3000162-2006-04-26.fm Usage<br />

1. Usage<br />

The <strong>SR1</strong>-K-1 and <strong>SR1</strong>-X are i<strong>de</strong>ntical. The <strong>de</strong>scriptions cover the following:<br />

<strong>SR1</strong>-K-1 … used for EXHAUSTO fans BESF and BESB with motor power relay (MPR).<br />

<strong>SR1</strong>-X … used for EXHAUSTO heat recovery units VEX 1.5, 2.5 and 3.5 with<br />

motor power relay (MPR).<br />

Other connections<br />

to VEX<br />

These instructions <strong>de</strong>scribe the connections between the VEX unit and <strong>SR1</strong>-X.<br />

The other connections to the unit are <strong>de</strong>scribed in the instructions placed in<br />

the plastic pocket on the unit itself.<br />

Operation It is possible to run two-speed operation controlled by an external clock function or a<br />

similar <strong>de</strong>vice. If the motor overheats, the automatic system box must be reset manually.<br />

2. Description<br />

The control system consists of a control panel and an automatic system box:<br />

Control panel The control panel is used to start and stop the fan, and to set the fan speed for normal<br />

operation. It features indicator lights for operation, overheated motor warning and<br />

minimum speed setting. The panel is supplied with low-voltage current from the<br />

automatic system box.<br />

Automatic system<br />

box<br />

Control panel<br />

Automatic system<br />

box<br />

The automatic system box contains a safety function that protects the motor against<br />

overheating, and a system for setting the fan speed via an external clock function or a<br />

similar <strong>de</strong>vice. The safety function that protects the motor against overheating consists<br />

of a thermal cut-out in the motor, which is linked to the automatic system box. When an<br />

error signal is sent from the thermal cut-out, the power supply to the motor is cut and the<br />

warning light is illuminated. To reset, switch off the function circuit breaker<br />

and then switch it on again.<br />

2/24<br />

Cable screw connection<br />

180<br />

Function circuit breaker<br />

for manual reset<br />

130