 10 minutter.<br />

Ledningsvolumen _____ liter<br />

Testtid ____ minutter<br />

Det afventes, at kunststofmaterialers temperatur stabiliseres, hvorefter testtiden begynder.<br />

Visuel kontrol af ledningsanlægget / kontrol pr. manometer.<br />

Er kontrol af U-rør- eller standrør-vandsøjle foretaget?<br />

Er der konstateret svagheder i løbet af testtiden?<br />

2. Belastningskontrol med forhøjet tryk<br />

Temperaturudligning og stationær temperaturtilstand i kunststofmaterialer afventes, hvorefter testtiden begynder.<br />

Testtryk < DN 50 maks. 3 bar Tesltryk > DN 50 maks. 1 bar Testtid 10 minutter<br />

Ja<br />

Nej<br />

Sted ________________________________________<br />

____________________________________________<br />

Underskrift: Ordregiver / Repræsentant<br />

Dato ________________________________<br />

____________________________________<br />

Underskrift / Repræsentant


Rapport: Tryktest for drikkevandsinstallationer<br />

Systemer:Sanpress, Sanpress Inox, Profipress<br />

Kontrolmedie: Vand<br />

Manometer med min. 0,1 mbars nøjagtighed bør anvendes<br />

Byggeri<br />

___________________________________________________________<br />

___________________________________________________________<br />

Byggeafsnit<br />

___________________________________________________________<br />

Ordregiver repræsenteret ved ___________________________________________________________<br />

Ordremodtager repræsenteret ved<br />

___________________________________________________<br />

Er alle beholdere, apparater og armaturer, der ikke er egnet til det tryk, der skal tilvejebringes,<br />

adskilt fra det anlæg/delafsnit, der skal testes i forbindelse med tryktesen.<br />

Er det anlæg/delafsnit, der skal testes, fyldt med filtreret vand og fuldstændig udluftet?<br />

Ja<br />

Nej<br />

Funktionstest af SC Contur<br />

Er en ventetid på 30 minutter til temperaturudligning ved større differencer (10 K) mellem<br />

omgivende temperatur og påfyldningsvandets temperatur efter påfyldning af anlægget overholdt?<br />

Trykket svarer til det disponible forsyningstryk på ____ bar, dog maksimalt 6,5 bar!<br />

Er der gennemført visuel kontrol/manometerkontrol af anlægget?<br />

Er der forekommet trykfald under funktionstesten?<br />

Er der konstateret utæthed under funktionstesten?<br />

Tryktest af anlægget<br />

Er tryktesten af anlægget gennemført med et minimumstryk på 15 bar?<br />

Testtiden er 10 minutter.<br />

Er der forekommet trykfald under testen?<br />

Er der konstateret utæthed under testen?<br />

Sted ________________________________________<br />

____________________________________________<br />

Underskrift: Ordregiver / Repræsentant<br />

Dato ________________________________<br />

____________________________________<br />

Underskrift: Ordregiver / Repræsentant


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Kombination af rør materialer i drikkevandsinstallationer<br />

Fig. D–173<br />

I dette kapitel blev givet et overblik over relevante aspekter i planlægning og anvendelse<br />

af <strong>Viega</strong>s <strong>metal</strong> pressesystemer. I etagefordelingen kan kravene til rørføring, i tillæg<br />

til kælder og stigledninger i <strong>metal</strong>, opfyldes med rørmaterialer i kunststof. Især<br />

PE-Xc rør i PE-beskyttelsesrør har vist sig særlig anvendelig.<br />

Sådanne rørsystemer samt installationsvægge med cisterner og skylleteknik til væghængte<br />

toiletter og urinaler, findes også i <strong>Viega</strong>s program. Yderligere information kan<br />

findes i Anvendelsesteknik bind 2 og på <strong>Viega</strong>s nationale webside.<br />

106


2 Varmeteknik – Rørsystemer af kobber<br />

2 Varmeteknik<br />

Rørsystemer af kobber<br />

Profipress – Systembeskrivelse<br />

Anvendelse<br />

Profipress er et varmeinstallationssystem med presforbindel sesteknik, især til varmekedler<br />

og andre dele i varmtvands varmeanlæg. Systemet er dimensioneret til<br />

varmeinstallationer iht. DS/EN 12828<br />

Driftstemperatur ≤ 110 °C<br />

Kapacitet ≤ 1MW.<br />

Foruden de rør og godstykkelser til min. 10 bar som kræves for drikkevandsinstallationer<br />

kan i varmeanlæg anvendes kobberrør med mindre godstykkelser iht.<br />

DS/EN1057 1) .<br />

Brug af Profipress til andre anvendelsesområder end de ovenfor beskrevne skal<br />

afstemmes med vores fabrik i Attendorn.<br />

1)<br />

Vedrørende min. godstykkelser<br />

se venligst<br />

Tab. H-1.<br />

QQFordelingsanlæg<br />

QQFordelings- og stigledninger<br />

QQSolvarmeanlæg<br />

QQFjernvarmeanlæg (> 110 °C – med FKM-tætningselement)<br />

Yderligere<br />

anvendelsesområder<br />

Fittings<br />

Med pres- og<br />

gevindtilslutning<br />

Fig. H–1 Fig. H–2<br />

107


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Rørmateriale<br />

Presfittingmateriale<br />

Tætningselement<br />

Levering<br />

Godkendelser<br />

System<br />

Rør<br />

Standardstørrelser<br />

[mm]<br />

Profipress<br />

Profipress XL<br />

Tekniske data<br />

Kobberrør iht. DS/EN 1057 (Minimum godstykkelse se Tab. H-1)<br />

QQPresfittings 12 – 108 mm kobber<br />

QQPresfittings med gevindtilslutning<br />

12 - 54 mm rødgods<br />

64,0 – 108,0 mm kobber<br />

EPDM, sort (ethylen-propylen-dien-monomer gummi); op til 110 °C; ikke modstandsdygtigt<br />

over for kulbrinte-opløsningsmidler, klorerede kulbrintestoffer, terpentin og benzin<br />

Stænger og ruller (se tabel) kontrolmærket<br />

Profipress med SC-Contur DVGW-reg.nr. DW 8511 AP 3139<br />

Profipress XL DVGW-reg.nr. DW 8511 AT 2347<br />

Profipress kobber-rør iht. DS/EN 1057<br />

12 / 15 / 18 / 22 / 28 / 35 / 42 / 54<br />

64,0 / 76,1 / 88,9 / 108,0<br />

Kobberrør, som kan anvendes i varmeinstallationer<br />

d x s min.<br />

[mm]<br />

Volumen pr. løbende meter rør<br />

[liter/m]<br />

12 x 0,7 0,09<br />

15 x 0,8 0,14<br />

18 x 0,8 0,21<br />

22 x 0,9 0,32<br />

28 x 1,0 0,53<br />

35 x 1,0 0,83<br />

42 x 1,0 1,26<br />

54 x 1,2 2,04<br />

Profipress-XL<br />

64,0 x 2,0 2,83<br />

Tab. H–1<br />

76,1 x 2,0 4,08<br />

88,9 x 2,0 5,66<br />

108,0 x 2,5 8,33<br />

Størrelse<br />

Standard<br />

XL<br />

Materiale,<br />

presfittings<br />

Kobber<br />

Kobber<br />

108


2 Varmeteknik – Rørsystemer af kobber<br />

Komponenter<br />

Fig. H–3<br />

Rør<br />

Foruden de rør og godstykkelser til mindst 10 bar, der kræves inden for drikkevandsområdet,<br />

kan der i varmeanlæg også anvendes kobberrør med mindre godstykkelser<br />

iht. DS/EN 1057. (Minimum godstykkelse se Tab. H-1).<br />

Profipress-komponenter:<br />

Se også kapitlet Drikkevandsinstallation<br />

Presfittings<br />

Det omfattende Profipress-sortiment giver mulighed for mange forskellige former for<br />

installation og tilslutning af kedler og armaturer samt kælder-, fordelings- og stigledninger.<br />

Konstruktion af pre-fabrikerede fordelingsanlæg/skakte og forbindelse af ventiler, fitting<br />

og andre anvendelser er gjort mulig ved hjælp af flanger, adaptorer og gevind<br />

overgange til presforbindelser.<br />

109


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Profipress fittings<br />

SC-Contur er mærket<br />

med den grønne prik<br />

Nogle af fordelene ved <strong>Viega</strong> systemforbindelser<br />

QQTestet iht. DVGW-dokument W 534<br />

QQSC-Contur<br />

QQPresfittings til næsten alle former for<br />

tilslutning<br />

QQPresværktøj til opladning eller lysnettilslutning<br />

QQOver 500 systemkomponenter<br />

Fig. H–4<br />

XL-størrelser<br />

d x s<br />

[mm]<br />

Volumen pr. løbende meter rør<br />

[liter/m]<br />

64,0 x 2,0 2,83<br />

76,1 x 2,0 4,08<br />

88,9 x 2,0 5,66<br />

108,0 x 2,5 8,33<br />

Tab. H–2<br />

Størrelse<br />

XL<br />

Materiale,<br />

presfittings<br />

Kobber<br />

Alle XL- størrelserne er de samme som til drikkevandsinstallation. Direkte presforbindelse<br />

ved etablering af præfabrikerede fordelingsanlæg samt montering af ventiler, armaturer<br />

og instrumenter er mulig ved hjælp af flanger, overgangsstykker og forskruninger.<br />

Kobberfitting<br />

Til tilslutning af<br />

armaturer og ventiler<br />

Fig. H–5<br />

110


2 Varmeteknik – Rørsystemer af kobber<br />

Easytop kuglehaner<br />

Easytop kuglehaner er velegnede til varmeinstallationer iht. DS/EN 12828 og dimensioneret<br />

til en maksimal driftstemperatur på 105 °C. De anvendes især til fordelingsanlæg<br />

og montering af tilslutnings- og vedligeholdelses armaturer, instrumenter og apparater<br />

samt etage- og stigledningssafspærringer.<br />

Farvede hætter giver mulighed for mediemærkning. Eksempel: Opvarmning, fremløb:<br />

rød; opvarmning, tilbageløb: blå. Ny i sortimentet er Easytop kuglehanen med integreret<br />

pumpeforskruning, evt. med gravitationsventil.<br />

Varmefordeling med<br />

udvidelse af varmeanlægget<br />

– Easytop kuglehaner<br />

som afspærringsarmaturer<br />

– Udskiftelige afdækningsplader<br />

i rødt/<br />

blåt til hhv. frem- og tilbageløb<br />

Easytop kuglehaner<br />

Med integreret pumpeforskruning<br />

og evt.<br />

integreret gravitationsventil<br />

Fig. H–6<br />

111


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Tætningselementer<br />

Leveres med indlagt EPDM-tætningselement<br />

QQMaksimal ‚sikkerhedsteknisk dimensioneringstemperatur‘ 120 °C<br />

QQMaksimalt tilladt driftsovertryk 10 bar<br />

QQFKM-tætningselement (specialtilbehør)<br />

QQMaksimal tilladt driftstemperatur 140 °C<br />

QQMaksimalt tilladt driftsovertryk 16 bar<br />

Tætningselementer af (sort) EPDM er monteret som standard og har tilstrækkelig<br />

sikkerhedsreserve til gængse anvendelser inden for bygningsteknik.<br />

Hvis der stilles højere krav, fx til rørsolfangere, kan FKM-tætnings elementer efterbestilles<br />

til manuel udskiftning, eller der kan bestilles Profipress S i str. 12-35 mm,<br />

de har FKM monteret som standard.<br />

FKM-tætningselementer må ikke anvendes i gas- og drikkevands installationer.<br />

112


2 Varmeteknik – Rørsystemer af kobber<br />

Anvendelsesteknik<br />

Stigledninger<br />

I krydsfittingen strømmer vandet uden om det gennemgående rør, der ligger indeni.<br />

Dette princip giver mulighed for, at rørledninger kan krydse hinanden i ét niveau. Der<br />

monteres fladt på væggen eller i gulvkonstruktionen.<br />

Radiatortilslutning<br />

Afgrening fra stigledning<br />

til den ene side<br />

Fig. H–7<br />

Fordele<br />

QQLav monteringshøjde<br />

QQInstallation i ét niveau<br />

QQSkæring/bearbejdning af rør spares<br />

QQIdeelt, hvor pladsen er trang<br />

QQLet montering, også på gulvet<br />

QQLille materialeforbrug<br />

Krydset og overbøjningen muliggør direkte tilslutning til stigledningen, også under<br />

meget trange pladsforhold.<br />

Radiatortilslutning<br />

Afgrening fra stigledning<br />

til begge sider<br />

Fig. H–8<br />

Fordele<br />

QQTidsbesparende montering<br />

QQKan anvendes på meget trange steder<br />

QQPæn synlig installation<br />

QQGennemprøvet løsning til offentlige bygninger<br />

113


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Tilbageløbsforskruninger<br />

Tilbageløbsforskruninger til radiatorer kan leveres med prestilslutning i vinkel- eller<br />

gennemløbsform.<br />

Tilbageløbsforskruninger<br />

til radiatorer<br />

I vinkel- eller gennemløbsform<br />

med presmuffe<br />

til direkte presning<br />

Fig. H–9<br />

Fordele<br />

QQKold prestilslutningsteknik, ingen lodning<br />

QQIntet tidsspilde med af og gen-montering hvor evt. pakninger skal beskyttes mod<br />

varme<br />

QQIngen anløbning eller lodderester<br />

QQPænt udseende: Rødgods, forniklet<br />

Radiatortilslutning<br />

Renovering uden brandfare<br />

Fig. H–10<br />

Det kan ikke udelukkes, at lodning efterlader<br />

brændspor og materialerester.<br />

Fig. H–11<br />

Den kolde prestilslutningsteknik –<br />

rent arbejde fra begyndelsen.<br />

114


2 Varmeteknik – Rørsystemer af kobber<br />

Radiatortilslutning<br />

Tilslutning via central gulvfordeler<br />

Med gulvfordeleren undgår man at krydse rørledninger. Ill. H-12 viser radiatortilslutning<br />

via flere presforbundne gulvfordelere.<br />

QQPladsbesparende<br />

QQKrydsningsfrie ledninger med lav gulvkonstruktion<br />

QQKort montagetid<br />

QQDer er ikke brug for yderligere fittings<br />

QQInstallation af hele etagefordelingen med presfittings<br />

Tre presforbundne gulvfordelere giver fire udløb til radiatorindløbsåbning. For enden<br />

af fordeleren kan der presses en reduktionsmuffe, fx 22 x 15.<br />

Fordele ved<br />

gulvfordeleren<br />

Fordelerudvidelse<br />

En gulvfordeler skal vendes, så installationen sikres de korrekte forbindelser for<br />

frem- og tilbageløb.<br />

F<br />

F<br />

Gulvfordeler<br />

Som central<br />

boligfordeler<br />

F<br />

Fig. H–12<br />

115


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Radiatortilslutning<br />

Fra gulvet via central<br />

gulvfordeler<br />

Fig. H–13<br />

Anvendelsesmuligheder<br />

QQTil radiatortilslutning via flere presforbundne gulvfordelere.<br />

QQTil montering i utilgængelige områder for at undgå overbøjninger af rørledninger<br />

og skabe mulighed for lav indbygningshøjde.<br />

Gulvfordeler<br />

Med isoleringsboks<br />

Fig. H–14 Fig. H–15<br />

116


2 Varmeteknik – Rørsystemer af kobber<br />

Tilslutning med kryds-T-stykke<br />

Kryds-T-stykker<br />

I etagefordelingen<br />

Fig. H–16<br />

Kryds-T-stykke<br />

Med kobberrør fra gulvet<br />

Fig. H–17<br />

Ved drejning af kryds-T-stykkerne skal installationen sikres de korrekte forbindelser<br />

for fremløb og tilbageløb.<br />

Frie rør og presfittings skal isoleres og beskyttes mod ydre mekaniske påvirkninger.<br />

117


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Eksempel på<br />

anvendelse<br />

Afstande mellem rørledningens<br />

fastgøringer i<br />

forbindelse med kryds-Tstykke<br />

Fig. H–18<br />

Monteringsanvisninger<br />

Ved udlægning af rørledninger skal det sikres, at<br />

QQudlægningen er spændingsfri,<br />

QQrørene ikke forårsager skader på grund af termiske længdeudvidelser og ikke berører<br />

hinanden,<br />

QQder anvendes glidende rørfastgøringer, som ikke begrænser en ændring i rørenes<br />

længde,<br />

QQrørfastgøringerne ikke utilsigtet bliver til faste punkter.<br />

Kryds-T-stykke<br />

Med todelt<br />

isoleringsboks<br />

Fig. H–19 Fig. H–20<br />

118


2 Varmeteknik – Rørsystemer af kobber<br />

Tilslutning med T-stykke<br />

Montering med<br />

T-stykke<br />

Tilslutning fra gulve og<br />

via radiatortilslutningsblok<br />

fra væggen<br />

Fig. H–21 Fig. H–22<br />

Tilslutning med radiatortilslutningsblok<br />

Radiator med tilslutningsstykke og adaptersæt (til ventilradiatorer med indvendigt eller<br />

udvendigt gevind). Radiatortilslutningsblokken er installeret i væggen med kobberrør<br />

og udlagt i gulvkonstruktionens udligningslag.<br />

Hvis gulvkonstruktionen er > 90 mm, anbefaler vi radiatortilslutningsstykket med<br />

255 mm tilslutningshøjde.<br />

Montage<br />

Fig. H–23 Fig. H–24<br />

119


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Monteringsfordele ved en radiatortilslutningsblok<br />

QQTilslutningsafstand på 50 mm.<br />

QQRadiatoren monteres først, når pudsning, fliselægning, gulv- og malerarbejder er<br />

afsluttet.<br />

QQIngen ekstra arbejde, fordi radiatoren ikke skal af - og påmonteres flere gange.<br />

