<strong>Insulation</strong> testing<br />

Generator trans<strong>for</strong>mer<br />

Testing according to IEC 60076, IEC60836<br />

Power frequency 1 minute<br />

Phase to ground<br />

Phase to phase<br />

Across <strong>the</strong> isolating distance<br />

Lightning impulse 1.2/50 micro seconds<br />

Phase to earth and between phases<br />

Across isolating distance<br />

60 kV<br />

60 kV<br />

80 kV<br />

170 kV (8.9 pu phase-ground)<br />

195 kV<br />

Plat<strong>for</strong>m trans<strong>for</strong>mer<br />

Power frequency 1 minute 50 Hz 275 kV/70 kV<br />

50 seconds 120 Hz 272 kV/66 kV<br />

Lightning impulse IEC 60076 1.2/50 micro seconds<br />

HV <strong>wind</strong>ing Phase-Ground<br />

645 kV (8.58 pu)<br />

LV <strong>wind</strong>ing Phase-Ground<br />

196 kV<br />

© Vattenfall AB<br />