www.usa.siemens.com/techtopics<strong>TechTopics</strong> <strong>No</strong>. <strong>92</strong><strong>Heat</strong> <strong>generation</strong> <strong>estimation</strong> <strong>for</strong> SIMOVAC non-arc-resistant andSIMOVAC-AR arc-resistant medium-voltage controllers<strong>Siemens</strong> is often asked to provide estimated heat <strong>generation</strong>data <strong>for</strong> our equipment. This issue of <strong>TechTopics</strong> providesin<strong>for</strong>mation that allows calculation of approximate heatgenerated by the SIMOVAC non-arc-resistant andSIMOVAC-AR arc-resistant medium-voltage controllerequipment under assumed loading conditions.The heat <strong>generation</strong> data given in the table <strong>for</strong> motorcontrollers is on the basis of operation at 1.0 service factor,and assumes that each controller includes a 0.75 kVA controlpower trans<strong>for</strong>mer that is only lightly loaded when the motoris running. The current value <strong>for</strong> motor controllers is thecurrent typical <strong>for</strong> a machine using the fuse size shown.For trans<strong>for</strong>mer feeders with class E fuses installed in serieswith a class E controller, it is assumed that the continuouscurrent in amperes is in the range of 70 percent to 80percent of the E-rating of the fuse. For load-interrupterswitches (LIS) with fuses, fuse current is also assumed to bein the range of 70 percent to 80 percent of the fuse E-rating.As with motor controllers, the current used is consideredrepresentative of the current <strong>for</strong> a trans<strong>for</strong>mer protected bythe fuse size shown.For applications which differ from these assumptions,convert the heat <strong>generation</strong> shown <strong>for</strong> the typical currents tothat <strong>for</strong> the specific application by the ratio of the squares ofthe currents.For the main bus, the data assumes operation at full-ratedcontinuous current.To estimate the heat generated under actual loadingconditions, determine the component heat <strong>generation</strong> <strong>for</strong>each of the components indicated in the table, withadjustments if necessary <strong>for</strong> differing currents. For simplicity,assume that main bus loading in each vertical section isequal to the total estimated load of the controller lineup, andadjust the heat generated <strong>for</strong> each vertical section by thesquare of the percentage of total estimated load to ratedmain bus current. Space heater load should be assumed tobe continuous.Answers <strong>for</strong> infrastructure and cities.


Approximate heat <strong>generation</strong> (in watts) <strong>for</strong> SIMOVAC non-arcresistantand SIMOVAC-AR arc-resistant medium-voltage controllersComponentsizeContactor 400 AFuse sizeTypical fullloadamperes(FLA) 1Full-voltagenon-reversing(FVNR)Full-voltagereversing (FVR)2R 27 A 43 W3R 40 A 57 W4R 60 A 88 W6R 83 A 118 A9R 121 A 181 W12R 151 A 228 W18R 241 A 451 W24R 343 A 6<strong>92</strong> W15E 11 A 22 W20E 14 A 24 W25E 18 A 27 W30E 21 A 30 W40E 28 A 43 W50E 35 A 46 W65E 46 A 59 W80E 56 A 70 W100E 72 A 87 W125E 88 A 104 W150E 105 A 120 W175E 130 A 167 W200E 140 A 186 W250E 180 A 254 W300E 225 A 354 W350E 263 A 448 W400E 300 A 562 W450E 348 A 659 WApproximate heat <strong>generation</strong> (in watts) <strong>for</strong> SIMOVAC non-arcresistantand SIMOVAC-AR arc-resistant medium-voltage controllersComponentsizeContactor 720 AComponentsizeLIS switch 600 ALIS switch1,200 AComponent sizeFuse size Typical FLA 1 FVNRFVR38R 490 A 758 W48X 600 A 956 W57X 689 A 1,247 W450E 348 A 503 W600E 451 A 724 W750E 520 A 956 WFuse sizeVertical section with main busCurrentFVNRFVR450E 348 A 439 W600E 451 A 586 W750E 520 A 650 W900E 630 A 1,015 WComponent sizeSpace heaters per vertical sectionRated currentVoltage trans<strong>for</strong>mers (VTs) (set of three, includingisolation switch)FVNRFVR1,200 A 188 W2,000 A 206 W3,000 A 250 W4,000 A 413 WConversion factor: Watts x 3.415179 = BTU/hour.FVNRFVR200 W50 WFootnote:1See text <strong>for</strong> assumptions used <strong>for</strong> typical current. For motors, typicalcurrent is that <strong>for</strong> a machine typically protected by the size of fuseshown. For trans<strong>for</strong>mers, current is in the range of 70 percent to 80percent of the fuse E-rating, with specific value considered typical<strong>for</strong> a trans<strong>for</strong>mer protected by the fuse size shown.2


As an example of the method of calculation, consider alineup of controllers with six vertical sections, with thecomponents shown in this table.Component Quantity Watts/component TotalVertical section with 3,000 A main bus, with total loading 2,200 A 6 220 x (2,200/3,000)2 = 108 W 648 WControllers 400 A with 12R fuses 3 228 W 684 WController 400 A with 24R fuses 1 6<strong>92</strong> W 6<strong>92</strong> WControllers 400 A with 250E fuses 2 254 W 508 WController 720 A with 57X fuses 1 1,247 W 1,247 W600 A LIS with 450E fuses 1 439 W 439 WSpace heaters 6 200 W 1,200 WVTs, one set of three 1 50 W 50 WTotal heat <strong>generation</strong> <strong>for</strong> assembly5,468 W<strong>TechTopics</strong> are published <strong>for</strong> in<strong>for</strong>mational purposes only. <strong>Siemens</strong>makes no guaranty of accuracy or applicability to any specific customerprojects or applications, and assumes no responsibility <strong>for</strong> the readers’use of this in<strong>for</strong>mation. <strong>Siemens</strong> recommends that anyone seeking touse this in<strong>for</strong>mation in field operations consult with or verify itsapplicability through an independent qualified professional.The in<strong>for</strong>mation provided in this document contains merely generaldescriptions or characteristics of per<strong>for</strong>mance which in case of actualuse do not always apply as described or which may change as a result offurther development of the products. An obligation to provide therespective characteristics shall only exist if expressly agreed in the termsof contract.<strong>Siemens</strong> Industry, Inc.7000 <strong>Siemens</strong> RoadWendell, NC 27591Subject to change without prior notice.Order <strong>No</strong>.: IC1000-F320-A179-X-4A00All rights reserved.© 2013 <strong>Siemens</strong> Industry, Inc.For more in<strong>for</strong>mation, contact: +1 (800) 347-6659www.usa.siemens.com/techtopicsAll product designations may be trademarks or product names of<strong>Siemens</strong> AG or supplier companies whose use by third parties <strong>for</strong> theirown purposes could violate the rights of the owners.3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!