EMEX 110<br />

110, 50 & 24 volt AC/DC <strong>central</strong> <strong>power</strong> <strong>supply</strong> <strong>systems</strong><br />

Batteries<br />

Standard <strong>systems</strong> are supplied with Valve Regulated Lead Acid (VRLA) batteries,<br />

also known as ‘Sealed Lead Acid’. These batteries are sealed for their design life<br />

of 10 years.<br />

Lead Acid Planté and Nickel Cadmium batteries are available upon request,<br />

however, these batteries require a much larger physical area, and emit potentially<br />

explosive gases, meaning the battery room must be adequately ventilated in line<br />

with EN 50272 Special attention to EN 50272 should be observed.<br />

These reasons, along with the additional capital cost, generally outweigh the<br />

additional life obtained, as demonstrated below.<br />

Battery Initial cost Design life Maintenance<br />

VRLA ££ YY ££<br />

Ni-CAD £££££ YYYYY £££££<br />

Planté ££££ YYYY ££££<br />

Order Codes<br />

Rating<br />

Part no. Watts kVA Cabinet quality<br />

1 hour 110V AC/DC <strong>systems</strong><br />

ELD9100.120 1,900 2.0 1<br />

ELD9100.121 2,700 3.0 1<br />

ELD9100.122 4,000 4.0 1<br />

ELD9100.123 5,500 5.5 1<br />

3 hour 110V AC/DC <strong>systems</strong><br />

ELD9100.130 1,000 2.0 1<br />

ELD9100.131 1,600 2.0 1<br />

ELD9100.132 2,000 2.0 1<br />

ELD9100.133 2,700 3.0 1<br />

ELD9100.134 3,600 4.0 1<br />

ELD9100.135 4,860 5.5 2<br />

ELD9100.136 5,400 5.5 2<br />

15<br />

106 9AKK106354A3359 | <strong>Emergi</strong>-<strong>Lite</strong> | Product catalogue