Wiring Diagram<br />

Troubleshooting<br />

WARNING!: High voltage! Troubleshooting this <strong>fan</strong> <strong>control</strong> board involves<br />

working with high voltage which can result in personal injury, death<br />

and/or property damage.<br />

CAUTION!: Always disconnect power by removing a fuse or opening a circuit<br />

breaker before doing continuity checks. Verify power is not present<br />

before troubleshooting.<br />

CAUTION!: Troubleshooting tasks should only be performed by those trained to<br />

install or service HVAC equipment.<br />

LEGEND:<br />

CAP Run Capacitor<br />

TRAN Transformer<br />

JW1 Jumper Wire<br />

MTR Motor, Blower<br />

MC Micro<strong>control</strong>ler<br />

FU Fuse (ATO 3-amp)<br />

HI/LO Blower Motor Speed<br />

Change Relay (DPST)<br />

HUM Humidifier Relay (SPST-NO)<br />

BLWR Blower Motor Relay (SPST-NO)<br />

ILK Switch, Blower Door Interlock (SPST-NO)<br />

Plug Receptacle<br />

Junction<br />

Unmarked Terminal<br />

Terminal PCB<br />

Factory Wiring (115 VAC)<br />

Factory Wiring (24 VAC)<br />

Conductor on PCB<br />

Screw Connector<br />

Equipment Ground<br />

Note 1: PL1 and 10B1 indicates 7-PIN edge connector terminations that connect to<br />

<strong>control</strong> <strong>center</strong>. Refer to unit wiring diagram for specific unit wiring from <strong>control</strong><br />

<strong>center</strong> edge connector.<br />

Symptom<br />

Continuous low speed blower<br />

Blower speed not correct<br />

No <strong>fan</strong> for heating or cooling<br />

No <strong>fan</strong> delays<br />

No <strong>fan</strong> on heat call<br />

Status LED blinking<br />

Intermittent <strong>fan</strong> operation<br />

Remedy<br />

• Check for open fuse<br />

• Check for open limit<br />

• Check for 24 VAC at R and C terminals<br />

• Check if JW1 is cut<br />

• Check edge connector slot 1 and slot 5; with no<br />

power applied and the edge connector removed,<br />

there should be continuity between edge<br />

connector slot 1 and slot 5<br />

• Check if R18 is cut<br />

• Check wiring of LO and HI terminals<br />

• Check for 24 VAC at SEC1 and SEC2<br />

• Verify test pins are not shorted<br />

• Check for 24 VAC at R and C terminals<br />

• Check for 24 VAC at SEC1 and SEC2<br />

• Check edge connector slot 3 and slot 6; with no<br />

power applied and the edge connector removed,<br />

there should be continuity between edge<br />

connector slot 3 and slot 6<br />

• Status LED blinks when 24 VAC is applied to<br />

SEC1 and SEC2; there are no fault flash codes<br />

for this <strong>control</strong><br />

• Check for constant 24 VAC at R and C terminals<br />

• Bypass thermostat and test operation of <strong>fan</strong><br />

<strong>control</strong>; with no power applied, remove wires<br />

to thermostat; use a jumper wire to initiate a<br />

call for heat/cool blower; if operation is correct,<br />

thermostat or thermostat wire is faulty<br />

ONE-YEAR LIMITED WARRANTY<br />

The Seller warrants its products against defects in material or workmanship for a period of one (1)<br />

year from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace<br />

or issue a non-case credit for the purchase prices of the goods which are provided to be defective.<br />

The warranty and remedies set forth herein do not apply to any goods or parts thereof which have<br />

been subjected to misuse including any use or application in violation of the Seller’s instructions,<br />

neglect, tampering, improper storage, incorrect installation or servicing not performed by the Seller.<br />

In order to permit the Seller to properly administer the warranty, the Buyer shall: 1) Notify the Seller<br />

promptly of any claim, submitting date code information or any other pertinent data as requested by<br />

the Seller. 2) Permit the Seller to inspect and test the product claimed to be defective. Items claimed<br />

to be defective and are determined by Seller to be non-defective are subject to a $30.00 per hour<br />

inspection fee. This warranty constitutes the Seller’s sole liability hereunder and is in lieu of any other<br />

warranty expressed, implied or statutory. Unless otherwise stated in writing, Seller makes no warranty<br />

that the goods depicted or described herein are fit for any particular purpose.<br />

Patent No. 424,953<br />

7313 William Barry Blvd., North Syracuse, NY 13212<br />

(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276<br />

www.icm<strong>control</strong>s.com<br />

LIAF083-1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!