TCD <strong>Range</strong> Double Stage <strong>Compressor</strong><br />

Application envelopes of DORIN <strong>CO2</strong> compressors, valid for values lower than 10K for suction superheat.<br />

Transcritical compressors require a gas cooler rather than a condenser. This device will cool down the compressed CO 2 .<br />

Therefore the global efficiency of the system will strongly depend on how efficiently the heat exchange occurs inside the gas<br />

cooler. There will be found higher refrigerating capacity for lower gas cooler outlet temperature. The lower the gas coolers outlet<br />

temperature the higher the compressors cooling capacity.<br />

24<br />

<strong>Compressor</strong> performances for TCD <strong>Range</strong> compressors<br />

TRANSCRITICAL TWO STAGES<br />

T R ANS C R IT IC O DO P P IO S T ADIO / T R ANS C R IT IC AL T W O S T AG E S<br />

modello Model / model Type type<br />

t_evap t_ev<br />

(°c) (ºC)<br />

p_suc<br />

p_suc (bar) (bar)<br />

tgc_out<br />

(°c) (ºC)<br />

p_dis<br />

(bar) beta<br />

Capacity<br />

Capacity (Kw) (Kw)<br />

T C DH 334/4-D<br />

-50 6,84<br />

-45 8,34<br />

-40<br />

10,07<br />

-35 12,05<br />

-30 14,30<br />

-25 16,85<br />

-20<br />

19,72<br />

Input Input Power<br />

(Kw)<br />

15 75 11,0 2,4 2,8<br />

25 75 11,0 2,1 2,8<br />

15 75 9,0 3,0 3,0<br />

25 75 9,0 2,6 3,0<br />

15 75 7,4 3,7 3,2<br />

25 75 7,4 3,2 3,2<br />

25 90 8,9 3,2 3,6<br />

35 90 8,9 2,5 3,6<br />

15 75 6,2 4,5 3,4<br />

25 75 6,2 3,8 3,4<br />

25 90 7,5 3,9 3,8<br />

35 90 7,5 3,0 3,8<br />

25 100 8,3 4,0 4,1<br />

35 100 8,3 3,3 4,1<br />

15 75 5,2 5,4 3,6<br />

25 75 5,2 4,6 3,6<br />

25 90 6,3 4,7 4,1<br />

35 90 6,3 3,7 4,1<br />

35 110 7,7 4,0 4,6<br />

45 110 7,7 3,0 4,6<br />

15 75 4,5 6,5 3,8<br />

25 75 4,5 5,5 3,8<br />

25 90 5,3 5,7 4,3<br />

35 90 5,3 4,4 4,3<br />

35 100 5,9 4,7 4,6<br />

35 120 7,1 4,9 5,1<br />

45 120 7,1 3,8 5,1<br />

15 75 3,8 7,6 3,9<br />

25 75 3,8 6,5 3,9<br />

25 90 4,6 6,7 4,6<br />

35 90 4,6 5,2 4,6<br />

35 100 5,1 5,5 4,9<br />

35 120 6,1 5,8 5,5<br />

45 120 6,1 4,6 5,5<br />

Preliminary data subject to variation without notice<br />

Datas valid with 10K of suction gas useful superheat<br />

t_ev evaporating temperature (ºC) | p_suc suction pressure (bar_a) | tgc_out gas cooler outlet temperature (ºC)<br />

p_dis discharge presure (bar_a) | beta pressure ratio | Q refrigerating capacity (kW)