TABLE OF CONTENTS<br />

SPACE PLANNING AND <strong>DESIGN</strong> CRITERIA<br />

NOTE: THE <strong>STANDARDS</strong> MUST BE READ IN CONJUNCTION WITH THE PROJECT SPECIFIC <strong>DESIGN</strong><br />

BRIEF. SHOULD THERE BE ANY DISCREPANCIES BETWEEN THE TWO DOCUMENTS, THEN THE<br />

PROJECT SPECIFIC <strong>DESIGN</strong> BRIEF WILL TAKE PRECEDENCE.<br />

A. CONSTRUCTION REQUIREMENTS .............................................................................................1<br />

1. CONSTRUCTION REQUIREMENTS......................................................................................................................1<br />

1.1. Model Guestrooms ......................................................................................................................1<br />

1.2. Guarantees...................................................................................................................................1<br />

1.3. Substantial Completion Documentation......................................................................................1<br />

1.4. Catalogue Cuts and Shop Drawing Requirements ......................................................................3<br />

2. PRE-OPENING, OCCUPATION AND INSTALLATION REQUIREMENTS ..................................................................4<br />

2.1. General ........................................................................................................................................4<br />

2.2. Pre-Opening Offices....................................................................................................................5<br />

2.3. Installation and Occupation Schedule .........................................................................................6<br />

3. TURNOVER PROCEDURES GUEST ROOMS & GUEST FLOORS.............................................................................7<br />

3.1. Summary .....................................................................................................................................7<br />

3.2. Model Rooms ..............................................................................................................................7<br />

3.3. Procedures...................................................................................................................................8<br />

3.4. Inspection Checklist ....................................................................................................................9<br />

3.5. Model Rooms Manual.................................................................................................................9<br />

3.6. Guest Room Inspection Checklists............................................................................................10<br />

3.7. Inspection Report – Entrance Vestibule....................................................................................11<br />

3.8. Inspection Report - Closet.........................................................................................................12<br />

3.9. Inspection Report - Bathroom ...................................................................................................13<br />

3.10. Inspection Report – Bathroom Accessories...............................................................................14<br />

3.11. Inspection Report - Guestroom .................................................................................................15<br />

3.12. Inspection Report – Fan Coil Unit ............................................................................................16<br />

3.13. Inspection Report - Plumbing....................................................................................................17<br />

3.14. Inspection Report – Heating & Ventilation...............................................................................18<br />

3.15. Inspection Report - Electrical....................................................................................................19<br />

3.16. S<strong>amp</strong>le Guest Room Punch List................................................................................................20<br />

4. OUTLINE OF RESPONSIBILITIES......................................................................................................................21<br />

5. CLASSIFICATION OF RESPONSIBILITIES ..........................................................................................................36<br />

B. PUBLIC AREAS.........................................................................................................................53<br />

1. LOBBY AND CIRCULATION.............................................................................................................................53<br />

1.1. Main Entrance and Lobby .........................................................................................................53<br />

1.2. Registration and Check-out.......................................................................................................54<br />

1.3. Concierge ..................................................................................................................................55<br />

REV. MARCH 2006 - 1 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

TABLE OF CONTENTS<br />

1.5. Doorman’s Stand.......................................................................................................................56<br />

1.6. Parking Cashier .........................................................................................................................56<br />

1.7. Luggage Room ..........................................................................................................................56<br />

1.8. Business Centre.........................................................................................................................57<br />

1.9. Public Washrooms.....................................................................................................................57<br />

1.10. Functional Diagram: Lobby and Circulation.............................................................................59<br />

2. FOOD AND BEVERAGE....................................................................................................................................60<br />

2.1. Lobby Lounge ...........................................................................................................................60<br />

2.2. Lobby Bar..................................................................................................................................60<br />

2.3. Entertainment Bar and Lounge..................................................................................................60<br />

2.4. Three Meal Restaurant ..............................................................................................................61<br />

2.5. Specialty Restaurant..................................................................................................................62<br />

2.6. Functional Diagram: Food and Beverage..................................................................................63<br />

3. RECREATIONAL AREAS ..................................................................................................................................64<br />

3.1. Health Club Reception ..............................................................................................................64<br />

3.2. Guest Lounge ............................................................................................................................64<br />

3.3. Guest Luggage Storeroom.........................................................................................................65<br />

3.4. Health Club General Requirements...........................................................................................65<br />

3.5. Locker Rooms ...........................................................................................................................65<br />

3.6. Massage Rooms.........................................................................................................................66<br />

3.7. Herbal Wrap Rooms..................................................................................................................66<br />

3.8. Wet Treatment Rooms ..............................................................................................................67<br />

3.9. Sauna Room ..............................................................................................................................67<br />

3.10. Steam Room..............................................................................................................................67<br />

3.11. Janitor’s Closet..........................................................................................................................67<br />

3.12. Swimming Pools and Whirlpool ...............................................................................................68<br />

3.13. Outdoor Recreational Facilities.................................................................................................70<br />

3.14. Indoor Recreational Facilities ...................................................................................................71<br />

3.15. Arcade & Computer Games ......................................................................................................72<br />

4. RETAIL ...................................................................................................................................................73<br />

4.1. Retail Shops ..............................................................................................................................73<br />

4.2. Beauty Salon .............................................................................................................................74<br />

5. BALLROOMS AND MEETING ROOMS................................................................................................................75<br />

5.1. General Requirements ...............................................................................................................75<br />

5.2. Ballroom Pre-function Space ....................................................................................................75<br />

5.3. Ballroom Foyer Requirements ..................................................................................................76<br />

5.4. Main Ballroom Requirements ...................................................................................................76<br />

5.5. Junior Ballroom.........................................................................................................................78<br />

5.6. Meeting Rooms .........................................................................................................................78<br />

5.7. Meeting Planners Room ...........................................................................................................79<br />

5.8. Boardrooms...............................................................................................................................79<br />

5.9. Conference Facility Storage ......................................................................................................80<br />

5.10. Functional Diagram: Conference Facilities...............................................................................81<br />

5.11. Public Areas Standards Details .................................................................................................82<br />

C. GUESTROOM AREAS .............................................................................................................109<br />

1. CORRIDORS AND CIRCULATION ...................................................................................................................109<br />

1.1. General Requirements .............................................................................................................109<br />

1.2. Elevator Lobby........................................................................................................................109<br />

1.3. Guestroom Support .................................................................................................................110<br />

1.4. Location...................................................................................................................................112<br />

REV. MARCH 2006 - 2 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

TABLE OF CONTENTS<br />

2. STANDARD GUESTROOMS ............................................................................................................................113<br />

2.1. General Requirements .............................................................................................................113<br />

2.2. Guestroom Areas.....................................................................................................................113<br />

2.3. Bedroom Area .........................................................................................................................113<br />

2.4. Bathroom Area ........................................................................................................................114<br />

2.5. Clear Ceiling heights...............................................................................................................114<br />

2.6. Entry Door...............................................................................................................................114<br />

2.7. Bathroom Doors......................................................................................................................114<br />

2.8. Connecting Doors....................................................................................................................114<br />

2.9. Closets.....................................................................................................................................115<br />

2.10. Windows .................................................................................................................................115<br />

2.11. Mechanical and Electrical .......................................................................................................116<br />

2.12. Personal Bar ............................................................................................................................117<br />

2.13. Guest Bathroom ......................................................................................................................117<br />

2.14. Water Closet............................................................................................................................118<br />

2.15. Lanais and Terraces.................................................................................................................119<br />

2.16. Barrier-Free Guestrooms.........................................................................................................119<br />

2.17. Washroom Accessories ...........................................................................................................121<br />

3. <strong>FAIRMONT</strong> GOLD GUESTROOMS, LOBBY AND LOUNGE ...............................................................................122<br />

3.1. General Requirements .............................................................................................................122<br />

3.2. Guestrooms .............................................................................................................................122<br />

3.3. Elevator Lobby and Lounge....................................................................................................122<br />

3.4. Fairmont Gold Pantry..............................................................................................................123<br />

4. SUITES .................................................................................................................................................124<br />

4.1. General Requirements .............................................................................................................124<br />

4.2. Modular Requirements............................................................................................................124<br />

4.3 Outline of Finishes and Materials ...........................................................................................125<br />

4.4. Guest Area Standards Details..................................................................................................129<br />

D. BACK-OF-HOUSE...................................................................................................................138<br />

1. OFFICE AREAS .............................................................................................................................................138<br />

1.1. Front Desk Support .................................................................................................................138<br />

1.2. Executive Office, Administration, Accounting and Security ..................................................138<br />

1.3. Human Resources....................................................................................................................139<br />

1.4. Outline of Finishes and Materials ...........................................................................................141<br />

1.5. General Requirements .............................................................................................................144<br />

1.6. Standard Lighting Fixtures.......................................................................................................148<br />

1.7. Other Offices...........................................................................................................................148<br />

1.8. Minimum Finished Ceiling Heights:.......................................................................................151<br />

1.9. Garbage Compact Room .........................................................................................................151<br />

1.10. Maintenance Areas..................................................................................................................152<br />

1.11. Paint Shop ...............................................................................................................................154<br />

1.12. Carpentry Shop........................................................................................................................154<br />

2. EMPLOYEE FACILITIES .................................................................................................................................155<br />

2.1. Employee Entrance .................................................................................................................155<br />

2.2. Security Office ........................................................................................................................155<br />

2.3. Primary Service Corridor ........................................................................................................156<br />

2.4. Men’s and Women’s Locker Rooms.......................................................................................156<br />

2.5. Employee Cafeteria.................................................................................................................157<br />

2.6. Employee Washrooms.............................................................................................................157<br />

2.7. First Aid Station ......................................................................................................................157<br />

2.8. Training Room, Staff Meeting Room......................................................................................157<br />

REV. MARCH 2006 - 3 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

TABLE OF CONTENTS<br />

2.9. Functional Diagram: Employee Facilities Layout..................................................................159<br />

3. HOUSEKEEPING, LAUNDRY & VALET ..........................................................................................................160<br />

3.1. General Requirements .............................................................................................................160<br />

3.2. Night Cleaner’s Storeroom......................................................................................................165<br />

3.3. Functional Diagram : Typical Layout for Housekeeping & Laundry.....................................166<br />

4. KITCHEN AND FOOD PREPARATION .............................................................................................................167<br />

4.1. General Requirements .............................................................................................................167<br />

4.2. Storage ....................................................................................................................................167<br />

4.3. Room Service..........................................................................................................................168<br />

4.4. Flower Work Room.................................................................................................................168<br />

5. RECEIVING AND PURCHASING......................................................................................................................169<br />

5.1. Loading Area...........................................................................................................................169<br />

5.2. Offices.....................................................................................................................................170<br />

5.3. Back-of-House Standards Details ...........................................................................................171<br />

E. SERVICES AND SYSTEMS .......................................................................................................190<br />

1. MECHANICAL...............................................................................................................................................190<br />

1.1. General Requirements .............................................................................................................190<br />

2. PLUMBING .................................................................................................................................................199<br />

2.1. General Requirements .............................................................................................................199<br />

3. ELECTRICAL.................................................................................................................................................201<br />

3.1. General Requirements .............................................................................................................201<br />

3.2. Dimming Equipment...............................................................................................................204<br />

3.3. Telephone System ...................................................................................................................205<br />

3.4. Television System ...................................................................................................................210<br />

3.5. Closed Circuit Television Security and Assistance Systems...................................................210<br />

3.6. Background Music and AV Systems.......................................................................................211<br />

4. ELEVATORS .................................................................................................................................................215<br />

4.1. General Requirements Public Elevators..................................................................................215<br />

4.2. Service Elevators.....................................................................................................................216<br />

5. ELECTRONIC LOCKING SYSTEM ...................................................................................................................217<br />

5.1. Services and Systems Standards Details .................................................................................219<br />

6. TECHNOLOGY SERVICES – DATA CABLING SPECIFICATIONS ......................................................................221<br />

6.1. Equipment Price Breakdown....................................................................................................221<br />

6.2. Summary of Project..................................................................................................................222<br />

6.3 Specification Summary ............................................................................................................224<br />

6.4 Food & Beverage Point of Sales Cabling.................................................................................226<br />

6.5 Intermediate Distribution Frame (IDF) ....................................................................................227<br />

6.6. Network Equipment .................................................................................................................228<br />

6.7. Uninterruptable Power/Dedicated Power .................................................................................228<br />

6.8 Vendor Qualification................................................................................................................228<br />

6.9. Reference Standards.................................................................................................................230<br />

6.10. Warranties ................................................................................................................................230<br />

6.11. Vendor Submittals....................................................................................................................231<br />

6.12. Testing Requirements...............................................................................................................232<br />

7. TECHNOLOGY SERVICES – PRODUCT SPECIFICATIONS...................................................................................233<br />

7.1. Cabling Overview ....................................................................................................................233<br />

7.2. Horizontal Cabling ...................................................................................................................234<br />

7.3. Cross-connect/Interconnect Systems........................................................................................235<br />

REV. MARCH 2006 - 4 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

TABLE OF CONTENTS<br />

7.4. Data Communications Outlets..................................................................................................236<br />

7.5. Optical Fiber Backbone Cabling System .................................................................................238<br />

8. TECHNOLOGY SERVICES – COMMUNICATION SYSTEMS...............................................................................240<br />

8.1. Room Specifications ................................................................................................................240<br />

F. APPENDICES...........................................................................................................................243<br />

1. HARDWARE .................................................................................................................................................243<br />

1.1. General Requirements .............................................................................................................243<br />

1.2. Submittals to Fairmont Hotels & Resorts (FHR) ....................................................................244<br />

1.3. Quality Assurance ...................................................................................................................245<br />

1.4. Approved Manufacturers.........................................................................................................245<br />

1.5 Hardware Designation.............................................................................................................247<br />

1.6. Materials and Fabrication........................................................................................................248<br />

1.7. Hinges, Butts, and Pivots ........................................................................................................248<br />

1.8. Lock Cylinder and Keying ......................................................................................................249<br />

1.9. Key Control System ................................................................................................................250<br />

1.10 Locks, Latches, and Bolts........................................................................................................250<br />

1.11 Door Trim Units......................................................................................................................251<br />

1.12. Hardware for Sliding Doors ....................................................................................................251<br />

1.13 Weatherstripping and Seals.....................................................................................................251<br />

1.14 Thresholds...............................................................................................................................251<br />

1.15 Hardware finishes....................................................................................................................251<br />

1.16 Installation...............................................................................................................................252<br />

1.17 Adjusting, Cleaning, and Demonstrating ................................................................................252<br />

1.18 Hardware Schedule .................................................................................................................253<br />

1.19 TimeLox Locking System Requirements................................................................................253<br />

2. TYPICAL HARDWARE SPECIFICATIONS (PER DOOR) BY LOCATION...............................................................257<br />

2.1. Guestroom Entry Door:...........................................................................................................257<br />

2.2. Guestroom Sliding Balcony Door: ..........................................................................................257<br />

2.3 Guestroom Balcony French Door (Pair): ................................................................................257<br />

2.4 Guestroom Bathroom Door:....................................................................................................258<br />

2.5. Guestroom Water Closet Door:...............................................................................................258<br />

2.6. Guestroom Connecting Door: .................................................................................................258<br />

2.7. Guestroom Closet Door (Single):............................................................................................259<br />

2.8. Guestroom Closet Doors (Pair): ..............................................................................................259<br />

2.9. Gold Wing Guestroom Corridor Entry Doors (Pair):..............................................................259<br />

2.10 Gold Lounge Entry Doors (Pair):............................................................................................259<br />

2.11 Maids’ Closet, Pantry, Computer Room and Secured Storage Room Doors: .........................260<br />

2.12 Janitors’ Closet Doors:............................................................................................................260<br />

2.13 Guestrooms’ Ice Machine Room Door: ..................................................................................260<br />

2.14 Hotel Main Entry Doors (Pair):...............................................................................................260<br />

2.15 Guest Safety Deposit Box Door:.............................................................................................261<br />

2.16 Public Washroom Entry Door:................................................................................................261<br />

2.17 Public Washroom Stall Door:..................................................................................................261<br />

2.18 Ballroom and Meeting Room Entry Doors – (Pair with standard exiting devices):................262<br />

2.20 Ballroom and Meeting Room Service Doors (Pair): ...............................................................262<br />

2.21 Security Office (Dutch) Door:.................................................................................................263<br />

2.22 Head Cashier’s Office Door:...................................................................................................263<br />

2.23 Back-of-House Office Doors: .................................................................................................263<br />

2.24 Housekeeping Office (Dutch) Door: .......................................................................................264<br />

2.25 Staff Main Entry Door: ...........................................................................................................264<br />

2.26 Staff Change Room Entry Door: .............................................................................................264<br />

2.27 Kitchen Entry (off Service corridor) Doors:............................................................................265<br />

REV. MARCH 2006 - 5 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

TABLE OF CONTENTS<br />

2.28 Flower Shop Door:..................................................................................................................265<br />

2.29 Health Club and Spa Treatment Entry Door: ..........................................................................265<br />

2.30 Maintenance Entry Doors (Pair): ............................................................................................266<br />

2.31 Mechanical and Electrical Entry Doors (Pair):........................................................................266<br />

3. MECHANICAL QUESTIONNAIRE....................................................................................................................267<br />

<strong>DESIGN</strong> CRITERIA ...............................................................................................................................267<br />

MAIN SYSTEMS....................................................................................................................................267<br />

4. ELECTRICAL QUESTIONNAIRE......................................................................................................................275<br />

<strong>DESIGN</strong> CRITERIA AND GENERAL REQUIREMENTS...................................................................275<br />

SYSTEMS ...............................................................................................................................................275<br />

SPECIFICATIONS..................................................................................................................................288<br />

Note:<br />

All metric conversions are approximate.<br />

REV. MARCH 2006 - 6 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

A. CONSTRUCTION REQUIREMENTS<br />

1. CONSTRUCTION REQUIREMENTS<br />

1.1. Model Guestrooms<br />

The contractor shall construct one standard guestroom and one connecting double<br />

double, together with a guestroom corridor the length of both guestrooms, complete<br />

with all finishes and shall alter and adapt them as required at no additional cost to<br />

Fairmont Hotels & Resorts. They will be constructed minimum eighteen month prior to<br />

completion of the construction of the hotel and will be constructed off-site in space<br />

provided by Owner and will remain in their completed state until equivalent rooms are<br />

complete and safely accessible for sales personnel and guests on site<br />

In addition, the contractor shall finish out complete with furniture the first available<br />

standard guestroom and double-double in the hotel. These rooms will be finished as<br />

soon as possible including temporary waterproofing, etc.<br />

1.2. Guarantees<br />

The contractor shall guarantee the building free from defects for a period of not less<br />

than one year with the exception of the items included in these Design Standards for<br />

which a longer guarantee period is specified.<br />

1.3. Substantial Completion Documentation<br />

On substantial completion Fairmont Hotels & Resorts shall be provided with the<br />

following maintenance information either bound or in electronic format:<br />

a) Two sets of architectural, mechanical, electrical and interior<br />

design “as built” drawings. Drawings shall be on CD’s with hard<br />

copies on Mylar and shall be individually bound and clipped in<br />

sets<br />

b) Two bound summaries of all sub contracts awarded on the project<br />

detailing type of sub contract to show the name, address and<br />

telephone number of each contractor<br />

c) Two-framed valve charts listing each valve by number, system<br />

and function.<br />

Three months prior to substantial completion, Fairmont Hotels & Resorts<br />

shall be provided with the following:<br />

REV. MARCH 2006 - 1 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

Substantial Completion Documentation (continued)<br />

a) Two sets of operating and maintenance manuals for all<br />

mechanical and electrical equipment, kitchen and laundry<br />

equipment and IT equipment. The manuals shall include shop<br />

drawings, descriptive and technical data, maintenance and<br />

operating procedures, wiring diagrams, spare parts list, local<br />

supplier for spare parts, local service representatives, etc.<br />

Manuals shall be assembled in 2” (5 cm) black loose-leaf binders<br />

clearly identified as to their contents.<br />

b) Two sets of manufacturers recommended maintenance<br />

procedures for all architectural and interior design materials.<br />

Each set of maintenance procedures shall be bound and indexed<br />

in a loose-leaf folder.<br />

REV. MARCH 2006 - 2 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

1.4. Catalogue Cuts and Shop Drawing Requirements<br />

Description Date Received Date Approved<br />

Fixture Cuts<br />

Plumbing fixtures and trim<br />

Light fixtures and accessories<br />

Supply and return air grilles<br />

Bathroom exhaust grilles<br />

Access panels<br />

Guestroom thermostat and ceiling fan control switch<br />

Washroom accessories<br />

Life safety accessories<br />

Sprinkler head and escutcheon<br />

Shop Drawings and Cuts<br />

Millwork drawings for doorman’s station<br />

front/cashiers/concierge and health club reception, retail<br />

and back-of-house millwork (all millwork relating to<br />

operational functions)<br />

Elevators and accessories<br />

Signage<br />

REV. MARCH 2006 - 3 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

2. PRE-OPENING, OCCUPATION AND INSTALLATION REQUIREMENTS<br />

2.1. General<br />

The construction company is required to provide the following services:<br />

a) Fairmont Hotels & Resorts will be permitted to occupy the building in<br />

stages as it is completed for the purpose of installing the FF&E<br />

The contractor will be responsible for providing Fairmont Hotels &<br />

Resorts with the following services at no cost during the FF&E<br />

installation program:<br />

i) Heating, cooling and humidity control as required to protect the<br />

FF&E<br />

ii) Temporary Lighting<br />

iii) Completely clean all areas of the building prior to hand over to<br />

Fairmont Hotels & Resorts including interior and exterior glass,<br />

all finishes, vacuuming all floors, polishing all mirrors, chrome,<br />

plumbing fixtures, etc.<br />

iv) Removing from a central point on each floor all packing cases,<br />

boxes, wrapping, off-cuts, etc. brought into the building by<br />

Fairmont Hotels & Resorts.<br />

v) Exclusive use of at least two elevators during normal working<br />

hours and exclusive use of at least three elevators outside these<br />

hours including providing all necessary elevator operators.<br />

b) All areas must be fully operational and completely free of deficiencies<br />

when turned over to Fairmont Hotels & Resorts.<br />

c) Where an area includes equipment, including specialty equipment<br />

supplied and installed under an FF&E contract, all equipment must be<br />

connected, tested, and fully operational when turned over to Fairmont<br />

Hotels & Resorts, including:<br />

i) Food and beverage equipment<br />

ii) Laundry and valet equipment<br />

iii) Computer equipment<br />

iv) Telephone equipment<br />

v) Garbage compaction equipment<br />

The construction contractor is responsible for coordinating with the<br />

specialty equipment contractors, and Fairmont Hotels & Resorts, to<br />

ensure these requirements are met.<br />

REV. MARCH 2006 - 4 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

Occupation and Installation Requirements (continued)<br />

d) Entire guestroom floors must be turned over at one time, including all<br />

guestrooms, corridors, suites, and service areas<br />

e) A fully detailed turnover program detailing individual areas will be<br />

prepared and coordinated with the construction company, nine months<br />

prior to opening and will include FF&E staging areas, FF&E access<br />

routes, security etc.<br />

f) It is the Owner’s and construction contractor’s responsibility to obtain<br />

all necessary temporary or partial occupancy certificates.<br />

2.2. Pre-Opening Offices<br />

Hotel staffing generally commences about fifteen to eighteen months prior to opening<br />

and therefore offices are required off the construction site until the administrative<br />

offices in the hotel are available for occupancy (8 weeks prior to opening). The<br />

following are the design requirements for the off-site offices which do not form part of<br />

the General Contractors work.<br />

1. Area<br />

Approximately 2,500 ft 2 , excluding circulation. If the Sales Office and the<br />

Executive Office are adjacent, separate meeting rooms, washrooms, and copy<br />

and beverage areas are not necessary.<br />

2. Office Requirements<br />

Construction and furnishing specifications will be the same as for the hotel<br />

administration offices.<br />

3. Parking<br />

Adequate well illuminated parking for both staff and visitors.<br />

4. Washroom<br />

Fully functional, code compliant washrooms are required with the hose bib<br />

adjacent to vanity for housekeeping. Provide a small janitors room (30 ft 2 ).<br />

5. Beverage Area<br />

This area requires full size fridge, sink with counter and cabinets above and<br />

below, space and electrical for coffee machine, microwave oven and<br />

dishwasher.<br />

6. Copy Room<br />

Provide a full size copying machine, counter with open storage shelving above<br />

and below, wall phone, fax machine and postage machine.<br />

REV. MARCH 2006 - 5 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

2.3. Installation and Occupation Schedule<br />

Area<br />

Weeks Required<br />

Prior to Opening<br />

Elevators #1, #2 (Service) 18<br />

Guestroom Floors: (first two floors or 15% of rooms) 18<br />

Main Entry or Truck Dock 18*<br />

Housekeeping/Laundry/Valet 12<br />

Maintenance/Engineering 12<br />

Receiving/Storage 12<br />

Staff Cafeteria 10<br />

Administration Offices 8<br />

Ballroom 8<br />

Computer Room 8<br />

Front Desk 8<br />

Front Office 8<br />

Main Kitchen 8<br />

Meeting Rooms and Circulation/Pre-Function Area 8<br />

Dining: 3 Meal Dining/Specialty Dining 7<br />

Banquet Kitchen 6<br />

Staff Locker Rooms 6<br />

Retail 6<br />

Guestroom Floors: (last two floors – no later than) 4<br />

Deli/Café 3<br />

Lobby Lounge/Bar 3<br />

Elevator (Passenger) 2<br />

Lobby 1<br />

* For access to elevators<br />

REV. MARCH 2006 - 6 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3. TURNOVER PROCEDURES GUEST ROOMS & GUEST FLOORS<br />

