Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SD-821<br />
Date of Issue: 15/01/2013<br />
Issue Number: 5.3<br />
Page 5 of 5<br />
Connections:<br />
1. Fault Output Common<br />
2. Fault Output Normally Closed*<br />
3. <strong>Smoke</strong> Detection Output Common<br />
4. <strong>Smoke</strong> Detection Output Normally Closed*<br />
5. Supply +24Vac/dc, ±20%<br />
6. Supply 0V<br />
1 2 3 4 5 6<br />
COM NC COM NC +IN GND<br />
RELAY<br />
OUT<br />
RELAY<br />
OUT<br />
SUPPLY<br />
IN<br />
* See alarm conditions on page 4<br />
TEST<br />
Test & Reset<br />
button<br />
LED<br />
Self-Test, Failure Mode & Manual Reset:<br />
The output of the SD-821 can be manually overridden, to check integrity of the field wiring.<br />
Press the PCB mounted button for no more than 4 seconds, otherwise it change the reset mode function. In test mode both<br />
relay outputs will open, the external led will be yellow and the internal LED red.<br />
The external LED will flash red if the detector fails.<br />
Manual reset button<br />
Whilst every effort has been made to ensure the accuracy of this specification, <strong>Sontay</strong> cannot accept responsibility for damage, injury,<br />
loss or expense from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.<br />
Tel: +44 (0)1732 861200. - E-mail: sales@sontay.com. - Web: www.sontay.com.<br />
© 2012 <strong>Sontay</strong> Limited. All rights reserved