QQRadiator og tilslutningsledninger bliver ikke beskadiget under det øvrige bygningsarbejde.<br />

QQIngen midlertidig oplagring og ingen beskadigelse af radiatoren før den endelige<br />

montering.<br />

QQEn ekstra vandtryksprøve af varmeledningerne er ikke nødvendig (dog jf. DS 469).<br />

QQTryktest og prøveopvarmning uden radiatormontering (vinter).<br />

QQLav monteringsdybde i væggen.<br />

QQDet rustfri stål og det forniklede radiatortilslutningsstykke passer sammen i farven.<br />

Kort oversigt over fordelene<br />

Radiatortilslutningsstykke<br />

Montagemål<br />

Fig. H–25 Fig. H–26<br />

120


2 Varmeteknik – Rørsystemer af kobber<br />

Tilslutning med sokkellistetilslutningssæt<br />

Radiatortilslutningssæt<br />

med kompakt<br />

radiator<br />

Tovejs, med radiatortilslutningssæt<br />

fra fodpanel<br />

Fig. H–27<br />

Radiatortilslutningssæt<br />

til sokkelliste<br />

Montagemål<br />

Fig. H–28<br />

QQTil gængse fodpaneler<br />

QQPænt udseende med tilslutningsstykker af forniklet rødgods<br />

QQTil alle gængse radiatortyper<br />

121


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Adaptersæt til radiatorer<br />

Adapter sæt<br />

Radiatortil -<br />

slutningsstykker/-sæt<br />

Ventilradiator<br />

G 3/4<br />

Adaptersæt<br />

Rp 1/2<br />

Adaptersæt<br />

1022.5 1022.6<br />

1096.9 1096.8<br />

Tab. H–3<br />

Nødvendige adaptersæt og ventilradiatortilslutningsstykker til radiatorer med indvendigt<br />

og udvendigt gevind.<br />

122


2 Varmeteknik – Rørsystemer af kobber<br />

Isolering og udlægning af rørledninger*<br />

Afhængigt af anvendelsesområde og rørmateriale kræves der af følgende årsager isolering,<br />

udlægning og fastgøring af rørledninger.<br />

QQBeskyttelse mod kondensdannelse<br />

QQForebyggelse af udvendig korrosion<br />

QQBegrænsning af varmetab<br />

QQForebyggelse af knæklyde på grund af længdeudvidelse<br />

QQIngen overførsel af strømningsstøj<br />

Rør, som ikke allerede er beklædt eller isoleret fra producentens side, og alle form- og<br />

tilslutningsdele skal uafhængigt af varmeisoleringskrav isoleres på stedet for at forhindre<br />

udvendig korrosion og overførsel af strømningsstøj. Ved udlægningen skal rørledningerne<br />

fastgøres således, at driftsbetingede længdeændringer ikke giver anledning<br />

til knæklyde, som i høj grad kan forringe brugerkomforten.<br />

Hvis rørledninger udlægges på bærende underlag, skal de fastgøres. Den glatte overflade<br />

skal genetableres, så den kan danne underlag for skridtstøj- og evt. anden isolering.<br />

Til udfyldning over rørledningerne må der kun anvendes fast fyldmateriale.<br />

Isolering mod varmetab*<br />

Varmefordelingsledninger skal isoleres for at begrænse varmeafgivelsen. DS 469 og<br />

DS 452.<br />

Kobberrør<br />

SANCO®-rør, blanke<br />

WICU®-rør,<br />

leveres isoleret<br />

Eco<br />

Fig. H–29<br />

123


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Undtagelse fra<br />

isoleringspligten<br />

Varmefordelingsledninger<br />

Anvisningerne i DS 469 samt tillæg I og tillæg II skal følges. Der er europæiske regler<br />

under udarbejdelse. I det følgende gives anvisninger jf. det tyske energispareprogram<br />

EnEv. Ledningerne i varmeanlægget er også varmedistributionsledninger og skal isoleres<br />

iht. EnEv, bilag 5. Vigtige anvisninger vedrørende rørledninger i gulv:<br />

QQRørledninger i gulvkonstruktionen mellem opvarmede rum, også rum med forskellige<br />

brugere, behøver kun at isoleres med 9 mm – baseret på λ = 0,04 W/K.<br />

QQFor så vidt centralvarmeledninger iht. linje 1 til 4 befinder sig i en brugers opvarmede<br />

rum eller i bygningsdele mellem en brugers opvarmede rum, og deres varmeafgivelse<br />

kan påvirkes af fritliggende afspærringsanordninger, stilles der ingen<br />

minimumskrav til isoleringslagets tykkelse.<br />

Mindste isoleringstykkelser<br />

Lednings-/armaturtype<br />

Mindste isoleringstykkelse<br />

ved en varmeledningsevne<br />

på 0,035 W/(mK)<br />

1 Indvendig diameter op til 22 mm 20 mm<br />

2 Indvendig diameter fra 22 til 35 mm 30 mm<br />

3 Indvendig diameter fra 35 til 100 mm Lig indvendig diameter<br />

4 Indvendig diameter over 100 mm 100 mm<br />

5<br />

Ledninger og armaturer iht. linje 1 til 4 – i væg- og loftgennemføringer,<br />

i ledningers krydsningsområder, ved<br />

lednings tilslutningssteder og ved centrale ledningsnetfordelere<br />

1/2 af kravene i linje 1 til 4<br />

6<br />

Centralvarmeledninger iht. linje 1 til 4, som efter<br />

denne forordnings ikrafttræden udlægges i bygningsdele<br />

mellem opvarmede rum med forskellige brugere<br />

1/2 af kravene i linje 1 til 4<br />

7 Ledninger iht. linje 6, i gulvet 6 mm<br />

Centralvarmeledninger i opvarmede rum inden<br />

for en brugerenhed<br />

Ingen krav<br />

Tab. H–4<br />

124


2 Varmeteknik – Rørsystemer af kobber<br />

Rørledninger i gulvet<br />

Tabel H-4 viser mindste tykkelse for isoleringsmaterialer med en varme ledningsevne<br />

på 0,035 W/mK. Hvis der anvendes isoleringsmaterialer i andre varmeledningsgrupper<br />

end WLG 035, skal minimumstykkelserne omregnes. WICU-extra rør er kobberrør, som<br />

er isoleret med et materiale, der har en varmeledningsevne på 0,025 W/mK. Dette<br />

medfører automatisk en minimering af den totale udvendige diameter og giver mulighed<br />

for minimale gulvhøjder.<br />

Eksempler<br />

1<br />

2<br />

Ø 19<br />

Ø 15<br />

20 °C<br />

45<br />

Isolering af rørledninger<br />

i gulv<br />

kobber-rør 15 mm,<br />

kunststofbeklædt,<br />

i etageadskillelser mellem<br />

opvarmede rum<br />

med samme bruger<br />

3<br />

20<br />

4<br />

5<br />

25<br />

6<br />

7<br />

160<br />

8<br />

20 °C<br />

Fig. H–30<br />

1 Støbt cementgulv<br />

2 PE-folie<br />

3 Skridtlydisolering<br />

4 Udligningslag WLG 040<br />

(f. eks. Polystyrol plader)<br />

5 Rørledning, beklædt<br />

6 Udfyldning (Meabit / Perlit)<br />

7 Betondæk<br />

8 Rørfæste (Nylon)<br />

>><br />

125


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Isolering af rørledninger<br />

i gulv<br />

kobber-rør, 15 mm, med<br />

fabriksisolering<br />

(λ = 0,026 W / mK),<br />

i etageadskillelser mellem<br />

opvarmede rum<br />

med forskellige brugere<br />

1<br />

2<br />

3<br />

Ø 27<br />

Ø 15<br />

20 °C<br />

45<br />

15<br />

4<br />

35<br />

5<br />

6<br />

160<br />

7<br />

20 °C<br />

Fig. H–31<br />

1 Støbt cementgulv<br />

2 PE-folie<br />

3 Skridtlydisolering<br />

4 Udligningslag WLG 040<br />

(f. eks. Polystyrol plader)<br />

5 Fabriksisolering WLG 025<br />

6 Udfyldning (Meabit / Perlit)<br />

7 Betondæk<br />

Isolering af rørledninger<br />

i gulv<br />

kobber-rør, 15 mm,<br />

fabriksisolering<br />

(λ = 0,026 W / mK), i gulv<br />

på jord, udendørs eller i<br />

uopvarmede rum<br />

1<br />

2<br />

Ø 36<br />

Ø 15<br />

20 °C<br />

45<br />

3<br />

20<br />

4<br />

5<br />

45<br />

6<br />

7<br />

8<br />

Fig. H–32<br />

1 Støbt cementgulv<br />

2 PE-folie<br />

3 Skridtlydisolering<br />

4 Udligningslag WLG 040<br />

(f. eks. Polystyrol plader)<br />

5 Fabriksisolering WLG 025<br />

6 Udfyldning (Meabit / Perlit)<br />

7 Betondæk<br />

8 Jordfyld (skærver)<br />

126


2 Varmeteknik – Rørsystemer af kobber<br />

Blandingsinstallationer<br />

Da næsten al ilt drives ud, når anlægget varmes op, kan Profipress-systemet blandes<br />

med rør eller komponenter af andre <strong>metal</strong>materialer i varmeanlæg uden risiko for korrosion.<br />

For stor iltoptagelse i opvarmningsvandet skal forhindres gennem korrekt konstruktion<br />

af varmeanlægget, driftssikre armaturer og fagligt korrekt installation af ekspansionsbeholdere.<br />

Hvis det ikke med sikkerhed kan undgås, at ilt trænger ind i et opvarmningssystem,<br />

findes der flere metoder i det tekniske regelsæt VDI 2035 – fx kemisk binding af ilten.<br />

Tryktest<br />

Tryktest med vand<br />

Alle rørledninger bør i færdigmonteret, men endnu ikke tildækket stand gennemgå en<br />

tæthedsprøvning iht. DS 469.<br />

Anlægget testes med et tryk, der svarer til sikkerhedsventilens aktiveringstryk.<br />

Tryktest med luft<br />

Tryktesten af Profipress-systemet i varmeanlæg kan også udføres med trykluft eller<br />

inerte gasser.<br />

127


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Fjernvarmeanlæg<br />

Profipress kan anvendes i fjernvarmeanlæg.<br />

Med EPDM-tætningselement (standardtætningselement)<br />

QQMaksimal ‚sikkerhedsteknisk dimensioneringstemperatur´ 120 °C<br />

QQMaksimalt tilladt driftsovertryk 10 bar<br />

Med FKM-tætningselement (specialtilbehør) / Profipress S system<br />

QQMaksimal tilladt driftstemperatur 140 °C<br />

QQMaksimalt tilladt driftsovertryk 16 bar<br />

FKM-tætningselement<br />

Presssystem<br />

Betegnelse<br />

Anvendel sesområde<br />

Farve<br />

Profipress<br />

Fluorelastomer<br />

Solvarmeanlæg<br />

Vakuumrør<br />

Fjernvarmeanlæg<br />

sort, mat<br />

Størrelser DN 10 - DN 100<br />

Tab. H–5<br />

Bestelldaten<br />

Mål Artikelnr.: Stk. / kolli<br />

12 x 2,35 459 376<br />

15 x 2,50 459 390<br />

18 x 2,50 459 406<br />

22 x 3,00 459 413 5<br />

28 x 3,00 459 420<br />

35 x 3,00 459 437<br />

42 x 4,00 459 444<br />

54 x 4,0 459 451<br />

64 x 5,0 614461<br />

76,1 x 5,0 459 468 1<br />

88,9 x 5,0 459 475<br />

108,0 x 5,0 459 482<br />

Tab. H–6<br />

Fjernvarmestation<br />

Med ekstern varmtvandsbeholder<br />

Fig. H–33<br />

Hvis fjernvarmevandet indeholder tilsætningsstoffer (fx antikorrosions- eller -frostmidler),<br />

skal anvendelse af Profipress afstemmes med vores fabrik i Attendorn.<br />

128


2 Varmeteknik – Rørsystemer af kobber<br />

Systembeskrivelse Profipress S-pres fitting<br />

Anvendelse<br />

Profipress S-press fittings egner sig til varmesystemer med temperaturer over<br />

100 °C og kortvarigt temperaturer over 280 °C sammen med kobberrør i overensstemmelse<br />

med EN 1057.<br />

QQSolvarmeanlæg<br />

QQFjernvarmeanlæg<br />

QQLavtryksdampanlæg<br />

Anvendelse af Profipress-fitting er mulig hvis O-ringen skiftes ud med FKM-tætningselementer.<br />

Brug af systemet i anlæg med tilsætningsstoffer (fx antikorrosions- eller frostmidler)<br />

i opvarmningsvandet eller til andre end de beskrevne anvendelser skal afstemmes<br />

med vores fabrik i Attendorn.<br />

Driftsbetingelser for fjernvarmeanlæg<br />

QQDriftstryk<br />

p max ≤ 16 bar<br />

QQDriftstemperatur T max ≤ 140 °C<br />

Driftsbetingelser for lavtryksdampanlæg<br />

QQDriftstryk<br />

p max < 1 bar<br />

QQDriftstemperatur T max ≤120 °C<br />

Mærkning<br />

QQHvid prik på vulsten på SC-Contur.<br />

QQHvid firkant med ID-markering for FKM.<br />

Profipress S- og Profipress-presfittings med FKM-tætningselementer må ikke<br />

anvendes i drikkevands- og gasinstallationer.<br />

Mærkning<br />

Profipress S<br />

Orangefarvet<br />

pakning<br />

Fig. H–34 Fig. H–35<br />

129


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Anvendelsesteknik<br />

Rørføring<br />

QQFremløbet skal etableres med stigning og tilbageløbet med fald, således at anlægget<br />

kan tømmes om nødvendigt.<br />

QQVed tømning skal varmemediet opsamles i en beholder.<br />

QQVed udlægning af solfangerledningerne skal der tages højde for den termiske<br />

længdeekspansion.<br />

Hvis røret er 15 m langt ved en medietemperatur på 15 °C, bliver det ca. 21 mm længere,<br />

hvis mediets temperatur stiger til 100 °C.<br />

Rørmateriale<br />

I solvarmeanlæg kan der med Profipress også anvendes kobberrør med mindre godstykkelser<br />

i overensstemmelse med DS/EN 1057 1 . (Minimum godstykkelse se Tab. H-1).<br />

Pas på ved forisolerede rør!<br />

Den maksimale tilladelige driftstemperatur for isoleringsmaterialet<br />

er som regel kun 100 °C.<br />

Producentens angivelser skal overholdes.<br />

Skylning<br />

Til skylning af ledninger er det ved Profipress tilstrækkeligt at anvende den enkle skyllemetode,<br />

dvs. med vand og normalt ledningstryk. Hele solfangerkredsløbet skylles –<br />

inklusive solvarmeanlæg, solfanger og lagertank – i pumpens strømningsretning.<br />

For at undgå, at skyllevæsken koger eller fryser, bør anlægget ikke skylles ved<br />

ekstremt høje eller lave udetemperaturer.<br />

Tryktest<br />

Tryktesten skal udføres i overensstemmelse med solfangerproducentens anvisninger.<br />

Bemærk: Omfattende information om etablering af solvarmeanlæg kan evt. rekvireres<br />

fra Kupferinstitut Düsseldorf<br />

130


2 Varmeteknik – Rørsystemer af kobber<br />

Solvarmeanlæg<br />

Hustilslutning<br />

Fig. H–36<br />

131


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Rørsystemer af stål<br />

Prestabo – Systembeskrivelse<br />

Anvendelse<br />

Prestabo-systemet er beregnet til industri- og varmeanlæg og er uegnet til drikkevandsanlæg.<br />

Rør og fittings er derfor mærket med et rødt symbol „Nicht für<br />

Trinkwasserinstallationen“ (Uegnet til drikkevandsinstallationer).<br />

Prestabo-komponenter må kun anvendes sammen med elementer, som hører til<br />

systemet. Brug af systemet til andre end de beskrevne anvendelser skal afstemmes<br />

med vores fabrik i Attendorn.<br />

Prestabo presfittings er udstyret med SC-Contur og er synligt utætte i upresset<br />

tilstand.<br />

Drifsbetingelser ved anvendelse med EPDM-tætningselement<br />

Q Q Vand, lukket system med driftstemperaturer op til maks. 110 °C: p max ≤ 16 bar<br />

QQTrykluft, tør og fri for olie: p max ≤ 10 bar<br />

Drifsbetingelser ved anvendelse med FKM-tætningselement<br />

Q Q Vand: ved driftstemperaturer op til maks. 140 °C: max.p max ≤ 16 bar<br />

QQTrykluft, tør, men olieholdig: p max ≤ 10 bar<br />

Prestabo rør, presfittings<br />

og flanger<br />

Med rød mærkning:<br />

„Nicht für TW-Installationen<br />

geeignet“ (Uegnet<br />

til drikkevandsinstallationer)<br />

Fig. H–37 Fig. H–38<br />

132


2 Varmeteknik – Rørsystemer af stål<br />

Tekniske data<br />

Ulegeret stål, materialenr. 1.0308 iht. DS/EN 10305-3, udvendig forzinket. Rørstørrelser<br />

fra 15 til 54 mm kan også leveres med 1,0 mm PP-beklædning.<br />

Leveres fra fabrikken med EPDM-tætningselement som O-ring til driftstemperaturer<br />