3.1. Summary<br />

The purpose of this document is to provide direction to the opening team in expediting<br />

and simplifying the acceptance and turnover process of guestrooms and guest floors<br />

from the contractor to the owner for the installation of FF&E. By working with the<br />

owner in this acceptance process, we can expect to reduce the time required to punch<br />

list or “snag” the rooms and give the contractor the information required to bring the<br />

guestrooms and floors up to a standard to which Fairmont Hotels & Resorts can accept.<br />

By establishing these standards and criteria with the owner and contractor well in<br />

advance of turnover, it is likely that most deficiencies can be corrected during the<br />

initial “snag”, thus allowing the owner to accept rooms that will require minimal<br />

additional work to achieve Fairmont Hotels & Resorts Standards.<br />

3.2. Model Rooms<br />

The typical acceptance process has the owner, architects and various consultants<br />

inspecting the guestrooms and guest floors and identifying deficiencies or variances to<br />

the project specifications. A “punch list” is developed and issued to the contractor for<br />

his action. This punch list becomes a road map for the contractor and once complete<br />

allows the owner to accept the owner to accept the room for the installation of FF&E.<br />

Upon completion of the FF&E installation, the owner offers the room to Fairmont<br />

Hotels & Resorts for final acceptance. The Fairmont Hotels & Resorts operations team<br />

then re-inspects the room and issues a second punch list of deficiencies which the<br />

owner must have corrected.<br />

The difficulty usually lies in that additional architectural deficiencies are identified at<br />

this stage by Fairmont Hotels & Resorts, which could have and should have been<br />

identified in the initial inspection. Typically, the contractor is reluctant to perform<br />

additional work after the owner has accepted the room. This does not include damage<br />

to the room as a result of this FF&E installation. Repair to rooms that have been<br />

damaged by the installation of FF&E is handled as a separate repair program by the<br />

owner and would be a billable repair by the contractor.<br />

Therefore, the goal of this program and its procedures is to minimize the number of<br />

architectural deficiencies identified in the second “snag”.<br />

The Model Rooms once completed and approved for their architecture, finishes, MEP<br />

and FF&E, shall serve as the standard that the contractor must meet in all guestrooms.<br />

The snagging process shall focus on variances in the guestrooms being turned over<br />

from the approved model room. Where the guestroom conforms substantially to the<br />

model rooms architecturally, the snagging process should be limited to finishes, FF&E<br />

and MEP items.<br />

REV. MARCH 2006 - 7 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.3. Procedures<br />

The Hotel’s Director of Engineering, the Fairmont Design and Construction Manager,<br />

and the FF&E Coordinator will all participate in the initial snagging of a representative<br />

s<strong>amp</strong>le of guestrooms along with the owner’s representatives, the architect, consultants<br />

and the general contractor. The purpose of this joint effort is to establish a standard for<br />

both the contractor and the owner’s representatives who will perform the majority of<br />

the snagging.<br />

It is the intention of this program that Fairmont Hotels & Resorts participate in the<br />

initial snagging of about 5% of the guestrooms.<br />

The tools required for snagging are:<br />

• Small torpedo level<br />

• Electric socket tester<br />

• Tape measure<br />

• Snag checklist<br />

• Model room manual<br />

The room will be reviewed from two perspectives.<br />

1. Architecturally<br />

Doors and Hardware<br />

Window millwork<br />

Finishes, fixtures and accessories<br />

2. Mechanical, Electric and Plumbing<br />

HVAC<br />

Plumbing fittings and fixtures<br />

Lighting and power<br />

All punch list items are to be detailed in written format according to the above<br />

categories. Each item is to be numbered and the deficiency clearly identified using<br />

reference to the model room manual as necessary.<br />

Attached is a s<strong>amp</strong>le punch list, which can serve as a model.<br />

REV. MARCH 2006 - 8 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.4. Inspection Checklist<br />

Mechanical, Electric and Plumbing:<br />

Electric<br />

• All switches and outlets functional and properly installed<br />

• All 3 way switches functional<br />

• Designated switch/outlets relationship correct<br />

• Circuit breakers all labeled<br />

• All light bulbs and fixtures are functional and properly installed<br />

Plumbing<br />

• Hardware and fixtures securely mounted and functional<br />

• Toilet operates properly<br />

• Sink and tub stopper operation<br />

• Hot and cold lines are correct and properly designated<br />

• Shower mixing valve operates properly<br />

• Hand-held shower/diverter valve functional<br />

• Tub fixtures operate properly and tub porcelain is free from defects<br />

• All drains are clear and flowing<br />

• Proper access to all shut off valves<br />

HVAC<br />

• Fan coil is fully functional<br />

• Heating<br />

• Cooling<br />

• Fan operates on all settings<br />

• Dehumidification – unit sizing as per schedule<br />

• Noise levels as per design standards<br />

• Fan coil has proper access for repairs and maintenance<br />

• Fan coil has had all PM required and new filter<br />

• Toilet exhaust is functional<br />

3.5. Model Rooms Manual<br />

Once approved, the model rooms shall serve as the reference for construction of the<br />

typical rooms. Once approved, a manual shall be produced by the architect that<br />

documents all of the requirements of the model room. This manual can be utilized as a<br />

reference in the room acceptance process. The manual shall contain:<br />

REV. MARCH 2006 - 9 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

Model Room Manual (continued)<br />

• Architectural layout<br />

• Furniture plan and specifications<br />

• Millwork detail shop drawings<br />

• Electric schematic and rough in locations<br />

• Electric equipment cut-sheets<br />

• Data/Com schematics and rough in-locations<br />

• Hardware schedules and cut-sheets<br />

• Plumbing schedules and cut-sheets<br />

• Door and window cut-sheets<br />

• Finish schedule; paint carpet, marble, etc.<br />

• Fan coil schedule and cut-sheets<br />

• Lighting fixture schedules and cut-sheets<br />

• Fire protection schematic and cut-sheets<br />

• FF & E schedule and cut-sheets, mini bar, room safe, etc.<br />

3.6. Guest Room Inspection Checklists<br />

Attached are the Guestroom Inspection and Guestroom MEP Inspection Checklists.<br />

These checklists shall be used when inspecting rooms for acceptance and through to<br />

room turnover to operations. These lists shall form the basis of any punch list.<br />

REV. MARCH 2006 - 10 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.7. Inspection Report – Entrance Vestibule<br />

<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong><br />

GUESTROOM INSPECTION REPORT<br />

HOTEL: _____________________<br />

INSPECTION DATE _________________<br />

ROOM # _____________________<br />

ENTRANCE VESTIBULE<br />

DOOR<br />

DOOR FRAME<br />

DOOR HARDWARE AND LOCK<br />

CEILING<br />

ACCESS PANEL<br />

GRILLE<br />

LIGHT FIXTURE/S<br />

WALLS<br />

SWITCH/ES<br />

BASE & MOLDINGS<br />

FLOORING/CARPET<br />

GENERAL<br />

ACCEPT REJECT REINSPECT<br />

COMMENTS: ____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

NAME: _______________________________<br />

REV. MARCH 2006 - 11 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.8. Inspection Report - Closet<br />

CLOSET<br />

DOOR<br />

DOOR FRAME<br />

DOOR HARDWARE<br />

CEILING<br />

ACCESS PANEL<br />

GRILLE<br />

LIGHT FIXTURE/S<br />

WALLS<br />

SWITCH/ES<br />

BASE & MOLDINGS<br />

FLOORING/CARPET<br />

WALL SAFE<br />

GENERAL<br />

ACCEPT REJECT REINSPECT<br />

COMMENTS: ____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

NAME: _______________________<br />

REV. MARCH 2006 - 12 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.9. Inspection Report - Bathroom<br />

BATHROOM<br />

DOOR<br />

DOOR FRAME<br />

DOOR HARDWARE<br />

CEILING<br />

ACCESS PANEL/S<br />

EXHAUST GRILLE<br />

LIGHT FIXTURE/S<br />

WALLS & WALLS COVERINGS<br />

SWITCH/ES<br />

BASE & MOLDINGS<br />

WALL TILES<br />

BATH TUB<br />

FLOOR TILES<br />

SHOWER GLASS<br />

SHOWER DRAIN<br />

GRAB BARS<br />

GENERAL<br />

ACCEPT REJECT REINSPECT<br />

COMMENTS: ____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

NAME: _______________________<br />

REV. MARCH 2006 - 13 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.10. Inspection Report – Bathroom Accessories<br />

BATHROOM ACCESSORIES<br />

BATH TUB<br />

SOAP DISH<br />

TOWEL BARS<br />

MIXING VALVE<br />

HAND HELD UNIT<br />

MIRRORS<br />

ELECTRIC OUTLETS<br />

TOILET PAPER HOLDER<br />

SPARE TOILET PAPER HOLDER<br />

ROBE HOOK<br />

SINK<br />

SINK HARDWARE<br />

VANITY TOP<br />

WATER CLOSET<br />

DRAINAGE<br />

FIXTURE AND VALVES<br />

GENERAL<br />

ACCEPT REJECT REINSPECT<br />

COMMENTS: ____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

NAME: _______________________<br />

REV. MARCH 2006 - 14 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.11. Inspection Report - Guestroom<br />

GUESTROOM<br />

CEILING<br />

WINDOWS<br />

WALLS<br />

GRILLE/S<br />

THERMOSTAT<br />

RECEPTACLES<br />

BASE & MOLDINGS<br />

FLOORS/CARPET<br />

WALLCOVERINGS<br />

CONNECTING DOORS/FRAMES/HARDWARE<br />

GENERAL<br />

ACCEPT REJECT REINSPECT<br />

COMMENTS: ____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

NAME: _______________________<br />

REV. MARCH 2006 - 15 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.12. Inspection Report – Fan Coil Unit<br />

<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong><br />

GUESTROOM INSPECTION REPORT<br />

HOTEL: _____________________<br />

INSPECTION DATE _________________<br />

ROOM # _____________________<br />

FAN COIL UNIT<br />

ACCESS PROVIDED FOR ALL VALVES<br />

ACCESS PROVIDED TO ALL CONTROLS<br />

ACCESS PROVIDED FOR FAN MOTOR MAINTENANCE<br />

AIR VENTS INSTALLED AS REQUIRED AND ACCESSIBLE<br />

CONFIRM REMOVAL OF TEMPERATURE FILTER/S<br />

COIL CLEAN AND FINS UNDAMGED<br />

GRILLES ARE LEVEL AND PLUMB<br />

INSULATION COMPLETE AND AS PER SPECIFICATIONS<br />

OPERATION OF ALL VALVES CONFIRMED<br />

DRAIN PAN CHECKED FOR PITCH AND DRAINAGE<br />

FAN SPEED(S) OPERATION CONFIRMED<br />

NOISE LEVEL OF UNIT CHECKED AGAINST SPEC (35 NTC)<br />

OPERATION OF THERMOSTATS AND CONTROLS CONFIRMED<br />

ACCEPT REJECT REINSPECT<br />

COMMENTS: ____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

NAME: _______________________________<br />

REV. MARCH 2006 - 16 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.13. Inspection Report - Plumbing<br />

PLUMBING<br />

FIXTURES MOUNTED AT PROPER HEIGHTS<br />

FIXTURES LEVEL AND SECURE<br />

FIXTURES AND TRIM AS PER APPROVED SCHEDULES<br />

WATER CLOSET FLANGE INSTALLED PROPERLY<br />

CHECK WC INSTALLATION AND WATER FEEDS (LONG BEND)<br />

CHECK FOR DAMAGE TO FIXTURES AND PROCELAIN<br />

TEST CHECK OF ALL PLUMBING AND FIXTURES<br />

ACCEPT REJECT REINSPECT<br />

COMMENTS: ____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

NAME: _______________________________<br />

REV. MARCH 2006 - 17 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.14. Inspection Report – Heating & Ventilation<br />

HEATING & VENTILATION<br />

TOILET EXHAUST BOOT INSULATED<br />

EXHAUST GRILLE SQUARE AND SECURE<br />

PROPER AIR EXHAUST AS PER <strong>DESIGN</strong><br />

ACCESS PROVIDED FOR ALL DAMPERS<br />

EXHAUST GRILLE LOCATION AS SPECIFIED<br />

CHECK DUCT WORK CONSTRUCTION & SEAL<br />

HEATING ELEMENT INSTALLED AS SPECIFIED<br />

FINS CLEAN AND FREE OF DAMAGE<br />

COVERS IN PLACE AND SECURE<br />

AUTOMATIC VALVES INSTALLED AND OPERATIONAL<br />

ACCEPT REJECT REINSPECT<br />

COMMENTS: ____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

____________________________________________________________________________<br />

NAME: _______________________________<br />

REV. MARCH 2006 - 18 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.15. Inspection Report - Electrical<br />

ELECTRICAL<br />

ALL ELECTRICAL TRIM AND FIXTURES AS PER SCHEDULES<br />

ALL TRIM AND FIXTURES INSTALLED AS PER DRAWINGS<br />

ALL ITEMS SECURE AND PROPERLY WIRED<br />

ALL ITEMS UL, CSA AND HYDRO APPROVED<br />

CONFIRM 3 WAY SWITCHING IF SPECIFIED<br />

CONFIRM OPERATION OF GFI’S IF SPECIFIED IN BATHROOM<br />

ROOM CIRCUIT BREAKERS LABELED<br />

ACCEPT REJECT REINSPECT<br />

COMMENTS: ______________________________________________________________________________________<br />

_____________________________________________________________________________________<br />

_____________________________________________________________________________________<br />

_____________________________________________________________________________________<br />

_____________________________________________________________________________________<br />

NAME: _______________________________<br />

REV. MARCH 2006 - 19 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

3.16. S<strong>amp</strong>le Guest Room Punch List<br />

Room #501<br />

Inspector ________________<br />

Date: 12/1/01<br />

Doors<br />

1. Door deadbolt not engaging freely.<br />

2. Door frames chipped.<br />

Windows<br />

1. Side window glass scratched<br />

2. Lock not engaging<br />

Millwork<br />

1. Molding chipped at bathroom door<br />

2. Millwork damaged at closet entrance<br />

Finishes<br />

1. Bath shower – missing grout<br />

2. Paint chipped on bath ceiling<br />

Electric<br />

1. Bedroom outlet not working<br />

2. Wall switch at entrance not turning on floor l<strong>amp</strong> outlet<br />

3. Circuit Breakers not labeled<br />

Plumbing<br />

1. Shower drain clogged<br />

2. Shower Gooseneck loose and not caulked<br />

3. Toilet runs continuously<br />

4. Sink stopper not working<br />

HVAC<br />

1. Fan not working on low speed<br />

2. Heat not working<br />

3. Fan rattling on high speed.<br />

REV. MARCH 2006 - 20 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CONSTRUCTION REQUIREMENTS<br />

4. OUTLINE OF RESPONSIBILITIES<br />

REV. MARCH 2006 - 21 -<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

OUTLINE OF RESPONSIBILITIES-WITH RESPECT TO<br />

<strong>FAIRMONT</strong> <strong>HOTELS</strong> STANDARD PROCEDURES<br />

RELATING TO FF&E AND OS&E ITEMS ONLY<br />

Key:<br />

A/E Architect/Engineer<br />

DCC Direct Construction Cost<br />

FC FF&E Contractor<br />

FFE FF&E Cost<br />

PA Purchasing Agent<br />

GC General Contractor<br />

IDC Interior Design Consultant<br />

FHR Fairmont Hotels & Resorts<br />

KDC Kitchen Design Consultant<br />

OSE OS&E Cost<br />

NOTE: Where two or more “key initials” are grouped together, then the first key initial becomes the ultimate responsibility for that item.<br />

Please refer to “Classification or Responsibilities” for a more comprehensive document for the entire project team.<br />

