Technical Information<br />
Error messages on the display<br />
On the main display, errors are indicated alternately on line 1 and line 2.<br />
The error menu provides a more detailed plain text description. The table<br />
which follows contains a selection of possible error types:<br />
H W Temp<br />
Alarm<br />
( Cold)<br />
Sensor<br />
error,<br />
cold<br />
side<br />
( short<br />
circuit<br />
, breakag<br />
e,<br />
jumpers<br />
missing<br />
)<br />
H W Temp<br />
Alarm<br />
( Hot)<br />
Sensor<br />
error,<br />
hot<br />
side<br />
( short<br />
circuit<br />
, breakag<br />
e,<br />
jumpers<br />
missing<br />
)<br />
Delta-T Alarm<br />
T emperat<br />
ure<br />
differe<br />
nce<br />
outside<br />
of<br />
range<br />
-10<br />
. . . + 200°C<br />
S W Temp<br />
Alarm<br />
( Cold)<br />
Tempera<br />
ture<br />
alarm,<br />
cold<br />
side<br />
( value<br />
outside<br />
of<br />
the<br />
measuri<br />
ng<br />
range)<br />
S W Temp<br />
Alarm<br />
( Hot)<br />
Tempera<br />
ture<br />
alarm,<br />
hot<br />
side<br />
( value<br />
outside<br />
of<br />
the<br />
measuri<br />
ng<br />
range)<br />
Option overflo<br />
w<br />
Relay<br />
switchi<br />
ng<br />
frequen<br />
cy<br />
exceede<br />
d or<br />
RTC<br />
daa<br />
invalid<br />
Option Alarm<br />
Program<br />
ming<br />
does<br />
not<br />
match<br />
hardwar<br />
e<br />
Overflo w Alarm<br />
Power<br />
or<br />
flow<br />
capacit<br />
y exceede<br />
d<br />
Undervo ltage<br />
Alarm<br />
Supply<br />
voltage<br />
is<br />
too<br />
low,<br />
e.<br />
g.<br />
for<br />
bus<br />
supply<br />
OvervoltageAlarmSupplyvoltageistoohigh Namur breakag<br />
e<br />
Namur<br />
pulser<br />
is<br />
faulty<br />
or<br />
broken,<br />
I<<br />
0.<br />
2 mA<br />
Serial EEprom<br />
alarm<br />
2 Faulty compone<br />
nt<br />
/ Problem<br />
s on<br />
I C-bus<br />
Backup alarm<br />
2 Faulty compone<br />
nt<br />
/ Problem<br />
s on<br />
I C-bus<br />
RAMalarmFaultycomponent EPROM/ FLASH<br />
alarm<br />
aulty<br />
compone<br />
nt<br />
M-Bus error messages<br />
The M-Bus protocol contains error messages in coded form.<br />
3.7<br />
M-Bus communications interface<br />
The CALEC ® <strong>light</strong> incorporates the standardised M-Bus interface (in<br />
conformity with EN 1434-3), featuring variable data format which<br />
enables all the parameters to be read out. The same interface can also<br />
be used to program the enabled auxiliary functions and options with the<br />
help of the Aquametro-CALTOOL and MBUSTOOL software.<br />
Bidirectional optocouplers are used to isolate the bus with the interface<br />
from the unit. The M-Bus connection is made to terminals 24 / 25,<br />
regardless of polarity.<br />
F 3171e-12<br />
The optical interface conforms electrically and mechanically with the<br />
ZVEI standard, IEC 1107 (EN61107), but it supports the M-Bus protocol<br />
in conformity with EN 1434.<br />
VD 3-171 E 10 Aquametro AG