OTHER<br />

BUILDING<br />

5 m (min) 5 m (min)<br />

5 m (min)<br />

Attached AN store – plan view<br />

AN<br />

STORE<br />

AN<br />

STORE<br />

AN store located inside a non-dedicated<br />

building – plan view<br />

240/240/240 FRL wall<br />

5 m<br />

(min)<br />

5 m<br />

(min)<br />

isolation area in which no goods may<br />

be stored or activities conducted<br />

OTHER<br />

BUILDING<br />

Attached AN store – plan view<br />

5 m (min)<br />

AN<br />

STORE<br />

5 m<br />

(min)<br />

AN<br />

STORE<br />

AN store located inside a non-dedicated<br />

building – plan view<br />

5 m<br />

(min)<br />

5 m (min)<br />

Figure 3.1 Examples illustrating the required isolation <strong>of</strong> AN stores <strong>of</strong> 10 t or less<br />

3.5 Silo <strong>storage</strong><br />

All silos used for AN <strong>storage</strong> must comply with the requirements listed below.<br />

• The silo must be constructed from non-combustible, corrosion-resistant materials.<br />

• Materials and fittings containing zinc, copper or other incompatibles, which could<br />

come into contact with AN during normal operations or in the event <strong>of</strong> spillage, must<br />