Nominal<br />

Minimum<br />

Nominal Outside Diameter Wall Thickness Nominal Inner Min. Bend Radius Max. Pulling Weight*<br />

Size (inches) (inches) Diameter (inches) Unsupported (inches) Tension (lbs.) (lb/kft)<br />

13mm 0.625 0.055 0.500 8 210 46<br />

1/2” 0.840 0.076 0.668 10 390 85<br />

3/4” 1.050 0.095 0.840 12 605 130<br />

1” 1.315 0.120 1.055 14 950 204<br />

1 1 /4” 1.660 0.151 1.338 18 1,520 320<br />

1 1 /2” 1.900 0.173 1.533 20 1,760 416<br />

2” 2.375 0.216 1.917 26 3,105 640<br />

3 ” 3.500 0.318 2.826 48 6,740 1,386<br />

4” 4.500 0.409 3.633 60 11,145 2,295<br />

ConQuest ® Conduit Products<br />

SDR 13.5<br />

Nominal<br />

Minimum<br />

Nominal Outside Diameter Wall Thickness Nominal Inner Min. Bend Radius Max. Pulling Weight*<br />

Size (inches) (inches) Diameter (inches) Unsupported (inches) Tension (lbs.) (lb/kft)<br />

1/2” 0.840 0.062 0.696 10 320 71<br />

3/4” 1.050 0.078 0.874 12 505 111<br />

1” 1.315 0.097 1.101 14 790 169<br />

1 1 /4” 1.660 0.123 1.394 18 1,260 265<br />

1 1 /2” 1.900 0.141 1.598 20 1,455 344<br />

2 ” 2.375 0.176 2.002 26 2,580 532<br />

3” 3.500 0.259 2.951 48 5,590 1,154<br />

4” 4.500 0.333 3.794 60 9,250 1,905<br />

SCH 40<br />

Nominal<br />

Minimum<br />

Nominal Outside Diameter Wall Thickness Nominal Inner Min. Bend Radius Max. Pulling Weight*<br />

Size (inches) (inches) Diameter (inches) Unsupported (inches) Tension (lbs.) (lb/kft)<br />

3/4” 1.050 0.113 0.804 12 705 149<br />

1” 1.315 0.133 1.029 14 1,050 219<br />

1 1 /4” 1.660 0.140 1.360 18 1,420 295<br />

1 1 /2” 1.900 0.145 1.590 20 1,700 353<br />

2 ” 2.375 0.154 2.047 26 2,300 472<br />

SCH 80<br />

Nominal<br />

Minimum<br />

Nominal Outside Diameter Wall Thickness Nominal Inner Min. Bend Radius Max. Pulling Weight*<br />

Size (inches) (inches) Diameter (inches) Unsupported (inches) Tension (lbs.) (lb/kft)<br />

3/4” 1.050 0.154 0.722 12 920 189<br />

1” 1.315 0.179 0.936 14 1,360 276<br />

1 1 /4” 1.660 0.191 1.255 18 1,875 383<br />

1 1 /2” 1.900 0.200 1.476 20 2,270 465<br />

2 ” 2.375 0.218 1.913 26 3,140 645<br />

3” 3.500 0.300 2.864 48 6,395 975<br />

4” 4.500 0.337 3.786 60 9,345 1,950<br />

NOTES<br />

Standard Dimension Ratio (SDR) is the ratio between the wall thickness and the outside diameter of a specific conduit.<br />

Schedule 40 & Schedule 80 dimensions are a specific wall thickness to each conduit diameter.<br />

Other wall thicknesses are available upon request.<br />

Specifications are subject to change without notice.<br />

*Weight does not include the reel.<br />

Reel weights listed on page 24.<br />