Designer’s Guide / SYNC Boiler<br />

Reminder: the flow rates and other values listed on the preceding page are for each heat<br />

exchanger. When combined in common water piping, the flow rates will double. Increase pipe<br />

size accordingly. Use 2-1/2” minimum common manifold pipe size.<br />

ADDITIONAL CIRCULATOR PUMP SPECIFICATIONS<br />

1. Maximum operating pressure for the pump must exceed system operating pressure.<br />

2. Maximum water temperature should not exceed the nameplate rating.<br />

3. Cast iron circulators may be used in closed loop systems.<br />

Important<br />

THE BOILER PUMP MUST BE A CONTINUOUS SPEED PUMP THAT KEEPS A CONSTANT FLOW THROUGH<br />

THE BOILER.<br />

WATER FLOW<br />

Is the minimum planned flow rate for the system loop below that of the<br />

minimum allowable flow rate through the boiler<br />

The lowest potential System Loop Flow Rate MUST be ~10% greater than the<br />

Boiler Loop flow rate.<br />