REV. MARCH 2006 22<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

1. GUESTROOMS<br />

A. Furnishings, including moveable<br />

furniture, beds and frames, loose<br />

l<strong>amp</strong>s and mirrors, wastebasket, etc.<br />

IDC/FHR IDC IDC PA FC FFE<br />

B. Artwork and Pictures<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

DCC<br />

C. Floor Coverings<br />

- carpet and pad<br />

- installation of carpet and pad<br />

- hard surfaces<br />

IDC<br />

---<br />

IDC<br />

IDC<br />

---<br />

IDC<br />

D. Loose Rugs and Pad IDC IDC IDC PA FC FFE<br />

IDC<br />

---<br />

IDC<br />

PA<br />

---<br />

GC<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

E. Window Treatments (incl. Hardware)<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

DCC<br />

F. Wall Coverings<br />

- paint<br />

- vinyl and fabric<br />

- millwork & marble<br />

IDC<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

IDC<br />

A/E / IDC<br />

A/E / IDC<br />

A/E<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

FFE<br />

DCC<br />

G. Fixed Lighting<br />

- chandeliers<br />

- chandelier assembly<br />

- blocking and backing<br />

- wall sconces and hanging fixtures<br />

- l<strong>amp</strong>ing (bulbs)<br />

IDC<br />

A/E<br />

A/E<br />

IDC<br />

FHR/IDC<br />

IDC<br />

A/E<br />

A/E<br />

IDC<br />

---<br />

IDC<br />

A/E<br />

A/E<br />

IDC<br />

---<br />

PA<br />

GC<br />

GC<br />

PA<br />

GC<br />

---<br />

GC<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

FFE<br />

DCC<br />

23<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

H. Closet (clothes rod, shelf, and robe hooks) IDC IDC A/E GC GC DCC<br />

I. Bar<br />

- mini fridge/bar<br />

- sink/faucet<br />

- counter top, shelves and refrigerator<br />

surround<br />

- conduit (rough-in)<br />

- millwork/glass/fixed mirror, blocking and<br />

backing<br />

IDC/FHR<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

IDC<br />

A/E<br />

A/E<br />

A/E<br />

IDC / A/E<br />

IDC<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

FC/GC*<br />

GC<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

DCC<br />

DCC<br />

J. Telephone System<br />

- location<br />

- equipment, including instruments,<br />

consoles, message unit, register, etc.<br />

- rough-in, wiring, backboards, etc.<br />

FHR<br />

FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

---<br />

GC<br />

GC<br />

---<br />

GC<br />

GC<br />

---<br />

DCC<br />

DCC<br />

K. TV/VCR/DVD Systems<br />

- sets<br />

- conduit, wiring and rough-in<br />

- antenna cable or dish system<br />

FHR<br />

A/E<br />

A/E<br />

---<br />

A/E<br />

A/E<br />

---<br />

A/E<br />

A/E<br />

PA<br />

GC<br />

GC<br />

FC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

L. Bed Headboard<br />

-blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

GC<br />

M. Live Plants<br />

- planters<br />

- containers (portable)<br />

- plant material<br />

IDC / A/E<br />

IDC<br />

IDC<br />

A/E<br />

---<br />

IDC<br />

A/E<br />

---<br />

IDC<br />

GC<br />

PA<br />

FHR<br />

GC<br />

FC<br />

FC<br />

DCC<br />

FFE<br />

LEASE<br />

Note: * When built-in done by GC, otherwise by FC<br />

24<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

N. Door Chimes<br />

- wiring<br />

- annunciator and button<br />

A/E<br />

IDC/FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

O. Valance<br />

- backing board<br />

- fabric and finishing<br />

A/E<br />

IDC/FHR<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

GC<br />

PA<br />

GC<br />

FC<br />

DCC<br />

FFE<br />

P. Ceiling Fan and Control IDC/FHR IDC A/E GC GC FFE<br />

Q. Room Safe<br />

- enclosure (millwork)<br />

FHR<br />

IDC<br />

IDC<br />

IDC / A/E<br />

IDC<br />

IDC / A/E<br />

PA<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

2. GUEST BATHROOMS<br />

A. Floor Coverings<br />

- hard surfaces IDC IDC / A/E IDC /A/E GC GC DCC<br />

B. Wall Coverings<br />

- paint<br />

- millwork &marble<br />

- vinyl<br />

C. Vanities<br />

- hard surface, millwork<br />

IDC<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

IDC<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

FFE<br />

IDC IDC A/E GC GC DCC<br />

D. Fixed Lighting As Guestrooms<br />

E. Telephone Systems As Guestrooms<br />

F. T.V. As Guestrooms<br />

G. Loose Accessories IDC IDC IDC PA FC FFE<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

25


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

H. Loose Mirrors<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

I. Plumbing Fixtures and Accessories IDC IDC /A/E IDC /A/E GC GC DCC<br />

J. Hardware IDC A/E A/E GC GC DCC<br />

K. Loose Rugs and Pads IDC --- IDC PA FC FFE<br />

3. GUESTROOM CORRIDORS AND ELEVATOR LOBBIES<br />

A. Furnishings, including moveable<br />

furnishings, mirrors, draperies,<br />

accessories, loose l<strong>amp</strong>s, etc.<br />

IDC IDC IDC PA FC FFE<br />

B. Floor Coverings<br />

- carpet and pad<br />

- installation of carpet and pad<br />

- hard surfaces<br />

IDC<br />

---<br />

IDC<br />

IDC<br />

---<br />

IDC<br />

C. Loose Rugs and Pads IDC IDC IDC PA FC FFE<br />

D. Millwork IDC A/E A/E GC GC DCC<br />

IDC<br />

---<br />

IDC<br />

PA<br />

---<br />

GC<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

E. Wall Coverings<br />

- paint<br />

- vinyl and fabric<br />

- millwork and marble<br />

IDC<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

FFE<br />

DCC<br />

F. Window Treatments (incl. Hardware)<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

DCC<br />

26<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

G. Fixed Lighting & Telephone Systems As Guestrooms<br />

H. Room Numbers & Signage IDC IDC IDC GC GC DCC<br />

4. GUESTROOM LEVELS SERVICE AREA<br />

A. Ice Maker<br />

-enclosure (millwork)<br />

KDC<br />

A/E<br />

KDC<br />

A/E<br />

KDC<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

B. Sinks A/E A/E A/E GC GC DCC<br />

C. Fixed Shelving A/E A/E A/E GC GC DCC<br />

D. Corner Guards & Rubbing Rails A/E A/E A/E GC GC DCC<br />

5. PUBLIC AREAS<br />

A. Moveable Furnishings<br />

Fixed Counters and Shelving<br />

Fixed Seating (framing only)<br />

IDC/FHR<br />

IDC/FHR<br />

IDC/FHR<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

GC<br />

FC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

B. Artwork and Pictures<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

DCC<br />

C. Loose Screens, Dividers IDC IDC IDC PA FC FFE<br />

D. Wall Plaques, Murals, Reliefs<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

DCC<br />

27<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

E. Wall Coverings<br />

- paint<br />

- vinyl and fabric<br />

- millwork & marble<br />

IDC<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

IDC<br />

A/E / IDC<br />

A/E / IDC<br />

A/E<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

FFE<br />

DCC<br />

F. Live Plants<br />

- planters<br />

- containers (portable)<br />

- plant material<br />

IDC / A/E<br />

IDC<br />

IDC<br />

A/E<br />

---<br />

IDC<br />

A/E<br />

---<br />

IDC<br />

GC<br />

PA<br />

FHR<br />

GC<br />

FC<br />

FC<br />

DCC<br />

FFE<br />

LEASE<br />

G. Special Ceilings<br />

- surface features<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

H. Floor Coverings<br />

- selection<br />

- installation<br />

- hard surface<br />

IDC<br />

---<br />

IDC<br />

IDC<br />

---<br />

IDC / A/E<br />

IDC<br />

---<br />

IDC / A/E<br />

PA<br />

---<br />

GC<br />

---<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

I. Loose Rugs & Pads IDC IDC IDC PA FC FFE<br />

J. Window Treatments (incl. Hardware)<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

DCC<br />

K. Fixed Lighting<br />

- chandeliers<br />

- chandelier assembly<br />

- blocking and backing<br />

- wall sconces and hanging fixtures<br />

- l<strong>amp</strong>ing (bulbs)<br />

IDC<br />

A/E<br />

A/E<br />

IDC<br />

FHR/IDC<br />

IDC<br />

A/E<br />

A/E<br />

IDC<br />

---<br />

IDC<br />

A/E<br />

A/E<br />

IDC<br />

---<br />

PA<br />

GC<br />

GC<br />

PA<br />

GC<br />

---<br />

GC<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

FFE<br />

DCC<br />

28<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

L. Signs, room names, etc:<br />

- decorative package (interior)<br />

- decorative package (exterior)<br />

IDC<br />

A/E / FHR<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

M. Exterior Lighting A/E A/E A/E GC GC DCC<br />

N. Safety Deposit Boxes<br />

- enclosure (millwork)<br />

FHR<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

O. Bars & Service Counters<br />

- sinks and equipment<br />

- rough-in<br />

KDC<br />

A/E<br />

KDC<br />

A/E<br />

KDC<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

P. Drinking Fountains A/E A/E A/E GC GC DCC<br />

Q. Ballroom Partitions IDC/FHR A/E A/E GC GC DCC<br />

R. Vitrines<br />

- built-in<br />

- blocking and backing<br />

- electrical rough-in connection<br />

IDC<br />

A/E<br />

A/E<br />

IDC<br />

A/E<br />

A/E<br />

IDC<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

DCC<br />

6. PUBLIC WASHROOMS<br />

A. Fixed Counters IDC/FHR IDC IDC GC GC DCC<br />

B. Artwork & Pictures<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

DCC<br />

29<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

C. Toilet Partitions IDC IDC / A/E IDC / A/E GC GC DCC<br />

D. Wall Plaques, Murals, Reliefs<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

DCC<br />

E. Wall Coverings<br />

- paint<br />

- vinyl and fabric<br />

- millwork & marble<br />

IDC<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

FFE<br />

DCC<br />

F. Special Ceilings<br />

- surface features<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

G. Floor Coverings<br />

- carpet and pad<br />

- installation of carpet and pad<br />

- hard surfaces<br />

IDC<br />

---<br />

IDC<br />

IDC<br />

---<br />

IDC<br />

H. Loose Rugs & Pads IDC IDC IDC PA FC FFE<br />

I. Hardware IDC A/E A/E GC GC DCC<br />

IDC<br />

---<br />

IDC<br />

PA<br />

---<br />

GC<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

30


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

J. Fixed Lighting Fixtures<br />

- wall sconces & hanging fixtures<br />

- recessed downlights & wallwash fixtures<br />

- cove & built-in fixtures<br />

- artwork lighting & spot & accent lighting<br />

- circuiting, switching, conduit & rough-in<br />

- l<strong>amp</strong>ing<br />

IDC<br />

IDC<br />

IDC<br />

IDC<br />

IDC<br />

---<br />

IDC<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

---<br />

K. Signs, Room Names, etc.<br />

- decorative packages IDC IDC IDC PA GC DCC<br />

L. Loose Accessories IDC IDC IDC PA FC FFE<br />

M. Plumbing Fixtures and Accessories IDC IDC /A/E IDC /A/E GC GC DCC<br />

7. ELEVATOR CABS<br />

IDC<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

---<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

DCC<br />

DCC<br />

DCC<br />

A. Passenger<br />

- cabs (interior finishes)<br />

- doors & frames<br />

- carpet & pad<br />

IDC<br />

IDC<br />

IDC<br />

IDC<br />

IDC<br />

IDC<br />

IDC<br />

IDC<br />

IDC<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

FFE<br />

B. Service<br />

- cab interior finishes doors & frames A/E A/E A/E GC GC DCC<br />

8. BACK OF HOUSE<br />

A. Kitchen Equipment<br />

- stainless steel counters, worktables<br />

- rough-in and hook-up<br />

- hand sinks, curbs, bases, millwork<br />

KDC<br />

KDC<br />

KDC<br />

KDC<br />

A/E<br />

A/E<br />

KDC<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

DCC<br />

31<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

B. Walk-in Refrigerator<br />

- including insulated floor<br />

KDC<br />

KDC<br />

KDC<br />

A/E<br />

KDC<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

C. Office furnishings<br />

- office equipment<br />

- office counters & fixed casework<br />

FHR<br />

FHR<br />

FHR<br />

A/E<br />

FHR<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

D. Storeroom Shelving<br />

- fixed wood, metal A/E A/E A/E GC GC DCC<br />

E. Floor Coverings<br />

- carpet and pad<br />

- installation of carpet and pad<br />

- hard surfaces<br />

IDC<br />

---<br />

IDC<br />

IDC<br />

---<br />

IDC<br />

IDC<br />

---<br />

IDC<br />

PA<br />

---<br />

GC<br />

GC<br />

GC<br />

GC<br />

FFE<br />

DCC<br />

DCC<br />

F. Wall Coverings<br />

- paint<br />

- vinyl, fabric<br />

- ceramic tile<br />

A/E / FHR<br />

A/E / FHR<br />

A/E / FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

DCC<br />

G. Window Treatments (incl. Hardware)<br />

- blocking and backing<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

IDC<br />

A/E<br />

PA<br />

GC<br />

FC<br />

GC<br />

FFE<br />

DCC<br />

H. Laundry Chute A/E A/E A/E GC GC DCC<br />

I. Laundry<br />

- equipment<br />

- millwork<br />

- rough-in & hook-up (incl. lint filters)<br />

LC<br />

LC<br />

LC<br />

LC<br />

A/E<br />

A/E<br />

LC<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

DCC<br />

32<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

9. MISCELLANEOUS EQUIPMENT<br />

A. Telephone System<br />

- location<br />

- equipment, incl. instruments, consoles,<br />

message unit<br />

- conduit, cable, backboards, etc.<br />

- circuiting, installation & termination of<br />

cable<br />

FHR<br />

FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E/FHR<br />

A/E<br />

A/E<br />

A/E<br />

---<br />

GC<br />

GC<br />

GC<br />

---<br />

GC<br />

GC<br />

GC<br />

---<br />

DCC<br />

DCC<br />

DCC<br />

B. Front Desk, Accounting, and Pointof-Sale<br />

Computer Systems and<br />

Equipment<br />

- computers, printers, etc<br />

- circuiting, installation & termination of<br />

cable<br />

- conduit and rough-in<br />

- UPS<br />

FHR<br />

FHR / A/E<br />

A/E<br />

A/E<br />

---<br />

A/E<br />

A/E<br />

A/E<br />

---<br />

A/E<br />

A/E<br />

A/E<br />

PA<br />

GC<br />

GC<br />

GC<br />

FC<br />

GC<br />

GC<br />

GC<br />

OSE<br />

DCC<br />

DCC<br />

DCC<br />

C. Closed Circuit T.V. Equipment<br />

- cameras, monitors, etc.<br />

- circuiting, conduit & rough-in<br />

A/E / FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

D. Emergency Voice Communication<br />

System<br />

- exitway speakers, emergency & fireman's<br />

telephone & interface with hotel voice<br />

communication systems<br />

- circuiting, conduit & rough-in<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

33<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

E. A/V Systems<br />

- equipment<br />

- circuiting, conduit, & rough-in<br />

A/E / FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

F. Misc. Voice Communication<br />

Systems Equipment<br />

- ballroom & meeting room PA system,<br />

pocket page, and hand-held radios<br />

- circuiting, conduit, & rough-in<br />

A/E / FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

G. Misc. Call Light and Alarm Systems<br />

Equipment<br />

- taxi call lights, hold-up alarm, exit door<br />

alarms<br />

- circuiting, conduit, & rough-in<br />

A/E / FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

H. Fire Alarm System Equipment<br />

- fireman central control station, manual<br />

alarm stations, smoke detectors, sprinkler<br />

flow switches, annunciators, alarms, etc.<br />

- circuiting, conduit, & rough-in<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

I. Dimmer Systems Equipment<br />

- circuiting, conduit & rough-in<br />

A/E / FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

J. Portable A/V Equipment FHR --- --- PA FC OSE<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

34


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong> OUTLINE OF RESPONSIBILITIES<br />

Item<br />

Design<br />

or<br />

Select<br />

Construction<br />

Drawings<br />

Construction<br />

Specifications<br />

Purchase<br />

or<br />

Provide<br />

Install<br />

Cost<br />

K. Life Safety Control Systems<br />

Equipment<br />

- smoke control devices, elevator controls,<br />

stairway door unlocking<br />

- circuiting, conduit, & rough-in<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

