Operating instructions<br />

<strong>CFA</strong> <strong>MOBIL</strong><br />

8. Servicing<br />

Tightening screw 4 Motor clamping screws<br />

For this purpose, the clamping screws of the motor should be unscrewed and the<br />

tightening screws tightened as required. Subsequently, retighten the motor clamping<br />

screws. Care should be taken to ensure that the belt pulleys are flush. Otherwise the wear<br />

on the V-belt will be excessive.<br />

Replacing of the V-belt<br />

Unscrew the clamping screws as described above and unscrew the tightening screws<br />

such that the motor can be pushed forward up to the stop. Subsequently, put on the new<br />

belt and tension it as described above.<br />

8.3. Servicing of the pump<br />

8.3.1. Servicing intervals<br />

after 50 operating hours:<br />

Oil change<br />

Subsequently, every 200 operating hours or after six months:<br />

Oil change<br />

If required, i.e. in the case of condensation forming in the crankcase:<br />

Oil change<br />