Type PTC<br />

Bushing with external plug connection<br />

44<br />

Fig. A H<br />

1<br />

2<br />

105<br />

60<br />

105<br />

60<br />

105<br />

60<br />

184<br />

140<br />

228<br />

183<br />

230<br />

184,5<br />

PTC 24/250<br />

Identification<br />

PTC 24/250-R<br />

Corto<br />

PTC 36/400<br />

PTC 24/400-R<br />

Corto<br />

PTC 36/630<br />

PTC 24/630-R<br />

Corto<br />

• We recommend the use of flange<br />

Type Drawing<br />

<strong>General</strong> characteristics<br />

The PTC bushings can be used as a fixed part in medium voltage<br />

inlet for oil or SF6 insulated devices, such as transformers or switchgears.<br />

They are equipped with a connection for the reading of low voltage by a light signal box.<br />

Application<br />

For indoor application, suitable for vertical or horizontal installation.<br />

Working voltage<br />

24 - 36 kV<br />

Reference st<strong>and</strong>ards<br />

IEC 60137 (electrical tests)<br />

DIN 47636/HN 52-S-61 (coupling interface)<br />

1922<br />

I-6284-02<br />

1930<br />

I-7113-02<br />

1933<br />

I-6274-02<br />

1935<br />

NI-959<br />

1923<br />

I-6250-2<br />

1936<br />

I-7094-04<br />

Maximum<br />

operation<br />

voltage<br />

24 kV<br />

24 kV<br />

36 kV<br />

24 kV<br />

36 kV<br />

24 kV<br />

Electrical data St<strong>and</strong>ards C M kg.<br />

Nominal<br />

current<br />

250 A<br />

250 A<br />

400 A<br />

400 A<br />

630 A<br />

630 A<br />

Lightning<br />

impulse<br />

voltage<br />

whitst<strong>and</strong><br />

125 kV<br />

125 kV<br />

170 kV<br />

125 kV<br />

170 kV<br />

125 kV<br />

Dry power<br />

frequency<br />

voltage<br />

whitst<strong>and</strong><br />

55 kV<br />

55 kV<br />

75 kV<br />

55 kV<br />

75 kV<br />

55 kV<br />

Coupling<br />

type<br />

DIN 47636<br />

HN 52-S-61<br />

DIN 47636<br />

HN 52-S-61<br />

EN 50180<br />

HN 52-S-61<br />

EN 50181<br />

HN 52-S-61<br />

EN 50181<br />

DIN 47636<br />

EN 50181<br />

DIN 47636<br />

Connetion<br />

type<br />

Sliding<br />

contact •<br />

Sliding<br />

contact •<br />

Sliding<br />

contact •<br />

Sliding<br />

contact •<br />

M16<br />

M16<br />

Threded<br />

hole Weight<br />

M8<br />

M8<br />

M10<br />

M10<br />

M10<br />

M10<br />

1,3<br />

1,1<br />

2,3<br />

1,9<br />

2,3<br />

1,9