DCC<br />

L. T.V. System<br />

- antenna, cable services/satellite dish<br />

- in-room movie system connected to house<br />

cable<br />

- circuiting, conduit, & rough-in<br />

A/E<br />

FHR<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

A/E<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

DCC<br />

LEASE<br />

DCC<br />

35<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

5. CLASSIFICATION OF RESPONSIBILITIES<br />

GUESTROOMS<br />

BUDGET <strong>DESIGN</strong> CONTRACT<br />

DOCS<br />

PURCH.<br />

INSTALL<br />

1 LIFE SAFETY COMMUNICATION SYSTEM<br />

A EMPTY CONDUIT<br />

GC ME<br />

ME<br />

GC GC<br />

B EQUIPMENT<br />

GC ME<br />

ME<br />

GC GC<br />

2 FURNITURE<br />

A MOVABLE<br />

I<br />

I<br />

I<br />

PA PA<br />

B FIXED<br />

GC<br />

I<br />

I<br />

GC GC<br />

3 ARTWORK<br />

I<br />

I<br />

I<br />

PA PA<br />

A BLOCKING<br />

GC<br />

I<br />

A<br />

GC GC<br />

4 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I<br />

PA GC<br />

B OTHER (when defined)<br />

GC<br />

I A/I*** GC GC<br />

C BASE<br />

GC<br />

I A/I***<br />

5 CEILINGS<br />

A DRYWALL<br />

GC I/A<br />

A<br />

GC GC<br />

B PLASTER<br />

GC I/A<br />

A<br />

GC GC<br />

C OTHER<br />

GC<br />

I<br />

A<br />

GC GC<br />

6 WALL COVERINGS<br />

A VINYL<br />

GC<br />

I<br />

I<br />

PA GC<br />

B PAINT<br />

GC<br />

I<br />

I<br />

GC GC<br />

C OTHER<br />

GC<br />

I<br />

I<br />

GC GC<br />

7 CONNECTING DOOR AND SILENCER GC I***/A A GC GC<br />

8 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I<br />

PA PA<br />

b Direct Connection<br />

PA<br />

I<br />

ME<br />

PA GC**<br />

B FLUORESCENT<br />

GC I/A/ME ME<br />

GC GC<br />

C INCANDESCENT<br />

GC I/A/ME ME<br />

GC GC<br />

9 DOORS<br />

A FINISHERS<br />

GC I/A<br />

A<br />

GC GC<br />

B HARDWARE<br />

GC I/A<br />

A<br />

GC GC<br />

10 DRAPERY<br />

I<br />

I<br />

I<br />

PA PA<br />

A BLOCKING<br />

GC A/I<br />

A<br />

GC GC<br />

B WOOD SHUTTERS<br />

GC<br />

I<br />

I<br />

GC GC<br />

11 ELECTRICAL GC ME ME C GC<br />

12 LINENS O O/I O PA O<br />

13 MECHANICAL GC ME ME GC GC<br />

14 RADIO AND/OR TV<br />

A EMPTY CONDUIT<br />

GC ME<br />

ME<br />

GC GC<br />

B EQIPMENT<br />

O<br />

O<br />

O<br />

PA PA<br />

C WIRE<br />

O<br />

O<br />

O<br />

O<br />

O<br />

15 SLIDING DOOR ASSEMBLY GC I/A I/A GC GC<br />

16 SPRINKLER SYSTEM OR/<br />

GC ME/A ME/A GC GC<br />

LIFE SAFETY SYSTEM<br />

17 TELEPHONES<br />

A EMPTY CONDUIT<br />

GC ME/I ME/I GC GC<br />

B EQUIPMENT & WIRE<br />

O ME/I/O ME/I/O O<br />

O<br />

18 SMOKE DETECTOR GC ME/I ME/I GC GC<br />

19 GRAPHICS-ROOM COLLATERAL PIECE O G/O G/O O O<br />

20 BALCONY FLOORING GC A A GC GC<br />

21 CLOSET-SHELVING RODS / HOOKS GC ID/A ID/A GC GC<br />

22 BAR<br />

A CABINET AND TOP<br />

GC ID ID/A GC GC<br />

B REFRIGERATOR<br />

PA FHR ID/A PA GC<br />

23 CEILING FAN GC ID ID/ME GC GC<br />

24 ROOM SAFE PA ID ID PA PA<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

36


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH. INSTALL<br />

DOCS<br />

BATHROOM<br />

1 BATH LINEN O O/I O O O<br />

2 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I<br />

PA GC<br />

B OTHER<br />

GC I/A A/I*** GC GC<br />

3 CEILINGS<br />

A DRYWALL<br />

GC I/A<br />

A<br />

GC GC<br />

B PLASTER<br />

GC I/A<br />

A<br />

GC GC<br />

C OTHER<br />

GC I/A A/I*** GC GC<br />

4 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I<br />

PA PA<br />

b Direct Connection<br />

PA ME<br />

ME PA GC**<br />

B FLUORESCENT<br />

GC ME<br />

ME GC GC<br />

C INCANDESCENT<br />

GC ME<br />

ME GC GC<br />

5 ELECTRICAL GC ME ME GC GC<br />

6 FLOOR AND WALL TILE & BASE GC I/A A GC GC<br />

7 HARDWARE AND ACCESSORIES GC I I/A GC GC<br />

8 EXHAUST FAN GC ME/I ME GC GC<br />

9 MIRRORS<br />

GC<br />

I<br />

A<br />

GC GC<br />

A BLOCKING<br />

GC<br />

A<br />

A<br />

GC GC<br />

10 MECHANICAL GC ME ME GC GC<br />

11 SHOWER ENCLOSURE I I I PA O<br />

12 SHOWER HEAD GC I/ME ME GC GC<br />

13 SHOWER DOOR ASSEMBLY GC I/A A GC GC<br />

14 TILE GROUT GC I A GC GC<br />

15 VANITY MILLWORK GC I A/I*** GC GC<br />

16 VANITY TOP MATERIAL GC I A/I*** GC GC<br />

17 WALL<br />

A VINYL<br />

B STONE / MARBLE<br />

C OTHER<br />

18 TELEPHONES<br />

A EMPTY CONDUIT<br />

B EQUIPMENT<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

I<br />

I<br />

I<br />

ME/I<br />

ME/I/O<br />

I***<br />

I***<br />

A/I***<br />

19 GRAPHICS-ROOM COLLATERAL PIECES O G/O G/O O O<br />

20 PLUMBING FIXTURES GC ID ID/ME O O<br />

GUEST FLOOR CORRIDORS<br />

1 ARTWORK I I I PA PA<br />

2 ASH URNS<br />

A FIXED<br />

B LOOSE<br />

3 FLOORS<br />

A CARPETING<br />

B OTHER<br />

C BASE (WOOD & VINYL)<br />

4 CEILINGS<br />

A LAY-IN<br />

B SPRAY-IN<br />

C OTHER<br />

5 WALL COVERING<br />

A VINYL<br />

B PAINT<br />

C OTHER<br />

GC<br />

I<br />

I<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

ME<br />

ME/I<br />

A<br />

I<br />

I<br />

I***<br />

A/I***<br />

A<br />

A<br />

A<br />

I<br />

I<br />

A/I***<br />

PA<br />

GC<br />

GC<br />

GC<br />

O<br />

GC<br />

PA<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

O<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

37


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH. INSTALL<br />

DOCS<br />

6 DOORS<br />

A FINISHES<br />

GC<br />

I<br />

A GC GC<br />

B HARDWARE<br />

GC<br />

A/I<br />

A GC GC<br />

7 HANDRAIL / PLANTER GC I A GC GC<br />

8 ELEVATOR FOYER GC A/I A GC GC<br />

9 FIRE CABINET GC A/ME/I ME GC GC<br />

10 FIRE EXTINGUISHER GC A/ME A GC GC<br />

11 FURNITURE I I I PA PA<br />

12 MIRRORS, PICTURES, ETC.<br />

I<br />

I<br />

I<br />

PA PA<br />

A BLOCKING<br />

GC<br />

A/I<br />

A GC GC<br />

13 TELEPHONES<br />

A EMPTY CONDUIT<br />

GC ME/I<br />

ME GC GC<br />

B EQUIPMENT & WIRE<br />

O ME/I/O ME/I O<br />

O<br />

14 PLANTERS<br />

A FIXED<br />

GC A/L/LS<br />

I/A GC GC<br />

B MOVABLE<br />

I/LS L/LS<br />

I<br />

PA PA<br />

15 PLANT MATERIAL GC/LS I/LS LS GC GC<br />

16 ROOM # & DIRECTIONAL SIGNAGE I G/O/I*** G PA/G GC<br />

17 LIGHTING<br />

A DECORATIVE<br />

I<br />

I<br />

I<br />

PA PA<br />

a Direct Connection<br />

PA<br />

I<br />

ME PA GC***<br />

B FLUORESCENT<br />

GC<br />

I/A<br />

ME GC GC<br />

C INCANDESCENT<br />

GC<br />

I/A<br />

ME GC GC<br />

18 COMMUNICATION SYSTEM<br />

A EMPTY CONDUIT<br />

GC<br />

ME<br />

ME GC GC<br />

B EQUIPMENT & WIRE<br />

GC<br />

ME<br />

ME GC GC<br />

19 ELECTRICAL GC ME ME GC GC<br />

20 MECHANICAL GC ME ME GC GC<br />

ELEVATORS<br />

1 CAB INTERIOR – GUEST ELEVATORS GC I A/I GC GC<br />

2 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I<br />

PA GC<br />

B OTHER<br />

GC<br />

I<br />

I<br />

GC GC<br />

3 DOOR EXTERIOR GC I A GC GC<br />

4 DOOR FRAME AND SILL GC I/A A GC GC<br />

5 SIGNAGE & NUMBERING; PROMO. SIGNAGE O G/O/I****/A*** G PA/G G<br />

6 LIGHTING<br />

A<br />

B<br />

C<br />

DECORATIVE<br />

FLUORESCENT<br />

INCANDESCENT<br />

I<br />

GC<br />

GC<br />

I<br />

I<br />

I<br />

I<br />

ME/A<br />

ME/A<br />

7 SYSTEM (ELEVATOR) GC A A GC GC<br />

8 TELEPHONE CABINET GC I/A A GC GC<br />

MAIDS CLOSET<br />

1 ALL ACCESSORIES O O O PA O<br />

2 CEILINGS<br />

A LAY-IN<br />

B SPRAY-ON<br />

C OTHER<br />

3 LIGHTING<br />

A FLUORESCENT<br />

B INCANDESCENT<br />

4 TELEPHONES<br />

A EMPTY CONDUIT<br />

B EQUIPMENT<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

O<br />

A/I<br />

A/I<br />

A/I<br />

ME/A<br />

ME/A<br />

ME/I<br />

ME/I/O<br />

A<br />

A<br />

A<br />

ME/A<br />

ME/A<br />

ME<br />

ME/I<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

O<br />

GC**<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

O<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

38


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH. INSTALL<br />

DOCS<br />

5 WALL COVERING<br />

A VINYL<br />

GC<br />

A/I<br />

A<br />

PA GC<br />

B PAINT<br />

GC<br />

A/I<br />

A GC GC<br />

C OTHER<br />

GC<br />

A/I<br />

A GC GC<br />

6 SINK ASSEMBLY GC ME ME GC GC<br />

7 SHELVING GC A/O A GC GC<br />

8 FLOORS<br />

A<br />

B<br />

CARPETING<br />

OTHER<br />

9 ELECTRICAL GC ME ME GC GC<br />

10 MECHANICAL GC ME ME GC GC<br />

SERVICE ELEVATOR LANDINGS<br />

1 FLOORS<br />

A CARPETING<br />

B OTHER<br />

2 CEILINGS<br />

A LAY-IN<br />

B SPRAY-ON<br />

C OTHER<br />

3 WALL COVERING<br />

A VINYL<br />

B PAINT<br />

C OTHER<br />

4 LIGHTING<br />

A FLUORESCENT<br />

B INCANDESCENT<br />

I<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

A/I<br />

A/I<br />

A/I<br />

A/I<br />

A/I<br />

A/I<br />

A/I<br />

A/I<br />

A/I<br />

A/I<br />

ME/A<br />

ME/A<br />

5 LINEN CHUTE N/A<br />

6 SHELVING/NAME BOARD GC O A GC GC<br />

7 GRAPHICS AND SIGNAGE I O/A/G G PA/G G<br />

ELECTRICAL, MECHANICAL,<br />

TELEPHONE ROOM GC A/ME A/ME GC GC<br />

VENDING AREAS<br />

1 WALLS GC A/I A/I*** GC GC<br />

2 FLOORS GC A/I A/I*** GC GC<br />

3 ICE MACHINE O O K/ME* PA GC**/[A<br />

4 SINKS GC A/ME ME GC GC<br />

5 DRINK MACHINE GC O K/ME* PA GC**/PA<br />

ROUGH CARPENTRY<br />

(ALL LEVELS)<br />

GC A A GC GC<br />

EMERGENCY STAIRWELL<br />

GC A/ME A/ME GC GC<br />

ELEVATOR PENTHOUSE<br />

GC A/ME A/ME GC GC<br />

STAFF LOCKER ROOMS<br />

1 ASH URNS (FIXED) GC A A GC GC<br />

2 BENCHES<br />

A PRE-FAB<br />

B MILLWORK<br />

GC<br />

GC<br />

O<br />

A<br />

I<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

O<br />

A<br />

PA<br />

GC<br />

PA<br />

GC<br />

PA<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

39


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH. INSTALL<br />

DOCS<br />

3 CEILINGS<br />

A LAY-IN<br />

GC<br />

A<br />

A GC GC<br />

B SPRAY-ON<br />

GC<br />

A<br />

A GC GC<br />

C OTHER<br />

GC<br />

A<br />

A GC GC<br />

4 ELECTRICAL / PLUMBING GC ME ME GC GC<br />

5 DIRECTIONAL SIGNAGE I G/O G PA/G G<br />

6 LOCKERS GC A/O A GC GC<br />

7 MIRRORS<br />

GC<br />

A<br />

A GC GC<br />

A BLOCKING<br />

GC<br />

A<br />

A GC GC<br />

8 PAINT OR TILE WALLS GC A/I A GC GC<br />

9 SHOWER CURTAINS<br />

A RODS<br />

O<br />

A<br />

A GC GC<br />

B CURTAINS<br />

GC<br />

O<br />

O<br />

PA O<br />

10 SHOWERS GC ME/A ME GC GC<br />

11 COMMUNICATION SYSTEM<br />

A EMPTY CONDUIT<br />

GC<br />

ME<br />

ME GC GC<br />

B EQUIPMENT & WIRE<br />

GC<br />

ME<br />

ME GC GC<br />

12 TILE FLOOR GC A/I A/I GC GC<br />

13 TOILET, URINAL & SHOWER PARTITIONS GC A/I A/I GC GC<br />

14 LIGHTING GC ME/A ME GC GC<br />

STORE ROOMS<br />

1 FIRE EXTINGUISHERS GC A/ME A/ME GC GC<br />

2 LIGHTING<br />

GC<br />

ME<br />

ME GC GC<br />

A FLUORESCENT<br />

GC<br />

ME<br />

ME GC GC<br />

B INCANDESCENT<br />

GC A/O<br />

A GC GC<br />

3 WIRE PARTITIONS K K K PA GC<br />

4 SHELVING AND PALLETS (FOOD SERVICE) GC A/O A GC GC<br />

5 SHELVING AND PALLETS (OTHER) GC A A PA GC<br />

6 WALL COVERING<br />

A VINYL<br />

B PAINT<br />

C OTHER<br />

7 CEILINGS<br />

A LAY-IN<br />

B SPRAY-ON<br />

C OTHER<br />

8 FLOORS<br />

A CARPETING<br />

B OTHER<br />

HOUSEKEEPING<br />

1 CEILINGS<br />

A LAY-IN<br />

GC<br />

A<br />

A GC GC<br />

B SPRAY-ON<br />

GC<br />

A<br />

A GC GC<br />

C OTHER<br />

GC A<br />

A GC GC<br />

2 CONTROL DESK (FIXED) GC O A GC GC<br />

3 EQUIPMENT O O O PA PA<br />

4 FURNITURE I I I PA PA<br />

5 SIGNAGE I G/I/I****/A*** G PA/G G<br />

6 LIGHTING<br />

A<br />

B<br />

FLUORESCENT<br />

INCANDESCENT<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

ME/A<br />

ME/A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

A<br />

ME<br />

ME<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

40


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH. INSTALL<br />

DOCS<br />

7 WALL COVERING<br />

A VINYL<br />

GC<br />

A<br />

A<br />

PA GC<br />

B PAINT<br />

GC<br />

A<br />

A GC GC<br />

C OTHER<br />

GC<br />

A<br />

A GC GC<br />

8 SHELVING MILLWORK GC A/O A GC GC<br />

9 SHELVING PREFAB O O O PA GC<br />

10 SINK ASSEMBLY GC ME/A ME GC GC<br />

11 FLOORS<br />

A<br />

B<br />

CARPETING<br />

OTHER<br />

MAINTENANCE SHOP<br />

1 BUILT-IN SHELVING GC A/O A/O GC GC<br />

2 CABINETRY GC A/O A/O GC GC<br />

3 ELECTRICAL GC ME ME GC GC<br />

4 FLOORS<br />

A CARPETING<br />

GC<br />

A<br />

A<br />

PA GC<br />

B OTHER<br />

GC<br />

A<br />

A GC GC<br />

5 CEILINGS<br />

A LAY-IN<br />

GC<br />

A<br />

A GC GC<br />

B SPRAY-ON<br />

GC<br />

A<br />

A GC GC<br />

C OTHER<br />

GC<br />

A<br />

A GC GC<br />

6 WALL COVERING<br />

A VINYL<br />

GC<br />

I<br />

A<br />

PA GC<br />

B PAINT<br />

GC<br />

A<br />

A GC GC<br />

C OTHER<br />

GC<br />

I<br />

A GC GC<br />

7 FURNITURE AND FILES I I I PA PA<br />

8 HAND TOOLS O O O PA O<br />

9 KEY CABINETS GC A A GC GC<br />

I<br />

GC<br />

10 MOVABLE SHELVING O O O PA PA<br />

11 PORTABLE EQUIPMENT O O O PA PA<br />

12 WIRE PARTITIONS GC A/O A GC GC<br />

13 SINK ASSEMBLY GC ME/A ME GC GC<br />

14 SPARE STOCK O O O PA PA<br />

15 STATIONARY EQUIPMENT O O O PA PA<br />

16 WORK BENCHES (PRE-FAB) GC A/O A GC GC<br />

17 LIGHTING GC ME/A ME GC GC<br />

STAFF DINING ROOM<br />

1 CASH REGISTER O O O PA PA/GC*<br />

2 CEILINGS<br />

A LAY-IN<br />

GC<br />

I/A A/I*** GC GC<br />

B SPRAY-ON<br />

GC<br />

I/A A/I*** GC GC<br />

C OTHER<br />

GC<br />

I/A A/I*** GC GC<br />

3 WALL COVERING<br />

A VINYL<br />

GC<br />

I/A<br />

I*** GC GC<br />

B PAINT<br />

GC<br />

I/A<br />

I*** GC GC<br />

C OTHER<br />

GC<br />

I/A<br />

I*** GC GC<br />

4 COOKING VENTILATION SYSTEM K/GC K/ME K/ME PA GC<br />

5 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I<br />

PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

6 FURNITURE I I I PA PA<br />

7 SIGNAGE I G/O/I****/A** G PA/G G<br />

8 HAND SINK GC K/ME K/ME GC GC<br />

I<br />

A<br />

A<br />

A<br />

PA<br />

GC<br />

GC<br />

GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

41


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH. INSTALL<br />

DOCS<br />

9 KITCHEN EQUIPMENT K/GC K K PA GC<br />

10 KITCHEN EQUIPMENT HOOK-UP GC K/ME K/ME GC GC<br />

11 KITCHEN EQUIPMENT SET IN PLACE K K/ME PA GC<br />

12 LIGHTING<br />

A FLUORESCENT<br />

GC ME/A<br />

ME GC GC<br />

B INCANDESCENT<br />

GC ME/A<br />

ME GC GC<br />

13 ELECTRICAL GC ME ME GC GC<br />

14 OTHER EQUIPMENT HOOK-UP GC ME ME GC GC<br />

15 OTHER EQUIPMENT SET IN PLACE GC ME ME GC GC<br />

16 PLUMBING AND MECHANICAL GC ME ME GC GC<br />

17 COMMUNICATION SYSTEM<br />

A EMPLOYEE CONDUIT<br />

GC<br />

ME<br />

ME GC GC<br />

B EQUIPMENT<br />

GC<br />

ME<br />

ME GC GC<br />

18 STAINLESS STEEL FABRICATION K/GC K K PA PA<br />

GUEST LAUNDRY / LAUNDRY<br />

1 ELECTRICAL GC ME/K/O ME/K/O GC GC<br />

2 EQUIPMENT K/GC K/ME K/ME PA GC<br />

3 FLOORS<br />

A CARPETING<br />

B OTHER<br />

4 WALL COVERING<br />

A VINYL<br />

B PAINT<br />

C OTHER<br />

5 CEILINGS<br />

A LAY-IN<br />

B SPRAY-ON<br />

C OTHER<br />

6 FURNITURE I I I PA PA<br />

7 MECHANICAL AND PLUMBING GC ME/K ME/K GC GC<br />

8 WORK TABLES K K K PA PA<br />

9 SHELVING AND RACKS, MILLWORK GC K/O/A K/O/A GC GC<br />

10 SHELVING AND RACKS, PORTABLE K K K PA PA<br />

11 VENTILATION GC K/ME K/ME GC GC<br />

12 LIGHTING GC ME ME GC GC<br />

13 PORTABLE EQUIPMENT (CARTS) K K/O K/O PA PA<br />

ROOM SERVICE<br />

1 CEILINGS<br />

A LAY-IN<br />

GC<br />

A<br />

A GC GC<br />

B SPRAY-ON<br />

GC<br />

A<br />

A GC GC<br />

C OTHER<br />

GC<br />

A<br />

A GC GC<br />

2 COOKING VENTILATION SYSTEM GC K/ME K/ME PA GC<br />

3 ELECTRICAL GC ME ME GC GC<br />

4 EQUIPMENT K K/O K PA PA<br />

5 SIGNAGE I A/G G PA/G G<br />

6 KITCHEN EQUIPMENT K/GC K/ME K/ME PA GC/K<br />

7 LIGHTING<br />

A FLUORESCENT<br />

GC<br />

ME<br />

ME GC GC<br />

B INCANDESCENT<br />

GC<br />

ME<br />

ME GC GC<br />

8 PORTABLE EQUIPMENT (CARTS) K K/O K PA PA<br />

9 STAINLESS STEEL FABRICATION K K K PA PA<br />

10 FLOORS<br />

A<br />

B<br />

CARPETING<br />

OTHER<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

A<br />

A<br />

A<br />

A<br />

A/I<br />

A<br />

A<br />

A<br />

A<br />

A/I<br />

A<br />

A<br />

A<br />

A<br />

A/I<br />

A<br />

A<br />

A<br />

A<br />

A<br />

PA<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

42


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH. INSTALL<br />

DOCS<br />

11 WALL COVERING<br />

A VINYL<br />

GC A<br />

A<br />

PA GC<br />

B PAINT<br />

GC A<br />

A GC GC<br />

C OTHER<br />

GC A/I<br />

A GC GC<br />

D TILE<br />

GC A<br />

A GC GC<br />

12 MILLWORK; STORAGE & WORK STATIONS GC A/O A GC GC<br />

PURCHASING/RECEIVING/STORAGE<br />

1 BUILT-IN SHELVING & TABLES-LOCKING GC A/O A GC GC<br />

2 CEILINGS<br />

A LAY-IN<br />

GC A<br />

A GC GC<br />

B SPRAY-ON<br />

GC A<br />

A GC GC<br />

C OTHER<br />

GC A<br />

A GC GC<br />

3 ELECTRICAL GC ME ME GC GC<br />

4 FURNITURE AND FILES I I I GC GC<br />

5 SIGNAGE I G/O G PA/G G<br />

6 WALL COVERING<br />

A VINYL<br />

GC A<br />

A GC GC<br />

B PAINT<br />

GC A<br />

A GC GC<br />

C OTHER<br />

GC A<br />

A GC GC<br />

7 PLATFORM SCALE K K/A K/A PA PA<br />

8 REFRIGERATION HOOK-UP TC K/ME ME PA K/GC<br />

9 REFRIGERATION AND SET IN PLACE K/GC K K PA K/GC<br />

10 SHELVING AND PALLETS – WIRE K K/O K PA PA<br />

11 FLOORS<br />

A<br />

B<br />

CARPETING<br />

OTHER<br />

12 LIGHTING GC ME ME GC GC<br />

13 LOADING DOCK EQUIPMENT GC A A GC GC<br />

14 DUMPSTER / COMPACTOR GC A A GC GC<br />

15 CORNER GUARDS / RUB RAILS GC A A GC GC<br />

PERSONNEL AND SECURITY<br />

1 BUILT-IN DESKS AND SHELVING GC A/I/O A GC GC<br />

2 CEILINGS<br />

A LAY-IN<br />

GC A<br />

A GC GC<br />

B SPRAY-ON<br />

GC A<br />

A GC GC<br />

C OTHER<br />

GC A<br />

A GC GC<br />

3 ELECTRICAL GC ME ME GC GC<br />

4 LIGHTING<br />

A FLUORESCENT<br />

GC ME<br />

ME GC GC<br />

B INCANDESCENT<br />

GC ME<br />

ME GC GC<br />

5 FURNITURE AND FILES I I I PA PA<br />

6 COMMUNICATION SYSTEM<br />

A EMPTY CONDUIT<br />

GC ME/O ME GC GC<br />

B EQUIPMENT & WIRE<br />

GC ME/O ME GC GC<br />

7 TV SURVEILLANCE SYSTEM<br />

A EMPTY CONDUIT<br />

GC ME/O ME GC GC<br />

B EQUIPMENT & WIRE<br />

A AV/A AV/A AV AV<br />

8 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I<br />

PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

GC<br />

GC<br />

A/I<br />

A/I<br />

A<br />

A<br />

PA<br />

GC<br />

GC<br />

GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

43


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

9 WALL COVERING<br />

A VINYL<br />

B PAINT<br />

C OTHER<br />

BUDGET <strong>DESIGN</strong> CONTRACT<br />

DOCS<br />

GC<br />

GC<br />

GC<br />

I<br />

I<br />

I<br />

I***<br />

A<br />

A<br />

PURCH.<br />

PA<br />

GC<br />

GC<br />

INSTALL<br />

10 SECURITY COMPUTER EQUIPMENT SEC SEC SEC/ME GC GC<br />

OFFICES ADMINISTRATION<br />

SALES AND ACCOUNTING<br />

1 BUILT-IN SHELVING & MILLWORK<br />

GC I/O I GC GC<br />

2 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

3 CEILINGS<br />

A LAY-IN<br />

GC<br />

I/A A/I*** GC GC<br />

B SPRAY-ON<br />

GC<br />

I/A A/I*** GC GC<br />

C OTHER<br />

GC<br />

I/A A/I*** GC GC<br />

4 COMPUTER SYSTEMS<br />

A EMPTY CONDUIT<br />

GC<br />

ME<br />

ME GC GC<br />

B SYSTEM & WIRE<br />

O<br />

O<br />

O O/PA O/PA<br />

5 DRAPERIES<br />

I<br />

I<br />

I PA PA<br />

A BLOCKING<br />

GC<br />

A/I<br />

A GC GC<br />

6 ELECTRICAL GC ME ME GC GC<br />

7 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I PA PA<br />

b Direct Connection<br />

PA<br />

I<br />

ME PA GC**<br />

B FLUORESCENT<br />

GC ME/I<br />

ME GC GC<br />

C INCANDESCENT<br />

GC ME/I<br />

ME GC GC<br />

8 FURNITURE AND FILES I I I PA PA<br />

9 DOORS<br />

A FINISHES<br />

GC<br />

I<br />

A/I*** GC GC<br />

B HARDWARE<br />

GC<br />

I/A<br />

A GC GC<br />

10 DIRECTIONAL GRAPHICS & SIGNAGE I G/O/1****/A*** G PA/G G<br />

11 OFFICE MACHINES O O O PA PA<br />

12 PICTURES, MIRRORS, ETC.<br />

I<br />

I<br />

I PA PA<br />

A BLOCKING<br />

GC<br />

A/I<br />

A GC GC<br />

13 TELEPHONE AND TELEX<br />

A EMPTY CONDUIT<br />

GC<br />

ME<br />

ME GC GC<br />

B EQUIPMENT & WIRE<br />

O ME/I/O ME/I I O<br />

9 WALL COVERING<br />

A VINYL<br />

GC<br />

I<br />

I PA GC<br />

B PAINT<br />

GC<br />

I<br />

A/I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

LOBBY AND PUBLIC FOYERS<br />

1 FLOORS<br />

A CARPETING<br />

B OTHER<br />

2 CEILINGS<br />

A LAY-IN<br />

B SPRAY-ON<br />

C OTHER<br />

3 CHANDELIERS<br />

A BLOCKING & SUPPORT<br />

4 DRAPERIES AND TRACKS<br />

A BLOCKING<br />

I<br />

GC<br />

GC<br />

GC<br />

GC<br />

I<br />

GC<br />

I<br />

GC<br />

I<br />

I<br />

I/A<br />

I/A<br />

I/A<br />

I<br />

A/I<br />

I<br />

I/A<br />

I<br />

I/A<br />

A/I<br />

A/I<br />

A/I<br />

I/ME<br />

A<br />

I<br />

A<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC**<br />

GC<br />

PA<br />

GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

44


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH. INSTALL<br />

DOCS<br />

5 FURNITURE<br />

A LOOSE<br />

I<br />

I<br />

I PA PA<br />

B FIXED<br />

GC<br />

I/O<br />

I GC GC<br />

6 DIRECTIONAL GRAPHICS & SIGNAGE I G/O/I****/A*** G PA/G G<br />

7 MIRRORS, PICTURES, ARTIFACTS<br />

I<br />

I<br />

I PA PA<br />

A BLOCKING<br />

GC<br />

I<br />

I GC GC<br />

8 WALL COVERING<br />

A VINYL<br />

GC<br />

A/I<br />

A PA GC<br />

B PAINT<br />

GC<br />

I<br />

I GC GC<br />

C OTHER<br />

GC<br />

I<br />

I GC GC<br />

9 PLANTERS<br />

A FIXED<br />

GC<br />

I<br />

I GC GC<br />

B MOVABLE<br />

GC I/LS/A I/A PA PA<br />

10 PLANT MATERIAL I I/LS I PA PA<br />

11 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

PA<br />

L/I<br />

I PA PA<br />

b Direct Connection<br />

PA<br />

L/I L/I/ME/A PA GC**<br />

B FLUORESCENT<br />

GC LI/I/ME L/ME GC GC<br />

C INCANDESCENT<br />

GC LI/I/ME L/ME GC GC<br />

D DIMMING<br />

GC<br />

I/L<br />

L/ME GC GC<br />

12 STORE FRONTS GC I A GC GC<br />

13 TELEPHONES<br />

A EMPTY CONDUIT<br />

GC ME/I<br />

ME GC GC<br />

B EQUIPMENT<br />

O ME/I/O ME/I O O<br />

14 WALL SCONCES I I I PA GC<br />

15 SAFE DEPOSIT BOXES GC I I/A GC GC<br />

PUBLIC RESTROOMS<br />

1 BUILT-IN VANITIES GC I I/A GC GC<br />

2 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I PA PA<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

