The comput<strong>in</strong>g centre <strong>in</strong> <strong>Zeuthen</strong> – an overview<br />

> 19 people<br />

> UPS:<br />

Tak<strong>in</strong>g care of any comput<strong>in</strong>g / telecommunication<br />

related work (there is no comput<strong>in</strong>g manpower <strong>in</strong><br />

the experiments)<br />

3 systems runn<strong>in</strong>g <strong>in</strong> parallel with 160 kW capacity each<br />

➔ 1 UPS runn<strong>in</strong>g as redundancy buffer<br />

> Air condition<strong>in</strong>g system:<br />

5 water-cooled Rittal racks with 20 kW cool<strong>in</strong>g power each<br />

Air condition<strong>in</strong>g with heat exchanger: 130 kW cool<strong>in</strong>g power<br />

Air condition<strong>in</strong>g with cooled water: 100 kW cool<strong>in</strong>g power<br />

In summer months we clearly see we reached the limit of the current air cool<strong>in</strong>g<br />

capacity<br />

> Currently more than 900 active server / storage systems<br />

~240 kW susta<strong>in</strong>ed power consumption<br />

Andreas Haupt | <strong>IT</strong>-<strong><strong>in</strong>frastructure</strong> <strong>in</strong> <strong>Zeuthen</strong> | June 6, 2011 | Page 10