Impaginato <strong>G4</strong> copia 30-06-2009 15:26 Pagina 7<br />

Code Version Unit. Note<br />

040021 Thecno 1 On request<br />

040022 Printer 1 On request<br />

Code Version Unit. Note<br />

040440 AS 25 W - 12 V cc. 1<br />

040441 AS 60 W - 12 V cc. 1<br />

040442 AS 100 W - 12 V cc. 1<br />

040443 AS 60 W - 24 V cc. 1<br />

DOMESTIC ROOMS<br />

Installation<br />

zone<br />

NON DOMESTIC ROOMS<br />

ZONE 2 ROOMS<br />

Rooms with high probability of leakage<br />

ZONE 1 ROOMS<br />

Rooms with high probability of leakage<br />

Data Logger THECNO<br />

Can be connected at the series<br />

SGM 895 probes.<br />

It allows to check the working<br />

process of the SGM 895 probes,<br />

to self certifyng and print<br />

your own job.<br />

Stored data: · serial number<br />

· working process<br />

· interruption numbers<br />

· alarm numbers<br />

· working days before revision<br />

· calibration numbers<br />

AS Switching series<br />

power supplier<br />

Usable to keep in charge the<br />

back up batteries and to control<br />

the 12/24 V solenoid valves with<br />

our gas leak command center.<br />

Power supply: 230 V - 50 ÷ 60 Hz<br />

Outlet: see version<br />

Protection grade: IP 54<br />

GAS LEAKAGE DETECTORS GUIDE<br />

<strong>Gas</strong><br />

type<br />

Methane CH4 GPL<br />

Propane - Buthane<br />

Methane CH4 GPL<br />

Propane - Buthane<br />

Methane CH4 GPL<br />

Propane - Buthane<br />

Methane CH4 GPL<br />

Propane - Buthane<br />

Detector<br />

type<br />

33916 - 47916 - 48916 - 50916<br />

GS 911 K - GS 910 - CH CO<br />

Probes SG 500<br />

Centralines CX190K - BX180<br />

BX 280 - BX 444 - BX 449<br />

GS100M/300M<br />

Probes SG544 - SGM595 -<br />

SG580 - SG585<br />

Centralines BX<br />

180/280 - BX 444 - BX 449 -<br />

GS 500M/300M<br />

Probes<br />

SGM595 - SG580 - SG 585<br />

Centralines BX<br />

180/280 - BX 444 - BX 449 -<br />

GS100M/300M<br />

Probes - SG 585<br />

Acoustic and<br />

flashing alarm<br />

Power supply: see version<br />

Protection grade: IP 54<br />

Buzzer: 90 dB<br />

Code Version Unit. Note<br />

040406 SA 12 V cc. 1<br />

040408 SA 24 V cc. 1<br />

040407 SA 220 V. 1<br />

<strong>Detectors</strong> test cans<br />

Technical features:<br />

Methane: 20% of L.I.E. 80% air<br />

Propane: 20% of L.I.E. 80% air<br />

Buthane: 20% of L.I.E. 80% air<br />

Carbon oxide: 100 ppm, remaing air<br />

Carbon oxide: 300 ppm carbon oxide<br />

150 ppm Idrogen, remaining air<br />

N.B. Please specify on order<br />

phase the gas type<br />

For example: 040446/Methane<br />

Code Version Unit. Note<br />

040446 Can 1 On request<br />

040447 Spraying valve 1 On request<br />

Sensibility<br />

Within 20% of L.I.E.<br />

1° Step 10% of L.I.E.<br />

2° Step 20% of L.I.E.<br />

1° Step 10% of L.I.E.<br />

2° Step 20% of L.I.E.<br />

1° Step 10% of L.I.E.<br />

2° Step 20% of L.I.E.<br />

Response<br />

time<br />

30” Alarm<br />

Immediate 1° step<br />

Within 30” 2° step<br />

Immediate 1° step<br />

Within 30” 2° step<br />

Immediate 1° step<br />

Within 30” 2° step<br />

Protection<br />

grade<br />

IP 42<br />

Centrals IP 42<br />

Probes IP44-55<br />

<strong>Detectors</strong> IP42-55<br />

Centrals IP 42<br />

Probes IP44-55<br />

<strong>Detectors</strong> IP 55<br />

Centrals IP 42<br />

Probes DPE-EX<br />

<strong>Detectors</strong> DPE-EX<br />

<strong>G4</strong> - <strong>Gas</strong> <strong>Leak</strong> <strong>Detectors</strong> & <strong>Gas</strong> <strong>Solenoid</strong> <strong>Valves</strong><br />

ZONE 0<br />

Following EN 50054 explosives gases<br />

2003 norms<br />

The detector has to find the 100% of LIE<br />

Methane CH4 GPL<br />

Propane - Buthane<br />

Centralines BX180/280<br />

BX 444 - BX 449 - GS100M/300M<br />

Probes - SG 585<br />

1° Step 10% of L.I.E.<br />

2° Step 20% of L.I.E.<br />

Immediate 1° step<br />

Within 30” 2° step<br />

Centrals IP 42<br />

Probes DPE-EX<br />

<strong>Detectors</strong> DPE-EX<br />

DOMESTIC ROOMS<br />

Carbon Monoxide<br />

CO<br />

50916<br />

CO 922 - CH CO<br />

30 ppm<br />

50 ppm<br />

100 ppm<br />

300 ppm.<br />

120 Minutes<br />

60 Minutes<br />

10 Minutes<br />

Immediate<br />

IP 42<br />

NON DOMESTIC ROOMS<br />

Carbon Monoxide<br />

CO<br />

Centralines BX180/280<br />

BX 444 - BX 449 - GS100M/300M<br />

Probes CO 100 - CO 265<br />

30 ppm<br />

50 ppm<br />

100 ppm<br />

300 ppm.<br />

120 Minutes<br />

60 Minutes<br />

10 Minutes<br />

Immediate<br />

Centrals IP 42<br />

Probes IP44-55<br />

<strong>Detectors</strong> IP42-55<br />