MCCB's WITH INTEGRATED EARTH LEAKAGE PROTECTION<br />

3-Pole ZE125-NJ ZS125-NJ ZS125-GJ ZE250-NJ ZS250-NJ ZS250-GJ<br />

4-Pole ZE125-NJ4 ZS125-NJ4 ZS125-GJ4 ZE250-NJ4 ZS250-NJ4<br />

ZS250-GJ4<br />

Current<br />

020A (12.5-20)<br />

Rating<br />

In<br />

032A (20-32)<br />

050A (32-50)<br />

063A (40-63)<br />

240-525VAC Suitable for<br />

Single Phase installation<br />

100A (63-100)<br />

125A (80-125)<br />

AC Breaking Capacity Icu 400V/415V 25kA<br />

525V 8kA<br />

Protection<br />

Earth Leakage 30mA - 3A<br />

Thermal 0.63-1 x In<br />

Magnetic Fixed 10-12 x In<br />

Dimensions see CB E125<br />

020A (12.5-20)<br />

032A (20-32)<br />

050A (32-50)<br />

063A (40-63)<br />

100A (63-100)<br />

125A (80-125)<br />

36kA<br />

22kA<br />

30mA - 3A<br />

0.63-1 x In<br />

10-12 x In<br />

S125<br />

020A (12.5-20)<br />

032A (20-32)<br />

050A (32-50)<br />

063A (40-63)<br />

100A (63-100)<br />

125A (80-125)<br />

65kA<br />

25kA<br />

30mA - 3A<br />

0.63-1 x In<br />

10-12 x In<br />

S125<br />

250A<br />

(160-250)<br />

25kA<br />

10kA<br />

30mA - 3A<br />

0.63-1 x In<br />

10-13 x In<br />

E250<br />

250A<br />

(160-250)<br />

36kA<br />

25kA<br />

30mA - 3A<br />

0.63-1 x In<br />

10-13 x In<br />

S250<br />

250A<br />

(160-250)<br />

65kA<br />

25kA<br />

30mA - 3A<br />

0.63-1 x In<br />

10-13 x In<br />

S250<br />

MCCB'S with Intergral Earth LEAKAGE & Remote Trip & Alarm Feature<br />

Adjustable Undervoltage Feature Selectable 50% or 70%<br />

3-Pole ZE125-NJ ZI ZS125-NJ ZI ZS125-GJ ZI ZE250-NJ ZP ZS250-NJ ZP ZS250-GJ ZP<br />

4-Pole ZE125-NJ4 ZI ZS125-NJ4 ZI ZS125-GJ4 ZI ZE250-NJ4 ZP ZS250-NJ4 ZP ZS250-GJ4 ZP<br />

Current<br />

Rating<br />

In<br />

020A (12.5-20)<br />

032A (20-32)<br />

050A (32-50)<br />

020A (12.5-20)<br />

032A (20-32)<br />

050A (32-50)<br />

020A (12.5-20)<br />

032A (20-32)<br />

050A (32-50)<br />

250A<br />

(160-250)<br />

250A<br />

(160-250)<br />

250A<br />

(160-250)<br />

AC Breaking Capacity Icu 400V/415V<br />

525V<br />

063A (40-63)<br />

100A (63-100)<br />

125A (80-125)<br />

25kA<br />

8kA<br />

063A (40-63)<br />

100A (63-100)<br />

125A (80-125)<br />

36kA<br />

22kA<br />

063A (40-63)<br />

100A (63-100)<br />

125A (80-125)<br />

65kA<br />

25kA<br />

25kA<br />

10kA<br />

36kA<br />

25kA<br />

65kA<br />

25kA<br />

Protection<br />

Earth Leakage<br />

Thermal<br />

Magnetic Fixed<br />

30mA - 3A<br />

0.63-1 x In<br />

10-12 x In<br />

30mA - 3A<br />

0.63-1 x In<br />

10-12 x In<br />

30mA - 3A<br />

0.63-1 x In<br />

10-12 x In<br />

30mA - 3A<br />

0.63-1 x In<br />

10-13 x In<br />

30mA - 3A<br />

0.63-1 x In<br />

10-13 x In<br />

30mA - 3A<br />

0.63-1 x In<br />

10-13 x In<br />

Dimensions see CB E125<br />

S125<br />

S125<br />

E250<br />

S250<br />

S250<br />

Note: This range can only accommodate one alarm and two auxillary contact blocks, no shunts or UVTs can be fitted.<br />

MCCB's WITH INTEGRATED EARTH LEAKAGE PROTECTION<br />

Voltage presence LED<br />

Trip indicator<br />

Type A tripping for greatest<br />

accuracy of protection.<br />

Test button<br />

Selectivity: 30mA, 100mA,<br />

300mA, 500mA, 1A or 3A<br />

Adjustable time delay:<br />

60,200, 400 or 700ms<br />

For Accessories see page 6 & 7<br />

NOTE: No shunt or UVT's can be fitted. Only 2 x AUX & 1 x AL contact blocks<br />