VAMP 321 - featuresApplicationFault in the cable termination will be tripped onlight only criteria trough T2 of VAMP 321.Fault in the cable termination or currenttranformer will be tripped on light only criteriatrough T2 upstream.Fault in the bus bar will be tripped on light &current criteria trough T1. Should the CB fail tooperate a circuit breaker failure protection CBFPtrips upstream breaker via T3.Possible fault in the outgoing feeder is tripped byT1 contact of the VAMP 321 and simultaneouslythrough output of VAM I/O unit<strong>Schneider</strong> <strong>Electric</strong> - Division - Name – Date19