≤ 110 °C og driftstryk op til 16 bar<br />

6 m stænger, tæthedstestet og kontrolmærket<br />

12 / 15 / 18 / 22 / 28 / 35 / 42 / 54 / 64,0 / 76,1 / 88,9 / 108,0<br />

QQSolvarmeanlæg (uden PP-beklædt rør)<br />

QQKlimaanlæg<br />

QQVarmeanlæg<br />

QQTrykluftanlæg<br />

QQVakuumanlæg<br />

QQAnlæg til tekniske gasser<br />

Tekniske data – Prestabo-rør, blankt<br />

Rør Ø udvendig x s<br />

[mm]<br />

Volumen<br />

pr. lb. m rør<br />

[liter / m]<br />

Vægt<br />

pr. lb. m rør<br />

[kg / m]<br />

Vægt<br />

pr. 6 m stang<br />

[kg]<br />

Artikelnr.<br />

12 x 1,2 0,07 0,32 1,9 650 339<br />

15 x 1,2 0,13 0,41 2,5 559 441<br />

18 x 1,2 0,19 0,50 3,0 559 458<br />

22 x 1,5 0,28 0,80 4,6 559 465<br />

28 x 1,5 0,49 1,00 5,9 559 472<br />

35 x 1,5 0,80 1,20 7,4 559 496<br />

42 x 1,5 1,19 1,50 9,0 559 489<br />

54 x 1,5 2,04 2,00 11,7 559 502<br />

64,0 x 2,0 2,83 3,06 18,3 598 327<br />

76,1 x 2,0 4,08 3,66 21,9 598 334<br />

88,9 x 2,0 5,66 4,29 25,7 598 341<br />

108,0 x 2,0 8,49 5,23 31,4 598 358<br />

Tekniske data – Prestabo-rør, beklædt<br />

17 x 2,2 0,13 0,45 2,7 577 117<br />

20 x 2,2 0,19 0,60 3,3 577 124<br />

24 x 2,5 0,28 0,82 4,9 577 131<br />

30 x 2,5 0,49 1,10 6,4 577 148<br />

37 x 2,5 0,80 1,30 8,1 577 551<br />

44 x 2,5 1,19 1,60 9,7 577 568<br />

56 x 2,5 2,04 2,10 12,6 577 575<br />

Tab. H–7<br />

Rør- og presfittingsmateriale<br />

Tætningselement<br />

Tilstand ved levering<br />

Størrelser [mm]<br />

Anvendelsesområder<br />

Tekniske data<br />

Blankt rør<br />

Tekniske data<br />

Mål inkl. 1,0 mm<br />

PP-beklædning<br />

133


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Komponenter<br />

Rør<br />

Udførelser<br />

Tætningselementer<br />

Prestabo stålrør er tyndvæggede, længdesvejsede rør af ulegeret stål,<br />

materialenr. 1.0308 iht. DS/EN 10305-3, med et udvendig zinklag fra 8 til 15 μm (blåkromateret).<br />

De er formstabile, har lille varmeekspansion og er dermed ideelle til kælderog<br />

stigledninger i varmeinstallationer.<br />

Udførelser<br />

QQBlank – alle størrelser. Varme ledninger isoleres efterfølgende.<br />

QQBeklædt – 15 til 54 mm: Med PP-beklædning til installationer, hvor der stilles krav til<br />

udseendet.<br />

QQStænger, 6 m lange, med <strong>metal</strong>lisk, blank ydre og indre overflade.<br />

QQRørenderne er beskyttet mod tilsmudsning med røde kunststofhætter.<br />

QQAlle rør er tæthedstestet.<br />

Tilbehør<br />

FKM-tætningselement til udskiftning for højere belastninger<br />

Mærkning<br />

Uegnet til drikkevand (se<br />

også næste side)<br />

Fig. H–39<br />

134


2 Varmeteknik – Rørsystemer af stål<br />

Mærkning<br />

1 2 4 5 6 7<br />

Mærkning<br />

Blankt og beklædt rør<br />

1 2 3 4 5 6 7<br />

Advarsel!<br />

„Nicht für Trinkwasserinstallationen<br />

zugelassen!“<br />

(Ikke godkendt til<br />

drikkevandsinstallationer!)<br />

Fig. H–40<br />

1 Systemnavn<br />

2 Materialenummer iht. DIN<br />

3 Beklædningsmateriale<br />

4 Nominel diameter x godstykkelse<br />

5 Kode for rørfabrikant<br />

6 Fremstillingsdato, måned og år<br />

7 Serienummer<br />

1 2 3 4 5 6<br />

Rørmærkning<br />

Sendzimir-galvaniseret<br />

rør.<br />

Se venligst s. 184 for<br />

yderligere information<br />

om anvendelsesområder<br />

Fig. H–41<br />

1 Systemproducent / systemnavn<br />

2 Materialenummer<br />

3 Nominel diameter x godstykkelse<br />

4 Serienummer<br />

5 Certificeringsmærke / -nummer<br />

6 Trykniveau<br />

Opbevaring og transport<br />

For at beskytte Prestabo-stålrørene, skal der tages højde for følgende henvisninger<br />

vedrørende transport og opbevaring af rørene:<br />

QQFjern først emballage og beskyttelsesfolier (gælder kun rør pakket ind i PP-folie)<br />

umiddelbart før anvendelse.<br />

QQRørenderne skal forblive lukket med de ved leveringen monterede endehætter indtil<br />

anvendelse.<br />

QQRørende må ikke opbevares på hårde gulve uden beskyttelse.<br />

QQDer må ikke klæbes beskyttelsesfolie el.lign. på rørene.<br />

QQDe må ikke trækkes ud over ladkanter.<br />

QQRengøring af røroverflader må kun foretages med rengøringsmiddel til stål.<br />

135


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Presfittings<br />

Alle presfittings er fremstillet af ulegeret stål, materialenr. 1.0308 iht. DS/EN 10305-3,<br />

udvendigt galvaniseret med et udvendig zinklag fra 8 til 15 μm (blåkromateret).<br />

SC-Contur<br />

Ved påfyldning af anlægget synliggør SC-Contur presfittings, som ved en fejl ikke er<br />

presset. Upressede presfittings detekteres med sikkerhed i trykområdet 1– 6,5 bar ved<br />

vandudsivning eller ved trykfald på testmanometeret og kan straks presses. Trykprøvning<br />

med luft/inert gas i området 110 mbar – 3 bar.<br />

Prestabo<br />

Presfittingsystem med<br />

SC-Contur<br />

Fittings 15,0 til<br />

108,0 mm af ulegeret<br />

stål, udvendigt<br />

galvaniseret<br />

Leveres med EPDM-tætningselement<br />

Fig. H–42<br />

Særlige tekniske egenskaber<br />

QQSC-Contur – med rød markering på vulsten<br />

QQPræcis indstik mht. diameter, længde og rethed<br />

QQFast indstiksdybde med integreret anslag<br />

QQLeveres med tætningselement af EPDM<br />

QQPresmuffevulstens volumen er nøjagtigt afpasset efter tætningselementet<br />

QQAnerkendt teknik<br />

QQOmfattende fittingssortiment<br />

QQ<strong>Viega</strong> presmaskiner – ledningsfri eller til lysnet – til økonomisk enmandsmontering<br />

136


2 Varmeteknik – Rørsystemer af stål<br />

Tætningselementer<br />

EPDM<br />

Prestabo presfittings er fra fabrikkens side monteret med EPDM-tætnings elementer,<br />

hvilket er tilstrækkeligt til de fleste anvendelsesområder. Nedenstående tabel viser<br />

nogle typiske tilfælde:<br />

Prestabo med EPDM-tætningselement<br />

Anvendelsesområde<br />

[°C] [bar]<br />

T max p max<br />

Anvendelsesområde<br />

Bemærkninger<br />

Pumpevarmeanlæg til<br />

max.<br />

Varme<br />

varmt vand, 95 °C,<br />

– DS/EN 12828<br />

105<br />

radiatorindløbsåbning<br />

Solvarmeanlæg Solvarmekredsløb – 6 Til plane solfangere<br />

Klimaanlæg<br />

– 10<br />

Trykluft Alle ledningsdele 20 10<br />

Inhibitorer til vandkølere,<br />

se Materialebestandighed<br />

Tør, maks. oliekoncentration<br />

25 mg / m³<br />

Vakuum Alle ledningsdele 20 - 0,8<br />

Tekniske gasser Alle ledningsdele 20 – Forespørgsel nødvendig!<br />

Tab. H–8<br />

FKM<br />

Til anvendelsesområder med højere temperaturer og tryk kan Prestabo presfittings<br />

monteres med et FKM-tætningselement.<br />

I så fald skal standard-tætningselementerne af EPDM udskiftes med FKM-elementerne.<br />

Eksempler findes i nedenstående tabel.<br />

Anvendelsesområder for Prestabo med FKM-tætningselement<br />

Lukket sekundært kredsløb<br />

Anvendelsesområde<br />

Anvendelsesområde<br />

T max<br />

[°C]<br />

Fjernvarme<br />

Fjernvarmeanlæg efter indføring<br />

i huset<br />

140 16<br />

Damp Lavtryksdampanlæg 120 < 1<br />

Solvarmeanlæg<br />

Solvarmekredsløb – 6<br />

Tab. H–9<br />

Maks. driftstryk<br />

[bar]<br />

Bemærkninger<br />

Til solfangere med<br />

evakuerede glasrør<br />

Bestillingsdata til FKM-tætningselementer<br />

Mål [mm] Art.nr. Mål [mm] Art.nr.<br />

12 x 2,35 459 376 42 x 4,00 459 444<br />

15 x 2,50 459 390 54 x 4,00 459 451<br />

18 x 2,50 459 406 64,0 x 5 614 461<br />

22 x 3,00 459 413 76,1 x 5 614 485<br />

28 x 3,00 459 420 88,9 x 5 614 478<br />

35 x 3,00 459 437 108,0 x 5 614 492<br />

Tab. H–10<br />

FKM-tætningselementer<br />

må ikke anvendes i drikkevands-<br />

og<br />

gasinstallationer<br />

137


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Anvendelsesteknik<br />

Udvendig korrosionsbeskyttelse*<br />

Uddrag af DIN 50929<br />

„Hvor korrosionsbelastningen på grund af fugt kun er lejlighedsvis og kortvarig, er<br />

varmgalvaniserede/galvanisk forzinkede ståltyper også tilstrækkeligt bestandige over<br />

for korrosion“.<br />

Prestabo rør og fittings er beskyttet mod korrosion med et udvendigt zinklag fra 8 til<br />

15 μm (blåkromateret). I vedvarende fugtige omgivelser, eller hvor der er risiko for kondensdannelse,<br />

fx i kølekredsløb, skal der anvendes en ubrudt ydre korrosionsbeskyttelse,<br />

som med sikkerhed forhindrer eventuelle korrosionsfremmende påvirkninger.<br />

Dette gælder også for afisolerede afsnit af kunststofbeklædte Prestabo-rør samt for<br />

form- og tilslutningsdele. Producentens anvendelsesforskrifter skal overholdes.<br />

Bygningsdele som fx gulve og murværk i badeværelser, storkøkkener eller slagterier<br />

kan være vedvarende fugtbelastede og stiller derfor øgede krav til den udvendige<br />

korrosionsbeskyttelse af Prestabo rørledninger. Følgende beskyttelsesmetoder<br />

har vist sig effektive<br />

QQAnvendelse af isoleringsslanger af celleplast med lukkede celler med omhyggelig<br />

tildækning af alle stød- eller skærekanter med egnet klæbemateriale<br />

QQFugtbeskyttelse af rørledninger i gulvkonstruktionen med mellemlægsfolie<br />

QQUdlægning af rørledningerne uden for fugtrisiko-området.<br />

Ved anvendelse i industrianlæg, hvor den omgivende luft stiller øgede krav til den<br />

udvendige korrosionsbeskyttelse, skal den pågældende fabriks normer desuden overholdes.<br />

Indvendig korrosionsbeskyttelse (trefasegrænsen)<br />

Ved <strong>metal</strong>materialer kan der forekomme korrosion omkring trefasegrænsen –<br />

vand / materiale / ilt. Denne korrosion kan undgås, hvis anlægget altid er fuldstændig<br />

fyldt med vand efter den første påfyldning og udluftning. Hvis anlægget ikke skal<br />

idriftsættes straks efter installeringen, anbefales det at tryk- og tæthedstestes med luft<br />

eller inerte gasser.<br />

138


2 Varmeteknik – Rørsystemer af stål<br />

Isolering og udlægning af rørledninger<br />

Afhængigt af anvendelsesområde og rørmateriale kræves der af følgende årsager isolering,<br />

udlægning og fastgørelse af rørledninger<br />

QQBeskyttelse mod kondensdannelse<br />

QQForebyggelse af udvendig korrosion<br />

QQBegrænsning af varmetab<br />

QQForebyggelse af knæklyde på grund af længdeudvidelse<br />

QQIngen overførsel af strømningsstøj<br />

Rør, som ikke allerede er beklædt eller isoleret ved leveringen, og alle form- og tilslutningsdele<br />

skal uafhængigt af varmeisoleringskrav isoleres på stedet for at forhindre<br />

udvendig korrosion og overførsel af strømningsstøj. Ved udlægningen skal rørledningerne<br />

fastgøres således, at driftsbetingede længdeændringer ikke giver anledning til<br />

knæklyde, som i høj grad kan forringe brugerkomforten.<br />

Isolering mod varmetab<br />

For at begrænse varmeafgivelsen fra rørledninger til varmefordelingen skal der isoleres<br />

i overensstemmelse de nationale regler, DS 469.<br />

139


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Eksempel med rørledninger i gulv<br />

Isolering af rørledninger<br />

i gulv<br />

Prestabo rør 15 mm,<br />

beklædt med kunststof, i<br />

etageadskillelser mellem<br />

opvarmede rum<br />

1<br />

2<br />

Ø 17<br />

Ø 15<br />

20 °C<br />

45<br />

3<br />

4<br />

5<br />

20<br />

25<br />

6<br />

7<br />

8<br />

20 °C<br />

160<br />

Fig. H–43<br />

1 Støbt cementgulv<br />

2 PE-folie<br />

3 Skridtlydisolering<br />

4 Udligningslag WLG 040<br />

(f. eks. Polystyrol plader)<br />

5 Rørledning (PP-beklædt)<br />

6 Udfyldning (Meabit / Perlit)<br />

7 Betondæk<br />

8 Rørfæste (Nylon)<br />

Isolering af rørledninger<br />

i gulv<br />

Prestabo-rør 15 mm,<br />

med 9 mm isolering<br />

(λ = 0,04 W / mK) i<br />

etageadskillelser mellem<br />

to opvarmede rum<br />

1<br />

2<br />

Ø 33<br />

Ø 15<br />

20 °C<br />

45<br />

EnEV, tillæg 5, tabel 1,<br />

linje 7 (Tyskland)<br />

3<br />

4<br />

15<br />

35<br />

5<br />

6<br />

160<br />

7<br />

20 °C<br />

Fig. H–44<br />

1 Støbt cementgulv<br />

2 PE-folie<br />

3 Skridtlydsisolering<br />

4 Udligningslag WLG 040<br />

(fx polystyrolplader)<br />

5 Varmeisoleringsrør<br />

6 Udfyldning (Meabit / Perlit)<br />

7 Betondæk<br />

140


2 Varmeteknik – Rørsystemer af stål<br />

Diagrammet viser den lineære varmeafgivelse i watt/meter fra Prestabo-rør afhængigt<br />

af rørdiameter og temperaturdifferencen mellem medie og omgivelser. Kurverne gælder<br />

for uisolerede Prestabo-rør – blanke og pp-beklædte.<br />

∆T er differencen mellem varm rørledning T P og omgivelsestemperatur T U<br />

∆T = T P - T U<br />

Varmetab fra<br />

Prestabo rør<br />

Blank og coated, ikke<br />

isoleret<br />

Varmeafgivelse [W / m]<br />

Temperaturdifference<br />

ΔT [K]<br />

Fig. H–45<br />

141


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Potentialeudligning*<br />

Prestabo-systemet er et elektrisk ledende system og skal derfor medtages i potentialudligningen.<br />

Hvis et rørledningssystem eller dele deraf etableres eller udskiftes i forbindelse<br />

med en sanering, skal potentialudligningen efterprøves af en elektroinstallatør.<br />

Den, der etablerer det elektriske anlæg, har ansvaret for potentialudligningen!<br />

Blandingsinstallationer<br />

Prestabo-systemet kan anvendes med enkelte elementer af rødgods (<strong>Viega</strong> Sanpress). Til<br />

overgange fra Prestabo til dele af kobber eller rustfrit stål skal der benyttes en rødgodsfitting.<br />

Da der ved opvarmning af anlægget sker en termisk uddrivning eller en binding til<br />

<strong>metal</strong>overfladen af hele iltindholdet, er der ingen korrosionsrisiko. Det skal undgås, at der<br />

optages ilt i varmeanlæggets vand, hvilket kræver korrekt installation af anlægget og<br />

ekspansionsbeholderen samt anvendelse af egnede armaturer. Hvis det ikke kan undgås,<br />

at der optages ilt, giver VDI 2035 anvisninger på yderligere forholdsregler – fx kemisk<br />

binding af ilten. Blanding af komplette installationssystemer er ikke tilladt.<br />

Rørføring og fastgøring<br />

Til fastgøring af rørene anvendes gængse rørbøjler med kloridfri, lydisolerende indlæg.<br />

De generelle regler for fastgøringsteknik er gældende.<br />

QQFastgjorte rørledninger må ikke benyttes som holdere for andre rørledninger og byggekomponenter<br />

QQRørkroge er ikke tilladt<br />

QQOverhold afstanden til fittings<br />

QQVær opmærksom på udvidelsesretningen – indarbejd faste og glidende punkter i<br />

planlægningen<br />

De fastgørelsesafstande, der er angivet i tabellen, skal overholdes for at undgå vibrationsstøj.<br />

Anbefalede afstande mellem fastgøringer<br />

Rørstørrelse<br />

[mm]<br />

Afstand mellem fastgøringer<br />

af stangrør<br />

[m]<br />

Rørstørrelse<br />

[mm]<br />

Afstand mellem fastgøringer<br />

af stangrør<br />

[m]<br />

12 1,25 42 3,00<br />

15 1,25 54 3,50<br />

18 1,50 64,0 4,00<br />

22 2,00 76,1 4,25<br />

28 2,25 88,9 4,75<br />

35 2,75 108,0 5,00<br />

Tab. H–11<br />

142


2 Varmeteknik – Rørsystemer af stål<br />

Længdeudvidelse<br />

Rørledninger udvider sig forskelligt i længden ved opvarmning afhængigt af materiale.<br />