C TILE<br />

GC<br />

I<br />

A/I*** GC GC<br />

3 CEILINGS<br />

A LAY-IN<br />

GC<br />

I/A A/I*** GC GC<br />

B SPRAY-ON<br />

GC<br />

I/A A/I*** GC GC<br />

C OTHER<br />

GC<br />

I/A A/I*** GC GC<br />

4 WALL COVERING<br />

A VINYL<br />

GC<br />

I<br />

I GC GC<br />

B PAINT<br />

GC<br />

I<br />

I GC GC<br />

C OTHER<br />

GC<br />

I<br />

I*** GC GC<br />

5 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I PA PA<br />

b Direct Connection<br />

PA<br />

I<br />

ME/A PA GC<br />

B FLUORESCENT<br />

GC I/ME I/ME GC GC**<br />

C INCANDESCENT<br />

GC I/ME I/ME GC GC<br />

6 FURNITURE I I I GC GC<br />

7 HARDWARE AND ACCESSORIES GC I I/A GC GC<br />

8 ELECTRICAL GC ME ME GC GC<br />

9 MIRRORS AND COAT HOOKS GC I/A I/A GC GC<br />

10 PLANTERS<br />

A<br />

B<br />

FIXED<br />

MOVABLE<br />

GC<br />

I<br />

I/LS/A<br />

I/LS<br />

I/A<br />

I<br />

GC<br />

PA<br />

GC<br />

PA<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

45


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT<br />

DOCS<br />

PURCH.<br />

INSTALL<br />

11 PLANT MATERIAL LS I/LS LS GC GC<br />

12 PLUMBING AND FIXTURES GC I/ME ME GC GC<br />

14 DIRECTIONAL GRAPHICS & SIGNAGE I I/A/G G PA/G GC<br />

FRONT OFFICE<br />

1 COMPUTER O O O/ME PA PA<br />

2 BUILT-IN DESK UNIT – BACK SIDE GC I/O I GC GC<br />

3 BUILT-IN DESK UNIT – FRONT SIDE GC I I GC GC<br />

4 BUILT-IN SHELVING/CABINETRY GC I/O I GC GC<br />

5 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

6 ELECTRICAL GC ME ME GC GC<br />

7 FILES & FURNITURE I I I PA PA<br />

8 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I PA PA<br />

b Direct Connection<br />

PA<br />

I<br />

ME/A PA GC**<br />

B FLUORESCENT<br />

GC I/ME<br />

ME GC GC<br />

C INCANDESCENT<br />

GC I/ME<br />

ME GC GC<br />

9 OFFICE MACHINES O O O PA PA<br />

10 SAFE OR SECURITY VAULT<br />

A BUILT-IN<br />

GC A/O<br />

A GC GC<br />

B PORTABLE<br />

O<br />

O<br />

O PA PA<br />

11 SAFETY DEPOSIT BOXES GC A/O A GC GC<br />

12 COMMUNICATION SYSTEM<br />

A EMPTY CONDUIT<br />

GC<br />

ME<br />

ME GC GC<br />

B EQUIPMENT & WIRE<br />

GC<br />

ME<br />

ME PA GC<br />

13 TELEPHONES<br />

A EMPTY CONDUIT<br />

GC ME/I<br />

ME GC GC<br />

B EQUIPMENT & WIRE<br />

O ME/I/O ME/I O O<br />

14 CEILINGS<br />

A LAY-IN<br />

GC<br />

I/A A/I*** GC GC<br />

B SPRAY-ON<br />

GC<br />

I/A A/I*** GC GC<br />

C OTHER<br />

GC<br />

I/A A/I*** GC GC<br />

15 WALL COVERING<br />

A VINYL<br />

GC<br />

I<br />

I PA GC<br />

B PAINT<br />

GC<br />

I<br />

I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

RESERVATIONS and BACK OFFICE<br />

1 BUILT-IN CABINETRY / SHELVING GC I/O I GC GC<br />

2 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

3 CEILINGS<br />

A LAY-IN<br />

GC<br />

I/A A/I*** GC GC<br />

B SPRAY-ON<br />

GC<br />

I/A A/I*** GC GC<br />

C OTHER<br />

GC<br />

I/A A/I*** GC GC<br />

4 FURNITURE AND FILES I I I PA PA<br />

5 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I PA PA<br />

b Direct Connection<br />

PA<br />

I<br />

ME/A PA GC**<br />

B FLUORESCENT<br />

GC I/ME<br />

ME GC GC<br />

C INCANDESCENT<br />

GC I/ME<br />

ME GC GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

46


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT<br />

DOCS<br />

PURCH. INSTALL<br />

6 ELECTRICAL GC ME ME GC GC<br />

7 TELEPHONES<br />

A EMPTY CONDUIT<br />

GC ME/I<br />

ME GC GC<br />

B EQUIPMENT & WIRE<br />

O ME/I/O ME/I O O<br />

8 WALL COVERING<br />

A VINYL<br />

GC<br />

I<br />

I PA GC<br />

B PAINT<br />

GC<br />

I<br />

I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

RESERVATIONS and BACK OFFICE<br />

1 BUILT-IN CABINETRY / SHELVING GC I/O I GC GC<br />

2 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

3 CEILINGS<br />

A LAY-IN<br />

GC<br />

I/A A/I*** GC GC<br />

B SPRAY-ON<br />

GC<br />

I/A A/I*** GC GC<br />

C OTHER<br />

GC<br />

I/A A/I*** GC GC<br />

4 FURNITURE AND FILES I I I PA PA<br />

5 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I PA PA<br />

b Direct Connection<br />

PA<br />

I<br />

ME/A PA GC**<br />

B FLUORESCENT<br />

GC I/ME<br />

ME GC GC<br />

C INCANDESCENT<br />

GC I/ME<br />

ME GC GC<br />

6 ELECTRICAL GC ME ME GC GC<br />

7 TELEPHONES<br />

A EMPTY CONDUIT<br />

GC ME/I<br />

ME GC GC<br />

B EQUIPMENT & WIRE<br />

O ME/I/O ME/I O O<br />

8 WALL COVERING<br />

A VINYL<br />

GC<br />

I<br />

I PA GC<br />

B PAINT<br />

GC<br />

I<br />

I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

GENERAL CASHIER OFFICE<br />

1 BUILT-IN CABINETRY / SHELVING GC I/O I GC GC<br />

2 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

3 CEILINGS<br />

A LAY-IN<br />

GC<br />

I/A A/I*** GC GC<br />

B SPRAY-ON<br />

GC<br />

I/A A/I*** GC GC<br />

C OTHER<br />

GC<br />

I/A A/I*** GC GC<br />

4 DROP VAULT O O/A O O GC<br />

5 FURNITURE AND FILES I I I PA PA<br />

6 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I PA PA<br />

b Direct Connection<br />

PA<br />

I<br />

ME/A PA GC**<br />

B FLUORESCENT<br />

GC I/ME<br />

ME GC GC<br />

C INCANDESCENT<br />

GC I/ME<br />

ME GC GC<br />

7 ELECTRICAL GC ME ME GC GC<br />

8 WALL COVERING<br />

A VINYL<br />

GC<br />

I<br />

I PA GC<br />

B PAINT<br />

GC<br />

I<br />

I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

47


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH INSTALL<br />

DOCS<br />

.<br />

9 SAFE GC A A GC GC<br />

10 COMMUNICATION SYSTEM<br />

A EMPTY CONDUIT<br />

GC<br />

ME<br />

ME GC GC<br />

B EQUIPMENT & WIRE<br />

GC<br />

ME<br />

ME PA GC<br />

PBX SWITCHBOARD ROOM<br />

1 BUILT-IN CABINETRY GC A/O/I A GC GC<br />

2 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

3 CEILINGS<br />

A LAY-IN<br />

GC<br />

I/A<br />

A/I*** GC GC<br />

B SPRAY-ON<br />

GC<br />

I/A<br />

A/I*** GC GC<br />

C OTHER<br />

GC<br />

I/A<br />

A/I*** GC GC<br />

4 FURNITURE AND FILES O O O PA PA<br />

5 LIGHTING<br />

A FLUORESCENT<br />

GC ME/I<br />

ME GC GC<br />

B INCANDESCENT<br />

GC ME/I<br />

ME GC GC<br />

6 ELECTRICAL<br />

A STANDARD<br />

GC<br />

ME<br />

ME GC GC<br />

B BACK-UP EMERGENCY SYSTEM<br />

GC<br />

ME<br />

ME GC GC<br />

C GROUND<br />

GC<br />

ME<br />

ME GC GC<br />

7 WALL COVERING<br />

A VINYL<br />

GC<br />

I<br />

I PA GC<br />

B PAINT<br />

GC<br />

I<br />

I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

MEETING / BANQUET ROOM<br />

1 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

2 CEILINGS<br />

A LAY-IN<br />

GC<br />

I/A<br />

A/I*** GC GC<br />

B SPRAY-ON<br />

GC<br />

I/A<br />

A/I*** GC GC<br />

C OTHER<br />

GC<br />

I/A<br />

A/I*** GC GC<br />

3 DRAPERIES (SHUTTERS)<br />

I<br />

I<br />

I PA PA<br />

A BLOCKING<br />

GC<br />

A/I<br />

A GC GC<br />

4 FURNITURE<br />

A LOOSE<br />

I<br />

I<br />

I PA PA<br />

B FIXED<br />

GC<br />

I/O<br />

I GC GC<br />

5 DOORS<br />

A FINISH<br />

GC<br />

I<br />

A/I*** GC GC<br />

B HARDWARE<br />

GC<br />

I/A<br />

A/I*** GC GC<br />

6 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I PA PA<br />

b Direct Connection<br />

PA<br />

I<br />

ME/A PA GC**<br />

B FLUORESCENT<br />

GC I/ME<br />

ME GC GC<br />

C INCANDESCENT<br />

GC I/ME<br />

ME GC GC<br />

D DIMMING<br />

GC<br />

I/L<br />

L/ME GC GC<br />

7 ELECTRICAL GC ME/AB ME GC GC<br />

8 MOVABLE PARTITION WALL<br />

A WALL UNIT<br />

GC<br />

A<br />

A GC GC<br />

B APPLIED FINISH<br />

GC<br />

I<br />

I PA GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

48


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH. INSTALL<br />

DOCS<br />

9 WALL COVERING<br />

A VINYL<br />

GC<br />

I<br />

I PA GC<br />

B PAINT<br />

GC<br />

I<br />

I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

10 PLANTERS<br />

A FIXED<br />

GC I/LS/A I/A GC GC<br />

B MOVABLE<br />

I<br />

I/LS<br />

I/LS PA PA<br />

11 PLANT MATERIAL GC/LS I/LS LS GC GC<br />

12 AUDIO-VISUAL EQUIPMENT<br />

A FIXED<br />

GC A/AV/O A/AV GC GC<br />

B MOVABLE<br />

O AV/O<br />

AV O PA<br />

C EMPTY CONDUIT<br />

GC ME/AV/O ME GC GC<br />

13 TABLES, CHAIRS, STAGING I I I PA PA<br />

14 WALL SCONCES I I/ME I/ME PA GC<br />

15 WALL TAPESTRY/ART<br />

I<br />

I<br />

I PA PA<br />

A BLOCKING<br />

GC<br />

I<br />

I/A GC GC<br />

16 DIRECTIONAL GRAPHICS & SIGNAGE O G/O/I****/A*** G PA G<br />

FOOD & BEVERAGE (ALL LEVELS)<br />

1 COMPUTER SYSTEM O/GC O O/ME PA O/GC<br />

2 CEILINGS<br />

A LAY-IN<br />

GC<br />

I<br />

A/I GC GC<br />

B SPRAY-ON<br />

GC<br />

I<br />

A/I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I GC GC<br />

3 BACK BAR UNIT GC I/K/O I/K GC GC<br />

4 BUILT-IN CABINETRY/SHELVING GC I/K/O I/K GC GC<br />

5 BUILT-IN COUNTER AND STOOLS GC I/K/O I/K GC GC<br />

6 BUILT-IN SERVICE STATION GC I/K/O I/K GC GC<br />

7 FLOORS<br />

A CARPETING<br />

I<br />

I<br />

I PA GC<br />

B OTHER<br />

GC<br />

I<br />

A/I*** GC GC<br />

8 CASHIER/HOST STATION GC I/O I GC GC<br />

9 CHANDELIERS<br />

I<br />

I/ME I/ME PA GC**<br />

A BLOCKING & SUPPORT<br />

GC<br />

A/I<br />

A/I GC GC<br />

10 DECORATIVE WINDOWS/DOORS GC I I GC GC<br />

11 DIVIDERS & SHUTTERS DECORATIVE<br />

A FIXED<br />

GC<br />

I<br />

I GC GC<br />

B MOVABLE<br />

I<br />

I<br />

I PA PA<br />

12 DOWN LIGHTS GC I/ME/L ME/L PA PA<br />

13 DRAPERIES AND TRACKS<br />

I<br />

I<br />

I PA PA<br />

A BLOCKING<br />

GC<br />

I<br />

I/A GC GC<br />

14 ELECTRICAL GC ME ME GC GC<br />

15 PLUMBING GC ME ME GC GC<br />

16 FRONT & BACK BAR UNITS HOOK-UP K/GC K/I K/ME GC GC<br />

17 FURNITURE<br />

A LOOSE<br />

B FIXED<br />

18 GRAPHICS<br />

A SIGNAGE<br />

B CAMERA READY ARTWORK<br />

I<br />

GC<br />

I<br />

I/G<br />

I<br />

I<br />

I/G/O<br />

G/O<br />

I<br />

I<br />

G<br />

G<br />

PA<br />

GC<br />

PA/G<br />

O<br />

PA<br />

GC<br />

G<br />

O<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

49


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT<br />

DOCS<br />

PURCH.<br />

INSTALL<br />

19 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

b Direct Connection<br />

B FLUORESCENT<br />

C INCANDESCENT<br />

D DIMMING SYSTEM<br />

20 COMMUNICATION SYSTEM<br />

A EMPTY CONDUIT<br />

B EQUIPMENT & WIRE<br />

21 WALL COVERING<br />

A VINYL<br />

B PAINT<br />

C OTHER<br />

22 PICTURES, ARTIFACTS, ETC.<br />

A BLOCKING<br />

23 PLANTERS<br />

A FIXED<br />

B MOVABLE<br />

I<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

I<br />

GC<br />

GC<br />

I<br />

I<br />

I<br />

I/ME<br />

I/ME<br />

I/L<br />

ME<br />

ME<br />

I<br />

I<br />

I<br />

I<br />

I/A<br />

I/LS/A<br />

I/LS<br />

I<br />

ME/A<br />

ME<br />

ME<br />

L/ME<br />

24 PLANT MATERIAL LS I/LS LS GC GC<br />

25 TOP OF TABLE ITEMS O O/I O O O<br />

26 WALL SCONCES I I/ME ME PA GC<br />

27 WAITER STATIONS GC I/K I/K/ME GC GC<br />

RETAIL AREAS<br />

1 BUILT-IN CABINETRY GC A/O/I A GC GC<br />

ME<br />

ME<br />

I<br />

I<br />

I***<br />

I<br />

A<br />

I/A<br />

I<br />

PA<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

PA<br />

PA<br />

GC**<br />

GC<br />

GC<br />

GC<br />

2 FLOORS<br />

A CARPETING<br />

GC<br />

I<br />

I PA GC<br />

B OTHER<br />

I<br />

I<br />

A/I*** PA GC<br />

3 CEILINGS<br />

A LAY-IN<br />

GC<br />

I<br />

A/I GC GC<br />

B SPRAY-ON<br />

GC<br />

I<br />

A/I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I GC GC<br />

4 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

I<br />

I<br />

I PA PA<br />

b Direct Connection<br />

PA<br />

I<br />

ME/A PA GC**<br />

B FLUORESCENT<br />

GC I/ME ME GC GC<br />

C INCANDESCENT<br />

GC I/ME ME GC GC<br />

5 ELECTRICAL GC ME ME GC GC<br />

6 MECHANICAL GC ME ME GC GC<br />

SPA<br />

1 BUILT-IN CABINETRY GC A/O/I A GC GC<br />

2 FLOORS<br />

A CARPETING<br />

B OTHER<br />

3 CEILINGS<br />

A LAY-IN<br />

B SPRAY-ON<br />

C OTHER<br />

4 LIGHTING<br />

A DECORATIVE<br />

a Plug-In<br />

b Direct Connection<br />

B FLUORESCENT<br />

C INCANDESCENT<br />

GC<br />

I<br />

GC<br />

GC<br />

GC<br />

I<br />

PA<br />

GC<br />

GC<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I/ME<br />

I/ME<br />

I<br />

A/I***<br />

A/I<br />

A/I<br />

A/I<br />

I<br />

ME/A<br />

ME<br />

ME<br />

PA<br />

PA<br />

GC<br />

GC<br />

GC<br />

PA<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

PA<br />

GC<br />

GC<br />

GC<br />

GC<br />

GC<br />

PA<br />

GC**<br />

GC<br />

GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

50


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

BUDGET <strong>DESIGN</strong> CONTRACT PURCH INSTALL<br />

DOCS .<br />

5 ELECTRICAL GC ME ME GC GC<br />

6 SPA EQUIPMENT<br />

O SPA/O I/ME GC GC<br />

A HYDROTHERAPY EQUIPMENT<br />

O SPA/O I/ME GC GC<br />

B EXERCISE EQUIPMENT<br />

O SPA/O I/ME O O<br />

KITCHEN AND PANTRIES<br />

1 CABINETRY/SHELVING K/GC K/O K GC GC<br />

2 CEILINGS<br />

A LAY-IN<br />

GC<br />

I<br />

A/I GC GC<br />

B SPRAY-ON<br />

GC<br />

I<br />

A/I GC GC<br />

C OTHER<br />

GC<br />

I<br />

A/I GC GC<br />

3 COOKING VENTILATION<br />

A EQUIPMENT<br />

K/O K/O<br />

K PA GC<br />

B DUCT WORK AND FANS<br />

GC ME<br />

ME GC GC<br />

C HOOK-UP<br />

GC ME/K ME GC GC<br />

4 REFRIGERATION<br />

A EQUIPMENT & INSTALLATION<br />

K<br />

K/O<br />

K PA K<br />

B HOOK-UP<br />

GC ME/K ME GC GC/K<br />

C SPECIAL BLOCK-OUT OR FOUNDATION<br />

GC A/K<br />

A GC GC<br />

5 FABRICATED STAINLESS STEEL K K K PA GC<br />

6 FURNITURE AND FILES I I I PA PA<br />

7 DIRECTIONAL GRAPHICS & SIGNAGE I G/O G PA/G PA<br />

8 KITCHEN EQUIPMENT<br />

K<br />

K/O<br />

K PA GC<br />

A FINAL HOOK-UP<br />

GC ME<br />

ME GC GC<br />

9 LIGHTING<br />

A FLUORESCENT<br />

GC ME<br />

ME GC GC<br />

B INCANDESCENT<br />

GC ME<br />

ME GC GC<br />

10 ELECTRICAL GC ME ME GC GC<br />

11 WALL COVERINGS<br />

A PANELING<br />

GC A/I<br />

A GC GC<br />

B OTHER<br />

GC A/I<br />

A GC GC<br />

12 PLUMBING GC ME ME GC GC<br />

13 FLOORS<br />

A CARPETING<br />

GC<br />

I<br />

I PA GC<br />

B OTHER<br />

I<br />

I<br />

A GC GC<br />

LANDSCAPE (EXTERIOR)<br />

1 PLANT MATERIAL LS LS LS GC GC<br />

2 IRRIGATION LS LS LS GC GC<br />

3 DRAINAGE SYSTEM LS/GC LS LS GC GC<br />

4 IRRIGATION & DRAINAGE SLEEVES GC LS LS GC GC<br />

5 FINAL GRADING GC LS LS GC GC<br />

6 PLANTERS<br />

A FIXED<br />

B LOOSE<br />

LS/GC<br />

LS<br />

7 LIGHTING LS/GC LS/L ME GC GC<br />

8 SWIMMING POOL GC LS LS GC GC<br />

PARKING ROADWAYS, WALKS and<br />

RETAINING<br />

LS/GC LS/L A/LS GC GC<br />

LS<br />

LS<br />

LS<br />

LS<br />

GC<br />

PA<br />

GC<br />

PA<br />

PARKING, EXTERIOR GRAPHICS &<br />

EXTERIOR BUILDING SIGNAGE<br />

GC G/A G GC GC<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

51


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

CLASSIFICATION OF RESPONSIBILITIES<br />

UNIFORMS<br />

BUDGET <strong>DESIGN</strong> CONTRACT<br />

DOCS<br />

PURCH<br />

.<br />

INSTALL<br />

O I****/O O PA O<br />

EXTERIOR<br />

1 BUILDING SIGNAGE & DIRECTIONALS GC G/A G GC GC<br />

2 FLAGPOLS GC A A GC GC<br />

LEGEND<br />

A Architect L Lighting Consultant SPA Spa Consultant<br />

AV Audio/Visual Consultant LS Landscape Consultant * Rough-In<br />

G Graphics Consultant ME Mechanical/Electrical Engineer ** Rough-In and Final Connection<br />

GC General Consultant O Owner/Operator *** Finish Schedule Only<br />

I Interior Design Consultant PA Purchasing Agent **** Consultant Only<br />

K Kitchen and Laundry Consultant<br />

SEC Security Consultant<br />

REV. MARCH 2006<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.<br />

52


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

B. PUBLIC AREAS<br />

1. LOBBY AND CIRCULATION<br />

1.1. Main Entrance and Lobby<br />

Provide a porte cochère to protect the entrance lobby from the weather and appropriate<br />

spaces to assist arriving and departing guests. The entrance design must leave the guests<br />

with an excellent first and last impression.<br />

Luggage handling activities should not interfere with the guests’ entrance and direct<br />

access to valet parking office, bellmen’s store, service elevators, luggage storage, etc.<br />

The entrance lobby is to be adjacent to the vehicle arrival location and connects directly<br />

to the main lobby.<br />

A taxi holding area and valet parking holding area adjacent to porte cochere.<br />

Porte cochere width should be not less than 40' 0" (12.2 m) with three driveway lanes.<br />

Clear height should be not less than 10' 0" (3.0 m) to curb line and 14' 0" (4.3 m) over<br />

driveway.<br />

Adequate drainage must be provided and the driveway sloped accordingly.<br />

The sidewalk outside main entrance doors should be not less than 15' 0" (4.6 m) wide<br />

and minimum distance between columns and curb line shall be 4' 0" (1.2 m). Elsewhere<br />

the sidewalk should be 10' 0" (3.0 m) wide. Curb to be approximately 4" (10 cm) high<br />

and in contrasting material to sidewalk and driveway paving so as to be clearly visible<br />

to pedestrians. Two 3' 0" (91 cm) wide curb drops to be incorporated in curb.<br />

In cold climates overhead radiant heating is required outside main entrance doors.<br />

Heaters are to be controlled by a thermostat and a time clock with manual override.<br />

Electric snow melting must be incorporated in sidewalk in climates with heavy<br />

snowfall.<br />

Weatherproof duplex electric outlets are required for maintenance of the area. A screw<br />

down, recessed 3/4" (2 cm) cold water hose bib for washing down. 110V x 20 <strong>amp</strong><br />

weatherproof outlet (separate circuit) for high-pressure hose unit.<br />

Landscape planters must have sufficient drains, duplex outlets and hose points are to<br />

ensure proper plant lighting and maintenance.<br />

Three anodised aluminium finish of a colour selected with internal halyards flagpoles<br />

shall be provided at the porte cochere. If freestanding, they shall be not more than 40'<br />

0" (12.2 m) high and less than 15’0” (4.6 m) high.<br />

REV. MARCH 2006 53<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Main Entrance and Lobby (continued)<br />

In cold and windy climates, a revolving door shall be provided at the main entrance<br />

with a pair of swing doors on either side. A vestibule shall be provided at the swing<br />

doors. Revolving doors shall be not less than 7' 0" (2.1 m) inside diameter and 9' 0"<br />

(2.7 m) high. If the above entrance detail cannot be provided, two sets of doors shall be<br />

provided. Comprising two single 3' 0" (91 cm) doors and one pair of doors 6' 0" (1.8<br />

m) wide. Each door to be 9’0” (2.7 m) high. All doors shall be provided with high<br />

quality balanced hardware. The exterior doors should open out. All doors shall be<br />

framed in metal finish of a colour to be selected, and shall incorporate a weatherstrip<br />

and special decorative pulls and pushes. Doors shall be of the “narrow frame” design<br />

and a special decorative gold leaf or etched design shall be provided on the glass.<br />

Four stainless steel 3/8" (0.7 cm) diameter rods with 4" (10 cm) projection shall be<br />

installed, 16” (41 cm) apart and 7’0” (2.1 m) above the finished floor, on the two<br />

columns or walls closest to the main entrance doors for garment bags.<br />

Swift valet access to/from the porte cochere to valet parking area, both with and<br />

without cars, is essential.<br />

A doorman’s station is to be discretely located close to the main entrance doors as<br />

possible, but concealed from the guests’ direct view.<br />

Direct access to service corridor leading to service elevators and luggage store is<br />

essential, to prevent crossing public areas. All to serve as access to valet parking<br />

manager’s office, bellman’s store, etc.<br />

In resorts provide remote area, concealed from public view, for buses waiting for<br />

groups.<br />

The double volume main lobby establishes the image of the hotel and serves as the<br />

main circulation space and functions as a control point. Provide seating, meeting and<br />

greeting environment as well as reception/cashiers’ desk, concierge desk, guest safety<br />

deposit box room, concierge storage and house and pay telephones.<br />

The main lobby is adjacent to the main entrance, with visual access to the front desk<br />

and elevator core. Concealed, pin hole CCTV cameras to cover front desks and main<br />

entrance doors.<br />

1.2. Registration and Check-out<br />

Provide freestanding, stand-up counter for registration and checkout. This area will be<br />

staffed 24 hours a day and serves as a control point, with the staff visually supervising<br />

REV. MARCH 2006 54<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Registration and Check-out (continued)<br />

access to the building. Staff are to have easy access to the guest from behind the<br />

counter, however the reverse is not to be encouraged.<br />

The front desk should preferably be located in a separate foyer off the main lobby and<br />

should not be the principal greeting element for arriving guests. Its location must<br />

facilitate the view to the lobby entrance, guest elevators and concierge desk and provide<br />

easy and direct access from the main lobby. The hotel’s front offices must be located<br />

with direct access to the front desk.<br />

Registration desk to have a minimum of four stations for an average 400 room Hotel.<br />

One station to be added per 100 rooms. Each station is approximately 6’0” (1.8 m)<br />

long.<br />

Barrier-free house and pay telephones are to be adjacent to the front desk.<br />

1.3. Concierge<br />

Provide counter or desk area for guest service and information assistance with one<br />

station per 200 guestrooms. A minimum of two stations is to be provided. Each station<br />

is approximately 6’0” (1.8 m) long.<br />

A concierge work and storage area (approximately 250 ft 2 ) (23 m 2 ) with direct access to<br />

the concierge desk is imperative.<br />

A typical concierge storage room is to have both open and lockable shelving (floor to<br />

ceiling height) as well as duplex electrical outlets and telephone outlets (airline ticket<br />

verification), fax machine and copier.<br />

1.4. Guest Safety Deposit Box<br />

Guest safety deposit box room adjacent to front desk. Guest entry door into safety<br />

deposit retrieval room to be in direct sight of front desk. This door to have an electric<br />

strike, activated from the front desk.<br />

An assistance buzzer with retrieval room connected to the front desk.<br />

Shall be elegantly finished to the same standard as the other public areas of the hotel<br />

and shall contain the following functional items:<br />

Safety deposit boxes for a typical 400-room hotel as follows:<br />

a) 1 Bank of 60 boxes each 2 ½" high x 5" wide x 24" deep (6 x 13 x 61 cm),<br />

b) 1 Bank of 24 boxes each 5" high x 5" wide x 24" deep (13 x 13 x 61 cm), and<br />

c) 1 Bank of 24 boxes each 5" high x 10" wide x 24" deep (13 x 25 x 61 cm).<br />

The boxes shall be built-in and concealed behind veneered hardwood doors. The floor<br />

shall be designed to support the weight of these boxes.<br />

Box “collection” counter approximately 18" (46 cm) wide and 42" (107 cm) AFFL.<br />

REV. MARCH 2006 55<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Guest Safety Box (continued)<br />

Duplex outlet mounted 39" (99 cm) AFFL adjacent to counter.<br />

Press button, to operate buzzer located in the front desk cashier’s area.<br />

Electric strike for lock on guest entry door controlled from button at front desk cashier’s<br />

area.<br />

Closed circuit TV (CCTV) camera to cover safety deposit boxes (staff side).<br />

1.5. Doorman’s Stand<br />

Provide a workstation (approximately 6 ft 2 - 0.5 m 2 ) within a freestanding stand for the<br />

doorman.<br />

The station should be located as close to the main entrance doors as possible, but<br />

concealed from guests’ direct view.<br />

The station is to have a duplex electrical outlet, wall telephone and computer systems<br />

outlets as well as a well-lit work service with lockable cupboards above and below. It<br />

will also house a small fridge (FF & E) as well as waste bin (FF & E) and four lockable<br />

drawers.<br />

1.6. Parking Cashier<br />

Payment for valet parking will be handled by the parking cashier (approximately 70 ft 2 -<br />

6.5 m 2 ) who should be located adjacent to the hotels’ porte cochere. It should be also<br />

been located so as to facilitate entry and exit of valet to the hotel’s parking areas, but<br />

away from direct view of the hotel guests.<br />

A Dutch door with the upper section of the door formed of ¼” (0.6 cm) tempered glass<br />

with a Nissen speaker hole, a stainless steel sliding cash tray, with the lower section<br />

solid timber.<br />

The office will house lockable drawers and cupboards as well as telephone, duplex<br />

electrical outlets and computer systems outlets.<br />

An alarm button will activate a buzzer within the security office.<br />

1.7. Luggage Room<br />

The luggage room shall provide secure room for temporary storage of luggage,<br />

including wall shelving, for arriving or departing guests. In resorts, provide for<br />

additional capacity to handle sports equipment. The luggage room is also used for<br />

bellmen’s storage.<br />

The luggage room should be located near front desk and doorman’s stand and should<br />

have direct access to service elevators.<br />

REV. MARCH 2006 56<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

1.8. Business Centre<br />

The business center provides working and meeting facilities for guests as well as<br />

clerical, computer and communications support facilities. The number of additional<br />

board rooms, meeting rooms and semi-private guest offices to be determined by the<br />

specific program requirements.<br />

The business center should have direct access to public circulation and be located<br />

adjacent to hotel administration for guest convenience and efficient use of hotel staff<br />

and facilities. In some hotels the hotel administration reception will be combined with<br />

the business center administration.<br />

The room should have the following features:<br />

a) Standup reception desk with two guest chairs adjacent.<br />

b) Provide the following features at the reception desk:<br />

i) Duplex electrical outlets (UPS) for CRT and keyboard<br />

ii) Computer system outlets<br />

iii) Telephone outlets<br />

iv) Duplex electrical outlets.<br />

1.9. Public Washrooms<br />

Washrooms must be designed and finished to the same quality level as the other public<br />

areas of the hotel. It is most important that every effort is made to incorporate unique<br />

and residential design features.<br />

Washrooms should be conveniently located near the public areas e.g. main entrance,<br />

meeting rooms and food and beverage outlets.<br />

Where the public areas are on more than one floor or are very spread out, provide<br />

washrooms on each additional floor or in each section of large floors.<br />

Quantity of fixtures to be provided shall conform to local by-laws and building code<br />

requirements. Provide barrier-free WC stall as per local code requirements.<br />

All fixtures will be products as manufactured by the Kohler Company or other equal<br />

and approved.<br />

WC’s and urinals must be located in a separate area from vanities. Urinal privacy<br />

dividers, fixed to floor and wall, should be 3/4" (1.9 cm) granite, 1’6” (0.5 m) wide and<br />

4’6” (1.4 m) high.<br />

WC compartments shall be 3' 0" wide x 5' 6" long (0.9 x 1.7 m). Partitions will be full<br />

height drywall with a 2' 4" x 7' 0" x 1 3/4" (0.6 x 2.1m x 4.4 cm) solid core door<br />

undercut 1" (2.5 cm). Each compartment will have its own exhaust grille. Each door<br />

must have a “self closing” spring hinge and an occupancy indicator.<br />

REV. MARCH 2006 57<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Public Washrooms (continued)<br />

Women’s washrooms should have an area separate from the wet areas, with dry<br />

vanities, stools etc. for make-up.<br />

Lighting must be excellent with downlights above each urinals, decorative ceiling<br />

fixtures in WC rooms and general areas and wall sconces and downlights above each<br />

lavatory basin.<br />

A decorative mirror above each vanity. Plain sheets of mirror will not be acceptable.<br />

A janitor’s storage closet with floor sink and mop rack adjacent to each group of<br />

washrooms is to be provided. Provide wall mounted telephone.<br />

Each washroom is to have a full-length mirror not less than 2' 0" x 6' 6” (0.6 x 2.0 m)<br />

high.<br />

Provide at least one floor drain per washroom area and a recessed hose bibb with<br />

screwdriver stop and one waterproof duplex electrical outlet mounted 18" (46 cm) on<br />

center AFFL immediately below the vanity.<br />

REV. MARCH 2006 58<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

1.10. Functional Diagram: Lobby and Circulation<br />

Public<br />

Washrooms<br />

Telephones<br />

Front Desk<br />

LOBBY<br />

Concierge<br />

Luggage<br />

Bell Captain<br />

MAIN<br />

ENTRANCE<br />

Valet<br />

REV. MARCH 2006 59<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

2. FOOD AND BEVERAGE<br />

2.1. Lobby Lounge<br />

Provide guest seating area (allow 28 ft 2 - 2.6 m 2 per seat) for socializing, reading and<br />

relaxing. The lobby lounge shall be located adjacent to the main lobby and its design<br />

coordinated accordingly.<br />

2.2. Lobby Bar<br />

Provide beverage service and seating area (allow 24 ft 2 - 2.2 m 2 per seat) for socializing<br />

guests in a bar lounge to be located adjacent to the lobby lounge and main lobby.<br />

Limited food service menu will be provided.<br />

2.3. Entertainment Bar and Lounge<br />

An entertainment lounge with beverage service and a variety of seating (allow 28 ft 2 -<br />

2.6 m 2 per seat) and socializing areas for guest entertainment. Limited food service<br />

menu shall be provided.<br />

Waiters will pick up drinks from a separate service bar, which may be part of a guests’<br />

stool bar.<br />

Service stands (FF & E) shall be provided adjacent to the stool bar. The incandescent<br />

lighting level in the service stand area is to be kept as low as practical with a local wall<br />

box dimmer. Each service stand will require the following features:<br />

a) Duplex electrical outlet (UPS) for point of sale and telephone<br />

b) Point of sale cable outlet<br />

c) Telephone<br />

d) Duplex electrical outlets<br />

The service bar (approximately 250 ft 2 - 23.2m 2 shall incorporate the following features:<br />

a) Lock up system for back bar display<br />

b) Adjustable display shelving for back bar<br />

c) Telephone outlets<br />

d) Point of sale (UPS) outlets<br />

e) Lighting dimming control, background music volume control<br />

f) Under-counter refrigerators<br />

g) Glass washing equipment<br />

h) Alcohol dispensing equipment<br />

i) Stools, each stool requiring 24” (61 cm) of bar counter.<br />

REV. MARCH 2006 60<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Entertainment Bar & Lounge (continued)<br />

