Find this product online at www.eland.co.uk | Electrical <strong>Cable</strong> | Rubber Flexible <strong>Cable</strong><br />

Voltage Drop (per ampere per metre)<br />

Conductor<br />

Cross<br />

Sectional<br />

Area<br />

mm²<br />

1 Two<br />

Core or 2<br />

Single Core<br />

<strong>Cable</strong>s DC<br />

mV/A/m<br />

Two Core <strong>Cable</strong><br />

Single Phase AC<br />

mV/A/m<br />

1 Three Core, Four Core or<br />

Five Core <strong>Cable</strong><br />

Three Phase AC<br />

mV/A/m<br />

2 Single Core <strong>Cable</strong>s Touching<br />

Single Phase AC*<br />

mV/A/m<br />

1 2 3 4 5<br />

1.00 - - - -<br />

1.50 30.6 30.6 26.5 26.50<br />

2.50 19.0 19.0 16.4 16.40<br />

4.00 13.0 13.0 11.0 10.20<br />

6.00 8.4 8.4 7.3 6.75<br />

10.00 5.0 5.0 4.3 4.00<br />

16.00 3.1 3.1 2.7 2.52<br />

r x z r x z r x z<br />

25.00 2.000 2.00 0.175 2.00 1.700 0.150 1.700 - - -<br />

35.00 1.420 - - - 1.200 0.150 1.200 1.420 0.210 1.430<br />

50.00 0.990 - - - 0.900 0.145 0.910 0.990 0.210 1.010<br />

70.00 0.700 - - - 0.610 0.140 0.630 0.700 0.200 0.720<br />

95.00 0.530 - - - 0.460 0.135 0.480 0.530 0.195 0.560<br />

120.00 0.410 - - - 0.360 0.135 0.390 0.410 0.190 0.460<br />

150.00 0.330 - - - 0.290 0.130 0.320 0.330 0.190 0.380<br />

185.00 0.270 - - - 0.240 0.130 0.270 0.270 0.190 0.330<br />

240.00 0.210 - - - 0.185 0.130 0.220 0.210 0.185 0.280<br />

300.00 0.165 - - - 0.145 0.125 0.195 0.170 0.180 0.250<br />

400.00 0.125 - - - - - - 0.130 0.175 0.220<br />

630.00 0.073 - - - - - - 0.084 0.170 0.190<br />

Conductor operating temperature: 85ºC<br />

1. The voltage drop figures given above are based on a conductor operating temperature of 85ºC and are therefore not accurate when the operating temperature<br />

is in excess of 85ºC.<br />

2. * A larger voltage drop will result if the cables are spaced.<br />

The above table is in accordance with Table 4H2B of the 16th Edition of IEE Wiring Regulations.<br />

For cables having conductors of 16mm 2 or less cross-sectional area their inductances can be ignored and<br />

(mV/A/m)r values only are tabulated. For cables having conductors greater than 16mm 2 , cross-sectional area<br />

the impedance values are given as (mV/A/m)z, together with the resistive component (mV/A/m)r and the reactive component (mV/A/m)x.<br />

The above paragraph is extracted from Appendix 4 of the 16th Edition of IEE Wiring Regulations.<br />

The information contained within this datasheet is for guidance only. When selecting accessories such as cleats, glands, etc please note that actual cable<br />

dimensions may vary due to manufacturing tolerances.<br />

sales@eland.co.uk www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700<br />

Page 5 of 5