For at undgå uønskede spændinger i rørnettet skal der tages hensyn til dette ved projektering<br />

og etablering af rørledningsanlæg. Det er især vigtigt at overholde den korrekte<br />

anvendelse af<br />

QQfaste punkter og glidende punkter<br />

QQRørstrækninger til udligning af udvidelser, for eksempel kompen sationsbøjninger<br />

QQAksialkompensatorer<br />

Rørledningers længdeudvidelse ∆l er afhængig af følgende fysiske størrelser<br />

QQmediets temperaturvariation ∆T,<br />

QQledningslængden l 0 og<br />

QQLængdeudvidelseskoefficienten α.<br />

∆l kan aflæses af diagrammer som Ill. H-46 eller beregnes.<br />

Eksempel<br />

Givne driftsbetingelser<br />

QQDriftstemperaturen ligger mellem 10 og 60 °C – dermed er ∆T = 50 K<br />

QQLedningsafsnittet har en længde på l 0 = 20 m.<br />

QQLængdeudvidelseskoefficienten for galvaniserede stålrør er a = 0,0120 [mm / mK]<br />

Indsætning af værdierne i formlen<br />

∆l = α [mm / mK]· L [m] · ∆T [K]<br />

hvoraf følger: ∆l = 0,0120 [mm / mK] · 20 [m] · 50 [K] = 12 mm<br />

Længdeudvidelsen ∆l bliver 12 mm.<br />

143


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Længdeudvidelse af Prestabo rørledninger<br />

Prestabo længdeudvidelse<br />

Længdeudvidelse Δl [mm]<br />

Rørlængde l 0 [m]<br />

Temperaturdifference<br />

∆T [K]<br />

Fig. H–46<br />

Bestemmelse af længdeudvidelsen<br />

Gå fra x-aksen lodret opad fra værdien for temperaturdifferencen til rørstørrelsen. Længdeudvidelsen<br />

kan nu aflæses til venstre på y-aksen.<br />

Længdeudvidelse Forskellige materialer<br />

Rustfrit stål (1.4401)<br />

galvaniseret stål<br />

kobber<br />

kunststof<br />

Tab. H–12<br />

Længdeudvidelses-koefficient <br />

[mm / mK]<br />

0,0165<br />

0,0120<br />

0,0166<br />

0,08 – 0,18<br />

Længdeudvidelse ved rørlængde<br />

= 20 m og ∆T = 50 K<br />

[mm]<br />

16,5<br />

12,0<br />

16,6<br />

80 – 180<br />

144


2 Varmeteknik – Rørsystemer af stål<br />

Udligning af længdeudvidelser<br />

Længdeudvidelse af rørledninger ved opvarmning kompenseres over vejende af rørnettets<br />

elasticitet. Er dette ved meget lange rørledninger ikke muligt skal anvendes<br />

udligningbøjninger. Disse kan udføres som Z- eller U-udligning. Udligningsbøjninger<br />

er ledningsstrækninger med befæstigelser der kan optage længdeudvidelsen uden at<br />

forårsage mekanisk skade på installationen.<br />

Dette opnås ved at udvidelsesbevægelsen placeres på ledningsstrækninger som er<br />

lange og dermed fleksible nok. Dette kaldes Kompensationsstykker.<br />

Bestemmelse af den nødvendige udbøjning er enkel,<br />

QQFastlæggelse af den størst mulige temperaturforskel ›∆T‹.<br />

QQBestemmelse af rørlængden ›l 0 ‹.<br />

QQVed hjælp af disse værdier beregner man ledningsafsnittets totale forlængelser – i<br />

eksemplet fra forrige kapitel ∆l = 12 mm.<br />

QQI diagrammerne (ill. H-74 og H-75) kan man straks aflæse den nødvendige længde<br />

på kompensationsstykket, L BZ eller L BU .<br />

Beregning af kompensationsstykker<br />

Kompensationsstykker<br />

Z-form med kompensationsstykke<br />

L BZ<br />

og som T-tilslutning<br />

Ø ≤ 54 mm<br />

Fig. H–47 Fig. H–48<br />

Kompensationsstykker<br />

U-form med<br />

kompensationsstykke<br />

L BU Ø ≤ 54 mm<br />

Fig. H–49<br />

145


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Kompensationsstykker<br />

Z- og T-Form<br />

Længdebestemmelse af<br />

kompensationsstykker<br />

(Ø ≤ 54 mm)<br />

Udvidelseskompensation Δl [mm]<br />

Længde på kompensationsstykke<br />

L BZ [m]<br />

Fig. H–50<br />

Kompensationsstykker<br />

U-Form<br />

Udvidelseskompensation Δl [mm]<br />

Længde på kompensationsstykke<br />

L BU [m]<br />

Fig. H–51<br />

146


2 Varmeteknik – Rørsystemer af stål<br />

Kompensationsstykker<br />

Z-form med kompensationsstykke<br />

L BZ<br />

og som T-tilslutning<br />

Ø ≥ 64,0 mm<br />

Fig. H–52 Fig. H–53<br />

Kompensationsstykker<br />

U-form med<br />

kompensationsstykke<br />

L BU Ø ≥ 64,0 mm<br />

Fig. H–54<br />

147


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Kompensationsstykker<br />

Z- og T-Form<br />

Længdebestemmelse af<br />

kompensationsstykker<br />

(Ø ≥ 64,0 mm)<br />

Udvidelseskompensation Δl [mm]<br />

Længde på kompensationsstykke<br />

L BZ [m]<br />

Fig. H–55<br />

Kompensationsstykker<br />

U-Form<br />

Udvidelseskompensation Δl [mm]<br />

Længde på kompensationsstykke<br />

L BU [m]<br />

Fig. H–56<br />

148


2 Varmeteknik – Rørsystemer af stål<br />

Montering<br />

Opbevaring og transport<br />

For at undgå skader på zinklaget bør rørene ikke opbevares direkte på jorden. Ved<br />

transport skal de beskyttes mod skader og må ikke trækkes ud over f.eks. ladkanter.<br />

Forarbejdning<br />

Afkortning<br />

Blanke rør kan afkortes med rørskærer, fintandet <strong>metal</strong>sav eller automatisk sav. Der må<br />

ikke anvendes skæreskiver eller skærebrændere.<br />

På rør, der er leveret med beklædning, skal kunststofkappen fjernes i presfitting-området.<br />

Prestabo afisoleringsværktøj garanterer korrekt afisolering til indstiksdybden.<br />

Længderidser på rørets ydre overflade skal undgås.<br />

Afisolering<br />

Afisoleringsværktøjet sikrer 1 , at alt plastmateriale fjernes præcist i presseområdet 2 .<br />

Skader på <strong>metal</strong>overfladen undgås og der fjernes kun det nødvendige materiale som<br />

kræves for fittingens indstiksdybde 3 .<br />

Det frarådes at anvende andet værktøj.<br />

Bemærk: Klingerne skal ikke slibes, men udskiftes.<br />

Afisoleringsredskab<br />

Fjerner præcis<br />

så meget af beklædningen,<br />

som presfittingen<br />

behøver<br />

(farven på afisoleringsredskabet<br />

kan variere)<br />

1 2 3<br />

Fig. H–57<br />

149


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Afgratning<br />

Rørenderne skal efter afkortning afgrates omhyggeligt udvendigt og indvendigt for at<br />

undgå skader på tætningselementet eller for at undgå afskråning af presfittingen ved<br />

monteringen.<br />

Bukning<br />

Prestabo-rør, blankt, 12, 15, 18, 22 og 28 mm kan koldbøjes med gængse bukkeværktøjer.<br />

Korrekt montage af presfittings kræver, at rørenderne er mindst 50 mm lange.<br />

Bemærk: Beklædte Prestabo-rør bør ikke bukkes, fordi der endnu ikke findes egnet<br />

bukkeværktøj.<br />

Mindste vinkelbenlængde<br />

Ved bukning<br />

af Prestabo-rør<br />

Fig. H–58<br />

150


2 Varmeteknik – Rørsystemer af stål<br />

Eksempler på montering<br />

Varmeanlæg<br />

Fordelerinstallation<br />

med Prestabo<br />

Fig. H–59<br />

Radiatortilslutning<br />

Easytop kuglehaner<br />

Fig. H–60 Fig. H–61<br />

Presværktøjer<br />

Presteknik i vanskeligt<br />

tilgængelige områder.<br />

Fig. H–62 Fig. H–63<br />

151


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Fastgøringsmetoder<br />

Rørledninger kan udlægges med faste punkter eller med glidende fastgørelser.<br />

QQFaste punkter er stift forbundet med komponenten<br />

QQGlidende punkter giver mulighed for aksialudvidelse<br />

Faste punkter skal arrangeres således, at<br />

QQtorsionsspændinger som følge af længdeændringer så vidt muligt udelukkes<br />

QQlige rørledninger uden retningsændring kun har et fast punkt<br />

Glidende fastgøringspunkter skal anbringes med tilstrækkelig afstand til fittings, og<br />

der skal tages hensyn til længdeudvidelse som følge af opvarmning.<br />

Faste punkter og glidende<br />

punkter<br />

Hold afstand til fittings<br />

Tag højde for<br />

udvidelsesretningen<br />

Fig. H–64 Fig. H–65<br />

Fastgøring<br />

med et fast punkt<br />

Fig. H–66<br />

152


2 Varmeteknik – Rørsystemer af stål<br />

Forsænket installation<br />

En rørledning, som ikke er forsænket eller løber i en installationsskakt, har tilstrækkelig<br />

plads til at bevæge sig under udvidelse. Hvis den skal forsænkes eller lægges i støbte<br />

gulve, skal der skaffes plads ved hjælp af blødt isoleringsmateriale – fx skumplast. Det<br />

gælder især omkring T-stykker og bøjninger, fordi der her forekommer særlig kraftige<br />

mekaniske påvirkninger.<br />

Forsænket<br />

rørlægning<br />

Med isolering<br />

Fig. H–67<br />

Udlægning i støbt gulvbelægning<br />

Rørledninger under svømmende gulv lægges ofte i isoleringen, hvor der er tilstrækkelig<br />

plads til udvidelse. Der, hvor rørledningerne føres lodret ud gennem gulvet, skal<br />

der gøres tilstrækkelig plads ved at anvende et egnet isoleringsmateriale.<br />

Udlægning i støbt<br />

gulvkonstruktion<br />

Loftgennemføring<br />

Fig. H–68 Fig. H–69<br />

153


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Udlægning i støbeasfaltbelægning<br />

Etagefordelingsledninger med Prestabo fittings kræver en fagligt korrekt gulvkonstruktion.<br />

I Gulvvarmeanlæg skal Prestabo fittings beskyttes med 20 cm ikke brændbart materiale<br />

på alle sider. Anlægget skal fyldes, før det støbte gulv etableres.<br />

Asfaltgulv<br />

(støbeasfalt)<br />

Fagligt korrekt<br />

gulvkonstruktion<br />

3<br />

2<br />

4<br />

5<br />

1<br />

6<br />

Fig. H–70<br />

1 Råbetondæk<br />

2 Sandfyld bag kantisoleringen<br />

3 Fliser<br />

4 Asfaltgulv (støbeasfalt) med<br />

tildækning<br />

5 Tildækning af pap<br />

6 Udlignings-/isoleringslag<br />

154


2 Varmeteknik – Rørsystemer af stål<br />

Pladsbehov ved presning<br />

Rørstørrelser 12 til 54 mm<br />

Mindste pladsbehov, hvis man skal kunne arbejde hurtigt og bekvemt med etablering<br />

af presforbindelsen, fremgår af tabellerne nedenfor.<br />

Man skal være opmærksom på, at pladsbehovet varierer efter, hvilken presmaskine der<br />

anvendes.<br />

Presning mellem rørledninger<br />

Vulst på presfittingen<br />

Pladsbehov<br />

Presning mod en bygningsdel<br />

Fig. H–71 Fig. H–72<br />

Rør-ød a<br />

[mm]<br />

Tab. H–13<br />

Lysnettilslutning<br />

Pressgun 4 E<br />

PT2<br />

PT3-EH<br />

Akku<br />

Pressgun 4 B<br />

PT3-AH<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

12 20 50<br />

15 20 50<br />

18 20 55<br />

22 25 60<br />

28 25 70<br />

35 30 85<br />

42 45 100<br />

54 50 115<br />

Rør-ød a<br />

[mm]<br />

Tab. H–14<br />

Akku<br />

Picco<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

12 25 60<br />

15 25 60<br />

18 25 60<br />

22 25 65<br />

28 25 65<br />

Presværktøjer<br />

Med forskelligt pladsbehov<br />

155


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Presning mellem rør og væg<br />

Mindste<br />

pladsbehov<br />

Pressgun 4 B / 4 E, PT2, PT3-AH, PT3-EH<br />

Vulst på presfittingen<br />

Picco<br />

Fig. H–73 Fig. H–74<br />

Rør-ø d a<br />

[mm]<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

c<br />

[mm]<br />

12 25 40 65<br />

15 25 40 65<br />

18 25 40 75<br />

22 30 40 80<br />

28 30 50 85<br />

35 50 50 95<br />

42 50 70 115<br />

54 55 80 140<br />

Rør-ø d a<br />

[mm]<br />

a<br />

[mm]<br />

b<br />

[mm]<br />

c<br />

[mm]<br />

12 30 40 70<br />

15 30 40 70<br />

18 30 40 70<br />

22 30 40 75<br />

28 30 40 80<br />

Tab. H–15 Tab. H–16<br />

Presning mellem bygningsdele<br />

Afstand til væg<br />

Hvis en kardan bakke/<br />

tang anvendes kan a min<br />

reduceres<br />

Pladsbehov minimum a min [mm]<br />

DN<br />

Rør-ø d a<br />

[mm]<br />

PT2<br />

PT3-AH<br />

PT3-EH<br />

Pressgun Picco<br />

Picco<br />

Pressgun<br />

4B / 4E<br />

Afstand mellem<br />

presningerne<br />

Kantning undgås<br />

Tætning er sikret<br />

156<br />

Tab. H–17<br />

Tab. H–18<br />

10 – 50 12 – 54 45 50 35 50<br />

DN<br />

Rør-ø d a<br />

[mm]<br />

Mindsteafstand a<br />

[mm]<br />

10 12 0<br />

12 15 0<br />

15 18 0<br />

20 22 0<br />

25 28 0<br />

32 35 10<br />

40 42 15<br />

50 54 25


2 Varmeteknik – Rørsystemer af stål<br />

Rørstørrelser 64,0 – 108,0 – Prestabo XL<br />

Fig. H–75<br />

Rør-ød a<br />

a<br />

b<br />

[mm]<br />

[mm] [mm]<br />

64,0 110 185<br />

Tab. H–19<br />

76,1 110 185<br />

88,9 120 200<br />

108,0 135 215<br />

Fig. H–76<br />

Rør-ød a a b c<br />

[mm] [mm] [mm] [mm]<br />

64,0 110 185 130<br />

Tab. H–20<br />

76,1 110 185 130<br />

88,9 120 200 140<br />

108,0 135 215 155<br />

Pladsbehov ved bygningsdele<br />

Rør-ø d a<br />

[mm]<br />

64,0<br />

76,1<br />

88,9<br />

108,0<br />

Mindsteafstand a [mm]<br />

15<br />

Afstand mellem<br />

presningerne<br />

Kantning undgås<br />

Tætning er sikret<br />

Tab. H–21<br />

Rør-ø d a<br />

[mm]<br />

64,0<br />

76,1<br />

88,9<br />

108,0<br />

Mindsteafstand a [mm]<br />

20<br />

Afstand til væg<br />

Tab. H–22<br />

157


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Presning med presringe 12 - 54 mm<br />

Fig. H–77<br />

Tab. H–23<br />

Rør-ø d a<br />

[mm]<br />

a<br />

[mm]<br />

Fig. H–78<br />

b<br />

[mm]<br />

12<br />

45<br />

40<br />

15 50<br />

18<br />

55<br />

45<br />

22 60<br />

c<br />

[mm]<br />

28 50 70 45<br />

35 55 75 50<br />

42 60 85 55<br />

54 65 90 65<br />

35<br />

40<br />

158


2 Varmeteknik – Rørsystemer af stål<br />

Udførelse af presforbindelse 12 til 54 mm<br />

Prestabo-rør forbindes enkelt og sikkert med presfittings. Beklædte rørs ender skal<br />

først afisoleres med <strong>Viega</strong> afisoleringsværktøj i presfitting-området – resten af monteringen<br />

er ens for begge rørtyper.<br />

QQRørskærer eller fintandet stålsav<br />

QQAfgrater og farvestift til afmærkning af indstiksdybde<br />

QQ<strong>Viega</strong> presmaskine med en bakke, der passer til rørdiameteren<br />

