05.11.2012 Views

Vacuum Circuit Breakers

Vacuum Circuit Breakers

Vacuum Circuit Breakers

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

Types and ordering information<br />

7.2kV & 24kV<br />

Cradle<br />

46<br />

LVB 20 G 13 D 06 1A 2B B, C1, D1<br />

LG VCB<br />

Rated voltage<br />

06 7.2kV<br />

20 24kV<br />

LG Cradle<br />

Installation method<br />

P Fixed type<br />

E E class draw-out type<br />

F F class draw-out type<br />

G G class draw-out type<br />

M<br />

G class draw-out type<br />

+ Bushing<br />

Breaking current<br />

13 12.5kA<br />

16 16kA<br />

20 20kA<br />

25 25kA<br />

32 31.5kA<br />

40 40kA<br />

Note) In case 24kV, only<br />

both of 12.5kA,<br />

16kA, 25kA and<br />

25kA are available.<br />

Revision No.<br />

A Conventional<br />

D Pro-MEC<br />

E Pro-MEC<br />

(Minimized type)<br />

Note) E type is available for<br />

24kV enclosed type G<br />

class only. (Distance<br />

between phase and<br />

phase is 210mm.)<br />

Breaking current<br />

8 8kA<br />

13 12.5kA<br />

16 16kA<br />

20 20kA<br />

25 25kA<br />

32 31.5kA<br />

40 40kA<br />

Rated current<br />

06 630A<br />

12 1250A<br />

20 2000A<br />

30 3150A<br />

Note) In case 24kV, only<br />

both of 12.5kA,<br />

16kA and 25kA are<br />

available.<br />

Control voltage<br />

00 -<br />

1A DC110V<br />

1B DC220V<br />

1C DC48V<br />

1D DC24V<br />

1E DC125V<br />

Auxiliary switch<br />

00 -<br />

2B 4a4b(AMP Jack)<br />

2E 10a10b(AMP Jack)<br />

2G 4a4b(Phoenix Jack)<br />

2H 10a10b(Phoenix Jack)<br />

Note) “00”is for Earthing<br />

Truck and Dummy VCB.<br />

Accessories<br />

B Position Switch (RUN/TEST:2a2a)<br />

C1 Button Padlock (ON)<br />

C2 Button Padlock (OFF)<br />

C3 Button Padlock (ON/OFF)<br />

D1 Button Cover (ON)<br />

D2 Button Cover (OFF)<br />

D3 Button Cover (ON/OFF)<br />

Button padlock (ON)<br />

E<br />

+ Button cover (OFF)<br />

Button padlock (OFF)<br />

F<br />

+ Button cover (ON)<br />

G Key Lock<br />

Secondary Trip Coil<br />

H<br />

(Preparatory trip coil)<br />

J Fire-endurable wiring cable ass’y<br />

K Opening Latch Checking Switch<br />

P1 Dummy VCB (AMP Jack)<br />

P2 Dummy VCB ( Phoenix Jack)<br />

Q Earthing Truck (Lower)<br />

R Earthing Truck (Upper)<br />

S Pad Lock (G class)<br />

T Enclosed type, Tulip contact<br />

Optional accessories<br />

N CTD (Capacitor Trip Device)<br />

O Rectifier<br />

LCL 20 G 13 D 06 A, B, C<br />

Rated voltage<br />

06 7.2kV<br />

20 24kV<br />

Installation method<br />

E E class draw-out type<br />

F F class draw-out type<br />

G G class draw-out type<br />

Revision No.<br />

A Conventional<br />

D Pro-MEC<br />

E<br />

Pro-MEC<br />

(Minimized type)<br />

Note) E type is available for<br />

24kV enclosed type G<br />

class only. (Distance<br />

between phase and<br />

phase is 210mm.)<br />

Rated current<br />

04 400A<br />

06 630A<br />

12 1250A<br />

20 2000A<br />

30 3150A<br />

Accessories<br />

A MOC (3a4b)+ TOC (3a4b)<br />

B Earthing Switch<br />

Earthing Switch Position Switch +<br />

C<br />

Earthing Switch Locking coil<br />

T Enclosed type, Tulip contact<br />

Note) ‘A’, ‘B’, ‘C’ is for ‘G’ class only

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!