31.10.2014 Views

ELRC-1 Earth Leakage Relay - Doepke UK Ltd

ELRC-1 Earth Leakage Relay - Doepke UK Ltd

ELRC-1 Earth Leakage Relay - Doepke UK Ltd

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Earth</strong> <strong>Leakage</strong> <strong>Relay</strong><br />

<strong>ELRC</strong>-1<br />

ELECTRICAL CHARACTERISTICS<br />

Auxiliary Voltage Supply<br />

Frequency<br />

Maximum Consumption<br />

Current tripping adjustment range IN<br />

Tripping time adjustment range<br />

Output: 2 change over contacts<br />

Working Temperature<br />

Storing Temperature<br />

Relative Humidity<br />

Insulation Test<br />

Standards<br />

Wiring method<br />

Terminals protection according with DIN 40050<br />

24-48V ac/dc / 110 Vac/dc - 230 - 400 Vac ± 20%<br />

50÷60 Hz<br />

3VA<br />

0,025÷0,25A K=0,1 - 0,25÷2,5A K=1 - 2,5÷25A K=10<br />

0,02 ÷ 0,5 sec. K=1 - 0,2 ÷ 5 sec. K=10<br />

5A 250V<br />

-10 + 60°C<br />

-20 + 80°C<br />

90%<br />

2,5 kV 60 sec.<br />

CEI 41-1 - IEC 255 - VDE 0664<br />

Tscrew terminals for cross section wire 2,5 mm2<br />

IP20<br />

WIRING DIAGRAM<br />

DIMENSIONS<br />

Supply<br />

Load<br />

TIPO<br />

<strong>ELRC</strong>-1/35<br />

<strong>ELRC</strong>-1/60<br />

<strong>ELRC</strong>-1/80<br />

<strong>ELRC</strong>-1/110<br />

Auxiliary device for remote control<br />

Dimensions - mm<br />

A B C D E F G H<br />

35 100 60 110 47 70 60 50<br />

60 100 60 110 47 70 60 50<br />

80 150 110 160 70 70 60 50<br />

110 150 110 160 70 70 60 50<br />

DIMENSIONS<br />

AD<br />

DESCRIPTION<br />

1) Push button for manual reset<br />

2) Signalisation lamp for presence of auxiliary supply<br />

(green led)<br />

3) Signalisation lamp for relay tripped (red led)<br />