QQAfisoleringsværktøj<br />

Beklædt<br />

Prestabo-rør<br />

1 2<br />

Det beklædte Prestabo-rør afkortes vinkelret<br />

med en fintandet sav.<br />

Rørenden afisoleres med afisoleringsværktøj.<br />

Fig. H–79<br />

Fig. H–80<br />

3 Fig. H–81<br />

Røret afgrates indvendig og udvendigt.<br />

Fortsæt som for Prestabo-rør, blankt<br />

(se næste side)<br />

Der skal anvendes rørskærer eller fintandet stålsav. Der må ikke anvendes olie eller<br />

fedt!<br />

159


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Prestabo-rør, blankt<br />

Fig. H–82<br />

Fig. H–83<br />

1 2<br />

Det blanke Prestabo-rør afkortes vinkelret.<br />

Røret afgrates indvendigt og udvendigt.<br />

Fig. H–84<br />

Fig. H–85<br />

3 4<br />

Det kontrolleres, at tætningselementet<br />

er placeret korrekt.<br />

Presfittingen skubbes ind over røret, til<br />

den støder imod.<br />

Fig. H–86<br />

Fig. H–87<br />

5 6<br />

Marker indstiksdybden.<br />

Sæt presbakken på presværktøjet. Skub<br />

holdebolten ind, til den går i indgreb.<br />

160


2 Varmeteknik – Rørsystemer af stål<br />

Prestabo-rør, blankt<br />

7 8<br />

Presbakken åbnes og sættes vinkelret på<br />

fittingen.<br />

Indstiksdybden kontrolleres og presningen<br />

påbegyndes.<br />

Fig. H–88<br />

Fig. H–89<br />

9<br />

Efter afsluttet presning åbnes presbakken.<br />

Fig. H–90<br />

161


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Etablering af presforbindelse 64,0 til 108,0 mm<br />

Nødvendigt værktøj<br />

Prestabo-rør forbindes enkelt og sikkert med presfittings.<br />

QQRørskærer eller fintandet stålsav<br />

QQAfgrater og farvestift til afmærkning af indstiksdybden<br />

QQ<strong>Viega</strong> presmaskine med en presbakke, som passer til rørstørrelsen, og en passende<br />

presring<br />

Blank Prestabo-rør<br />

Fig. H–91<br />

Fig. H–92<br />

1 2<br />

Røret afkortes vinkelret med rørskærer<br />

eller fintandet sav. Anvend ikke olie eller<br />

fedt.<br />

Pas på ved opspændingen! Rørenderne<br />

skal være helt runde.<br />

Fig. H–93<br />

Fig. H–94 3 4<br />

Røret afgrates indvendigt og udvendigt.<br />

Marker indstiksdybden.<br />

ø 64,0 mm = 43 mm<br />

ø 76,1 mm = 55 mm<br />

ø 88,9 mm = 55 mm<br />

ø 108,0 mm = 65 mm<br />

162


2 Varmeteknik – Rørsystemer af stål<br />

Prestabo-rør, blankt<br />

5 6<br />

Kontroller, at tætningselementet og skæreringen<br />

sidder korrekt.<br />

Skub presfittingen til den markerede<br />

indstiksdybde på røret.<br />

Fig. H–95<br />

Fig. H–96<br />

7 8<br />

Sæt presringen på fittingen, og kontroller,<br />

at placeringen er korrekt.<br />

Prestangen åbnes og sættes ind i presringens<br />

holdere.<br />

Fig. H–97<br />

Fig. H–98<br />

9 10<br />

Start presmaskinen, og udfør presningen.<br />

Fjern kontrolmærkatet. Det viser, at<br />

forbindelsen nu er „sammenpresset“.<br />

Fig. H–99<br />

Fig. H–100<br />

163


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Tryktest – i Danmark iflg. DS 469 – hér et eksempel jvf. tyske regler:<br />

Kriterier<br />

QQVandtryktest er iflg. VOB tillægsydelser, som hører med til entrepenørens kontraktmæssige<br />

ydelse. Anlægget testes med et tryk, der svarer til sikkerhedsventilens aktiveringstryk.<br />

QQVed tæthedstest med oliefri trykluft eller inerte gasser skal der udarbejdes detaljerede<br />

beskrivelser af ydelsen, hvorefter der indgås aftale herom.<br />

QQAlle rørledninger skal gennemgå en tryktest i færdig, men endnu ikke tildækket<br />

stand.<br />

QQTryktesten af varmeanlæg kan også udføres med trykluft eller inerte gasser.<br />

QQDer skal føres protokol over tryktest.<br />

164


3 Gasinstallation* – Grundlag<br />

3 Gasinstallation*<br />

Grundlag<br />

Nationalt forord<br />

Gasdrevne<br />

husholdningsapparater<br />

Gaskomfur<br />

Varme<br />

Terrassevarmer<br />

Gasinstallationer bliver ofte lavet med <strong>metal</strong> rør. De gældende landespecifikke installationsmetoder<br />

skal altid følges. De følgende informationer baserer sig på anerkendte<br />

metoder og teknikker som anvendes i Tyskland og skal opfattes som anbefalinger. De<br />

kan anvendes i det omfang egne nationale regler/forskrifter ikke taler imod.<br />

Der arbejdes løbende på at udvide godkendelserne på dimensioner, tryk og div. gas<br />

komponenter.<br />

I det følgende er hentet eksempler baseret på tysk lovgivning. Vi håber det kan give<br />

inspiration til yderligere godkendelser og anvendelser i Danmark.<br />

Det skal altid sikres at evt. anvendelser er tilladt i henhold til det danske gasreglement<br />

som altid skal overholdes: www.sik.dk<br />

På boligopvarmningsområdet anvendes der i Tyskland i dag over 40 % naturgas som<br />

energibærer. 75 % af nybyggeriet bliver allerede udstyret med naturgasvarmeanlæg.<br />

Foruden naturgasopvarmning med central drikkevandsopvarmning er naturgas til<br />

madlavning og tørring af vasketøj ikke nogen nyhed. Det gælder imidlertid om, at kunderne<br />

bliver klar over, hvor alsidig naturgas og naturgasdrevne husholdningsapparater<br />

er. Nye, videreudviklede gasdrevne produkter som tørretumblere, kaminer, infrarøde<br />

lamper eller terrassegriller udvider konstant paletten af anvendelsesmuligheder i husholdningen.<br />

Opvaskemaskine<br />

Grill<br />

Sauna<br />

Kamin<br />

Tørretumbler<br />

Fig. G–1<br />

165


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

<strong>Viega</strong>s systemfilosofi<br />

Krav til en‚ innovativ gasledningsinstallation‘ på husholdningsområdet<br />

QQTeknisk perfekt og økonomisk installation<br />

QQKorte montagetider<br />

QQBrandsikre gasledninger, som også kan udlægges i et utilgængeligt område<br />

QQIngen ekstra sikkerhedsanordninger<br />

QQRørtilslutninger iht. HTB-krav<br />

QQPresfittings skal kunne tilsluttes alle rørtyper, som er godkendt til gasinstallation<br />

Et hus, hvor alt<br />

er naturgasdrevet<br />

Fig. G–2<br />

1 Stikledning med HAE<br />

(hovedafbryder)<br />

2 Gasmåler med tilslutningsplade<br />

3 Etagefordeler<br />

4 Gasvarmeenhed<br />

5 Gastørretumbler<br />

6 Gaskomfur<br />

7 Forsænket gasstikdåse<br />

8 Gasovn/kamin<br />

9 Udendørs gasstikdåse med gasgrill<br />

166


3 Gasinstallation* – Grundlag<br />

Krav til gasstikdåser<br />

Her skal der tages hensyn til nationale regelsæt, som begrænser eller forbyder denne<br />

form for apparattilslutning.<br />

Brugen af flytbare gasprodukter – fx gaskomfurer, tørretumblere, terrassevarmere og<br />

terrassegriller – kræver, at der installeres gasstikdåser.<br />

Det forventes af gasstikdåser, at<br />

QQdet er muligt at tilslutte apparater via en fleksibel gasledning med stik, således at<br />

brugeren uden risiko kan sætte stikket i og tage det ud igen, så tit det skal være,<br />

QQsikkerhedsstandarderne overholdes og<br />

QQde er udformet, så de ligner elektriske stikdåser.<br />

Konstruktive løsninger skal garantere, at sikkerhedsstandarderne overholdes. Mulige<br />

risici og sikkerhedsanordninger<br />

QQUdtrængende gas, hvis slangen rives ud eller beskadiges<br />

– Overvågning af gasstrømmen<br />

QQUautoriseret manipulation af stikket<br />

– Sikring med lukkeanordninger i flere trin, eller som kan aflåses<br />

QQUdtrængende gas i tilfælde af brand<br />

– Sikring med termiske spærreanordninger<br />

QQUkorrekt tilslutning af apparater<br />

– Sikkerhedshanstik på apparatet<br />

<strong>Viega</strong> stikdåser til montering med eller uden forsænkning samt tilhørende fleksible<br />

gastilslutningsledninger opfylder alle disse krav.<br />

Design-gasstikdåse<br />

til forsænket<br />

montering<br />

Fig. G–3 Fig. G–4<br />

167


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Systembeskrivelse<br />

Profipress G / Profipress G XL<br />

Anvendelse<br />

Rørledningssystemerne Profipress G og Profipress G XL med presfittings er velegnede<br />

til gasser iht. DVGW-AB G 260 til husholdningsbrug. For installationen gælder<br />

forskrifterne i DVGW-dokument G 600, TRGI 2008 og TRF 1996. Der må kun<br />

anvendes kobberrør iht. DS/EN1057 1) i forbindelse med DVGW-AB-GW 392.<br />

Der eksisterer godkendelser til<br />

QQGasser iht. DVGW-dokument G 260<br />

QQGas og flaskegas i Gasfase2 til husholdningsbrug<br />

Tryk maks.<br />

5 bar<br />

Trýk maks. ved HTB-krav<br />

1 bar<br />

Drifts- og omgivelsestemperatur maks 70 ºC<br />

Vedrørende brug af Profipress G / XL til andre anvendelser end de ovenfor<br />

beskrevne skal afstemmes med vores fabrik i Attendorn.<br />

1)<br />

Mindste godstykkelse se venligst Tab. H-1.<br />

2)<br />

Til flaskegasinstallationer i områder, hvor kravene for højere termisk belastning (HTB) er gældende,<br />

med et aktiveringstryk for trykreguleringsanordninger > 1 bar, skal der anvendes Sanpress Inox G<br />

(Sikkerhedsafspærringsventil).<br />

Profipress G<br />

Presfittings af kobber<br />

Specialfittings, flanger<br />

og armaturer af rødgods<br />

eller messing<br />

Fig. G–5<br />

168


3 Gasinstallation* – Systembeskrivelse<br />

Tekniske data<br />

Kobberrør iht. DS/EN 1057<br />

Af kobber / rødgods<br />

Løbende egenkontroller og kontrol ved materialetestinstituttet NRW<br />

Med en gul prik på begge sider af presfittingen<br />

Gult HNBR-tætningselement<br />

<strong>Viega</strong> presmaskiner (se kapitlet Værktøj)<br />

Profipress G 12 – 54 mm med presbakker<br />

Profipress G XL 64,0 mm med presring<br />

Profipress G DG-4550 AU 0070<br />

Profipress G XL DG-8531 BR 0258<br />

Kobberrør til anvendelse i gasinstallationer<br />

Udvendig Ø x godstykkelse<br />

d a x s<br />

Stænger<br />

Ringe<br />

[mm]<br />

hård halvhård blød<br />

12 x 0,8<br />

15 x 1,0<br />

18 x 1,0<br />

22 x 1,0<br />

28 x 1,0<br />

35 x 1,2<br />

42 x 1,2<br />

54 x 1,5<br />

64 x 2,0<br />

Tab. G–1<br />

Profipress G<br />

XL<br />

Rør<br />

Presfittings<br />

Kvalitetskontrol<br />

Mærkning<br />

Tætningselement<br />

Presværktøjer<br />

DVGW godkendelsesnummer<br />

Kobberrør<br />

Iht. DS/EN 1057<br />

Profipress G XL<br />

Presfittings og flanger<br />

Fig. G–6<br />

169


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Mærkning af presfittings<br />

Profipress G og Profipress G XL-Pressfitting er mærket<br />

QQGas<br />

til gasledninger<br />

QQPN 5 til driftstryk på 5 bar<br />

QQGT 1 til højere termisk belastning (HTB ved et driftstryk på 1 bar)<br />

Q Q til godkendelse i Holland<br />

Profipress G /<br />

XL-presfittings<br />

Som presfittings eller<br />

med gevindtilslutning<br />

Den gule prik er mærket<br />

for SC-Contur – den<br />

gule firkant for mediet<br />

Fig. G–7<br />

Fordele ved systemsamlingen<br />

QQSC-Contur<br />

QQPresfittings til mange forskellige former for tilslutning<br />

QQPresværktøj til batteridrift eller lysnettilslutning<br />

HTB (højere termisk belastning)-krav<br />

Krav til komponenter i<br />

gasinstallationer<br />

Kriteriet for højere termisk belastningsevne (HTB) er baseret på antændelsestemperaturen<br />

for naturgas i luft (ca. 640 °C).<br />

For at forhindre, at der dannes en eksplosiv blanding på grund af uforbrændt udtrængende<br />

gas, må der i tilfælde af brand ikke på noget sted trænge så meget gas ud med<br />

en lavere temperatur, at det udgør en risiko. På baggrund heraf er der opstillet et krav om<br />

en temperatur på 650 °C i 30 min., som er anerkendt teknisk praksis.<br />

170


3 Gasinstallation* – Systembeskrivelse<br />

Gasanlæg<br />

Profipress G og Profipress G XL presfittings kan anvendes i de nedenfor beskrevne gasanlæg.<br />

Gasanlæg iht. DVGW TRGI 2008<br />

QQLavtryk < 100 mbar, middeltryk ≥ 100 mbar til 1 bar<br />

QQIndustri-, håndværks- og procesanlæg iht. de relevante DVGW-bestemmelser og<br />

tekniske regler – eks.: DWGW-AB G 614, „Frit udlagte gasledninger på fabriksområdet<br />

bag leveringsstedet“<br />

Fig. G–8<br />

Anlæg til flydende gas iht. TRF 1996<br />

Til installationer med flydende gas i områder, hvor kravene for højere termisk belastning<br />

(HTB) er gældende, med et aktiveringstryk for sikkerhedsventilen > 1 bar skal der anvendes<br />

Sanpress Inox G.<br />

QQMed gasbeholdere i middeltryksområdet<br />

– efter trykreguleringsanordning, 1. trin på gasbeholderen, op til et tilladt driftstryk<br />

for PZ = 5 bar<br />

QQMed gasbeholder i lavtryksområdet<br />

– efter trykreguleringsanordning 2. trin<br />

QQMed trykbeholdere (gasflasker) < 14 kg<br />

– efter trykreguleringsanordning til små flasker<br />

QQMed trykbeholdere (gasflasflasker) ≥ 14 kg<br />

– efter trykreguleringsanordning til store flasker<br />

171


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Sanpress Inox G / Sanpress Inox G XL<br />

Anvendelse<br />

Rørledningssystemerne Sanpress Inox G og Sanpress Inox G XL med presfittings<br />

er godkendt til gasser iht. DVWG-dokument G 260. Installationen skal udføres i<br />

overensstemmelse med DVWG-Arbeitsblatt G 600, TRGI 2008 og TRF 1996.<br />

Der må udelukkende anvendes Sanpress rustfri stålrør iht. DS/EN 10088 og DVGW-<br />

Arbeitsblatt GW 541 - materiale 1.4401.<br />

Godkendelser<br />

QQGasser iht. DVGW-Arbeitsblatt G 260<br />

QQFlydende gas i gasfasen til husholdnings- og håndsværkmæssig brug<br />

Drifts- og omgivelsestemperatur maks. 70 ˚C<br />

Sanpress Inox G – PN 5 / GT 5<br />

QQTryk maks.<br />

5 bar<br />

QQTrýk maks. ved HTB-krav<br />

5 bar<br />

Sanpress Inox G XL – PN 5 / GT 5<br />

QQTryk maks.<br />

5 bar<br />

QQTrýk maks. ved HTB-krav<br />

5 bar<br />

Vedrørende brug af Sanpress Inox G / XL til andre anvendelser end de ovenfor<br />

beskrevne skal afstemmes med vores fabrik i Attendorn.<br />

Sanpress Inox G-fittings<br />

Over 170 artikler giver<br />

næsten ubegrænsede<br />

installations- og tilslutningsmuligheder<br />

Fig. G–9<br />

172


3 Gasinstallation* – Systembeskrivelse<br />

Tekniske data<br />

Sanpress og Sanpress XL rør er tyndvæggede lasersvejste rustfaste stålrør i materiale<br />

(Werkstoff-Nr) 1.4401 (X5 CrNiMo 17-12-2) med 2,3 % Mo for en optimal korrosionsbestandighed.<br />

Alle størrelser af rustfrit stål 1.4401<br />

Løbende egenkontroller og kontrol ved materialetestinstituttet NRW<br />

Gul firkant og gul prik på presmuffen<br />

Gult HNBR-tætningselement<br />

<strong>Viega</strong> presmaskiner (se kapitlet Værktøj)<br />

Sanpress Inox G 15til 54 mm<br />

med presbakker<br />

Sanpress Inox XL 64,0 til 108,0 mm med presring<br />

Sanpress Inox G DG-8531 B0 0393<br />

Sanpress Inox G XL DG-8531 BR 0333<br />

Rør<br />

Presfittings<br />

Kvalitetskontrol<br />

Mærkning<br />

Tætningselement<br />

Presværktøjer<br />

DVGW godkendelsesnummer<br />

Godkendte rustfri stålrør<br />

d a x s<br />

[mm]<br />

Volumen pr. løb.<br />

meter rør<br />

[liter/m]<br />

Vægt pr. løbende<br />

meter rør<br />

[kg / m]<br />

15 x 1,0 0,13 0,35<br />

18 x 1,0 0,20 0,43<br />

22 x 1,2 0,30 0,65<br />

28 x 1,2 0,51 0,84<br />

35 x 1,5 0,80 1,26<br />

42 x 1,5 1,19 1,52<br />

54 x 1,5 2,04 1,97<br />

64,0 x 2,0 2,83 3,04<br />

76,1 x 2,0 4,08 3,70<br />

88,9 x 2,0 5,66 4,34<br />

108,0 x 2,0 8,49 5,30<br />

Tab. G–2<br />

Materiale,<br />

presfittings<br />

Rustfrit stål<br />

Sanpress Inox G<br />

Presfittings og flanger<br />

Fig. G–10<br />

173


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Mærkning af presfittings<br />

