MCCB's WITH INTEGRATED EARTH LEAKAGE PROTECTION<br />
3-Pole ZE125-NJ ZS125-NJ ZS125-GJ ZE250-NJ ZS250-NJ ZS250-GJ<br />
4-Pole ZE125-NJ4 ZS125-NJ4 ZS125-GJ4 ZE250-NJ4 ZS250-NJ4<br />
ZS250-GJ4<br />
Current<br />
020A (12.5-20)<br />
Rating<br />
In<br />
032A (20-32)<br />
050A (32-50)<br />
063A (40-63)<br />
240-525VAC Suitable for<br />
Single Phase installation<br />
100A (63-100)<br />
125A (80-125)<br />
AC Breaking Capacity Icu 400V/415V 25kA<br />
525V 8kA<br />
Protection<br />
Earth Leakage 30mA - 3A<br />
Thermal 0.63-1 x In<br />
Magnetic Fixed 10-12 x In<br />
Dimensions see CB E125<br />
020A (12.5-20)<br />
032A (20-32)<br />
050A (32-50)<br />
063A (40-63)<br />
100A (63-100)<br />
125A (80-125)<br />
36kA<br />
22kA<br />
30mA - 3A<br />
0.63-1 x In<br />
10-12 x In<br />
S125<br />
020A (12.5-20)<br />
032A (20-32)<br />
050A (32-50)<br />
063A (40-63)<br />
100A (63-100)<br />
125A (80-125)<br />
65kA<br />
25kA<br />
30mA - 3A<br />
0.63-1 x In<br />
10-12 x In<br />
S125<br />
250A<br />
(160-250)<br />
25kA<br />
10kA<br />
30mA - 3A<br />
0.63-1 x In<br />
10-13 x In<br />
E250<br />
250A<br />
(160-250)<br />
36kA<br />
25kA<br />
30mA - 3A<br />
0.63-1 x In<br />
10-13 x In<br />
S250<br />
250A<br />
(160-250)<br />
65kA<br />
25kA<br />
30mA - 3A<br />
0.63-1 x In<br />
10-13 x In<br />
S250<br />
MCCB'S with Intergral Earth LEAKAGE & Remote Trip & Alarm Feature<br />
Adjustable Undervoltage Feature Selectable 50% or 70%<br />
3-Pole ZE125-NJ ZI ZS125-NJ ZI ZS125-GJ ZI ZE250-NJ ZP ZS250-NJ ZP ZS250-GJ ZP<br />
4-Pole ZE125-NJ4 ZI ZS125-NJ4 ZI ZS125-GJ4 ZI ZE250-NJ4 ZP ZS250-NJ4 ZP ZS250-GJ4 ZP<br />
Current<br />
Rating<br />
In<br />
020A (12.5-20)<br />
032A (20-32)<br />
050A (32-50)<br />
020A (12.5-20)<br />
032A (20-32)<br />
050A (32-50)<br />
020A (12.5-20)<br />
032A (20-32)<br />
050A (32-50)<br />
250A<br />
(160-250)<br />
250A<br />
(160-250)<br />
250A<br />
(160-250)<br />
AC Breaking Capacity Icu 400V/415V<br />
525V<br />
063A (40-63)<br />
100A (63-100)<br />
125A (80-125)<br />
25kA<br />
8kA<br />
063A (40-63)<br />
100A (63-100)<br />
125A (80-125)<br />
36kA<br />
22kA<br />
063A (40-63)<br />
100A (63-100)<br />
125A (80-125)<br />
65kA<br />
25kA<br />
25kA<br />
10kA<br />
36kA<br />
25kA<br />
65kA<br />
25kA<br />
Protection<br />
Earth Leakage<br />
Thermal<br />
Magnetic Fixed<br />
30mA - 3A<br />
0.63-1 x In<br />
10-12 x In<br />
30mA - 3A<br />
0.63-1 x In<br />
10-12 x In<br />
30mA - 3A<br />
0.63-1 x In<br />
10-12 x In<br />
30mA - 3A<br />
0.63-1 x In<br />
10-13 x In<br />
30mA - 3A<br />
0.63-1 x In<br />
10-13 x In<br />
30mA - 3A<br />
0.63-1 x In<br />
10-13 x In<br />
Dimensions see CB E125<br />
S125<br />
S125<br />
E250<br />
S250<br />
S250<br />
Note: This range can only accommodate one alarm and two auxillary contact blocks, no shunts or UVTs can be fitted.<br />
MCCB's WITH INTEGRATED EARTH LEAKAGE PROTECTION<br />
Voltage presence LED<br />
Trip indicator<br />
Type A tripping for greatest<br />
accuracy of protection.<br />
Test button<br />
Selectivity: 30mA, 100mA,<br />
300mA, 500mA, 1A or 3A<br />
Adjustable time delay:<br />
60,200, 400 or 700ms<br />
For Accessories see page 6 & 7<br />
NOTE: No shunt or UVT's can be fitted. Only 2 x AUX & 1 x AL contact blocks<br />
12<br />
TS