01.01.2015 Views

Polytrauma Rehabilitation Center Design Guide - Office of ...

Polytrauma Rehabilitation Center Design Guide - Office of ...

Polytrauma Rehabilitation Center Design Guide - Office of ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Polytrauma</strong> <strong>Rehabilitation</strong> <strong>Center</strong> <strong>Design</strong> <strong>Guide</strong> May, 2008<br />

Inpatient Unit<br />

2.6.3. Nurse Station - Option 1<br />

Function:<br />

Nurse Station - Option 1 provides for a decentralized nursing model via a corridor niche with direct<br />

observation into two paired patient rooms. Shared wall is the patient headwall for both rooms. <strong>Design</strong><br />

considerations include type <strong>of</strong> equipment (computers, etc.), charting and filing to be done at satellite stations<br />

and whether such is to be part <strong>of</strong> the niche or portable. Square footage shown is for one satellite station<br />

serving two patient rooms. For a 12 bed unit with all standard rooms this total should be multiplied by six (6).<br />

In addition, a separate staff workroom for centralized functions and patient consultations / privacy should be<br />

provided.<br />

Note: Where VA standard items are shown, non-institutional & sustainable options should<br />

be considered if feasible.<br />

Space Requirement:<br />

100 NSF [9.29 NSM]<br />

Architectural:<br />

Floor Finish:<br />

Vinyl Composition Tile<br />

Base:<br />

RB<br />

Wall Finish:<br />

Gypsum Wallboard<br />

Ceiling:<br />

Gypsum Wallboard, Acoustical Tile<br />

Ceiling Height:<br />

9’-0” w/ lower s<strong>of</strong>fit<br />

Noise (STC Rating):<br />

NA<br />

Slab Depression:<br />

None<br />

Special Construction: None<br />

Hardware: 23 (If doors are needed)<br />

Doors:<br />

None<br />

Windows:<br />

View window with integral blinds or switchable glazing<br />

HVAC:<br />

Individual Room<br />

Temperature Control: 75° in summer 70° in winter with 5° dead-band as stipulated in ASHRHE<br />

90.1 - 2007<br />

Min. Air Changes/Hour: 4 AC/H<br />

Min. % Outside Air: 25%<br />

Pressure:<br />

N/A<br />

Noise Criteria: NC 40<br />

Individual Room Temperature: Required<br />

Electrical:<br />

Lighting Levels:<br />

Gen. Illum:<br />

Task Illum:<br />

Over Bed:<br />

Emergency Egress:<br />

Emergency Power:<br />

Medical Gases:<br />

Night Lights:<br />

Vanity Light:<br />

One Receptacle<br />

per PBPU:<br />

Nurse Call:<br />

Inpatient Unit<br />

2x2 parabolic fluorescent<br />

Dimmable fluorescent downlight<br />

N/A<br />

1fc Ave.<br />

No<br />

No<br />

N/A<br />

N/A<br />

Reporting station optional<br />

2-41<br />

<strong>Office</strong> <strong>of</strong> Construction<br />

& Facilities Management