Sanpress Inox G / XL pressfittings er mærket med<br />

QQGas<br />

til gasledninger,<br />

QQPN 5 til driftstryk på 5 bar,<br />

QQGT/5 (1) til højere termisk belastning (HTB ved et driftstryk på 5 bar)<br />

SC-Contur<br />

Ikke pressede tilslutninger<br />

findes ved tryk- og<br />

tæthedstest<br />

Markeret indstiksdybde<br />

Op til 108,0 mm med<br />

mærkning til gas<br />

Sanpress Inox G<br />

XL-presfittings<br />

Fig. G–11<br />

Cylindrisk<br />

rørføring<br />

Markeret indstiksdybde<br />

Dobbelt<br />

presning<br />

Fig. G–12<br />

Pressfittings med SC-Contur<br />

Også Sanpress Inox G-systemet er udstyret med SC-Contur, hvilket ses af den gule prik<br />

på alle vulster. Ikke pressede forbindelser detekteres under tryk- og tæthedstesten ved,<br />

at manometret viser et trykfald.<br />

Anlæg til flydende gas TRF 1996<br />

Se kapitlet Profipress G<br />

174


3 Gasinstallation* – Systembeskrivelse<br />

Montering<br />

Generelle regler for montering af gasledninger<br />

Følgende betingelser gælder for udlægning af gasledninger<br />

QQGasledninger må lægges frit (1), under puds uden hulrum (2) eller i skakter hhv.<br />

kanaler (3).<br />

QQLedninger med driftstryk > 100 mbar må ikke forsænkes.<br />

QQDe skal lægges således, at de ikke udsættes for fugt eller dryp- og kondensvand fra<br />

andre ledninger eller bygningsdele.<br />

QQAfspærringsanordninger og løsbare tilslutninger skal være placeret, så de er tilgængelige.<br />

QQDe må ikke placeres i støbte gulve (se næste side).<br />

Rørføring<br />

Iht.<br />

DVGWTRGI 2008<br />

<br />

<br />

<br />

Fig. G–13<br />

Eksempler på udlægning<br />

Fritlagt<br />

Under puds uden hulrum<br />

I ventilerede kanaler<br />

Forsænkede installationer<br />

QQSkal være spændingsfri.<br />

QQSkal korrosionsbeskyttes.<br />

QQLøsbare tilslutninger (forskruninger) er ikke tilladt.<br />

QQKobberrør må ikke komme i kontakt med nitrit- eller amminiakholdige stoffer, og<br />

rustfri stålrør må ikke komme i kontakt med kloridholdige stoffer.<br />

175


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Rørføring og fastgøring<br />

Gasledninger må ikke fastgøres til andre ledninger eller benyttes som holdere for<br />

andre ledninger. Gasledninger må fastgøres til bygningsdele med tilstrækkelig styrke<br />

ved hjælp af ikke brændbare rørholdere (for eksempel rørbøjler af <strong>metal</strong>) og almindelige<br />

plugs (af kunststof), hvis rørtilslutningen har en tilsvarende mekanisk aksial stabilitet<br />

se DVGW-TRGI 2008 5.3.7 Tab. 8. Profipress G / XL og Sanpress Inox G / XL-tilslutninger<br />

er ikke løsbare, træk- og tryk rørtilslutninger.<br />

Profipress G og Sanpress<br />

Inox G<br />

prestilslutninger<br />

Fig. G–14<br />

Anbefalede værdier<br />

for horisontalt<br />

udlagte rørledninger<br />

Fastgøringsafstande<br />

Udvendig Ø x godstykkelse<br />

d a x s<br />

[mm]<br />

Fastgøringsafstand<br />

[m]<br />

Profipress G<br />

Sanpress Inox G<br />

12 x 1,0<br />

–<br />

1,25<br />

15 x 1,0 15 x 1,0 1,25<br />

18 x 1,0 18 x 1,0 1,50<br />

22 x 1,0 22 x 1,2 2,00<br />

28 x 1,5 28 x 1,2 2,25<br />

35 x 1,5 35 x 1,5 2,75<br />

42 x 1,5 42 x 1,5 3,00<br />

54 x 2,0 54 x 1,5 3,50<br />

64,0 x 2,0 XL 64,0 x 2,0<br />

4,00<br />

– 76,1 x 2,0 4,25<br />

XL<br />

– 88,9 x 2,0 4,75<br />

– 108,0 x 2,0 5,00<br />

Tab. G–3<br />

Standard<br />

Standard<br />

176


3 Gasinstallation* – Systembeskrivelse<br />

Udlægning i gulvkonstruktionen<br />

Gasledninger må ikke udlægges i støbte gulve – heller ikke delvis.<br />

Tilladte udlægningstyper<br />

på rådæk i et udligningslag eller i skridtlydisolering<br />

delvis i en udsparing i rådækket og delvis i et udligningslag eller en skridtlydisolering<br />

eller<br />

fuldstændig i en udsparing i rådækket.<br />

Gasledninger, som udlægges under støbte gulve, skal beskyttes mod korrosionsskader.<br />

DVGW-TRGI 2008, Pt. 3.3.8.5: Krav til jordlagte rørsystemer<br />

1<br />

Gasledninger i<br />

gulvkonstruktionen<br />

2<br />

3<br />

4<br />

5<br />

Fig. G–15<br />

Gulvbelægning<br />

Støbt gulv<br />

Skridtlydisolering / udligningslag<br />

Spærrefolie<br />

Rådæk<br />

Korrosionsbeskyttelse<br />

Frit udlagte ledninger i rum behøver normalt ingen udvendig korrosionsbeskyttelse.<br />

Undtagelser<br />

QQI rum med aggressive byggematerialer; fx kobberrør i bygningsdele med nitrit- eller<br />

ammoniakholdige materialer eller rustfri stålrør i kloridholdige omgivelser<br />

QQI aggressiv atmosfære<br />

QQHvis de er udlagt i udsparinger i rådækket, udligningslaget eller skridtlydisoleringen,<br />

skal de behandles som jordudlagte udendørs ledninger i overensstemmelse<br />

med DVGW-TRGI 2008, Pt. 3.3.8.5<br />

177


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Krav iht. DVGW-TRGI 2008<br />

Til efterfølgende korrosionsbeskyttelse skal der anvendes korrosions beskyttende<br />

bevikling eller påkrympningsslanger.<br />

QQtil rør af kobber eller rustfrit stål ved belastningsklasse A (ikke ætsende jord) eller B<br />

(ætsende jord)<br />

QQtil armaturer, rørtilslutninger og formstykker ved belastningsklasse A og B, krympematerialer<br />

også klasse C<br />

178


4 Anvendelser inden for industri og håndværk – Systembeskrivelse<br />

4 Anvendelser inden for<br />

industri og håndværk<br />

Systembeskrivelse<br />

Anvendelse<br />

Presfittingssystemerne Profipress / Profipress G samt Sanpress Inox og Sanpress<br />

Inox G er velegnede til anvendelse inden for industrien til transport af specialmedier.<br />

Valg af system afhænger af de aktuelle driftsbetingelser såsom tryk, temperatur<br />

og de transporterede mediers koncentration. Rørsystemerne kan anvendes til<br />

gængse specialmedier efter tabellerne I–10 til I–15. Hvorvidt Prestabo-systemet<br />

og andre systemer egner sig til andre medier, kan afklares ved med en materialeforespørgsel<br />

(Tjekliste s. 197) til fabrikken i Attendorn.<br />

Profipress / Sanpress Inox / Profipress G / Sanpress Inox G / Prestabo<br />

Systemerne Profipress / Profipress G samt Sanpress Inox og Sanpress Inox G anvendes<br />

foruden til drikkevands- gas og varmeinstallationer i stigende omfang i industrien til<br />

transport af specialmedier.<br />

De forskellige driftstilstande i medierne, for eksempel tryk, temperatur og koncentration,<br />

kræver, at system og tætningsmateriale vælges med omhu. Specialmedier med<br />

angivne driftsbetingelser som for eksempel tekniske gasser, forskellige typer olie, smøremidler<br />

osv. kan testes på grundlag af egne laboratorieundersøgelser hos <strong>Viega</strong> eller<br />

i særlige tilfælde også af andre institutter.<br />

Ud fra disse informationer udarbejdes der anbefalinger vedrørende anvendelsen, som<br />

garanterer, at udførelse og anlæg er sikre for montører og bygherrer.<br />

Presfittingssystemerne af kobber og rustfrit stål foretrækkes i følgende anlæg<br />

QQTrykluft<br />

QQKølevand<br />

QQTekniske gasser<br />

QQIndustrivand<br />

QQRenset procesvand<br />

QQOlieholdige medier<br />

Anvendelsesområder<br />

179


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Profipress / Profipress G<br />

Presfittings sortiment<br />

Fig. I–1<br />

Godkendt til<br />

QQGas og flydende gas<br />

QQFyringsolie og dieselolie<br />

QQVåde sprinkleranlæg<br />

QQIltledninger<br />

QQLABS-fri fittings (fri for stoffer, der forringer malingens befugtningsevne)<br />

Presfittings med SC-Contur<br />

SC-Contur er farvemærket på hver fitting<br />

QQGult<br />

for Profipress G-fitting og<br />

QQGrønt<br />

for Profipress-fitting,<br />

QQHvid<br />

Profipress med FKM tætningsring.<br />

Presfittings<br />

SC-Contur er markeret<br />

med farvede prikker<br />

Installation<br />

Med Profipress og Profipress<br />

XL<br />

Fig. I–2 Fig. I–3<br />

180


4 Anvendelser inden for industri og håndværk – Systembeskrivelse<br />

Tekniske data<br />

Må udelukkende anvendes med kobberrør iht. DS/EN 1057. Mindste godstykkelse se<br />

venligst Tab. H-1<br />

Presfittings med gevindtilslutning<br />

12 – 54 mm rødgods<br />

64,0 – 108,0 mm kobber<br />

Sort; EPDM (ethylen-propylen-dien-monomer gummi); op til 110 °C; ikke modstandsdygtigt<br />

over for kulbrinte-opløsningsmidler, klorerede kulbrintestoffer, terpentin og benzin<br />

Stænger og ruller (se tabel)<br />

Profipress med SC-Contur DVGW reg.nr. DW 8511 AP 3139<br />

Profipress XL DVGW reg.nr. DW 8511 AT 2347<br />

Kobberrør iht. DS/EN 1057 og DVGW-dokument GW 392<br />

12 / 15 / 18 / 22 / 28 /35 / 42 / 54<br />

64,0 / 76,1 / 88,9 / 108,0.<br />

Rørmateriale<br />

Presfittingmateriale<br />

Tætningselement<br />

Tilstand ved levering<br />

Godkendelser<br />

System<br />

Standardmål [mm]<br />

Profipress XL<br />

Kobberrør til drikkevandsinstallationer<br />

Udvendig‐Ø x<br />

Program<br />

godstykkelse<br />

Stænger<br />

Ringe<br />

d a x s<br />

[mm]<br />

hård halvhård blød<br />

Størrelser<br />

Materiale,<br />

presfittings<br />

Rørstørrelser,<br />

former<br />

12 x 0,8<br />

15 x 1,0<br />

18 x 1,0<br />

22 x 1,0<br />

28 x 1,0 –<br />

Standard<br />

35 x 1,2 – –<br />

42 x 1,2 – –<br />

Kobber<br />

54 x 1,5 – –<br />

64,0 x 2,0 – –<br />

76,1 x 2,0 – –<br />

88,9 x 2,0 – –<br />

XL<br />

108,0 x 2,5 – –<br />

Tab. I–1<br />

181


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Sanpress Inox / Sanpress Inox XL<br />

Rørmateriale<br />

Ref.-standard EN 10312<br />

Presfittingmateriale<br />

Tætningselement<br />

Tilstand ved levering<br />

Godkendelser<br />

System<br />

Rør<br />

Standardmål [mm]<br />

Sanpress Inox<br />

Sanpress Inox XL<br />

Tekniske data<br />

Sanpress- og Sanpress XL-rør er lasersvejsede ledningsrør af korrosionsfast stål.<br />

Materialenr. 1.4401 (X5 CrNiMo 17-12-2), med 2,3 % Mo for længere holdbarhed. Alternativ:<br />

Materialenr. 1.4521 (X2 CrMoTi 18-2), med en PRE-værdi på 24,1<br />

Rustfrit stål<br />

Sort; EPDM (ethylen-propylen-dien-monomer gummi); op til 110 °C; ikke modstandsdygtigt<br />

over for kulbrinte-opløsningsmidler, klorerede kulbrintestoffer, terpentin og<br />

benzin<br />

QQStænger, 6 m lange, med blank ydre og indre overflade<br />

QQRørender lukket med kunststofpropper<br />

QQAlle rør er tæthedstestet og kontrolmærket<br />

QQDW 8501 BL 0551 (15 til 54 mm)<br />

QQDW 8511 BQ 0245 (64 til 108 mm)<br />

QQEN 10088: Oversigt over rustfaste stål<br />

QQIht. DVGW-dokument W 541: Rør af ikke rustende ståltyper til drikkevandsinstallationer<br />

DVGW kontrolmærke TS 233 (N 012)<br />

15 / 18 / 22 / 28 / 35 /42 / 54<br />

64,0 / 76,1 / 88,9 / 108,0<br />

Sanpress Inox<br />

Presfittings<br />

15 – 54 mm<br />

af rustfrit stål<br />

XL-størrelser<br />

64 – 108 mm<br />

af rustfrit stål, med skærering,<br />

skillering<br />

og EPDM-tætningselement<br />

Alle størrelser<br />

med SC-Contur<br />

Fig. I–4 Fig. I–5<br />

182


4 Anvendelser inden for industri og håndværk – Systembeskrivelse<br />

Sanpress Inox-rør<br />

d x s<br />

[mm]<br />

Volumen<br />

pr. løbende<br />

meter rør<br />

[liter/m]<br />

Vægt<br />

pr. løbende<br />

meter rør<br />

[kg / m]<br />

Vægt<br />

pr. 6 m stang<br />

[kg]<br />

Størrelse<br />

Materiale,<br />

presfittings<br />

15 x 1,0 0,13 0,35 2,10<br />

18 x 1,0 0,20 0,43 2,55<br />

22 x 1,2 0,30 0,65 3,89<br />

28 x 1,2 0,51 0,84 5,02<br />

35 x 1,5 0,80 1,26 7,55<br />

42 x 1,5 1,19 1,52 9,13<br />

54 x 1,5 2,04 1,97 11,83<br />

Sanpress Inox XL-rør<br />

64,0 x 2,0 2,83 3,04 18,24<br />

76,1 x 2,0 4,08 3,70 22,20<br />

88,9 x 2,0 5,66 4,34 26,00<br />

108,0 x 2,0 8,49 5,30 31,80<br />

Tab. I–2<br />

Standard<br />

XL<br />

Rustfrit stål<br />

Rustfrit stål<br />

183


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Prestabo<br />

Anvendelse<br />

Prestabo-systemet er beregnet til industri- og varmeanlæg og må ikke anvendes<br />

til drikkevandsanlæg. Rør og fittings er derfor mærket med et rødt symbol „Nicht<br />

für Trinkwasserinstallationen“ (Uegnet til drikkevandsinstallationer).<br />

Sendzimir-galvaniserede Prestabo-rør kan også anvendes til våde sprinkleranlæg<br />

og trykluftanlæg.<br />

Prestabo presfittings<br />

Med tydelig rød mærkning:<br />

„Nicht für TW-<br />

Installationen geeignet”<br />

(Uegnet til drikkevandsinstallationer)<br />

Fig. I–6 Fig. I–7<br />

Egenskaber for sendzimir-galvaniserede rør til sprinkleranlæg<br />

QQRød linje, hvid skrift<br />

QQSymbol ”Nicht für Trinkwasserinstallationen” (Uegnet til drikkevandsinstallationer)<br />

QQSymbol ”Sprinkler”<br />

QQRørender med hvide hætter<br />

QQStørrelser 15-108 mm<br />

QQFra størrelse 22 mm og opefter, VdS-certificering for rør og presfittings<br />

