Designer’s Guide / SYNC Boiler<br />
Reminder: the flow rates and other values listed on the preceding page are for each heat<br />
exchanger. When combined in common water piping, the flow rates will double. Increase pipe<br />
size accordingly. Use 2-1/2” minimum common manifold pipe size.<br />
ADDITIONAL CIRCULATOR PUMP SPECIFICATIONS<br />
1. Maximum operating pressure for the pump must exceed system operating pressure.<br />
2. Maximum water temperature should not exceed the nameplate rating.<br />
3. Cast iron circulators may be used in closed loop systems.<br />
Important<br />
THE BOILER PUMP MUST BE A CONTINUOUS SPEED PUMP THAT KEEPS A CONSTANT FLOW THROUGH<br />
THE BOILER.<br />
WATER FLOW<br />
Is the minimum planned flow rate for the system loop below that of the<br />
minimum allowable flow rate through the boiler<br />
The lowest potential System Loop Flow Rate MUST be ~10% greater than the<br />
Boiler Loop flow rate.<br />