Provide facilities for live entertainment including two 110V x 15 <strong>amp</strong> electric al outlets.<br />

This facility shall be located and designed in such a way as to provide an effective<br />

acoustic separation from guestrooms. It should preferably be accessed directly from the<br />

main lobby.<br />

110 V x 15 <strong>amp</strong> duplex electrical outlets on 40’0” (12.2 m) centers for housekeeping<br />

purposes.<br />

2.4. Three Meal Restaurant<br />

A Three-Meal Restaurant facility (allow 24 ft 2 - 2.2 m 2 per seat) will serve breakfast,<br />

lunch and dinner. Restaurant size and other requirements such as buffet service, display<br />

kitchen, etc. shall be determined by the specific program requirements. Exterior views<br />

from the dining area are desirable.<br />

The Three-Meal Restaurant should be accessible from the main lobby and have direct<br />

access to the main kitchen.<br />

Typical table mix for urban hotel using a mixture of rectangular, square and round<br />

tables:<br />

a) 25% of 2’s (27” x 38” or 36” - 68 x 97 or 92 cm diameter)<br />

b) Two 6’s (54” – 138 cm diameter)<br />

c) Remainder 4’s (38” x 38” – 97 x 97 of which 25% should be<br />

convertible to 51” – 130 cm diameter table for 6’s).<br />

Typical table mix for resort hotel using a mixture of square and round tables:<br />

a) 50% of 2’s (27” x 38” or 36” – 68 x 97 cm or 92 cm diameter)<br />

b) Two 6’s (54” – 138 cm diameter)<br />

c) Remainder 4’s (38” x 38” – 97 x 97 cm of which 50% should be<br />

convertible to 51” - 130 cm diameter table for 6’s).<br />

Provide vestibule with separate exit/entry doors to kitchen to minimize sound and light<br />

transmission. Vestibule doors should operate automatically via infrared sensor. Each<br />

vestibule should be a minimum of 4’0” (1.2 m) wide.<br />

Service vestibule to house adjustable overhead shelving 15” (38 cm) wide with<br />

lockable drawers below as well as duplex electrical outlets and telephone outlets (credit<br />

card verification) and duplex electrical outlets (UPS) for computer equipment. An<br />

opening for soiled linen bin (FF & E) is to be allowed for. Lighting is this area is to be<br />

subdued with the overhead millwork unit having an incandescent strip light<br />

immediately above the work surface. The color scheme selected for this area is to be<br />

dark in nature. Volume of cabinet calculated on the basis of ½ cu. ft (0.02 m 3 ) per seat.<br />

REV. MARCH 2006 61<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Three Meal Restaurant (continued)<br />

Maitre d’s station is to incorporate the following features:<br />

a) Multi-line telephone and base station for cordless telephone<br />

b) A 110V x 15<strong>amp</strong> duplex electrical outlet<br />

c) Recessed light fixture to illuminate writing surface<br />

d) Sloped writing surface with drawer and cabinet with adjustable<br />

shelves.<br />

Service stands (FF & E) (one every 35 seats) shall be provided at locations not<br />

immediately adjacent to a seating arrangement. The incandescent lighting level in the<br />

service stand area is to be kept as low as practical with a local wall box dimmer. Each<br />

service stand will require the following features:<br />

a) Duplex electrical outlet (UPS) for point of sale and telephone<br />

b) Point of sale cable outlet<br />

c) Telephone<br />

d) Duplex electrical outlets.<br />

Coat check storage space (approximately 45 ft 2 - 4.2 m 2 ) adjacent the maitre d' station.<br />

Locate room lighting dimming control, background music volume control and ceiling<br />

fan control at a service stand and out of guests’ sight or in a control niche adjacent the<br />

maitre d’s stand.<br />

2.5. Specialty Restaurant<br />

This restaurant should provide a fine dining experience for hotel guests (allow 30 ft 2 –<br />

2.8 m 2 per seat). It is very important that the interior design of the room creates a rich,<br />

warm, friendly and welcoming ambience without being formal. Main entry doors<br />

should be of “open” design, e.g., wrought iron to be able to showcase the room when<br />

closed.<br />

The Specialty Restaurant should be easily accessible from the main lobby and adjacent<br />

or linked to the main kitchen. It should be visible from the public circulation area.<br />

Exterior views from the dining area are desirable.<br />

Service vestibule, service stations, maitre d' station, coat check and table mix<br />

requirements similar to Three Meal Restaurant.<br />

Locate room lighting dimming control and background music volume in a control niche<br />

adjacent the maitre d’s stand.<br />

Table sizes and mix similar to Three Meal Restaurant.<br />

REV. MARCH 2006 62<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

2.6. Functional Diagram: Food and Beverage<br />

Lobby Bar<br />

Main<br />

Kitchen<br />

Three Meal<br />

Restaurant<br />

Specialty<br />

Restaurant<br />

LOBBY<br />

Lobby<br />

Lounge<br />

REV. MARCH 2006 63<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

3. RECREATIONAL AREAS<br />

3.1. Health Club Reception<br />

The reception (approximately 300 ft 2 – 27.8 m 2 ) serves as the main arrival and control<br />

point for the recreation area. It should accommodate waiting, reception and registration<br />

areas. Other specific needs shall be determined by the specific program requirements.<br />

The reception area should be easily accessible by the guest. It should be adjacent to the<br />

swimming pool in order to share staff with other recreation areas and visible from the<br />

hotel public circulation area.<br />

The reception desk (approximately 14’0” - 4.3 m long) will have the following:<br />

a) Guest safety deposit boxes (allow 20)<br />

b) Telephone outlets<br />

c) Computer terminals, printers and duplex electrical outlets (all<br />

UPS)<br />

d) Duplex electrical outlets<br />

e) Monitor for CCTV’s in cardiovascular and weight rooms<br />

f) Buzzer for emergency button at steam and sauna rooms (with<br />

automatic roll over to telephone operators’ room if not answered<br />

within 30 seconds)<br />

g) Lockable drawers and cupboards. Cupboards to have adjustable<br />

shelving<br />

h) Lighting level and back ground music volume controls.<br />

3.2. Guest Lounge<br />

In properties with larger health clubs a relaxation lounge is required. Also in some<br />

hotels, especially resorts, a lounge is required for guests arriving before their rooms are<br />

ready, or whose flights departures are after normal check out times.<br />

This lounge together with the locker rooms and showers enable guests to freshen up,<br />

change and use the hotel facilities even though their room is not available. The lounge<br />

should also provide a quiet area for guests to read or just relax. It should be located<br />

adjacent to the club reception area and requires the following features:<br />

a) Telephone outlets<br />

b) Duplex electrical outlet<br />

c) TV with DVD/VCR<br />

d) Central stereo system with ceiling audio speakers<br />

REV. MARCH 2006 64<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Guest Lounge (continued)<br />

e) Local point, i.e. fireplace<br />

f) Seating for 15-20 guests. Dresser unit for coffee/tea/juice set up<br />

g) Magazine/newspaper display rack<br />

h) Pantry (approximately 100 ft 2 - 9.3 m 2 ) with domestic refrigerator,<br />

coffee maker, stainless steel sink, counters and cupboards as well<br />

as duplex electrical outlets and telephones.<br />

3.3. Guest Luggage Storeroom<br />

Located adjacent to reception (approximately 100 ft 2 - 9.3 m 2 ) with the following<br />

features:<br />

a) Heavy duty shelving 2’6” (0.8 m) wide (full length of two sides of<br />

room) x full height of room for guests’ suitcases<br />

b) Hanging rod 1” (2.5 cm) diameter x 6’0” (1.8 m) long for<br />

hanging garment bags<br />

c) Full height adjustable shelving 1’6” wide x 4’0” (0.5 x 1.2 m)<br />

long.<br />

3.4. Health Club General Requirements<br />

The purpose of these areas (allow a minimum of 6,000 ft 2 – 558 m 2 ) is to provide guest<br />

with exercise, cardiovascular, weight lifting equipment, fitness and relaxation activities.<br />

The facility will include lockers, changing rooms, showers, toilets, steam and saunas.<br />

The facilities should have direct access to the swimming pool activities.<br />

Exterior views are very desirable.<br />

3.5. Locker Rooms<br />

Locker rooms should be designed to the highest quality in keeping with the level<br />

attained in the hotel public areas. Wet areas should be kept separate from the dry areas<br />

and the guest should not have to cross one to reach the other.<br />

The locker rooms should include the following features:<br />

a) Stand-up grooming centres with clean towel storage, bins for<br />

used towels, under counter refrigerators and duplex electrical<br />

outlets for hair dryers<br />

b) Clothes rods and robe hooks, as well as open slatted shelving for<br />

shoes<br />

c) Full length mirrors<br />

d) Swimsuit dryer connected to 110V x 20 <strong>amp</strong> direct connection<br />

REV. MARCH 2006 65<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Locker Room (continued)<br />

e) Excellent lighting<br />

f) Changing cubicles and benches<br />

g) Half size and full size wooden lockers<br />

h) House telephones<br />

i) TV’s with DVD’s in relaxation areas<br />

j) Plumbing fixtures and vanity areas to be design using the same<br />

criteria as the guestrooms and public areas<br />

k) Ensue adequate air changes in wet areas (negative pressure to<br />

prevent moist air transferring to dry areas).<br />

3.6. Massage Rooms<br />

Massage rooms (each approximately 150 ft 2 – 14 m 2 ) are to have concealed cove<br />

lighting with an independent dimmer switch and temperature thermostat. All walls are<br />

to be soundproofed to achieve a rating of STC 54. Flooring to be carpet tile. The ceiling<br />

is to have built-in audio speakers connected to a CD player (FF & E). Each massage<br />

room will have 2’0” wide x 4’0” long (0.6 x 1.2 m) counter with sink and storage<br />

cabinets above and below. Duplex electrical outlets and telephone outlet. Robe hooks<br />

and towel bars.<br />

3.7. Herbal Wrap Rooms<br />

These rooms (each approximately 250 ft 2 – 23.2 m 2 ) are to have concealed cove lighting<br />

with independent dimmer switch and temperature thermostat. All walls are to be<br />

soundproofed to achieve a rating of STC 54. The ceiling is to have built-in audio<br />

speakers connected to a CD player (FF & E). Flooring to be stone. The room is also to<br />

have a 2’0” wide x 4’0” long (0.6 x 1.2 m) counter with sink and storage cabinets above<br />

and below. Duplex electrical outlets and telephone outlet. Robe hooks and towel bars.<br />

In addition, a storage/preparation room (approximately 150 ft 2 – 13.9 m 2 ) is required<br />

with the following features:<br />

a) 2’0” wide x 6’0” long (0.6 x 1.8 m) counter with stainless steel<br />

double bowled sink and storage cabinets above and below<br />

b) Storage shelving<br />

c) Ice machine<br />

d) Hydro collator<br />

e) Three-tier trolley<br />

f) Additional exhaust as required for herb cooker.<br />

REV. MARCH 2006 66<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

3.8. Wet Treatment Rooms<br />

The interior walls and floor of the wet treatment rooms (approximately 150 ft 2 – 14 m 2 )<br />

should be finished with stone. Concealed cove lighting with independent dimmer switch<br />

and temperature thermostat. All walls are to be soundproofed to achieve a rating of STC<br />

54. The room is also to have a 2’0” wide x 4’0” (0.6 x 1.2m) long counter with sink and<br />

storage cabinets above and below. Duplex electrical outlets and telephone outlet. Robe<br />

hooks and towel bars.<br />

In addition the rooms are to have the following features:<br />

a) Vichy shower and table<br />

b) 4” (10 cm) Diameter stainless steel floor drain<br />

c) Shower cubicle (as per guestroom shower requirements).<br />

3.9. Sauna Room<br />

The interior of the sauna (approximately 120 ft 2 – 11.1m 2 ) should be finished<br />

throughout in selected cedar, including the floor with three tiers of seating, each 2’0”<br />

(0.6 m) wide. The double glazed entry door with a wooden handle both sides, is to open<br />

out. Adjacent to the outside of the entry door will be the temperature control (set to a<br />

maximum of 180 F – 82 C), rob hooks and the emergency buzzer (connected to the<br />

reception desk).<br />

3.10. Steam Room<br />

The walls and ceiling (sloped) of the steam room (approximately 120 ft 2 – 11.1 m 2 ) is to<br />

be constructed in sand and cement plaster and finished with ceramic tiles. The floor and<br />

seating areas are to have non-slip stone finish. A tempered glass entry door with<br />

wooden handle both sides, is to open out. Adjacent to the outside of the entry door will<br />

be the temperature control, rob hooks and the emergency buzzer (connected to the<br />

reception desk). The floor is to incorporate a floor drain and the steam source requires<br />

access for regular maintenance.<br />

3.11. Janitor’s Closet<br />

A janitor’s closet (approximately 120 ft 2 – 11.1 m 2 ) will have the following features:<br />

a) Floor sink with hot and cold service sink faucet, with ceramic tile<br />

surround<br />

b) Adjustable shelving 16” wide by 4’0” (04. x 1.2 m) (minimum of<br />

four shelves)<br />

c) Mop rack<br />

d) Vinyl floor and vinyl baseboard<br />

e) Wall mounted telephone.<br />

REV. MARCH 2006 67<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

3.12. Swimming Pools and Whirlpool<br />

Provide swimming pools and whirlpool facilities in relation to specific program<br />

requirements (consideration for outdoor pools to be determined in relation to project<br />

location/climate). The water purification system should be a chlorine automatic feed<br />

system with modular cartridge filters. It is essential that any vibration arising from the<br />

swimming pools and whirlpool mechanical equipment be not transmitted to the building<br />

structure.<br />

Combination of lap pool, wadding pool and whirlpool to be considered in relation to<br />

specific program requirements.<br />

Water surface to be (approximately 1,500 ft 2 – 140 m 2 ) (Resort 10,000 ft 2 – 930 m 2 )<br />

minimum or as required by the specific program requirements. Maximum pool depth to<br />

be 4’6” (1.4 m). The water temperature to be regulated to a maximum of 80F (27C).<br />

A separate pool area (Resorts) should be provided for children (approximately 800 ft 2 –<br />

74 m 2 ) with water level from 2’ 0” (0.6 m) to maximum of 3’ 0” (0.9 m) deep. The<br />

pool should incorporate an area for small children where the water is from 0’ 0” to 1’ 0”<br />

(0 to 0.3 m) deep. Locate children’s pool remote from main pool(s) to minimise<br />

disturbance of adult guests.<br />

Access must avoid circulation through the main lobby. The facilities must be adjacent to<br />

the spa/health club to share staff and locker facilities. Proximity to the guestroom<br />

elevator core is required. Access to sunny location and exterior view is important.<br />

Water Depths:<br />

At shallow end 3’ 0” (0.9 m)<br />

At main drain (1/3 of pool length from deep end) 4’6” (1.4 m)<br />

At deep end 4’ 0” (1.2 m)<br />

Whirlpool 2’ 10” (0.8 m)<br />

Plunge Pool 4’ 0” (1.2 m)<br />

The whirlpool (approximately 250 ft 2 – 23.2 m 2 ) should be exceptionally large and<br />

unusual in shape, preferably not circular. It will generally be recessed in the pool deck<br />

although the surrounding wall may be up to 2’ 0” (0.6 m) high, i.e., whirlpool recessed<br />

1’ 6” (0.5 m) into pool deck. The wall should be wide enough to permit comfortable<br />

seating on top. Maximum depth should be 3’6” (1.1m).<br />

The water temperature to be regulated to a maximum of 105F (40C).<br />

An additional 50% extra aerator outlets shall be installed in the whirlpool in addition to<br />

minimum quantity recommended by whirlpool equipment suppliers to provide a really<br />

lavish aeration system. These outlets should be mounted 6” and 12” (15 x 30 cm)<br />

above the seat. Whirlpool aeration control shall be by means of a 15-minute time switch<br />

located near the whirlpool at 5’ 0” (1.5 m) to centre line above finished floor level.<br />

REV. MARCH 2006 68<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Swimming Pools and Whirlpool (continued)<br />

Where the switch may not be located near the whirlpool due to local code requirements,<br />

it shall be located outside the pool attendant’s office in a clearly visible position.<br />

Underwater lights to be provided at least equal to local code requirements and not less<br />

than two fixtures in the swimming pool and one in each plunge pool. No underwater<br />

light is required in the bottom of the whirlpool. Dry niche underwater lights are<br />

preferred.<br />

The plunge pool (approximately 130 ft 2 – 12 m 2 ) should have the water temperature to<br />

be regulated to a maximum of 80F (27C)<br />

Swimming pool, whirlpool and plunge pool to be finished with non-slip ceramic tiles.<br />

Depth markings indicating 3’0” , 4’0” and 4’6” (0.9m, 1.2 m and 1.4 m) are to be<br />

located on the pool deck and pool sides adjacent to pool edge on both long sides of<br />

pool.<br />

Lane and turn markings shall be in tile and in accordance with international standards.<br />

Minimum depth of water in swimming lanes is 3’ 6” (1.1 m).<br />

All built-in accessories to be stainless steel. Access ladder required at each end of<br />

swimming pool and plunge pool and handrails to whirlpool. Provide removable<br />

handicapped lift to pool.<br />

Vacuum cleaning system accessories connected to pool water circulation system and a<br />

water testing kit.<br />

Life grab hook with pole, life rings and wall mounting supports are to be provided in<br />

accordance with the current NFPA codes.<br />

All indoor pools shall be heated and air conditioned as required by local climate to<br />

maintain an air temperature of 80F (27C). All pools shall be de-humidified to minimize<br />

damage from condensation.<br />

Wall mounted emergency telephone and wall mounted house phone.<br />

The wall surrounding the swimming pool area in indoor pools must be carried up to the<br />

structure and sealed to prevent migration of chlorine odors and moisture to adjacent<br />

areas.<br />

The pool deck area design and paving finish are very important in resorts. Adequate<br />

space must be provided for chaise lounges and these areas must be arranged in a way<br />

that creates a sense of privacy for groups of chaises. Landscaping and changes in level<br />

are an excellent way of achieving this result. Locate some chaise lounges on grassed<br />

areas. 50% of pool deck area should be shaded – cabanas, trellis, umbrellas, landscaping<br />

Specific design requirements are as follows:<br />

a) Needs approximately one chaise for each guestroom plus 50%<br />

more for peak season<br />

REV. MARCH 2006 69<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Swimming Pools and Whirlpool (continued)<br />

b) Chaises arranged in groups of two with small table between<br />

c) Sufficient cabanas should be provided for 25% of chaises.<br />

There should be a minimum of one service cabana and it should contain a 6’ 0” x 8’ 0”<br />

x 2’ 0” (1.8 x 2.4 x 0.6 m) L-shaped storage counter (provided by the General<br />

Contractor) and finished with a material to withstand weather, with sufficient storage<br />

shelving with lockable hinged doors for one day’s towel par – two towels per chaise x<br />

two changes per day, i.e., total of four per chaise per day. (200 Towels = approx. 5’ 0”<br />

x 5’ 0” x 2’ 0” – 1.5 x 1.5 x 0.6 m) and two lockable drawers, 4” (10 cm) deep. Also,<br />

two telephone outlets and computer system outlet, as well as space for dirty towel cart<br />

(40” l x 29” w x 39” h – 102 x 74 x 99 cm), garbage pail, cold water dispenser and ice<br />

chest.<br />

All service cabanas must have good access route to and from service cabanas for towel<br />

delivery and collection. Provide shower and footpath at location of entry to pool deck<br />

from beach area and at all pathways leading from beach.<br />

For maintenance purposes provide a ¾” (1.9 cm) hose bibb at 150 ft (45 m) centers for<br />

washing deck together with a waterproof duplex outlet.<br />

Provide weatherproof speakers with volume control at pool bar.<br />

Proper windbreaks – glass screens, landscaping, berms – must be provided to shelter<br />

deck. Wind also dictates care when sighting waterfalls, fountains, etc.<br />

3.13. Outdoor Recreational Facilities<br />

Facilities may include, but are not limited to the following:<br />

Tennis courts:<br />

a) All courts shall be lighted using the latest non-glare lighting<br />

fixtures<br />

b) Plastic coated metal fence 10’0” high with 4’0” wide (3.0 x 1.2 m)<br />

access gate to surround each court. Where two courts are side by<br />

side, fencing between courts should be removable for possible<br />

tournament seating<br />

c) Allow for a covered seating at side of courts<br />

d) Duplex electrical outlet at each end of court for ball machine<br />

e) Hose bibb for washdown and court maintenance<br />

f) Waiting area with duplex electrical outlets for small fridge<br />

(FF&E), washrooms, telephones and storeroom (approximately<br />

100 ft 2 – 9.3 m 2 )<br />

REV. MARCH 2006 70<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Outdoor Facilities (continued)<br />

g) Lockable shelving (clean towels) and receptacle for used towels<br />

h) Tennis pro shop (approximately 400 ft 2 – 37 m 2 ) with retail area,<br />

office, workroom for restringing, etc. and storeroom. Clear view of<br />

tennis courts is essential.<br />

Some resorts may have half court size volleyball/basketball court. These are to have<br />

similar amenities as for tennis courts i.e. lighting, washrooms, etc.<br />

Resort beach activities should have access at one central point. The beach services<br />

pavilion and showers should be located at this point. The access route should be clearly<br />

separate from the pool area and pool bar, so that beach traffic does not compromise<br />

these areas. Service access to the beach for maintenance equipment, supplies, etc.<br />

should be completely separate from the guest access.<br />

A beach pavilion adjacent to the main access route from the hotel to the beach with a<br />

good view of the entire beach area<br />

The pavilion should have storage space for water sport activities, lockable drawers and<br />

cupboards for beach related items (suntan lotion, glasses, etc) as well as telephone<br />

outlets and duplex electrical outlets (some UPS), computer systems outlets,<br />

undercounter refrigerators (FF & E) for cold water and facial towels and clean towel<br />

storage (allow 12 ft 2 – 1.1 m 2 per 100 beach chairs) and used towel carts<br />

(approximately 3’0” x 3’0” – 0.9 x 0.9 m)<br />

Storage (approximately 200 ft 2 – 18.6 m 2 ) area adjacent the pavilion for beach chairs<br />

and beach sport related equipment<br />

Service cabanas, one per 1,000 ft (305 m) of beach).<br />

3.14. Indoor Recreational Facilities<br />

Facilities may include:<br />

a) Billiard/Pool room<br />

b) Table Tennis room<br />

c) Racquet/Squash courts<br />

Locate facilities near the recreation area to share staff and control point.<br />

A high noise factor generated by these games and their participants should be taken into<br />

account when locating these facilities.<br />

REV. MARCH 2006 71<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

3.15. Arcade & Computer Games<br />

Facilities may include:<br />

a) Game/Arcade room<br />

b) Computer game room<br />

Locate facilities near the reception area to share staff and control point.<br />

A high noise factor generated by these games and their participants should be taken into<br />

account when locating these facilities.<br />

REV. MARCH 2006 72<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

4. RETAIL<br />

4.1. Retail Shops<br />

The design of these units, their lighting and the stores in general must reflect the same<br />

quality level as the other public areas of the hotel. The retail shops are another area<br />

where the hotel can set itself ahead of the competition and the same quality level, as the<br />

premiere “designer” stores is essential.<br />

The use of display windows and vitrines should be maximised complete with special<br />

display lighting. Provide only one entry/exit per store.<br />

A combination of built-in and freestanding display units are required.<br />

Locate the following features in an area that has clear view of all parts of the store, but<br />

away from the main entrance:<br />

a) Adequate counter space for wrapping<br />

b) Jewellery display area incorporating glass top<br />

c) Concealed lighting<br />

d) Display shelves on full extension glides<br />

e) Down lighting at cash register and counter<br />

f) Power for jewellery display lighting<br />

g) Duplex (UPS) outlet<br />

h) Computer cable connection<br />

i) Two telephone outlets<br />

j) Duplex electrical outlets.<br />

A changing area (approximately 15 ft 2 – 1.4 m 2 ) is required in each clothing store.<br />

Brightly light, full-length mirror, small bench, two robe hooks and small hook for<br />

shoehorn.<br />

Storage drawers should be on full extension, heavy duty glides with proper pull<br />

hardware commensurate with weight and size of drawer.<br />

Typically glass shelving is better than solid shelving as it has a brighter look and gives a<br />

more open display. Solid, sloping shelving however, is fine for newspapers and<br />

magazines.<br />

All shelving should be adjustable with continuous, recessed support track for full height<br />

of display units.<br />

REV. MARCH 2006 73<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Retail Shops (continued)<br />

Provide storeroom and manager’s work area (approximately 150 ft 2 – 13.9 m 2 or 15%<br />

of store areas) whichever is the larger. Storage will need to be higher in remote<br />

locations to a maximum of 20%. Storeroom should have direct access from service<br />

corridor as well as direct access to retail shop. Provide adjustable shelving throughout -<br />

storage provided at the bottom of display units should be in drawers on full extension<br />

guides, not on shelves behind doors.<br />

Store Manager’s work area requires the following features:<br />

a) Duplex electrical outlets (UPS)<br />

b) Computer cable connection<br />

c) Telephone outlet<br />

d) Duplex electrical outlets.<br />

General down-lighting as well as display, accent and decorative lighting; all on<br />

dimmers located in manager’s work area.<br />

General-purpose duplex electrical outlets for store displays and housekeeping.<br />