QQ20 µm zinklag, indvendigt og udvendigt<br />

184


4 Anvendelser inden for industri og håndværk – Anvendelsesteknik<br />

Anvendelsesteknik<br />

SC-Contur – DVGW-kontrolleret sikkerhed<br />

Ved påfyldning af anlægget synliggør SC-Contur presfittings, som ved en fejl ikke er<br />

presset. Upressede presfittings detekteres med sikkerhed i trykområdet 1 – 6,5 bar ved<br />

vandudsivning eller ved trykfald på testmanometeret og kan straks presses.<br />

SC-Contur<br />

Fittings, som ikke er<br />

presset, bliver synlige,<br />

når anlægget fyldes<br />

Dobbelt presning<br />

Cylindrisk rørføring<br />

Markeret indstiksdybde<br />

Fig. I–8<br />

<strong>Viega</strong> test<br />

Testkriterier<br />

Krav iht.<br />

DVGW-W 534<br />

<strong>Viega</strong> testværdier<br />

Trykfasthed Min. 25 bar Mellem 50 og 200 bar<br />

Trykstød<br />

Temperaturændring<br />

Tætningselementer<br />

Undertryk<br />

Tab. I–3<br />

Skiftende hver 10,000 gange, mellem<br />

1 og 15 bar overtryk ved rumtemperatur<br />

og 95 °C<br />

Skiftende hver 10,000 gange, hver 15<br />

minutter ved 20 °C og 95 °C ved et<br />

tryk på 10 bar og en rørforspænding<br />

på 2 N / mm 2<br />

– 0,8 bar<br />

Specialtest<br />

Skiftende hver 100,000 gange, mellem<br />

1 og 15 bar overtryk ved rumtemperatur<br />

og 95 °C<br />

Skiftende hver 100,000 gange, hver<br />

15 minutter ved 20 °C og 95 °C ved<br />

et tryk på 10 bar og en rørforspænding<br />

på 2 N / mm 2<br />

For Sapress<br />

Sanpress Inox<br />

Profipress<br />

Testbelastningen af<br />

komponenterne<br />

ligger langt over de krævede<br />

værdier.<br />

185


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Tekniske data<br />

Tætningselementer<br />

Tætningselementer<br />

Forkortelse EPDM HNBR FKM<br />

Materiale<br />

Etylen-propylen-dienmonomer<br />

gummi<br />

Acrylnitril-butadienmonomer<br />

gummi<br />

Fluorelastomer<br />

Farve Sort, glinsende Gul sort, mat<br />

Temperatur<br />

[°C maks.]<br />

Tryk<br />

[bar]<br />

110 70 140<br />

16 PN5 / GT 1 16<br />

KTW Ja Nej Nej<br />

HTB Nej Ja Nej<br />

Anvendelsesområder<br />

Drikkevand Varme<br />

Solvarme<br />

(plane solfangere)<br />

Gasser iht. GW 260<br />

Fyringsolie<br />

Dieselolie iht.<br />

DS/EN 590<br />

Solvarme<br />

(rør-solfangere)<br />

Fjernvarme<br />

(efter forespørgsel)<br />

Tab. I–4<br />

Processkema<br />

Materialeforespørgsel<br />

Kunde <strong>Viega</strong> Eksternt<br />

Materiale<br />

forespørgsel<br />

1<br />

Modtagelse af<br />

materialeforespørgsel<br />

i servicecentret<br />

2<br />

Udfyld spørgeskema,<br />

fremskaf sikkerhedsdatablade<br />

Fremskaffelse af<br />

information<br />

Producent / bruger<br />

3<br />

Bearbejdning af data<br />

4<br />

Laboratorieforsøg<br />

Laboratorium Producent<br />

5<br />

Tilbagemelding til<br />

servicecenter<br />

6<br />

Installationens<br />

udførelse<br />

Resultat:<br />

Info til kunden<br />

Tab. I–5<br />

186


4 Anvendelser inden for industri og håndværk – Anvendelsesområder<br />

Flangetilslutninger<br />

I pressystemer af <strong>metal</strong> kan anvendes flangeforbindelser i størrelserne 28,0 til<br />

108,0 mm.<br />

Til Sanpress Inox findes flanger i rustfrit stål i størrelserne 15,0 til 108,0 – alternativt med<br />

presmuffer eller indvendigt gevind.<br />

Til flangesamlinger skal der vælges EPDM-tætninger eller asbestfrit tætningsmateriale<br />

afhængigt af anvendelsesområde.<br />

Flangetyper<br />

Fig. I–9<br />

Sanpress Inox<br />

Fast flange<br />

Rustfast stål 1.4401 (pres muffe)<br />

15 – 54 mm Model 2359<br />

64,0 – 108,0 mm Model 2359XL<br />

Fig. I–10<br />

Sanpress<br />

Løs flange, bevægelig<br />

Af stål, sort pulverlakering,<br />

med prestilslutning af rødgods<br />

28 – 54 mm Model 2259.5<br />

64 mm (kobber) Model 2459.5XL<br />

XL 76,1 – 108,0 mm Model 2259.5XL<br />

Anvendelsesområder<br />

Trykluftanlæg<br />

Trykluft er et af de vigtigste medier inden for industrien og skal bruges i store mængder<br />

i mange forskellige kvaliteter. Som komprimerbart medie stiller det store krav til rør<br />

og presfittings på tilslutningsstederne. Foruden sikkerheden er det afgørende, at der<br />

vælges det rigtige rørledningssystem til den aktuelle trykluftkvalitet. Trykluften produceres<br />

i kompressorer og indeholder findelt olie, som sætter sig indvendigt i rørledningerne<br />

og kan angribe nogle materialer. Kobberet i Systemerne Profipress / Profipress G<br />

og det rustfri stål i systemerne Sanpress Inox / Sanpress Inox G er resistent.<br />

De formonterede EPDM-tætningselementer i presfittings til systemerne Profipress og<br />

Sanpress bør anvendes til oliekoncentrationer ≤ 25 mg/m3. Ved højere oliekoncentrationer<br />

anbefaler vi systemerne Profipress G og Sanpress Inox G med HNBR-tætningselementer.<br />

187


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

<strong>Viega</strong> pres forbindelsessystemer<br />

Anvendelsesområder<br />

<strong>Viega</strong> presfittingssystem<br />

Profipress /<br />

Sanpress Inox<br />

Profipress G /<br />

Sanpress Inox G<br />

Sanpress<br />

Driftstryk pmax [bar]<br />

10 bar<br />

(Højere tryk efter forespørgsel)<br />

Oliekoncentration<br />

≤ 25 mg / m3 ≥ 25 mg / m3<br />

–<br />

Indsæt HNBR<br />

eller FKM<br />

Prestabo<br />

FKM<br />

Tab. I–6<br />

Tryluftforbrugere<br />

Med trykformindsker og<br />

olie- og vandudskiller<br />

Fig. I–11<br />

Kvalitetsklasser luft<br />

ISO 8573-1<br />

klasser<br />

Totalt olieindhold maks.<br />

[mg / m 3 ]<br />

1 ≤ 0,01<br />

2 ≤ 0,1<br />

3 ≤ 1,0<br />

4 ≤ 5,0<br />

5 ≤ 25,0<br />

Tab. I–7<br />

Ved etablering af trykluftledninger skal de gældende forskrifter og fagorganisationens<br />

sikkerhedsbestemmelser overholdes.<br />

Trykluftkompressor<br />

Fig. I–12<br />

Kilde: Fa. Kaeser<br />

188


4 Anvendelser inden for industri og håndværk – Anvendelsesområder<br />

Kølevandsanlæg<br />

Til transport af kølevand til industrielle fremstillingsprocesser anvendes der som regel<br />

vand, evt. med op til 50 % glykol. Rørledningssystemerne Profipress, Sanpress Inox og<br />

Sanpress kan anvendes til disse kølevandsanlæg.<br />

Anvendelse i forbindelse med bore- og køle-emulsioner skal afstemmes med<br />

vores fabrik i Attendorn. Profipress-systemet er uegnet til at transportere kølemidler.<br />

Kølevandskredsløb<br />

Hydraulisk anlæg<br />

Fig. I–13<br />

Rørledningssystemer med forskellige medier skal af hensyn til driftssikkerheden<br />

og reparation/vedligehold være tydeligt mærket.<br />

189


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Procesvandsanlæg<br />

Renset/behandlet vand til kemiske, medicinske og andre processer betegnes som teknisk<br />

vand, „procesvand“ eller „behandlet vand”. Det drejer sig om vand, som ikke er<br />

drikkevand*. Renset vand inddeles forskellige kategorier.<br />

Til disse kategorier hører:<br />

QQhelt eller delvis afsaltet vand<br />

QQafhærdet vand<br />

QQefterbehandlet vand<br />

QQdemineraliseret og deioniseret vand<br />

QQosmosevand etc.<br />

Før der udføres installation, skal der foretages en stikprøveanalyse, som afstemmes<br />

med vores fabrik i Attendorn.<br />

Renseanlæg til procesvand<br />

Anvisning for<br />

laboratorier<br />

Renset vand er mere<br />

kemisk aggressivt end<br />

drikkevand og indeholder<br />

<strong>metal</strong>ioner fra rørledningssystemerne<br />

Fig. I–14<br />

Sanpress Inox<br />

Anbefales til<br />

demineraliseret vand<br />

Demineraliseret vand indeholder ingen salte eller ioner deraf. Det har lav ledningsevne<br />

og høj opløsningsevne og forsøger derfor at opløse stoffer i sine omgivelser og fra rørledningernes<br />

materiale. I afhærdet vand er kalcium- og magnesiumioner fra karbonater<br />

udskiftet med natriumioner. I kobberledninger forhøjer den lave pH-værdi sandsynligheden<br />

for ensartet fladekorrosion. Rørledningssystemet Sanpress Inox og de tilhørende<br />

presfittings er velegnede til demineraliseret og afhærdet vand. Stoffer fra materialet<br />

afgives til vandet i knap målbare mængder.<br />

190


4 Anvendelser inden for industri og håndværk – Anvendelsesområder<br />

Anlæg til tekniske gasser<br />

„Tekniske gasser“ forstås normalt som overbegreb for de gasser, der anvendes i den<br />

kemiske og farmaceutiske industri.<br />

Komprimerede gasarter opdeles efter deres kvaliteter. Dette gælder også gasblandinger<br />

(naturgas etc.) opdeles på denne måde. Rørledningssystemerne Profipress,<br />

Profipress G, Sanpress Inox og Sanpress Inox G kan anvendes til at transportere mange<br />

af disse medier.<br />

Følgende tabel er ment som en støtte ved valg af det rigtige presfitting system med<br />

tætningsring til Profipress / Profipress G og Sanpress Inox / Sanpress Inox G.<br />

Tekniske gasser og egnede forbindelsessystemer<br />

Profipress /<br />

Sanpress Inox<br />

Med EPDMtætningselement<br />

Profipress G /<br />

Sanpress Inox G<br />

Med HNBR-tætningselement<br />

Till. driftstryk<br />

p max<br />

[bar]<br />

Trykluft 10 – 16 1)<br />

Kuldioxid CO 2 tørt – 16<br />

Kvælstof N 2 16<br />

Argon 10<br />

Corgon beskyttelsesgas<br />

(CO 2 +Ar)<br />

16<br />

Vakuum - 0,8<br />

Ilt – 16<br />

Naturgas og flaskegas – 5<br />

Tab. I–8<br />

1) 16 bar til og med<br />

ø 54 mm<br />

Anvendelse af gasser, der ikke er nævnt her, skal afstemmes med vores fabrik i<br />

Attendorn<br />

Fordelingsblok<br />

Til tekniske gasser<br />

Fig. I–15<br />

191


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Tekniske gasser anvendes mange steder i industrien. I den kemiske industri anvendes<br />

for eksempel kuldioxid til køling eller til slyngrensning. Ilt anvendes bl.a. til ozonproduktion,<br />

mens kvælstof og argon anvendes i store mængder i den kemiske og farmaceutiske<br />

industri som beskyttelsesgas ved inertisering. (Fjerne den atmosfæriske luft)<br />

I laboratorier til analyser og i industriproduktion, er der stigende brug for gasser af<br />

højeste renhed. De kommercielt tilgængelige kvaliteter er ikke gode nok, eller også forringes<br />

den høje kvalitet, fordi der senere trænger forurenende stoffer ind gennem<br />

lækager, eller fordi gasserne reagerer med materialerne i armaturer og rørledninger.<br />

Hvor grænserne for konventionelle industrigasser er nået, efterspørges gaskvaliteter<br />

med renheder over gennemsnittet. I disse „supergasser“ forekommer forurenende<br />

stoffer som mineraler og sporstoffer kun i ppm-området (parts-per-million). Gassers<br />

renhed angives ved hjælp af en punktnotation – en forkortet form af procentangivelsen.<br />

Tallet foran punktet definerer antallet af „niere“. Tallet efter punktet er det første tal,<br />

der ikke er „ni“.<br />

Eksempler<br />

QQKvælstof 3,8 Renhed 99,98 Vol.-%<br />

QQAcetylen 2,4<br />

3 „niere“, det sidste tal er „8“<br />

Renhed 99,4 Vol.-%<br />

2 „niere“, det sidste tal er „4“<br />

Forsyningsledning<br />

Til tekniske svejsegasser<br />

Fig. I–16<br />

192


4 Anvendelser inden for industri og håndværk – Anvendelsesområder<br />

Lavtryksdampanlæg<br />

Profipress-systemet må kun anvendes i lavtryksdampanlæg med FKM-tætningselement.<br />

QQTemperatur maksimalt 120 °C<br />

QQTryk maksimalt<br />

1 bar<br />

Betegnelse<br />

Fluorelastomer<br />

Med FKM-tætningselementer<br />

sammen<br />

med armaturer til dampanlæg<br />

Lavtryksdampanlæg<br />

Profipress S eller Profipress<br />

Presssystem med FKM-tætningselement<br />

Anvendelsesområde<br />

Solvarmeanlæg Vakuumrør<br />

Fjernvarmeanlæg<br />

Farve<br />

sort, mat<br />

Størrelser<br />

12 – 108 mm<br />

Fig. I–17<br />

Tab. I–9<br />

Lavtryksdampanlæg<br />

Anlæg til desinficering<br />

af hospitalssenge<br />

Fig. I–18<br />

Anvendelsesområder med højere temperatur- eller trykværdier skal afstemmes<br />

med vores fabrik i Attendorn.<br />

Anvendelse i skibsbyggeri<br />

Profipress er godkendt til skibsbyggeri. De bedes henvende Dem til vores salgsorganisation<br />

eller til serviceafdelingen for yderligere information.<br />

193


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Profipress / Sanpress Labs-frei<br />

I automobilindustrien og på malerværksteder må der kun anvendes rørledningssystemer,<br />

som er „Fri for stoffer, der forringer malingens befugtningsevne (LABS)“ som silikone,<br />

fedt, olie etc. Disse stoffer kan i produktionsprocessen give problemer med<br />

befugtning af overfladerne – med lakskader til følge.<br />

Hvis der kræves LABS-frie fittings, skal der anvendes „Profipress Labs-frei“ eller<br />

„Sanpress Labs-frei“. LABS-frie fittings er pakket enkeltvis og skal anvendes umiddelbart<br />

efter, at pakningen er åbnet. Disse presfittings er mærket med en blå prik. Til systemet<br />

hører også „Easytop-Schrägsitzventile Labs-frei“ (skråsædeventiler) og „Easytop-Kugelhähne<br />

Labs-frei“ (kuglehaner) i størrelserne 15 til 54 mm.<br />

Pakning<br />

produkterne er pakket<br />

separat i poser med<br />

påskriften: ,Labs-frei‘<br />

Fig. I–19<br />

LABS-fri fittings må ikke komme i kontakt med stoffer, som forringer malingens<br />

befugtningsevne!<br />

LABS-FRI Presfittings<br />

med SC-Contur<br />

Kendes på den blå prik<br />

Fig. I–20<br />

194


4 Anvendelser inden for industri og håndværk – Anvendelsesområder<br />

Easytop kuglehaner<br />

Easytop kuglehaner er velegnede til industri-installationer til ikke brændbare gasser. I<br />

trykluftanlæg og alle steder med ikke brændbare tekniske gasser er det maksimale<br />

driftstryk 10 bar.<br />

Profipress G kuglehaner er godkendt til brændbare gasser iht. DVGW-dokument G 260<br />

til PN 5, ved HTB-krav GT/1.<br />

Egenskaber<br />

QQLet at vedligeholde, monteringsvenlige<br />

QQPresteknik til hurtigt montage<br />

QQFarvede hætter for mediemærkning<br />

Mediemærkning<br />

Afspærring af enhed<br />

for vedligeholdelse<br />

Fig. I–21 Fig. I–22<br />

<strong>Viega</strong> systemer og<br />

kugleventiler i industriel<br />

anvendelse<br />

Fig. I–23<br />

195


Application technology for <strong>metal</strong>lic pipe installation systems – 2nd Edition<br />

Oversigt over anvendelsesmuligheder<br />

Flere forskellige driftstilstande i medierne – som tryk, temperatur og koncentration –<br />

kræver omhu ved valg af rør- og tætningsmateriale.<br />

Vi har på grundlag af hidtidige erfaringer med specialmedier udarbejdet informationsbrochuren<br />

„Einsatzbereiche <strong>metal</strong>lener Rohrsysteme“ (Anvendelse områder for<br />

rørsystemer i <strong>metal</strong>). Foruden installationer til vand beskrives også mulighederne for<br />

anvendelse til antifrostmidler, olie, køle- og smøremidler samt andre specialmedier og<br />

tekniske gasser.<br />

Formularen side 197 bedes anvendt ved forespørgsler.<br />

196


Spørgeskema til materialebestandighed<br />

<strong>Viega</strong> behandlingsnr.:<br />

Dato:<br />

Kundenr.:<br />

Kunde / Firma<br />

(Firmastempel)<br />

<strong>Viega</strong> projektnr.:<br />

Udarbejdet af:<br />

Manager: F + E<br />

1<br />

Gade/vej:<br />

Postnummer/by:<br />

Telefon:<br />

Contact Service Center<br />

E-Mail: service-werkstoffanfrage@viega.de<br />

2<br />

Kontaktperson:<br />

Slutkunde:<br />

Projekt:<br />

Projektstørrelse:<br />

(lb.m rør/fittings)<br />

Kontaktperson:<br />

Dato:<br />

(Udfyldes af <strong>Viega</strong>)<br />

Anbefaling<br />

3 Marker venligst <strong>Viega</strong> system med et kryds<br />

Copper /<br />

Gun<strong>metal</strong><br />

EPDM<br />

Copper /<br />

Gun<strong>metal</strong><br />

FKM<br />

Stainless steel<br />

EPDM<br />

Gun<strong>metal</strong><br />

EPDM<br />

Stainless steel<br />

EPDM<br />

Gun<strong>metal</strong><br />

EPDM<br />

Copper /<br />

Gun<strong>metal</strong><br />

HNBR<br />

Stainless steel<br />

HNBR<br />

Galvanized steel<br />

EPDM<br />

Galvanized steel<br />

EPDM<br />

Profipress<br />

Copper<br />

Profipress S<br />

Copper<br />

Sanpress-Pipe<br />

1.4401<br />

Stainless steel<br />

Sanpress-Pipe<br />

1.4401<br />

Stainless steel<br />

Sanpress-Pipe<br />

1.4521<br />

Stainless steel<br />

Sanpress-Pipe<br />

1.4521<br />

Stainless steel<br />

Profipress G<br />

Copper<br />

Sanpress Inox G<br />

Stainless steel<br />

Prestabo<br />

Galvanized steel<br />

Prestabo<br />

sendzimir<br />

Galvanized steel<br />

4 Det samlede anlægs funktion?<br />

5 Hvilke funktioner har <strong>Viega</strong>-komponenterne i anlægget?<br />

6<br />

7<br />

8<br />

Hvilke medier påvirker de materialer, der skal undersøges?<br />

(Vedlæg venlligst sikkerhedsdatablade og tekniske datablade)<br />

Kan der forventes yderligere bestanddele i mediet?<br />

Eksempel: Additiver, rengøringsmidler, spåner osv. Hvis ja, hvilke?<br />

Angiv koncentrationer.<br />

Hvor store mængder skal der transporteres?<br />

Angiv forholdet, hvis der er flere komponenter.<br />

9 Driftsbetingelser Trykstød<br />

Stagnation<br />

T max<br />

Ja<br />

Ja<br />

Nej<br />

Nej<br />

T min<br />

p max<br />

p min<br />

pH max<br />

pH min<br />

System<br />

anlæggets/komponentens<br />

placering<br />

åben<br />

udendørs<br />

lukket<br />

indendørs<br />

10 Hvor lang er systemets planlagte levetid?<br />

Vores anbefaling gælder de angivne anvendelses- og driftsbetingelser. Anbefalingen udvider ikke vores mangelansvar<br />

og forlænger ikke de lovpligtige mangelansvarsfrister.


