Wiring Diagram<br />
Troubleshooting<br />
WARNING!: High voltage! Troubleshooting this <strong>fan</strong> <strong>control</strong> board involves<br />
working with high voltage which can result in personal injury, death<br />
and/or property damage.<br />
CAUTION!: Always disconnect power by removing a fuse or opening a circuit<br />
breaker before doing continuity checks. Verify power is not present<br />
before troubleshooting.<br />
CAUTION!: Troubleshooting tasks should only be performed by those trained to<br />
install or service HVAC equipment.<br />
LEGEND:<br />
CAP Run Capacitor<br />
TRAN Transformer<br />
JW1 Jumper Wire<br />
MTR Motor, Blower<br />
MC Micro<strong>control</strong>ler<br />
FU Fuse (ATO 3-amp)<br />
HI/LO Blower Motor Speed<br />
Change Relay (DPST)<br />
HUM Humidifier Relay (SPST-NO)<br />
BLWR Blower Motor Relay (SPST-NO)<br />
ILK Switch, Blower Door Interlock (SPST-NO)<br />
Plug Receptacle<br />
Junction<br />
Unmarked Terminal<br />
Terminal PCB<br />
Factory Wiring (115 VAC)<br />
Factory Wiring (24 VAC)<br />
Conductor on PCB<br />
Screw Connector<br />
Equipment Ground<br />
Note 1: PL1 and 10B1 indicates 7-PIN edge connector terminations that connect to<br />
<strong>control</strong> <strong>center</strong>. Refer to unit wiring diagram for specific unit wiring from <strong>control</strong><br />
<strong>center</strong> edge connector.<br />
Symptom<br />
Continuous low speed blower<br />
Blower speed not correct<br />
No <strong>fan</strong> for heating or cooling<br />
No <strong>fan</strong> delays<br />
No <strong>fan</strong> on heat call<br />
Status LED blinking<br />
Intermittent <strong>fan</strong> operation<br />
Remedy<br />
• Check for open fuse<br />
• Check for open limit<br />
• Check for 24 VAC at R and C terminals<br />
• Check if JW1 is cut<br />
• Check edge connector slot 1 and slot 5; with no<br />
power applied and the edge connector removed,<br />
there should be continuity between edge<br />
connector slot 1 and slot 5<br />
• Check if R18 is cut<br />
• Check wiring of LO and HI terminals<br />
• Check for 24 VAC at SEC1 and SEC2<br />
• Verify test pins are not shorted<br />
• Check for 24 VAC at R and C terminals<br />
• Check for 24 VAC at SEC1 and SEC2<br />
• Check edge connector slot 3 and slot 6; with no<br />
power applied and the edge connector removed,<br />
there should be continuity between edge<br />
connector slot 3 and slot 6<br />
• Status LED blinks when 24 VAC is applied to<br />
SEC1 and SEC2; there are no fault flash codes<br />
for this <strong>control</strong><br />
• Check for constant 24 VAC at R and C terminals<br />
• Bypass thermostat and test operation of <strong>fan</strong><br />
<strong>control</strong>; with no power applied, remove wires<br />
to thermostat; use a jumper wire to initiate a<br />
call for heat/cool blower; if operation is correct,<br />
thermostat or thermostat wire is faulty<br />
ONE-YEAR LIMITED WARRANTY<br />
The Seller warrants its products against defects in material or workmanship for a period of one (1)<br />
year from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace<br />
or issue a non-case credit for the purchase prices of the goods which are provided to be defective.<br />
The warranty and remedies set forth herein do not apply to any goods or parts thereof which have<br />
been subjected to misuse including any use or application in violation of the Seller’s instructions,<br />
neglect, tampering, improper storage, incorrect installation or servicing not performed by the Seller.<br />
In order to permit the Seller to properly administer the warranty, the Buyer shall: 1) Notify the Seller<br />
promptly of any claim, submitting date code information or any other pertinent data as requested by<br />
the Seller. 2) Permit the Seller to inspect and test the product claimed to be defective. Items claimed<br />
to be defective and are determined by Seller to be non-defective are subject to a $30.00 per hour<br />
inspection fee. This warranty constitutes the Seller’s sole liability hereunder and is in lieu of any other<br />
warranty expressed, implied or statutory. Unless otherwise stated in writing, Seller makes no warranty<br />
that the goods depicted or described herein are fit for any particular purpose.<br />
Patent No. 424,953<br />
7313 William Barry Blvd., North Syracuse, NY 13212<br />
(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276<br />
www.icm<strong>control</strong>s.com<br />
LIAF083-1