Background music with control in manager’s work area.<br />

4.2. Beauty Salon<br />

The salon (approximately 500 ft 2 – 46.5 m 2 ) will provide full beauty services including<br />

hairdressing, manicure, pedicure and private facial rooms. It will include its own<br />

manager’s office and storage room. The entire salon will be built out by the tenant,<br />

although the General Contractor will provide floor drains and “rough-ins” for all<br />

services.<br />

Easy and direct access from the main circulation or as an integral part of the spa and<br />

health club.<br />

REV. MARCH 2006 74<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

5. BALLROOMS AND MEETING ROOMS<br />

5.1. General Requirements<br />

Ballrooms are to be designed to suit the requirements of the incentive group market.<br />

These groups use the rooms for major promotions as well as normal dinner and social<br />

functions.<br />

The Ballroom/meeting area foyer must relate directly with the main entry lobby by the<br />

public corridor. The requirements will be similar to those expressed under the main<br />

entry lobby section of these Design Standards.<br />

The circulation area serves as the main arrival and control point and it should<br />

accommodate business center, meeting coordinator, coat checkroom, phone and public<br />

washroom facilities.<br />

The lobby circulation links the pre-function area to the facility's main entrance and to<br />

the hotel's public circulation. The coat-check room, guests’ washrooms and telephones<br />

should be adjacent to it.<br />

Entrance to have direct access to guestroom service (luggage) elevators.<br />

All exposed grilles, diffusers, sprinkler escutcheons, speakers, etc shall be factory<br />

painted to match adjacent surface.<br />

Ductwork behind grilles and diffusers to be painted matt black.<br />

Where high temperature producing equipment is located beneath, above or adjacent to<br />

public areas, a special insulating wall or ceiling is to be provided to prevent heat<br />

transmission to these areas.<br />

Where very noisy and/or vibrating equipment is located beneath, above or adjacent<br />

public areas, a special isolating wall or ceiling is to be provided. This wall or ceiling is<br />

in addition to providing antivibration mountings for individual pieces of equipment.<br />

All walls to have a sound rating of not less than 54 dB (FSTC 54).<br />

5.2. Ballroom Pre-function Space<br />

Pre-function space (approximately 40% of net ballroom area) should accommodate<br />

group reception and registration area and provide assembly space for ballrooms and<br />

meeting rooms at beginning, intermission and post function activities and be private and<br />

separate from the hotel general circulation areas.<br />

Portable group registration desks (FF & E) shall have the following voice/data<br />

provisions should be concealed in the wall behind a baseboard access panel at each desk<br />

location:<br />

a) Duplex electrical outlets (UPS) for computer system (CRT,<br />

keyboard and printer)<br />

REV. MARCH 2006 75<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Ballroom Pre-function Space (continued)<br />

b) Computer cable outlets (computer and printer)<br />

c) Duplex electrical outlets.<br />

Multi-line telephone outlets for credit card verifier, located as follows:<br />

a) Main ballroom foyer - 4 desks (2 in each subdivision)<br />

b) Junior ballroom foyer - 2 desks (2 in each subdivision)<br />

c) Ballroom courtyard - 2 desks (2 in each subdivision).<br />

A (temporary) service bar at one end with direct access to the service corridor.<br />

Exterior views from the pre-function space are desirable in urban hotels and essential in<br />

resorts.<br />

5.3. Ballroom Foyer Requirements<br />

Each ballroom foyer, or where divisible into halves, each ballroom foyer subdivision<br />

must be able to function independently i.e. there must be provision for each to locally<br />

control the following features:<br />

a) Background music control (local control)<br />

b) Sound reproduction through background music speakers in lieu of<br />

background music (local control)<br />

c) Lighting dimming (local control)<br />

d) Supply and exhaust air system (local thermostat)<br />

e) Electrical services as shown on Fairmont Hotels and Resorts<br />

Standard Details<br />

f) Group registration requirements as shown on Fairmont Hotels and<br />

Resorts Standard Details.<br />

5.4. Main Ballroom Requirements<br />

Ballrooms are to be designed to suit the requirements of the incentive group market,<br />

which typically uses these rooms for major promotions as well as normal dinner and<br />

social functions.<br />

The banquet seating capacity (approximately 10 ft 2 – 0.9 m 2 /guest) will be affected by<br />

size and efficiency of configuration and is to be verified against an actual table and<br />

seating layout to ensure that the capacity required in specific program requirements is<br />

achieved.<br />

The main ballroom will be adjacent to the pre-function space and linked on the rear to<br />

the service corridor and main kitchen.<br />

REV. MARCH 2006 76<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Main Ballroom Requirements (continued)<br />

Provide windows where possible, yet room must be capable of complete black out.<br />

Minimum clear height of 18' 0" ( 5.5 m)under chandeliers and lowest ceiling level.<br />

All walls, including movable partition walls to have a sound rating of not less than 54<br />

dB (FSTC 54).<br />

Clear automobile access route must be provided to the ballroom together with an 8' 0"<br />

(2.4 m) wide pair of entry doors or removable panel.<br />

Ceiling design must incorporate anchor/suspension points for scenery etc. and power<br />

outlets/suspension bars for special lighting. Align pot lights with structural beams or<br />

special support beams - with the removal of the light can, the beam can be used to<br />

support a lighting truss, scenery anchors etc.<br />

A motorised projection screen is required at each end of the ballroom. The screen<br />

(approximately 14' 0" wide x 14' 0" high – 4.3 x 4.3 m)and the retaining box shall be<br />

mounted above the ceiling so that the screen is completely concealed when not in use.<br />

The switch operating the screen will be mounted on the wall in the adjacent control<br />

niche. The screen shall be without borders and with matt white reflective surface.<br />

Main ballroom to be sub-divisible into halves (double layer of partitioning) and thirds<br />

(single layer of partitioning).<br />

Each ballroom subdivision must be able to function independently i.e. there must be<br />

provision for each to locally control:<br />

a) Background music volume and on/off<br />

b) Sound reproduction through background music speakers in lieu of<br />

background music<br />

c) Head table and runway lighting<br />

d) General lighting dimming<br />

e) Remote control of lighting should also be available to enable light<br />

levels to be controlled by an audio-visual operator running a slide<br />

show.<br />

Each ballroom subdivision must incorporate:<br />

a) Supply air system with local control thermostat<br />

b) Exhaust air system<br />

c) Baseboard electrical requirements as shown on Fairmont Hotels<br />

and Resorts Standard Details.<br />

REV. MARCH 2006 77<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Main Ballroom Requirements (continued)<br />

d) One light fixture circuit, three way switched from the main<br />

entrance door and the service door<br />

e) Two pairs of entrance and two pairs of service doors (6' 6" – 2 m<br />

wide overall). One pair of service doors to open into ballroom.<br />

Ballrooms of approximately 7,000 ft 2 – (650 m 2 ) and larger will include two 200-<strong>amp</strong> x<br />

208V 3-phase breaker panels in the service corridor behind each ballroom subdivision,<br />

i.e., a total of 6 outlets. Acoustically rated conduit for connection between inside of<br />

ballroom and service corridor below each panel is to be provided.<br />

a) The service corridor behind the ballrooms to be painted a dark<br />

color and should have at least the following width:<br />

i) 4,000 to 7,000 ft 2 (372 to 650 m 2 ) ballroom,<br />

allow 12' 0" (3.7 m) wide<br />

ii) 7,000 to 10,000 ft 2 (650 to 929 m 2 ) ballroom,<br />

allow 15' 0" (4.6 m) wide<br />

iii) 10,000 to 15,000 ft 2 (929 to 1,394 m 2 ) ballroom,<br />

allow 18' 0" (5.5 m) wide.<br />

5.5. Junior Ballroom<br />

Fairmont Hotels & Resorts Design Standards for the main ballroom apply equal to the<br />

junior ballroom.<br />

The junior ballroom (approximately 50% of main ballroom) will provide function<br />

spaces for intermediate sized groups. It shall accommodate multi-purposes uses and<br />

may be divisible in half (single layer of partitioning) and is to have rear access from the<br />

service corridor and main kitchen.<br />

Minimum ceiling height shall be 18’0” (5.5 m) clear to underside of chandelier.<br />

Provide windows where possible.<br />

5.6. Meeting Rooms<br />

Provide meeting rooms (approximately 15 ft 2 – 1.4 m 2 /person) for smaller groups<br />

located adjacent to the pre-function areas. Consider a wider corridor in front of the<br />

meeting rooms as the pre-function space. Windows in meeting rooms are desirable in<br />

urban hotels. They are essential in a majority of meeting rooms for resort hotels.<br />

All walls to have a sound rating of not less than 54 dB (FSTC 54).<br />

All of the meeting rooms are to have direct back-of-the-house service.<br />

Minimum clear height of 12’ 0” ( 3.7 m) under chandeliers and lowest ceiling level.<br />

REV. MARCH 2006 78<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

Meeting Rooms (continued)<br />

Marker boards are to be provided by and built in by the general contractor. The marker<br />

boards are to be white porcelain surfaced steel for use with magnets and markers,<br />

complete with full length and anodized aluminum pen marker ledge. Include two<br />

complete sets of magnets for each board.<br />

Cork boards, where specified for bulletin boards, orientation units etc., are to be<br />

supplied and installed by the general contractor. They are to be 1/4" (0.6 cm) thick in<br />

widths as wide as possible with colours selected by the interior designer.<br />

Projection screens are to be provided and installed by the general contractor. The size is<br />

to be specified by the Interior Designer together with the Audiovisual Consultant. The<br />

matt white screens are to have patented automatic tensionizer, be electrically operated<br />

with self-storing housing in a recess within the ceiling.<br />

5.7. Meeting Planners Room<br />

Incentive group organizers or their clients typically send a Meeting Planner with each<br />

group to manage the group’s day-to-day activities and coordinate with the hotel where<br />

requirements change or additional facilities are required. These coordinators require a<br />

private area in which to work. Each hotel may have a number of groups at one time and<br />

therefore, two group planners offices shall be provided in each property. They should<br />

both be adjacent to the main meeting areas but separate from each other.<br />

Design requirements are as follows features:<br />

a) Office (approximately 150 ft 2 – 13.9 m 2 ) with four duplex outlets<br />

and three telephone outlets (one for fax machine and one for lap<br />

top adjacent to a duplex outlet)<br />

b) Storeroom (approximately 50 ft 2 – 4.6 m 2 ) entered directly off the<br />

office. Storeroom to have five 18" (46 cm) wide adjustable<br />

shelves for full length of two walls.<br />

5.8. Boardrooms<br />

Boardrooms (approximately 300 ft 2 – 27.9 m 2 ) shall provide function spaces for<br />

executive meetings. They shall have upgraded interior finishes.<br />

The functional relationship is similar to meeting rooms and Fairmont Hotels and<br />

Resorts Design Standards apply equally.<br />

Provide windows where possible.<br />

All walls to have a sound rating of not less than 54 dB (FSTC 54).<br />

REV. MARCH 2006 79<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

5.9. Conference Facility Storage<br />

Furniture and equipment storage (approximately 20% of net meeting area excluding<br />

foyers) for the ballrooms and meeting facilities is separate from the main hotel storage<br />

room.<br />

REV. MARCH 2006 80<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

5.10. Functional Diagram: Conference Facilities<br />

Conference<br />

Centre Storage<br />

Banquet<br />

Kitchen<br />

Main<br />

Ballroom<br />

Junior<br />

Ballroom<br />

Meeting Rooms<br />

and<br />

Boardrooms<br />

Pre-Function Pre-Function Pre-Function<br />

Public Circulation<br />

Meeting<br />

Coordination<br />

Office<br />

Public<br />

Washrooms<br />

Business<br />

Centre<br />

Conference Centre<br />

Lobby<br />

Public<br />

Phones<br />

Coat Check<br />

Room<br />

Conference<br />

Centre<br />

Entrance<br />

Lobby<br />

REV. MARCH 2006 81<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

5.11. Public Areas Standards Details<br />

Page<br />

TYPICAL DOORMAN’S BUILT-IN-STATION 83<br />

TYPICAL REGISTRATION DESK 84<br />

TYPICAL REGISTRATION DESK –SECTION A 85<br />

TYPICAL REGISTRATION DESK –SECTION B 86<br />

TYPICAL REGISTRATION DESK –SECTION C 87<br />

TYPICAL CONCIERGE DESK 88<br />

TYPICAL CONCIERGE DESK – SECTION A 89<br />

TYPICAL CONCIERGE DESK – SECTION B 90<br />

TYPICAL CONCIERGE DESK – SECTION C 91<br />

TYPICAL CONCIERGE DESK – SECTION D 92<br />

TYPICAL GUEST SAFETY DEPOSIT BOX ROOM 93<br />

TYPICAL GUEST SAFETY-DEPOSIT BOXES 94<br />

TYPICAL CONCIERGE WORK/STORAGE ROOM LAYOUT 95<br />

TYPICAL CONCIERGE WORK/STORAGE ROOM ELEVATIONS 96<br />

TYPICAL HEALTH CLUB RECEPTION DESK 97<br />

TYPICAL MASSAGE ROOM 98<br />

TYPICAL HEALTH CLUB SHOWER ENCLOSURE LAYOUT 99<br />

TYPICAL POOL SERVICE CABANA 100<br />

TYPICAL MEETING ROOM AND BALLROOM<br />

AUDIO VISUAL & ELECTRICAL LEGEND 101<br />

TYPICAL MEETING ROOM AND BALLROOM AUDIO VISUAL<br />

AND ELECTRICAL SYMBOLS AND COMPONENTS 102<br />

TYPICAL MEETING ROOM ELECTRICAL REQUIREMENTS 103<br />

TYPICAL BALLROOM ELECTRICAL REQUIREMENTS 104<br />

LAYOUT FOR BALLROOM PRE-FUNCTION 105<br />

TYPICAL MEETING ROOM & BALLROOM CONTROL NICHE 106<br />

TYPICAL MEETING ROOM, BALLROOM & PREFUNCTION<br />

BASEBOARD ACCESS PANEL 107<br />

TYPICAL MEETING ROOM ORIENTATION UNIT 108<br />

REV. MARCH 2006 82<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 83<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 84<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 85<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 86<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 87<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 88<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 89<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 90<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 91<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 92<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 93<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 94<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 95<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 96<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 97<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 98<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 99<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 100<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 101<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 102<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 103<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 104<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 105<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 106<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 107<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

REV. MARCH 2006 108<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

C. GUESTROOM AREAS<br />

1. CORRIDORS AND CIRCULATION<br />

1.1. General Requirements<br />

Provide a circulation corridor for guests and housekeeping at every Guestroom levels<br />

including the Entrée Gold level. Provide a lobby area in front of the passenger elevators.<br />

Doors to service areas to be recessed to prevent obstruction of guest traffic flow. All<br />

service to open from service area into guest corridor. These doors are to be finished to<br />

match guestroom entrance doors.<br />

Twistlock electrical receptacles at 40’0” (12.2 m) centers for maintenance at 12”<br />

(30 cm) AFFL.<br />

Duplex electrical outlets at 22” (56 cm) on center line AFFL at each furniture<br />

arrangement for desk lighting.<br />

All exposed grilles, diffusers, sprinkler escutcheons, speakers, etc shall be factory<br />

painted to match adjacent surface.<br />

Ductwork behind grilles and diffusers to be painted matt black.<br />

Where very noisy and/or vibrating equipment is located above or below guestrooms, a<br />

special isolating ceiling shall be provided. This ceiling is in addition to providing antivibration<br />

mountings for individual pieces of equipment.<br />

Transparent ½” x ½” (1.3 x 1.3 cm) corner guards shall be applied to all exposed<br />

exterior angles.<br />

Corridor: Minimum width of 6’0” (1.8 m).<br />

Provide a setback of 1’0” (0.30 m) at guestroom entry doors.<br />

Bulkhead: Minimum height of 8’0” (2.54 m)<br />

Length of corridor and dead-end condition: As per the governing bylaws.<br />

1.2. Elevator Lobby<br />

Elevator Lobby dimensions:<br />

a) Minimum width of 10' 0" (3.1 m) for single loaded elevator lobby<br />

b) Minimum width of 12' 0" (3.7 m) for double loaded elevator<br />

lobby<br />

Ceiling Height: Minimum height of 9’ 0” (2.7 m) to under slab, with coves or<br />

articulated ceiling in elevator lobbies<br />

The elevator lobby should be central to guestrooms served.<br />

Provide exterior views where possible from the elevator lobby.<br />

REV. MARCH 2006 109<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Elevator Lobby (continued)<br />

Provide ceiling coves and chandeliers together with marble trim around elevator<br />

entrances and painted or etched design on elevator doors.<br />

Duplex electrical outlet and telephone outlet at furniture arrangement mounted 22” (56<br />

cm) AFFL.<br />

1.3. Guestroom Support<br />

Provide space for guestroom support facilities and guests convenience, including:<br />

a) Self-service, water-cooled “Manitowoc QPA- 310” (or other equal<br />

and approved) ice dispensing machine in enclosed room. A solid<br />

core door is to be provided at the entrance to the room, together<br />

with full height millwork panels, hinged on the walls, mounted<br />

flush with the front face and installed on either side of the<br />

centrally located ice cube dispensing machine. Vinyl floor<br />

covering below and up to 2’0” (0.6 m) in front of the icedispensing<br />

machine, with the remainder of the area carpeted.<br />

Acoustic ceiling tiles on the entire wall and ceiling surface around<br />

unit to absorb equipment generated noise. The remainder of the<br />

room is to have drywall ceiling. All necessary services are to be<br />

provided to operate the ice dispensing machine together with ½”<br />

(1.3 cm) indirect copper drain lines from ½” (1.3 cm) F.P.T. sump<br />

drain and ½” (1.3 cm) F.P.T. melting tray drain and terminate at<br />

combination funnel floor drain. The room is to have a ceiling<br />

exhaust grille as a louvered door is unacceptable<br />

b) Housekeeping, linen and mini bar storage with the following<br />

features:<br />

Minimum 8' 0" (2.5 m) clear in front of elevators for ease of access<br />

Lockable maids’ room with 18" (46 cm) wide shelving for consumables and 10' (3 m)<br />

of shelving required per 20 bedrooms. As well as a linen storage and control cabinet.<br />

Each half of the cabinet should contain enough linen for all rooms and the volume of<br />

each half should be calculated on the basis of 3 cu. Ft. (0.09 m 3 ) per room. Cabinets to<br />

be lockable and all guestrooms floor cabinets to be keyed alike<br />

REV. MARCH 2006 110<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Guestroom support (continued)<br />

Storage space for maids’ housekeeping appliances. Allow approx. 5 ft 2 (0.5 m 2 ) per<br />

thirteen bedrooms and 5 ft 2 (0.5m 2 ) of storage space for spare chairs etc. Hanging rod<br />

2’ 0” long (0.6 m) at 5' 6" (1.7 m) AFFL to hang spare bathrobes as well as three 6" (60<br />

cm) long straight “hooks” to hang spare coat hangers<br />

A 24" (76 cm) square lockable access door to 30" diameter linen chute<br />

A 2' 0" wide x 1' 6" deep x high 6' 0" (0.6 x 0.5 x 1.8 m) lockable storage cabinet with<br />

six adjustable shelves for personal bar supplies<br />

All shelving to be plastic laminate faced<br />

Two timber rubbing rails, one at the base and one 2’0” (0.6 m) on centerline AFFL and<br />

corner guard treatment to all walls in service elevator foyer<br />

Where service elevator foyers have exterior windows, lighting shall be incandescent and<br />

the windows shall have fixed drapery panels to blend with the adjacent guestroom<br />

windows<br />

Service sink with ceramic tile surround to 4' 0" (1.2 m) AFFL. Tiles to project one<br />

course beyond sides of sink. Mop rack mounted at 5’0” (1.5 m) AFFL over sink<br />

Exhaust air grille in both service elevator foyer and maids’ room. Supply air grilles or<br />

ceiling transfer duct from corridor as required by climate<br />

Duplex outlets for housekeeping<br />

A wall mounted house telephone<br />

Electrical panels, dimmer equipment, switchgear etc. located in a service area must<br />

have locked access panels to controls. This equipment must not be located in the<br />

maids’ room.<br />

c) Guest laundry (required for resort location only) room<br />

containing side by side washer and dryer with shelves above and<br />

4 ft. (1.2 m) long adjacent counter 2’0” (0.6 m) wide with<br />

stainless steel sink and cabinets below.<br />

REV. MARCH 2006 111<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Guestroom support (continued)<br />

d) Staff powder room. Allow a staff powder room in each<br />

housekeeping area together with a full length mirror 2' 0" x 6' 0"<br />

(0.6 x 1.8 m)<br />

e) Janitor’s closet (approximately 40 ft 2 – 3.7 m 2 with floor sink<br />

and mop rack adjacent to housekeeping area.<br />

1.4. Location<br />

All guestroom support areas are to be visually and acoustically remote from the<br />

guestroom corridors. Ice dispensing, vending machines and guests laundry spaces to be<br />

located near the elevator core in a separate room adjacent to the guestroom corridor.<br />

The housekeeping storage should be part of the service elevator core. Provide access to<br />

mechanical, electrical and communications service rooms located on each floor.<br />

REV. MARCH 2006 112<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

2. STANDARD GUESTROOMS<br />

2.1. General Requirements<br />

The standard guestroom provides working, relaxing and sleeping areas in the comfort of<br />

a one-module unit. Typically the percentage of standard guestrooms is approximately<br />

85% of total guestrooms keys, however amount may vary depending on market<br />

requirements.<br />

Orientation and planning of guestroom wings as to provide desirable views. Connecting<br />

doors will typically be required on the following basis: (i) Urban hotels 15% to 20% of<br />

rooms depending on anticipated group and weekend business and (ii) Resorts 25% to<br />

30% of rooms. Room connections should be approximately 90% king to double/double<br />

and 10% king to king, but it will vary depending on hotel location and total room mix.<br />

Walls between guestrooms, public corridors, elevator shafts and back-of-house areas to<br />

have a sound rating of not less than 54 dB (FSTC 54).<br />

2.2. Guestroom Areas<br />

a) One module/1 key<br />

b) Minimum net area of 442 ft 2 – 41 m 2 for a king room, 471 ft 2 – 44<br />

m 2 for a double/double room. (Areas include interior bathroom<br />

and closet partitions)<br />

c) Dimensions are measured from interior face of exterior wall and<br />

common walls w/corridor and adjacent guestrooms)<br />

d) Minimum internal dimensions:<br />

i) King rooms: 14’6 Wide x 30’ 6” Long (4.4 x 9.3 m)<br />

(Resort 14’6” x 32’6” – 4.4 x 9.9 m)<br />

ii) Double/double rooms: 14’6 Wide x 32’6” Long (4.4 m<br />

x 9.9 m) (Resort 14’6” x 34’6” – 4.4 x 10.5 m).<br />

2.3. Bedroom Area<br />

a) Minimum internal area:<br />

i) King rooms: 261 ft 2 (24 m 2 ) (Resort 290 ft 2 – 27 m 2 )<br />

ii) Double/double: 292 ft 2 (27 m 2 ) (Resort 319 ft 2 – 30 m 2 ).<br />

b) Minimum internal dimensions:<br />

i) King rooms: 14’6’’ Wide x 18’0’’ Long (4.4 m x 5.5 m)<br />

(Resort 14’6” x 20’0” – 4.4 m x 6.1 m))<br />

ii)<br />

Double/double rooms: 14’6’’ Wide x 20’0’’ Long<br />

(4.4 x 6.1 m) (Resort 14’6” x 22’0” – 4.4 x 6.7 m).<br />

REV. MARCH 2006 113<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

2.4. Bathroom Area<br />

2.5. Clear Ceiling heights<br />

2.6. Entry Door<br />

a) Minimum of 103 ft 2 (9.6 m 2 )<br />

b) Minimum internal dimensions: 8' 6” Wide x 12' 2” Long<br />

(2.6 x 3.7 m)<br />

a) Bedroom: Minimum 9’ 0’’ (2.7 m)<br />

b) Entrance Vestibule: Minimum 7’ 8’’ (2.3 m)<br />

c) Bathroom: Minimum 7’ 8’’ (2.3 m).<br />

a) A solid core flush main entry door with mouldings, size 1 ¾” thick<br />

x 3’0” wide x 7’0” high (4.4 cm x 0.9 m x 2.1 m)<br />

b) A Time Lox 2300 cardkey unit complete with selected handle and<br />

turning inside knob or lever type which will withdraw both latch<br />

and deadbolt<br />

c) Delayed action door closer<br />

d) Hardware as specified in Appendix 2<br />

e) Stone threshold<br />

f) Undercut door ¼” (0.6 cm) above threshold.<br />

2.7. Bathroom Doors<br />

a) Guestroom bathroom doors to be a pair of flush solid core doors 1<br />

3/8” thick x 2’0” wide x 7’0” high (3.7 cm x 0.6 m x 2.1 m),<br />

undercut 1” above floor finish with full height bevelled edges<br />

mirror set in applied mouldings, to bathroom side of each door and<br />

applied mouldings on the other side<br />

b) Hardware as specified in Appendix 2<br />

2.8. Connecting Doors<br />

a) Guestroom connecting doors (each door) to be solid core door with<br />

applied mouldings on bedroom side, 1 3/8” thick x 2’6” wide x<br />

7’0” (3.7 cm x 0.8 m x 2.1 m) high with a FSTC rating of 39<br />

b) Hardware as specified in Appendix 2<br />

REV. MARCH 2006 114<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Connection Doors (continued)<br />

c) Stone threshold<br />

d) Undercut door ¼” (0.6 cm) above threshold.<br />

2.9. Closets<br />

a) A minimum length of 5’0” (1.5 m) of hanging rod (Resort hotels<br />

8’0” – 2.4 m), mounted at 5’9” (1.8 m) AFFL as well as a full<br />

height shelf unit including a built-in safe mounted 4’0” (1.2 m)<br />

AFFL)<br />

b) A clear interior depth of 2’0” (0.6 m)<br />

c) Shelf 15” (38 cm) wide open wood slatted shelf, mounted at 6’2”<br />

(1.9 m) AFFL<br />

d) A pair (two pairs in Resort hotels) of 1 3/8” (1.1 m) solid core<br />

doors with applied mouldings on one side<br />

e) Two single hooks for shoe horn and clothes brush mounted 3’6”<br />

AFFL on side wall<br />

f) Each closet must incorporate an interior light operated by a<br />

pressure switch in the frame of each door. Where there are three or<br />

more doors pressure switches must be provided to at least two.<br />

g) Hanger for iron and ironing board.<br />

2.10. Windows<br />

a) An operable section is required in all guest bedroom windows.<br />

The type of opening section e.g. pivot, side hung sash or sliding,<br />

depends upon the architect’s proposed fenestration details with<br />

maximum opening set at 4” (10.1 cm)<br />

b) Cylinder locks must be provided to all sliding doors on ground<br />

floor terraces. Provide thumb turn on inside<br />

c) Sliding balcony doors should be not less than 8’0” wide and 8’0”<br />

(2.4 x 2.4 m) high<br />

d) Insect screens should be provided to all opening sections where<br />

they would be a problem for the guest<br />

e) A removable plywood drapery valance and wood blocking together<br />

with drapery tracks are required<br />

f) Sound penetration through windows must be addressed where<br />

guestrooms face onto busy streets, etc<br />

REV. MARCH 2006 115<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Windows (continued)<br />