5 Værktøjssystemer – Systembeskrivelse<br />

5 Værktøjssystemer<br />

Systembeskrivelse<br />

Anvendelse<br />

<strong>Viega</strong> pressystemers funktionssikkerhed afhænger først og fremmest af, at de<br />

presmaskiner og presbakker, der anvendes, er i perfekt stand. Den brugsanvisning,<br />

der følger med ved køb af presværktøjer, skal følges. Ved udlån / overdragelse af<br />

presmaskiner skal alle produktinformationer medleveres.<br />

Presmaskiner kan anvendes ved temperaturer fra –5 til +40 °C. Hvis temperaturen<br />

er under 0 °C, bliver hydraulikolien tyktflydende, og maskinerne skal opvarmes til<br />

rumtemperatur, før de tages i brug. I modsat fald forringes deres funktionsevne,<br />

og mekanikken kan blive beskadiget.<br />

Hvis en presmaskine kommer under vand, skal den sendes til kontrol på en autoriseret<br />

servicestation.<br />

Uafhængig af lovmæssige reguleringer garanterer <strong>Viega</strong> at presningen er tæt.<br />

Presværktøj<br />

Modeller til lysnettilslutning<br />

eller batteridrift<br />

Fig. W–1<br />

199


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Presmaskiner<br />

Sikre presværktøjer, der ikke kræver megen vedligeholdelse, er en vigtig del af <strong>Viega</strong>s<br />

system-filosofi. De er optimeret til <strong>Viega</strong> presfitting-materialer og -mål og garanterer<br />

dermed sikkerhed og funktionsdygtighed ved almindelig anvendelse. Også, fordi de<br />

kan anvendes overalt – med og uden lysnet tilslutning. Vi anbefaler, at der anvendes<br />

følgende presmaskiner<br />

QQPressgun 4 E<br />

QQPressgun 4 B<br />

QQPressgun Picco<br />

QQPT3-EH<br />

QQPT3-AH<br />

QQPT2<br />

Pressgun 4 E 230 V<br />

Lysnet drevet<br />

presmaskine 230 V<br />

Fig. W–2<br />

Egenskaber<br />

QQTil alle størrelser presfittings fra 12 til 108 mm<br />

QQOptimal håndtering – ergonomisk pistolform til enhåndsbetjening<br />

QQVægtreduceret til 4,5 kg (uden presbakke)<br />

QQ180° drejbart hoved<br />

QQForsinket udløsning, boltsikring, tvangspresning og automatisk tilbageløb<br />

QQLave vedligeholdelses- og reparationsomkostninger<br />

QQService først efter 32,000 presninger<br />

200


5 Værktøjssystemer – Systembeskrivelse<br />

Pressgun 4 B<br />

Ledningsfri/akku<br />

presmaskiner<br />

18 V/2,2 Ah<br />

Litium-ion-batteri<br />

Fig. W–3<br />

Ledningsfri presmaskine med den nyeste litium-ion-teknik<br />

De ledningsfri/akku litium-ion-maskiner har 60 % større kapacitet, større ydeevne også<br />

ved lave temperaturer og ingen memory-effekt. Da maskinerne meget hurtigt når op<br />

på fuld styrke, udføres presningen på 3 til 4 sekunder, afhængigt af rørdimension.<br />

Egenskaber<br />

QQTil alle størrelser presfittings fra 12 til 108 mm<br />

QQOptimal håndtering – ergonomisk pistolform til enhåndsbetjening<br />

QQVægtreduceret til 4,35 kg (uden presbakke)<br />

QQ180° drejbart hoved<br />

QQForsinket udløsning, boltsikring, tvangspresning og automatisk tilbageløb<br />

QQLave vedligeholdelses- og reparationsomkostninger<br />

QQService først efter 32,000 presninger<br />

201


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Pressgun Picco<br />

Ledningsfri/akku<br />

presmaskiner<br />

18 V/2,2 Ah<br />

Lithium-ion-batteri<br />

Fig. W–4<br />

Picco er den mindste og letteste af <strong>Viega</strong> presmaskinerne. Den er ekstra handy og gør<br />

det muligt at arbejde under selv de trangeste pladsforhold og i snævre forvægskonstruktioner.<br />

Den anvendes især til installation af <strong>Viega</strong> kunststofrørsystemer og til reparationsarbejder<br />

i forbindelse med kundeservice. Picco presbakker er specielt konstrueret<br />

med henblik på at spare vægt og er derfor ikke kompatible med de andre <strong>Viega</strong><br />

presværktøjer.<br />

Egenskaber<br />

QQTil presfittings af <strong>metal</strong>, størrelser fra 12 til 35 mm<br />

QQTil presfitting af kunststof, størrelser fra 12 til 40 mm<br />

QQOptimal håndtering – ergonomisk pistolform til enhåndsbetjening<br />

QQVægtreduceret til 2,5 kg (uden presbakke)<br />

QQ180° drejbart hoved<br />

QQBoltsikring<br />

QQLave vedligeholdelses- og reparationsomkostninger<br />

QQService først efter 32,000 presninger<br />

Anvendelse af presværktøjer af andre mærker<br />

Certificering af <strong>Viega</strong> rørsystemer forudsætter bl.a. en bestået tilslutningsteknisk test<br />

iht. DWGW-dokument W 534 udført af et godkendt testinstitut. Til dette formål udføres<br />

prestilslutningerne principielt med <strong>Viega</strong> presværktøjer og <strong>Viega</strong> presbakker. Hvis<br />

håndværkeren i praksis anvender et presværktøj af et andet mærke, anbefales det af<br />

forsikringshensyn at indhente et egnethedsbevis hos den pågældende producent.<br />

<strong>Viega</strong> vil afvise reklamationer, hvis det kan påvises, at skaden er opstået, fordi der er<br />

anvendt et presværktøj af et andet mærke.<br />

202


5 Værktøjssystemer – Systembeskrivelse<br />

Tilbehør<br />

Kuffert med<br />

presbakker<br />

Pressgun 4E<br />

Pressgun 4B<br />

Fig. W–5<br />

Fig. W–6<br />

Litium-ion-batteri<br />

Pressgun 4B<br />

Oplader<br />

Fig. W–7<br />

Fig. W–8<br />

Pressgun Picco<br />

Kuffert uden presbakker<br />

Fig. W–9<br />

203


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Presværktøj<br />

Presringe med led/kardan funktion<br />

De patenterede <strong>Viega</strong> presringe og trækbakkens led/kardan funktion gør det muligt at<br />

dreje presringen op til 180°. Det er løsningen til prestilslutninger i vanskeligt tilgængelige<br />

rørføringer, rørskakter og forvægskonstruktioner.<br />

Til <strong>Viega</strong> rørledningssystemer af <strong>metal</strong><br />

Trækbakken og presringene er kompatible med alle <strong>Viega</strong> presmaskiner (med<br />

undtagelse af Picco presmaskinen).<br />

Presringsæt<br />

Kuffertsæt<br />

12 til 35 mm<br />

Med<br />

kardantrækbakke P1<br />

Uden ill.<br />

42 til 54 mm med Z 2<br />

Fig. W–10<br />

Fig. W–11<br />

Til XL presfittings<br />

Til <strong>Viega</strong> pressystemerne Sanpress Inox XL, Prestabo XL og Profipress XL (presfittings af<br />

kobber) i størrelserne XL 64,0/76,1/88,9 og 108,0 mm.<br />

Presringe<br />

64,0 til 108,0 mm<br />

Med<br />

kardantrækbakke Z 2,<br />

også som sæt i kuffert<br />

Fig. W–12<br />

204


5 Værktøjssystemer – Systembeskrivelse<br />

Preskæder / Presbakker<br />

Preskæde med trækbakke<br />

Til Sanpress XL presfittings af rødgods<br />

Størrelse 76,1 mm til 108,0 mm<br />

Fås også som kuffertsæt<br />

Fig. W–13<br />

Presbakker<br />

Til presfittingssystemer af kunststof og af<br />

<strong>metal</strong><br />

12 til 63 mm til kunststofsystemer<br />

12 til 54 mm til pressystemer af <strong>metal</strong><br />

Kompatible med alle <strong>Viega</strong> pres -mas kiner<br />

(med undtagelse af Picco)<br />

Fig. W–14<br />

Picco presbakker<br />

12 - 40 mm til kunststofsystemer<br />

12 - 35 mm til pressystemer af <strong>metal</strong><br />

Fig. W–15<br />

205


<strong>Installationssystemer</strong> i <strong>metal</strong> - 2. udgave<br />

Serviceanvisninger<br />

Presmaskiner<br />

<strong>Viega</strong> presmaskiners funktionssikkerhed og presfittingtæthed afhænger først og fremmest<br />

af presværktøjernes stand.<br />

<strong>Viega</strong> presmaskiner er elektrohydrauliske apparater, som under presarbejdet når op på<br />

et fast indstillet tryk. Kun et tæt hydrauliksystem uden olietab kan garantere driftssikkerhed<br />

og -pålidelighed. Som ved alt elektrohydraulisk værktøj vil der være et naturligt<br />

slid på presværktøjerne.<br />

Derfor skal de jævnligt til service eller eftersyn på et af de serviceværksteder, som <strong>Viega</strong><br />

har anvist. Se www.viega.dk angående kontakt<br />

Serviceintervaller for <strong>Viega</strong> presmaskiner<br />

Presmaskiner<br />

Serviceintervaller<br />

Pressgun Picco<br />

Pressgun 4 E<br />

Pressgun 4 B<br />

PT3-AH<br />

Picco<br />

PT3-H/EH<br />

PT2<br />

Modell 2478<br />

Modell 2475<br />

Tab. W–1<br />

Efter 32,000 presninger vises der en serviceindkaldelse på LED-skærmen. Efter<br />

yderligere 2,000 presninger sker der en sikkerheds udkobling. Service skal udføres<br />

senest efter 4 års forløb.<br />

Efter 22,000 presninger vises der en serviceindkaldelse på LED-skærmen. Efter<br />

yderligere 2,000 presninger sker der en sikkerheds udkobling. Service skal udføres<br />

senest efter 4 års forløb.<br />

Hvert andet år.<br />

Mindst en gang årligt.<br />

Efter 20,000 presninger vises der en serviceindkaldelse på LED-skærmen. Service<br />

skal udføres senest efter 4 års forløb.<br />

Presringe / Presbakker<br />

Vi anbefaler, at presringe og presbakker vedligeholdes jævnligt sammen med presmaskinerne<br />

for at sikre, at deres funktionsdygtighed bevares. Der udskiftes sliddele, preskonturerne<br />

korrigeres, og presbakkerne justeres.<br />

Pleje og rengøring<br />

Efter hver brug bør presværktøjerne rengøres med en klud. Værktøjerne skal opbevares<br />

tørt og rent! Eventuelt skal bevægelige dele smøres med olie. Desuden skal presbakkernes<br />

og indsatsernes konturer gnides blanke med fint ståluld eller fiberstof og<br />

smøres.<br />

206


5 Værktøjssystemer – Serviceanvisninger<br />

Værktøjsservice<br />

Reparation og vedligehold<br />

Østrig Ackerl 4020 Linz<br />

Indu Tools<br />

1850 Grimbergen<br />

Belgien<br />

Ridge Tool Europe<br />

3001 Heverlee<br />

Tjekkiet Mátl & Bulla 66461 Brno<br />

Danmark Scherer‘s 2610 Rodovre<br />

Finland Sähköhuolto Tissari Oy 70460 Kuopio<br />

Frankrig Fa. Striebel 67602 Selestat<br />

MEP Hire<br />

ML43NH Glasgow<br />

Storbritanien<br />

Broughten Plant Hire and Sales RN3 8UJ Romford, Essex<br />

Grækenland Ergon Equipment 15344 Athen<br />

Elmes<br />

39040 Neumarkt<br />

Italien<br />

O.R.E<br />

47900 Rimini<br />

Holland MG Service 5388 RT Nistelrode<br />

Norge Grønvold Maskinservice 0613 Oslo<br />

Spanien Tecno Izqueierdo 28026 Madrid<br />

Sverige AB Lindströms 39241 Kalmar<br />

Schweiz Von Arx 4450 Sissach<br />

Tab. W–2<br />

207


A – M<br />

Index<br />

A<br />

Adaptersæt til radiatorer 122<br />

Afisoleringsværktøj 149<br />

Afkortning af rør 84<br />

Aksialkompensator 46<br />

Aktiveringsenhed, prøveudtagning 61<br />

Anlæg til flydende gas 171<br />

Anvendelser inden for industri<br />

og håndværk 179<br />

Argon 191<br />

Asfaltgulv 154<br />

B<br />

Beregning af tryktab 24, 49, 99<br />

Blandingsinstallationer 81, 142<br />

Blyrør 17<br />

Brandbeskyttelse af rør 39<br />

Brandsluknings- og sikringsenheder 22<br />

Bukning af rør 84<br />

C<br />

Cirkulationsreguleringsventil 69<br />

Cirkulationsreguleringsventil 69<br />

Corgon beskyttelsesgas 191<br />

D<br />

Desinficering 27, 97<br />

Desinficering med brintoverilte 27<br />

Desinficering med klordioxid 27<br />

Drikkevand 16<br />

E<br />

Easytop-ventiler og komponenter 51<br />

EPDM 33, 112, 191<br />

F<br />

Fast punkt, rørfastgøring 85<br />

Fastgøringsmetoder 85<br />

Fjernvarmeanlæg 128<br />

FKM 107, 132<br />

Flangeadapter 59, 86<br />

Fordelere 59<br />

Friløbsventiler til forsænket installation 64<br />

G<br />

Gasanlæg 171<br />

Gasdrevne husholdningsapparater 165<br />

Gasstikdåser 167<br />

Glidepunkt, rørfastgøring 85<br />

Gulvfordeler 115<br />

H<br />

HNBR 191<br />

Hygiejnisk skyllefunktion 20<br />

I<br />

Idriftsætning 97<br />

Ilt 191<br />

Indstiksdybde 88<br />

Intern cirkulationsledning 71<br />

Isolering 37<br />

Isoleringsforskruning 81<br />

K<br />

Kalkdannelse 17<br />

Klorid 50<br />

Kobberrør 35<br />

Kølevandsanlæg 189<br />

Kombination af forskellige materialer 17<br />

Kombineret skråsæde 52<br />

Kompensationsstykke 145<br />

Korrosion af rustfri stålrør forårsaget af klorider 50<br />

Kuglehaner 68, 111<br />

Kvælstof 191<br />

L<br />

LABS-fri fittings 194<br />

Længdeudvidelseskompensatorer 40<br />

Lavtryksdampanlæg 193<br />

Ligesædeventiler til forsænket installation 63<br />

Lydisolering 38<br />

M<br />

Materialeforespørgsel 179, 186, 197<br />

208


P – V<br />

P<br />

Potentialudligning 82, 142<br />

Presforbindelse 159<br />

Presmaskiner 200<br />

Prestabo 132<br />

Presværktøj 204<br />

Procesvandsanlæg 190<br />

Profipress / Profipress XL 35, 107<br />

Profipress G / Profipress G XL 168<br />

Profipress S 129<br />

Prøveudtagning 18<br />

Prøveudtagningsventil 60<br />

Pseudomonas 27<br />

U<br />

Udvidelse 152<br />

V<br />

Værktøjsservice 207<br />

Vakuum 191<br />

Varmedesinficering 69<br />

Visign for Care 20<br />

R<br />

Radiatortilslutning 113<br />

Radiatortilslutningsblok 119<br />

Renhed af tekniske gasser 192<br />

Reparationsmuffe, Smartloop 79<br />

Rørfriktionstrykdifference 49<br />

Rørledninger i gulvet 125<br />

Rørsystemer af stål 132<br />

Rustfaste stålrør 31<br />

S<br />

Sanpress / Sanpress XL 33<br />

Sanpress Inox / Sanpress Inox XL 31<br />

Sanpress Inox G / Sanpress Inox G XL 172<br />

SC-Contur 25, 97, 185<br />

Smartloop-Inliner cirkulationsledning 71<br />

Sokkellistetilslutningssæt 121<br />

Solvarmeanlæg 129<br />

Steptec-installationsskaft 39<br />

Stigledninger 113<br />

T<br />

Tætningselementer 186<br />

Tekniske gasser 191<br />

Tilslutning med T-stykke 119<br />

Tilslutning varmtvandsbeholder 82<br />

Tømme/aftapningsventil 53<br />

Trykluftanlæg 187<br />

209

Hooray! Your file is uploaded and ready to be published.