INTRODUCTION<br />

Pentagon switchgear manufactures Outdoor type double break centre rotated Air break isolators which are <strong>structure</strong> mounted, Easy<br />

to install from 11KV to 245KV systems.<br />

The Isolator Consists of Three Phases and each phase has Three insulator posts. The fixed contacts are mounted on to the end<br />

insulator posts and tube (Moving contact) on to the centre rotating stack. All the three phases are ganged on a common operating<br />

mechanism for simultaneous closing and opening operation.It is suitable for direct connection to over head supply lines.<br />

TYPE OF ISOLATORS<br />

MOVING AND FIXED CONTACTS:<br />

The fixed contacts are made up of hard drawn electrolytic high conductivity copper strips and silver plated. The contacts are designed<br />

with “Reverse Loop” jaw controlled by powerful springs for achieving high contact pressure after the moving contacts are fully closed.<br />

The reverse loop is adopted to ensure maximum dependability under short circuit condition.<br />

The moving contacts are made up of hard drawn electrolytic high conductivity copper tubes with the ends are silver plated. The tube<br />

rotates freely on the insulator posts and the contact pressure is developed by its axial rotation and this is achieved directly from the<br />

rotating insulator posts through a lever and thus making the construction very simple.<br />

EARTHING SWITCHES:<br />

Earthing switch can be supplied for mounting as an integral part of the isolator and these earth switches are mechanically interlocked<br />

with the main Isolator.<br />

BASE:<br />

The mounting base for each phase is robust in construction and are Hot-Dip galvanized. The outer insulator stacks and the rotating<br />

Insulator stacks are mounted on this base <strong>structure</strong>.<br />

TERMINAL PADS / INSULATORS:<br />

Terminal pads of the isolator are made out of Copper / Aluminum flat projects out in the centre of the fixed contact acts to keep the insulator<br />

stacks of the isolator in line with the bus bar support.<br />

Porcelain Insulators used are of reputed makes only, meeting the requirement of cantilever strength, creepage distance and insulation<br />

levels.<br />

ARCING HORNS:<br />

OUTDOOR DOUBLE BREAK ISOLATORS<br />

33KV OUTDOOR ISOLATOR 11KV OUTDOOR ISOLATOR<br />

Range : 11KV to 245KV<br />

Installation : Outdoor<br />

Model : Double Break Centre rotated Air Break Isolator<br />

Mechanism : Banging / Turn & Twist<br />

Mounting : Horizontal<br />

Isolators are equipped with Arcing horns for breaking the magnetism current of transformers. They are of “make before” and “Break After”<br />

type and these are capable of breaking the magnetizing current of transformer up to 7 Amps.<br />

TM<br />

SALIENT FEATURES<br />

Fully type Tested as per IS-9921-1985 and IEC 60129.<br />

High contact pressure<br />

Strong wiping action of the fixed contacts jaws during closing<br />

operation to clear dirt and oxides at every operation<br />

Negligible maintenance<br />

High electrical and mechanical life<br />

More reliable<br />

Robust in construction and easy to operate<br />

TESTS :<br />

Isolators are Type tested as is 9922 in recocoginised aborories such as CPRI, ERDA, etc. Routine test are Conducted in <strong>our</strong> factory as per is 9921<br />

ISOLATOR TECHNICAL SPECIFICATION (WITH AND WITHOUT EARTH)<br />

Rated Voltage (KV) 11 22 33<br />

Maximum Operating Voltage (KV) 12 24 36<br />

Continuous Current (Amps) 200/400/800/1250 200/400/800/1250 400/800/1250<br />

Dynamic Current (KA) 20/62.5/62.5/62.5 20/62.5/62.5/62.5 62.5/62.5/62.5<br />

Short Time Withsand Current (KA) 8/25/25/25 8/25/25/25 25/25/25<br />

Magnetizing Current (KA) 7 7 7<br />

Line Charging Current (Amps) 6.3 6.3 6.3<br />

Operation Manual/Motor Manual/Motor Manual/Motor<br />

Type Banging/Turn & Twist Banging/Turn & Twist Manual/Motor<br />

Rated Voltage (KV) 110 230<br />

Mazimum OperatingVoltage (KV) 123 245<br />

Continuous Current(Amps) 800/1250 800/1250<br />

DynamicCurrent(KA) 62.5/79 62.5/100<br />

Short time Withstand Current(KA) 25/31.5 25/40<br />

Magnetizing Current(KA) 7 7<br />

Line Charging Current(KA) 6.3 6.3<br />

Operation Manual/Motor Manual/Motor<br />

Type Banging/Turn & Twist Banging/Turn & Twist<br />

NOTES :<br />

Manual Operating mechanism<br />

Hand lever operated<br />

Electro-Mechanical Interlock<br />

> B.O.M / M.O.M. Boxes will be Supplied on specific reqirement<br />

> We Manufacture other rating of isolators based on customer needs.<br />

> Insulators made by the reputed firms will be used<br />

Types of Mechanism<br />

Isolators can be supplied with the two types of mechanism.<br />

Provision for pad Locking<br />

Snap action Aux. Contacts for customers use.<br />

Motor Operating Mechanism<br />

Motor Coupled with a reduction worm gear to increase the output torque<br />

<strong>Electrical</strong> interlock between breaker and isolator<br />

Fool proof mechanical interlock between isolator and earth switch.<br />

Local / Remote control facility<br />

Manual operation in emergency<br />

Provision for pad locking<br />

Snap action Aux. Contacts for customers use<br />

DUE TO CONTINUOUS IMPROVEMENT IN DESIGN CHANGE OF PRODUCTS AND DIMENSIONS ARE INEVITABLE