2.2.4 Replacing the ET 200S pulse generator <strong>and</strong> positioning modules<br />
Contents<br />
Information that could not be included in the online help.<br />
STEP 7 Professional<br />
2.2 Editing devices <strong>and</strong> networks<br />
Replacing the ET 200S pulse generator <strong>and</strong> positioning modules<br />
This information is relevant to the "2 Pulse" pulse generator modules (6ES7 138-4DD00-<br />
0AB0) <strong>and</strong> "1 Step 5V" positioning modules (6ES7 138-4DC00-0AB0) from a project which<br />
was created with TIA Portal V<strong>11</strong>.0. When replacing these modules from the TIA Portal V<strong>11</strong>.0<br />
with a new version of these modules, the parameter settings are reset to the default values.<br />
This is the case with one of the following procedures:<br />
● Replacting the pulse generator module 6ES7 138-4DD00-0AB0 or the positioning module<br />
6ES7 138-4DC00-0AB0 with their successor modules 6ES7 138-4DD01-0AB0 or 6ES7<br />
138-4DC01-0AB0 by means of a device replacement.<br />
● Updating the module version using the appropriate button in the device properties in the<br />
Inspector window.<br />
2.2.5 Setting flow control for CM 1241 (RS232)<br />
Contents<br />
Information that could not be included in the online help.<br />
Values for XON <strong>and</strong> XOFF<br />
If flow control is enabled for the CM 1241 (RS-232) communications module <strong>and</strong> set to<br />
"XON/XOFF", you can enter identical values for the XON <strong>and</strong> XOFF characters. From a<br />
technical point of view, however, this configuration is impractical. You should therefore use<br />
different values for XON <strong>and</strong> XOFF.<br />
<strong>Readme</strong><br />
<strong>Programming</strong> <strong>and</strong> <strong>Operating</strong> <strong>Manual</strong>, <strong>11</strong>/20<strong>11</strong> 19