3.2.3 Wires and terminal lugs<br />
3-11<br />
Chapter 3 - Installation<br />
Refer to below for wires, terminal lugs, and screws used to connect the inverter power input and output.<br />
Inverter capacity<br />
Terminal<br />
screw<br />
Screw torque<br />
Wire size<br />
R(L1), S(L2), T(L3) U, V, W<br />
size<br />
kgf · cm lb · in mm 2 AWG or<br />
kcmil<br />
mm 2 AWG or<br />
kcmil<br />
5.5kW(7.5HP) M4 7.1 ~ 12.2 6.2~10.6 5.5 10 5.5 10<br />
2<br />
0<br />
0<br />
V<br />
7.5kW(10HP)<br />
11kW(15HP)<br />
15kW(20HP)<br />
18.5kW(25HP)<br />
22kW(30HP)<br />
30kW(40HP)<br />
M5<br />
M5<br />
M6<br />
M6<br />
M8<br />
M8<br />
24.5 ~ 31.8<br />
30.6 ~ 38.2<br />
61.2 ~ 91.8<br />
21.2~27.6<br />
26.6~33.2<br />
53.1~79.7<br />
8<br />
14<br />
22<br />
38<br />
38<br />
60<br />
8<br />
6<br />
4<br />
2<br />
2<br />
1/0<br />
8<br />
14<br />
22<br />
38<br />
38<br />
60<br />
8<br />
6<br />
4<br />
2<br />
2<br />
1/0<br />
5.5kW(7.5HP) M4<br />
3.5 12 3.5 12<br />
7.5Kw(10HP) M4 7.1 ~ 12.2 6.2~10.6 3.5 12 3.5 12<br />
11 kW(15HP) M4 5.5 10 5.5 10<br />
15 kW(20HP)<br />
18.5kW(25HP)<br />
M6<br />
M6<br />
30.6~38.2 26.6~33.2<br />
8<br />
14<br />
8<br />
6<br />
8<br />
14<br />
8<br />
6<br />
22~30kW<br />
(30~40HP)<br />
M8 61.2~91.8 53.1~79.7 22 4 22 4<br />
4<br />
0<br />
0<br />
V<br />
37~55kW<br />
(50~75HP)<br />
75~90kW<br />
(100~125HP)<br />
110~132Kw<br />
(150~200HP)<br />
160kW(250HP)<br />
M8<br />
M10<br />
M12<br />
M12<br />
67.3~87.5<br />
89.7~122.0<br />
182.4~215.0<br />
58.4~75.9<br />
77.9~105.9<br />
158.3~186.6<br />
38<br />
60<br />
100<br />
150<br />
2<br />
1/0<br />
4/0<br />
300<br />
38<br />
60<br />
100<br />
150<br />
2<br />
1/0<br />
4/0<br />
300<br />
220kW(300HP) M12 200 400 200 400<br />
280kW(350HP) M12<br />
250 500 250 500<br />
315kW(400HP)<br />
375kW(500HP)<br />
M12<br />
M12<br />
182.4~215.0 158.3~186.6<br />
325<br />
2×200<br />
700<br />
2×400<br />
325<br />
2×200<br />
700<br />
2×400<br />
450kW(600HP) M12 2×250 2×500 2×250 2×500<br />
* Apply the rated torque to terminal screws.<br />
* Loose screws can cause of short circuit or malfunction. Tightening the screw too much can damage the terminals and<br />
cause a short circuit or malfunction.<br />
* Use copper wires only with 600V, 75℃ ratings. For 7.5~11kW 240V type inverters, R(L1), S(L2), T(L3) and U, V, W<br />
terminals are only for use with insulated ring type connector.