SPECIFICATIONS<br />

Applications<br />

Evaporating Ranges: High Temperature: -10°F to +55°F (-12.2°C to +12.8°C)<br />

Med./Comm. Temperature: -5°F to +40°F (-20.6°C to +4.4°C)<br />

Low (Vapor Injection) Temp: -40°F to +5°F (-40°C to -15.0°C)<br />

Ambient Operating Temp:<br />

+80°F (+26.6°C) to +110°F (+43.3°C)<br />

Materials<br />

Base Plate:<br />

Physical Properties<br />

Steel, Hot Rolled and Painted or Cold Rolled Galvanized G90U; 16 Ga.<br />

Refrigerant/Oil: R404A/R507, R407C R22, R12<br />

Polyolester (POE)<br />

Synthetic Alkylate (AB)<br />

Fan Guard:<br />

Fan Blade:<br />

Fan Motor:<br />

Condenser:<br />

Wire<br />

Aluminum<br />

Permanent Split Capacitor (PSC)<br />

Copper Tube and Aluminum Fin<br />

Dimensions: Vary by model - see pages 58-59<br />

Connection Type: Vary by model - see pages 49-51<br />

Condensing Unit RelEASE VARIANT Codes<br />

Air Fan<br />

Cooled<br />

Receiver<br />

Tank<br />

Air Cooled Condensing Units<br />

XA Standard Unit •<br />

XB Std. Unit W/Receiver Tank • •<br />

XC Std. Unit W/Receiver Tank & BX Cable • • •<br />

XD Std. Unit W/BX Cable • •<br />

XE,XF,XK Physical Design Variant (Conduit) • • •<br />

XG,XH,XJ,XL,XP Physical Design Variant (Standard) • •<br />

XM Advanced Commercial Design • • • •<br />

XN Advanced Commercial Design • • •<br />

BX Cable<br />

DIMENSIONS<br />

See Item No.<br />

/ (BOM)*<br />

*Note: See Item No./Bill of Material (BOM) must be referred to in order to determine other features not represented in the model nomenclature or<br />

release varient codes.<br />

Width<br />

Length<br />

Accumulator<br />

Height<br />

Large Reciprocating<br />

LARGE RECIPROCATING MODEL NOMENCLATURE<br />

AWA 2 490 Z XD XG<br />

Family & Generation<br />

AW, AV, AG, AH Compressor Series<br />

Application Range<br />

4 High +10°F to +55°F (-12.2°C to +12.8°C)<br />

7, 9 Medium/Comm. -5°F to +40°F (-20.6°C to +4.4°C)<br />

2 Low -40°F to +5°F (-40.0°C to -15.0°C)<br />

Capacity<br />

First number is total digits, the remainder is capacity in Btu/h.<br />

This example 9000 Btu/h capacity.<br />

Refrigerant<br />

A = R12 C = R407C E = R22 Z = R404A/R507<br />

Release Variant<br />

Voltage/Frequency/Phase<br />

XD 208-230/60/1; 200/50/1<br />

XN 208-230/60/1; 200-220/50/1<br />

XT 200-230/60/3; 200-220/50/3<br />

XG 460/60/3; 380-420/50/3<br />

XF 208-230/60/3; 200-240/50/3<br />