Distribution panel system<br />
Combination sets (without devices)<br />
■ The combination set simplifies stock keeping and offers many combination<br />
possibilities for the panels builder.<br />
■ Combination sets 1 or 2 panel wide can be fitted above, between or<br />
below the distribu tion board panels.<br />
■ Combinations of combination sets and distribution board panels must<br />
have the same overall height as the cabinets in which they are installed.<br />
■ When two panels are assembled one above the other, 1 panel wide<br />
panels must be mounted above 1 panel wide panels, and 2 panel wide<br />
panels above 2 panel wide panels.<br />
ED61SA/ ED62SA<br />
The combination sets ED61S and ED62S have a 5-pole busbar<br />
system, 250 A, and are plugged into the distribution board panel<br />
from above or below. By fitting another Cu bar 12 x 5 mm<br />
(per conductor) (ZX101 or ZX102) it is possible to upgrade the<br />
busbar systems to 355 A. Busbar spacing 40 mm.<br />
Busbar connection terminals must be ordered separately.<br />
1 panel 2 panel<br />
wide wide<br />
Busbar<br />
connector<br />
Height 300 300<br />
Grid units 2 2<br />
Type ED61SA ED62SA ZX91<br />
Ord.no.F 37810 37811 39091<br />
ED71SA/ ED72SA<br />
The design of the combination sets ED71S and ED72S corresponds<br />
to the previous example, but they are installed between distribution<br />
board panels. By fitting another Cu bar 12 x 5 mm (per conductor)<br />
(ZX101 or ZX102) it is possible to upgrade the busbar systems<br />
to 355 A. Busbar spacing 40 mm.<br />
Busbar connection terminals must be ordered separately.<br />
Height 300 300<br />
Grid units 2 2<br />
Type ED71SA ED72SA ZX91<br />
Ord.no.F 37812 37813 39091<br />
ED55A/ED56A<br />
ED 55A<br />
ED 56A<br />
Prepared for DO and D fuse bases. With busbar system 3x 250 A<br />
(Cu 12 x 5). Busbar spacing 60 mm. Attachment at the top or bottom<br />
on the distribution board panel. Usable installation width for fuse<br />
base ED55 – 160 mm and ED56 – 410 mm. Cover with cut-out .<br />
Busbar connection terminals must be ordered separately.<br />
Maximum incoming line connection is 35 mm 2 .<br />
Height 300 300<br />
Grid units 2 2<br />
Type ED55A ED56A ZX110<br />
Ord.no.F 37808 37809 39110<br />
ED91SA/ ED92SA<br />
When busbars are installed and a lot of space is required for<br />
incoming or outgoing lines, or additional terminals need to be<br />
mounted, then the ED91SA or ED92SA, with a steplessly adjustable<br />
DIN rail for terminals, is ideal. By fitting another Cu bar 12 x 5 mm<br />
(per conductor) (ZX101 or ZX102) it is possible to upgrade the<br />
busbar systems to 355 A).<br />
Height 450 450<br />
Grid units 3 3<br />
Type ED91SA ED92SA ZX91<br />
Ord.no.F 37816 37817 39091<br />
07<br />
M<br />
M<br />
ED61MA/ ED62MA<br />
The combination sets ED61MA and ED62MA have a mounting plate,<br />
the depth of which is steplessly adjustable, for fitting extremely deep<br />
devices. These sets are plugged into the distribution board panel at<br />
the top or bottom. Maximum installation depth between mounting<br />
plate and cover is 178 mm (consider cabinet depth).<br />
ED61KA/ ED62KA<br />
The combination sets ED61KA and ED62KA with recessed DIN rails<br />
are primarily used to provide a generous terminal compartment and<br />
can be plugged into distribution board panels at the top or bottom.<br />
Terminal compartment 300 mm. Suitable for terminals up to 95 mm 2 .<br />
Use ZK90P2 insulating pieces in order to fit DIN rails with double<br />
insulation. Use the deep-mounting brackets ED33P2 in order to fit<br />
DIN rails to the rear.<br />
ED91KA/ ED92KA<br />
The combination sets ED91KA and ED92KA with recessed DIN rails<br />
are primarily used to provide a generous terminal compartment and<br />
can be plugged into distribution board panels at the top or bottom.<br />
Terminal compartment 450 mm. Suitable for terminals up to 95 mm 2 .<br />
Use ZK90P2 insulating pieces in order to fit DIN rails with double<br />
insulation. Use the deep-mounting brackets ED33P2 in order to fit<br />
DIN rails to the rear.<br />
Height 300 300<br />
Grid units 2 2<br />
Type ED61MA ED62MA<br />
Ord.no.F 37820 37821<br />
Height 300 300<br />
Grid units 2 2<br />
Type ED61KA ED62KA<br />
Ord.no.F 37822 37823<br />
Height 450 450<br />
Grid units 3 3<br />
Type ED91KA ED92KA<br />
Ord.no.F 37824 37825<br />
><br />
For busbar connection terminals, see page 7-62<br />
> For insulating pieces for DIN rails, see page 7-51<br />
> For deep-mounting brackets, see page 7-48<br />
F 2CPX0*****R9999 7-61