<strong>Polytrauma</strong> <strong>Rehabilitation</strong> <strong>Center</strong> <strong>Design</strong> <strong>Guide</strong> May, 2008<br />
Inpatient Unit<br />
2.6.3. Nurse Station - Option 1<br />
Function:<br />
Nurse Station - Option 1 provides for a decentralized nursing model via a corridor niche with direct<br />
observation into two paired patient rooms. Shared wall is the patient headwall for both rooms. <strong>Design</strong><br />
considerations include type <strong>of</strong> equipment (computers, etc.), charting and filing to be done at satellite stations<br />
and whether such is to be part <strong>of</strong> the niche or portable. Square footage shown is for one satellite station<br />
serving two patient rooms. For a 12 bed unit with all standard rooms this total should be multiplied by six (6).<br />
In addition, a separate staff workroom for centralized functions and patient consultations / privacy should be<br />
provided.<br />
Note: Where VA standard items are shown, non-institutional & sustainable options should<br />
be considered if feasible.<br />
Space Requirement:<br />
100 NSF [9.29 NSM]<br />
Architectural:<br />
Floor Finish:<br />
Vinyl Composition Tile<br />
Base:<br />
RB<br />
Wall Finish:<br />
Gypsum Wallboard<br />
Ceiling:<br />
Gypsum Wallboard, Acoustical Tile<br />
Ceiling Height:<br />
9’-0” w/ lower s<strong>of</strong>fit<br />
Noise (STC Rating):<br />
NA<br />
Slab Depression:<br />
None<br />
Special Construction: None<br />
Hardware: 23 (If doors are needed)<br />
Doors:<br />
None<br />
Windows:<br />
View window with integral blinds or switchable glazing<br />
HVAC:<br />
Individual Room<br />
Temperature Control: 75° in summer 70° in winter with 5° dead-band as stipulated in ASHRHE<br />
90.1 - 2007<br />
Min. Air Changes/Hour: 4 AC/H<br />
Min. % Outside Air: 25%<br />
Pressure:<br />
N/A<br />
Noise Criteria: NC 40<br />
Individual Room Temperature: Required<br />
Electrical:<br />
Lighting Levels:<br />
Gen. Illum:<br />
Task Illum:<br />
Over Bed:<br />
Emergency Egress:<br />
Emergency Power:<br />
Medical Gases:<br />
Night Lights:<br />
Vanity Light:<br />
One Receptacle<br />
per PBPU:<br />
Nurse Call:<br />
Inpatient Unit<br />
2x2 parabolic fluorescent<br />
Dimmable fluorescent downlight<br />
N/A<br />
1fc Ave.<br />
No<br />
No<br />
N/A<br />
N/A<br />
Reporting station optional<br />
2-41<br />
<strong>Office</strong> <strong>of</strong> Construction<br />
& Facilities Management