OTHER<br />
BUILDING<br />
5 m (min) 5 m (min)<br />
5 m (min)<br />
Attached AN store – plan view<br />
AN<br />
STORE<br />
AN<br />
STORE<br />
AN store located inside a non-dedicated<br />
building – plan view<br />
240/240/240 FRL wall<br />
5 m<br />
(min)<br />
5 m<br />
(min)<br />
isolation area in which no goods may<br />
be stored or activities conducted<br />
OTHER<br />
BUILDING<br />
Attached AN store – plan view<br />
5 m (min)<br />
AN<br />
STORE<br />
5 m<br />
(min)<br />
AN<br />
STORE<br />
AN store located inside a non-dedicated<br />
building – plan view<br />
5 m<br />
(min)<br />
5 m (min)<br />
Figure 3.1 Examples illustrating the required isolation <strong>of</strong> AN stores <strong>of</strong> 10 t or less<br />
3.5 Silo <strong>storage</strong><br />
All silos used for AN <strong>storage</strong> must comply with the requirements listed below.<br />
• The silo must be constructed from non-combustible, corrosion-resistant materials.<br />
• Materials and fittings containing zinc, copper or other incompatibles, which could<br />
come into contact with AN during normal operations or in the event <strong>of</strong> spillage, must<br />
<strong>Safe</strong> <strong>storage</strong> <strong>of</strong> <strong>solid</strong> <strong>ammonium</strong> <strong>nitrate</strong> – code <strong>of</strong> <strong>practice</strong> Page 6