2010 PRODUCT CATALOGUE
2010 PRODUCT CATALOGUE
2010 PRODUCT CATALOGUE
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Easy Installation<br />
Space saving<br />
Space saving by setting side Setting size<br />
by side without space in<br />
5.72 (Unit: m2)<br />
Easy wiring<br />
Transmission line:<br />
Non-polar 2-conductor transmission<br />
line prevents erroneous wiring.<br />
Transmission line<br />
Dimensions<br />
Outdoor unit goes into elevator<br />
Power supply wiring:<br />
Power supply for outdoor and<br />
indoor units is different.<br />
1,380<br />
800<br />
1,050<br />
•Outdoor unit<br />
3Ø 4W 380 - 415V 50Hz<br />
•Indoor unit:<br />
1Ø 2W 220 - 240V 50Hz<br />
1,300<br />
650<br />
(Unit : mm)<br />
1,500<br />
(Unit : mm)<br />
Outdoor unit<br />
Transmission line<br />
Transmission<br />
adaptor<br />
Central<br />
remote controller<br />
PC<br />
controller<br />
Installation space<br />
For individually<br />
10mm or more<br />
For continuous<br />
10mm or more<br />
Indoor unit<br />
FRONT<br />
SIDE<br />
300mm<br />
or more<br />
500mm<br />
or more<br />
300mm<br />
or more<br />
500mm<br />
or more<br />
h<br />
10mm or more<br />
Top air outlet<br />
L1 L2<br />
h<br />
10mm<br />
or more<br />
FRONT<br />
SIDE<br />
10mm<br />
or more<br />
Craning into place<br />
Protective boards<br />
H(1200mm)<br />
H(1200mm)<br />
10mm<br />
or more<br />
The outdoor unit can be lifted by crane<br />
and set down on the building roof.<br />
Front side<br />
intake port<br />
Back side<br />
intake port<br />
There is no height restriction for the side wall.<br />
The height(H) of front and rear wall should be less than1,200mm.<br />
If the height of wall exceeds 1,200mm by h mm, add h mm to the service<br />
space width for L1 and L2.<br />
H 1,200 : L1 500, L2 300 H 1,200 + h : L1 500 + h, L2 300 + h<br />
Four-direction pipe<br />
Four-direction piping allows a variety of<br />
installation configurations.<br />
Easy installation and pipe direction<br />
setting.<br />
1<br />
Front<br />
2<br />
Bottom<br />
4<br />
Back<br />
3<br />
Right<br />
Easy Maintenance<br />
Operating display<br />
Easy replacement<br />
By indicating the operating status and<br />
details of failures on a PCB in the<br />
outdoor unit, better service and quick<br />
and easy maintenance are possible.<br />
Operation display<br />
A pull-out plate ensures easy<br />
compressor replacement if necessary.<br />
Pump down control<br />
Pump down can be performed from the outdoor unit using the<br />
switch on the PCB.<br />
090