INTRODUCTION<br />
Pentagon switchgear manufactures Outdoor type double break centre rotated Air break isolators which are <strong>structure</strong> mounted, Easy<br />
to install from 11KV to 245KV systems.<br />
The Isolator Consists of Three Phases and each phase has Three insulator posts. The fixed contacts are mounted on to the end<br />
insulator posts and tube (Moving contact) on to the centre rotating stack. All the three phases are ganged on a common operating<br />
mechanism for simultaneous closing and opening operation.It is suitable for direct connection to over head supply lines.<br />
TYPE OF ISOLATORS<br />
MOVING AND FIXED CONTACTS:<br />
The fixed contacts are made up of hard drawn electrolytic high conductivity copper strips and silver plated. The contacts are designed<br />
with “Reverse Loop” jaw controlled by powerful springs for achieving high contact pressure after the moving contacts are fully closed.<br />
The reverse loop is adopted to ensure maximum dependability under short circuit condition.<br />
The moving contacts are made up of hard drawn electrolytic high conductivity copper tubes with the ends are silver plated. The tube<br />
rotates freely on the insulator posts and the contact pressure is developed by its axial rotation and this is achieved directly from the<br />
rotating insulator posts through a lever and thus making the construction very simple.<br />
EARTHING SWITCHES:<br />
Earthing switch can be supplied for mounting as an integral part of the isolator and these earth switches are mechanically interlocked<br />
with the main Isolator.<br />
BASE:<br />
The mounting base for each phase is robust in construction and are Hot-Dip galvanized. The outer insulator stacks and the rotating<br />
Insulator stacks are mounted on this base <strong>structure</strong>.<br />
TERMINAL PADS / INSULATORS:<br />
Terminal pads of the isolator are made out of Copper / Aluminum flat projects out in the centre of the fixed contact acts to keep the insulator<br />
stacks of the isolator in line with the bus bar support.<br />
Porcelain Insulators used are of reputed makes only, meeting the requirement of cantilever strength, creepage distance and insulation<br />
levels.<br />
ARCING HORNS:<br />
OUTDOOR DOUBLE BREAK ISOLATORS<br />
33KV OUTDOOR ISOLATOR 11KV OUTDOOR ISOLATOR<br />
Range : 11KV to 245KV<br />
Installation : Outdoor<br />
Model : Double Break Centre rotated Air Break Isolator<br />
Mechanism : Banging / Turn & Twist<br />
Mounting : Horizontal<br />
Isolators are equipped with Arcing horns for breaking the magnetism current of transformers. They are of “make before” and “Break After”<br />
type and these are capable of breaking the magnetizing current of transformer up to 7 Amps.<br />
TM<br />
SALIENT FEATURES<br />
Fully type Tested as per IS-9921-1985 and IEC 60129.<br />
High contact pressure<br />
Strong wiping action of the fixed contacts jaws during closing<br />
operation to clear dirt and oxides at every operation<br />
Negligible maintenance<br />
High electrical and mechanical life<br />
More reliable<br />
Robust in construction and easy to operate<br />
TESTS :<br />
Isolators are Type tested as is 9922 in recocoginised aborories such as CPRI, ERDA, etc. Routine test are Conducted in <strong>our</strong> factory as per is 9921<br />
ISOLATOR TECHNICAL SPECIFICATION (WITH AND WITHOUT EARTH)<br />
Rated Voltage (KV) 11 22 33<br />
Maximum Operating Voltage (KV) 12 24 36<br />
Continuous Current (Amps) 200/400/800/1250 200/400/800/1250 400/800/1250<br />
Dynamic Current (KA) 20/62.5/62.5/62.5 20/62.5/62.5/62.5 62.5/62.5/62.5<br />
Short Time Withsand Current (KA) 8/25/25/25 8/25/25/25 25/25/25<br />
Magnetizing Current (KA) 7 7 7<br />
Line Charging Current (Amps) 6.3 6.3 6.3<br />
Operation Manual/Motor Manual/Motor Manual/Motor<br />
Type Banging/Turn & Twist Banging/Turn & Twist Manual/Motor<br />
Rated Voltage (KV) 110 230<br />
Mazimum OperatingVoltage (KV) 123 245<br />
Continuous Current(Amps) 800/1250 800/1250<br />
DynamicCurrent(KA) 62.5/79 62.5/100<br />
Short time Withstand Current(KA) 25/31.5 25/40<br />
Magnetizing Current(KA) 7 7<br />
Line Charging Current(KA) 6.3 6.3<br />
Operation Manual/Motor Manual/Motor<br />
Type Banging/Turn & Twist Banging/Turn & Twist<br />
NOTES :<br />
Manual Operating mechanism<br />
Hand lever operated<br />
Electro-Mechanical Interlock<br />
> B.O.M / M.O.M. Boxes will be Supplied on specific reqirement<br />
> We Manufacture other rating of isolators based on customer needs.<br />
> Insulators made by the reputed firms will be used<br />
Types of Mechanism<br />
Isolators can be supplied with the two types of mechanism.<br />
Provision for pad Locking<br />
Snap action Aux. Contacts for customers use.<br />
Motor Operating Mechanism<br />
Motor Coupled with a reduction worm gear to increase the output torque<br />
<strong>Electrical</strong> interlock between breaker and isolator<br />
Fool proof mechanical interlock between isolator and earth switch.<br />
Local / Remote control facility<br />
Manual operation in emergency<br />
Provision for pad locking<br />
Snap action Aux. Contacts for customers use<br />
DUE TO CONTINUOUS IMPROVEMENT IN DESIGN CHANGE OF PRODUCTS AND DIMENSIONS ARE INEVITABLE