electrode and a known earth. One test should be<br />

made for every 2 square metres of flooring. The test<br />

may not be reliable if made within 24 hours of the<br />

flooring being laid or cleaned.<br />

5.8.5 Testing to a Grid<br />

The procedure of always testing the same points “on<br />

a grid” is not recommended. The whole floor should<br />

meet the specifıcation, not just selected points.<br />

To ensure continual performance of the whole floor,<br />

it should be periodically tested at random points.<br />

5.8.6 Test Results<br />

5.9 STATIC CONTROL SYSTEMS<br />

In many instances, a <strong>Polyflor</strong> ESD floorcovering is<br />

suffıcient to give the necessary control, but in highly<br />

static-sensitive areas, additional precautions may be<br />

necessary. These include:<br />

Dissipative clothing and footwear<br />

Wrist and heel straps<br />

Special work stations<br />

Dissipative packaging and sealing<br />

Ionisers and humidity controllers<br />

<strong>Polyflor</strong> ESD <strong>floorcoverings</strong> are manufactured to<br />

specific levels of conductance and are tested, prior<br />

to despatch, in laboratory conditions.<br />

On-site testing not only takes into account the<br />

floorcovering but also the adhesive, the subfloor and<br />

the environment. When installed and tested in<br />

accordance with the instructions laid down by<br />

<strong>Polyflor</strong> and detailed in this manual, the electrical<br />

resistance should be as follows:<br />

EARTH TEST RESULTS<br />

MINIMUM AVERAGE MAXIMUM AVERAGE<br />

Static Dissipative 1 x 10 6 ohms 1 x 10 9 ohms<br />

Electrostatic Conductive 5 x 10 4 ohms 2 x 10 6 ohms<br />

Conductive ROF Zero ohms 5 x 10 4 ohms<br />

The Customer Technical Support Department offers,<br />

for a fee, a fınished installation testing service – to<br />

ensure that the whole installation meets the<br />

specifıcation requirements. A Certificate of<br />

Conformance is issued on completion. We recommend<br />

that you discuss your testing requirements with our<br />

Customer Technical Support team, to ascertain staff<br />

availability etc.<br />