2.11. Mechanical and Electrical<br />

g) Where sliding louvered panels are used in lieu of drapes, a locking<br />

device must be provided on the panels to maintain security when<br />

exterior sliding doors are open.<br />

a) Convectors and grilles with concealed fixings to be painted to<br />

match adjacent surface. Ductwork behind grilles to be painted<br />

matt black<br />

b) Access to the control valves, fan motors and fan scrolls will be<br />

through a 1’6” x 2’6” (0.5 x 0.8 m) return air grille<br />

c) The horizontal fan coil unit is to be designed with a three speed<br />

motor and sized so the unit will provide the required heating or<br />

cooling output when the motor is running at slow speed. The unit<br />

sound level is not to exceed NC30 at slow speed and NC35 at<br />

medium speed. The valves, coils and thermostats must be silent in<br />

operation. The fan coil unit motor must run continuously at the<br />

selected speed and not cycle off when the desired temperature is<br />

achieved<br />

d) Energy smart thermostats to be mounted 54” (137 cm) to centre<br />

line AFFL<br />

e) Incorporate switch in frame of balcony door in humid climates to<br />

close down FCU when door is opened for extended periods of<br />

time<br />

f) Electrical outlets in party walls to be offset by at least 1’0”<br />

(0.3 m) to maintain specified sound ratings<br />

g) Light switches to be mounted 48” (120 cm) to centre line AFFL<br />

h) Electrical outlets to be mounted 1’0” (0.3 m) to centre line AFFL<br />

i) Locate 2 plex outlets at desk as shown on Fairmont Hotels and<br />

Resorts Design Standards Details<br />

j) Install door bell to all suites and guestroom that have extra long<br />

entry foyer<br />

k) Surface mounted ceiling fixtures in entry foyer and bedroom<br />

REV. MARCH 2006 116<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Mechanical and Electrical<br />

l) Provide three-way switching to guestroom entry foyer. Locate one<br />

switch at entry door and second switch centred on night stand<br />

(furthest from entry door) at 3’0” (0.9 m) to centre line AFFL<br />

m) Ceiling fan 4’0” (1.2 m) in diameter with variable speed control<br />

mounted 54” (137 cm) to centre line AFFL (next to thermostat) in<br />

resorts.<br />

2.12. Personal Bar<br />

Where space allows, provide a 3’0” (0.9m) wide built-in personal bar unit,<br />

which will include the following features:<br />

a) Granite counter top 3’0” (0.9 m) AFFL<br />

b) Granite splash back with bevelled edge<br />

c) Cabinet with “built in” refrigerator. Vent refrigerator through shaft<br />

at rear of personal bar, into the entry foyer ceiling above. Cabinet<br />

door to be connected to refrigerator door so that the two open<br />

simultaneously<br />

d) Mirror to back of personal bar<br />

e) Recessed ceiling fixture<br />

f) Duplex electrical outlet for refrigerator 1’6” (0.5 m) to centre line<br />

AFFL and duplex electrical outlet 3’6” (1.1 m) to centre line AFFL<br />

for personal bar (coffee maker)<br />

g) Where a built-in personal bar unit has not been allowed for, the<br />

refrigerator will be housed in the armoire.<br />

2.13. Guest Bathroom<br />

a) Granite vanity, mounted 2’10” (0.9 m) from top of floor to top of<br />

vanity to be 3/4” thick x 2’0” wide (1.9 cm x 0.6 m) with apron at<br />

front (1 ½” thick – 3.8 cm) and bevelled backsplash<br />

b) Provide a 6” (15 cm) wide glass shelf with all front edges bevelled<br />

at 8” (20 cm) above the vanity<br />

c) Wall sconces to either side of vanity and MR16 down light centred<br />

over lavatory basins<br />

REV. MARCH 2006 117<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Guest Bathrooms (continued)<br />

d) All fixtures will be products as manufactured by the Kohler<br />

Company or other equal and approved<br />

e) Light switches 4’0” (120 cm) to centre line AFFL on opposite wall<br />

to shower, on inside of bathroom<br />

f) Illuminated make-up mirror at 5’0” (1.5 m) on centre line AFFL<br />

with Smart Lite Model #12-01-04-02 at vanity as manufactured by<br />

Lion Industries (702) 345-1331, grounded duplex outlet 4’2”<br />

(1.3 m) on centre line AFFL below<br />

g) Ceiling fixture to centre of bathroom<br />

h) Plumbing fixtures to be as Fairmont Hotels & Resorts standards<br />

i) Where two lavatory basins are provided, each to have grounded<br />

duplex outlet<br />

j) Frameless clear glass shower stall with 2’0” (0.6 m) wide x 3/4<br />

room height frameless clear glass door with 1’6” (0.5 m) bar on<br />

either side of door. Internal dimensions of shower to be 3’0” long<br />

x 3’0” wide (0.9 x 0.9 m) x full room height<br />

k) Floor drain to shower located in corner adjacent to bath<br />

l) Shower exhaust grille located in other corner with ductwork<br />

behind painted matt black<br />

m) Vapour proof ceiling light fixture within shower enclosure<br />

n) Two double robe hooks on wall immediately adjacent shower entry<br />

door<br />

o) Walls to be stone finish within shower enclosure<br />

p) Floor to be stone with a non-slip finish within shower enclosure.<br />

2.14. Water Closet<br />

a) Wall mounted telephone 48” (122 cm) at centre line AFFL, above<br />

toilet paper holder<br />

b) Ceiling mounted light fixture<br />

c) Double robe hook<br />

d) Toilet paper holder<br />

e) Spare toilet paper holder<br />

REV. MARCH 2006 118<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Water Closet (continued)<br />

2.15. Lanais and Terraces<br />

f) All fixtures will be products as manufactured by the Kohler<br />

Company or other equal and approved<br />

g) Ceiling exhaust grille with ductwork behind painted matt black<br />

h) Undercut door ¾” (20 mm) above threshold .<br />

a) Minimum clear width from door to railing to be 6’0” (1.8 m)<br />

b) Curved top balustrade rail should be as thin as possible to assure<br />

least possible obstruction of view. Open balustrade should be<br />

carried to floor with minimal upstand wall<br />

c) Weatherproof duplex electrical outlet<br />

d) Non-slip floor finish<br />

e) Brass floor drain<br />

f) Ceiling fan 4’0” (1.2 m) in diameter with variable speed control<br />

mounted 54” (1.5 m) to centre line AFFL in resorts<br />

g) Where the guestroom lanai or terrace has direct access from the<br />

exterior, a footbath with delayed shut-off tap must be provided for<br />

sand removal.<br />

2.16. Barrier-Free Guestrooms<br />

Provide one handicap accessible guestroom per 100 guestrooms or as designated by<br />

local codes. They shall be situated on the lowest guestroom floors close to the elevator<br />

core. Half of the rooms should be connected to a room with a double/double bed<br />

combination and the other half to a king bed guestroom.<br />

Planning must in accordance with the recommendations of Americans with Disabilities<br />

Act (ADA).<br />

The guest bathrooms are to have the following features:<br />

a) Single entry door shall be 2’10” (0.9 m) wide<br />

b) Additional grab bars in bath recess and adjacent WC. Bars are to<br />

be of the type that are removable when room is not occupied by a<br />

handicapped guest<br />

c) The vanity apron shall be kept as shallow as possible with all<br />

exposed piping insulated.<br />

Top of vanity is to be 2’10” (0.9 m) AFFL<br />

d) All light switches are to be 4’ 0” (1.2 m) on centre line AFFL<br />

REV. MARCH 2006 119<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Barrier-Free Guestrooms (continued)<br />

a) Emergency bell connected to security office (with automatic<br />

replay to telephone operator’s if not answered within 30 seconds)<br />

b) Roll in shower with fold down seat and adjustable height hand<br />

held shower<br />

c) Illuminated make-up mirror sliding on a vertical bar<br />

d) Floor drain in bathroom.<br />

Guest bedrooms are to have the following different features from a standard guestroom:<br />

a) Entry door second peephole at 3’9” (1.1 m) on centre line AFFL<br />

b) Closet with main shelf at 4’9” (1.4 m) AFFL and hanging rail at<br />

4’6” (1. 3 m) AFFL<br />

c) Special strobe emergency light for hearing impaired, combined<br />

with smoke detector<br />

d) Special telephones<br />

e) Emergency bell connected to security office (with automatic<br />

replay to telephone operator’s if not answered within 30 seconds)<br />

f) Fire alarm outlet for vibrating pillow.<br />

REV. MARCH 2006 120<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

2.17. Washroom Accessories<br />

Item Description Mounting Height to<br />

Centre Line<br />

Towel bars<br />

4’ 6” (1.4 m)<br />

2’ 8” (0.8 m) at bidet<br />

1 @ bathtub 30 “ long (76<br />

cm)<br />

2 @ vanity each 18” long (46<br />

cm)<br />

1 @ bidet 18” long (46 cm)<br />

Toilet roll holder<br />

1 per bathroom<br />

2’ 4” (0.7 m) (2’ 6”- 0.8 m to<br />

centre line from back wall)<br />

Shower rod<br />

6’ 6” (2.0 m) in line with outside<br />

Double robe hook 1 on wall in WC room and 2<br />

on bathroom wall ( 1<br />

adjacent to shower)<br />

Soap dish Large polished stainless steel<br />

wire basket 1 per bathtub and<br />

2 per shower stall<br />

face of bath tub<br />

5’ 6” (1.7 m). Also provide one<br />

hook at 4’ 0” (1.2 m) in<br />

handicapped bathroom<br />

2’ 2” (0.6 m) on long side of tub;<br />

4’ 0” ( 1.2 m) in corner of shower<br />

Small glass soap dish 2’4” (0.7 m)<br />

adjacent to towel bar @<br />

bidets<br />

Bath grab bar 12” long (30 cm) Mounted horizontally 2’ 10” (0.9<br />

Shower head<br />

Shower arm<br />

½” (1.3 cm) Chrome plated<br />

brass with chrome plated<br />

escutcheon<br />

m) at one end of tub<br />

6’ 0” (1.8 m) from shower floor to<br />

under side of head. Mount head<br />

on side of shower (not opposite<br />

door)<br />

Shower control<br />

4’ 0” (1.2 m) to centre line valve<br />

above shower floor<br />

Tub hand shower<br />

Holding bracket:<br />

2’ 2” (0.6 m) from bottom of tub<br />

Tub filler spout Must have aerator 1’ 8” (0.5 m) to center line above<br />

floor level<br />

Spare toilet roll<br />

holder<br />

1’ 0” (0.3 m) adjacent to WC<br />

REV. MARCH 2006 121<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

3. <strong>FAIRMONT</strong> GOLD GUESTROOMS, LOBBY AND LOUNGE<br />

3.1. General Requirements<br />

Fairmont Gold, a hotel within a hotel, dedicated to a consistent high quality of service,<br />

is designed to meet all the needs and expectations of the discriminating business<br />

executive and leisure traveller. Within a private atmosphere of quiet residential<br />

surroundings, the specially trained staff provides friendly, personalized and efficient<br />

service.<br />

The added amenities and luxurious surroundings are simply an extension of the caring,<br />

comforting attitude of the hosts. Fairmont Gold is a consistent attitude of dedication to<br />

the well being of the Fairmont Hotels & Resorts guests.<br />

Typically, an upper floor(s) or a wing of a floor will be dedicated to Fairmont Gold.<br />

Minimum recommended is 50 rooms with a maximum of 85 rooms, depending upon<br />

lounge capacity. A minimum of 70% of the rooms is to be designated non-smoking. All<br />

rooms should preferably be on the same floor. If floor size is too small to accommodate<br />

the number of guestrooms required then the floor immediately below and/or above the<br />

Lounge could be used. A separate internal open stair should then be provided between<br />

the floors.<br />

3.2. Guestrooms<br />

Functional Requirements of Fairmont Gold guestrooms are similar to standard<br />

guestrooms, however, the Fairmont Gold have upgraded finishes, FF & E and<br />

amenities.<br />

3.3. Elevator Lobby and Lounge<br />

The elevator lobby on the Fairmont Gold floor should be obviously distinctive,<br />

reflecting the Fairmont Gold atmosphere. The reception area, located in close proximity<br />

to the elevator core, will have full time receptionists to check in/out guests, give<br />

messages, send faxes, etc. This area must incorporate outlets for multi-line phones and<br />

duplex outlets for computers and other related equipment.<br />

Provide storage cabinets adjacent the desk to conceal printers, credit card imprinters and<br />

credit card verifiers and well as telephone outlets for credit card verification and<br />

electrical outlets for related computer equipment.<br />

A work area (approximately 75 ft 2 – 7 m 2 ) where staff can store small items for guests<br />

and hang guest’s coats, send faxes, make copies, etc. This area is to include a counter<br />

2’0’’ wide x 8’0” long (0.6 x 2.4 m) with cabinets above and below, except below the<br />

workstation which is 3’6” (1.1 m) wide. Provide electrical outlets for telephones, fax<br />

machines, copier. This area to house the audio controls and variable fan speed controls<br />

for the lounge.<br />

REV. MARCH 2006 122<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Elevator Lobby and Lounge (continued)<br />

It is Fairmont Hotels and Resorts policy to offer to store Fairmont Gold floor guests’<br />

luggage away from their guestrooms, and a storeroom (approximately 150 ft 2 – 14 m 2 )<br />

is therefore required. This room should have a wall hung house phone as well as heavy<br />

duty plywood adjustable shelving, ¾” thick x 30” (1.9 x 76 cm) wide, with a total<br />

length of 30’0” (9.1 m), as well as 5’0” (1.5 m) of hanging rod 5’ 9” (1.8 m) AFFL.<br />

A separate lounge comprising 70% table seating and 30% soft casual seating. Allow for<br />

two individual desks with chairs. Total number of seats should be related to the number<br />

of Fairmont Gold guestrooms (50% for city hotels, 100% for destination/resort hotels)<br />

The lounge will include an honor bar and buffet facilities which must be in close<br />

proximity and preferably visible from the reception desk. Provide electrical outlets for<br />

hot food table, TV’s etc. Washrooms adjacent to the lounge. The storage area may also<br />

double as a place for guests' belongings after check out if they are not leaving the hotel<br />

until late in the day. Recessed ceiling speakers connected to audio located in lobby<br />

storage room.<br />

Resorts to have variable speed ceiling fans.<br />

3.4. Fairmont Gold Pantry<br />

The pantry kitchen (approximately 400 ft 2 – 37 m 2 ) with the appropriate equipment is to<br />

provide service to the Fairmont Gold lounge. Located with direct access to the Fairmont<br />

Gold lounge and the service elevator.<br />

REV. MARCH 2006 123<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

4. SUITES<br />

4.1. General Requirements<br />

Special suites or suites with living/dining areas of two modules or more are essentially<br />

entertaining suites. They should be located with the best possible views.<br />

4.2. Modular Requirements<br />

a) Junior suite (1key/1.5 modules total): Subject to the building<br />

configuration include a separate sitting area<br />

b) One bedroom suite (1key/2 modules total): Includes a master<br />

bedroom, separate living area with powder room, some connecting<br />

c) Two-bedroom suite (2 keys/4 modules total): Includes a master<br />

bedroom, separate 2 module living area with powder room and one<br />

bedroom connecting<br />

d) Special Presidential Suite (3 keys/5 to 7 modules total): Includes a<br />

foyer, 3 or 4 module living room, pantry, master bedroom and one<br />

or two bedrooms, some connecting. Includes a powder room next<br />

to the parlour and separate guest bathrooms for each bedroom.<br />

Sold either as a singly key or preferably with flexibility of separate<br />

keys for parlour and each bedroom<br />

e) Junior and one bedroom suite has the following features:<br />

i) Bedrooms to have walk-in closet and separate area with<br />

make up vanity<br />

ii)<br />

iii)<br />

iv)<br />

Living area to have additional telephone outlets and<br />

upgraded lighting<br />

A pair of solid wood French doors between the living room<br />

and the bedroom<br />

Built-in wet bar long with undercounter cupboards and minibar<br />

v) Powder room to include (i) WC and vanity for urban hotels<br />

and (ii) WC, vanity and shower for resort hotels<br />

vi) Desk to be located in living room and not in bedroom as per<br />

standard guestroom.<br />

f) Two bedroom and special suite have the following features:<br />

REV. MARCH 2006 124<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Modular Requirements (continued)<br />

i. Full height glazing and sliding doors to terrace or lanai<br />

ii.<br />

iii.<br />

iv.<br />

A single 3’6” (1.1 m) wide guest entry door<br />

Additional closet (approximately 12 ft 2 – 1.1m 2 ) space for<br />

guests’ coats<br />

Pantry (approximately 65 ft 2 – 6m 2 ) with direct access to<br />

corridor and suite, with counter and storage cupboards,<br />

small fridge, microwave, sink additional duplex electrical<br />

outlets and wall telephone<br />

v. Powder room to include (i) WC and vanity for urban hotels<br />

and (ii) WC, vanity and shower for resort hotels<br />

vi.<br />

vii.<br />

Upgraded master bedroom with full dressing area with<br />

additional closets, vanity and shelving<br />

Additional air conditioning and exhaust for the living/dining<br />

area<br />

viii. Chandelier to dining area with dimmer control<br />

ix.<br />

Additional accent and decorative lighting<br />

x. Audio system with built in speakers to living/dining areas.<br />

4.3 Outline of Finishes and Materials<br />

The following schedule of finishes has been prepared to establish a standard of finish<br />

for the major types of hotel areas. Its purpose is to direct the Consultants in their design<br />

and in the preparation of their own detailed room finish schedule<br />

Legend<br />

AT-CG<br />

AT-EG<br />

AT-M<br />

CP<br />

CT<br />

1' 0" x 1' 0" (0.3 x 0.3 m) textured ceiling tiles with concealed grid<br />

4' 0" x 2' 0" (1.2 x 0.6 m) lay in textured ceiling tiles with exposed grid.<br />

Tiles and grid finished white<br />

An acoustic tile ceiling that will resist heat, steam, water etc. and is<br />

easily cleaned e.g. metal tile with acoustic pad<br />

Carpet<br />

Ceramic tile, thin set. Joint between CT and bathtubs and WC’ be<br />

caulked with white, silicone caulking specially designed for this purpose<br />

REV. MARCH 2006 125<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

Outline of Finishes and Materials – Legend (continued)<br />

G<br />

ES<br />

LH<br />

M<br />

MONO<br />

QT<br />

RB<br />

RCB<br />

SGP<br />

SP<br />

VT<br />

VWC<br />

WD<br />

Granite laid to special pattern<br />

Exposed structure including all exposed services<br />

Smooth trowelled concrete with liquid hardener and dustproofer<br />

Marble laid to special pattern<br />

Monolithic floor finish e.g. Duron Resolast<br />

Slip resistant quarry tile<br />

2 ½" (5.7 cm) flat rubber or vinyl covered (use cheaper)<br />

2 ½" (5.7 cm) rubber or vinyl-coved base (use cheaper)<br />

Three coats semi-gloss enamel paint<br />

Smooth plaster with two coats flat latex paint<br />

12" x 12" (30 x 30 cm) vinyl tile<br />

Vinyl wall covering<br />

Stained or painted hardwood<br />

No. Area Floor Base Wall Ceiling<br />

1<br />

Bedroom Floors generally:<br />

a) Bedrooms CP 6" WD<br />

(15 cm)<br />

b) Entry Foyer CP 6" WD<br />

(15 cm)<br />

c) Closet CP 6" WD<br />

(15 cm)<br />

d) Bathroom M 4" M<br />

(10 cm)<br />

e) WC Room M 4"M<br />

(10 cm)<br />

VWC + 6" (15<br />

cm) Cornice<br />

VWC + 4" (10<br />

cm) cornice<br />

VWC<br />

M + 4" cornice<br />

(10 cm)<br />

VWC + 4"<br />

(10 cm) cornice<br />

SP<br />

Drywall<br />

Drywall<br />

Drywall<br />

with<br />

cove<br />

Drywall<br />

REV. MARCH 2006 126<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

No. Area Floor Base Wall Ceiling<br />

2 Suites and Adjoining Bedrooms:<br />

a) Bedrooms CP 6" WD<br />

(15 cm)<br />

Special VWC +<br />

6” WD Cornice<br />

SP<br />

(15 cm)<br />

b) Entry Foyer M/CP/<br />

WD<br />

4"<br />

M/WD<br />

(10 cm)<br />

Special VWC +<br />

4” WD Cornice<br />

SP<br />

(10 cm)<br />

c) Closet CP 6" M<br />

(15 cm)<br />

VWC<br />

Drywall<br />

d) Bathroom, Powder Room<br />

and WC Room<br />

M 4"M<br />

(10 cm)<br />

M + 4"<br />

(10 cm )<br />

Cornice<br />

Drywall<br />

with<br />

cove or<br />

special<br />

VWC<br />

e) Dining and Living WD/CP/<br />

M<br />

6" WD<br />

(15 cm)<br />

50% WD, 50%<br />

Special VWC +<br />

WD Cornice<br />

SP,<br />

WD,<br />

trim<br />

f) Bar and Pantry M 4"M<br />

(10 cm)<br />

3 Guestroom Corridor CP 6" WD<br />

(15 cm)<br />

4 Fairmont Gold floor(s) corridor(s) CP 6"<br />

(15 cm)<br />

WD/RC<br />

B<br />

Special VWC<br />

(include buildin<br />

cabinets with<br />

granite<br />

counters)<br />

VWC + 6"<br />

(15 cm) WD<br />

cornice trim.<br />

Wood arches to<br />

frame arrival<br />

areas at<br />

guestroom<br />

doors. 6"<br />

(15 cm) WD<br />

dado rail<br />

As item 3, but<br />

incl. WD<br />

wainscot<br />

Drywall<br />

Drywall<br />

with<br />

coves<br />

and WD<br />

trim<br />

Drywall<br />

with<br />

coves<br />

REV. MARCH 2006 127<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

No. Area Floor Base Wall Ceiling<br />

5 Guest Floor Elevator Foyer M 6" M<br />

(15 cm)<br />

M/WD frames<br />

to elevator<br />

door openings<br />

WD panelling<br />

or VWC<br />

Drywall<br />

with<br />

coves<br />

WD<br />

ceiling<br />

trim<br />

6 Ice Machine Room on guestroom<br />

floors<br />

RB/VT 6"<br />

(15 cm)<br />

WD/<br />

RCB<br />

VWC<br />

(acoustic tiles<br />

around<br />

machine)<br />

Drywall<br />

REV. MARCH 2006 128<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

4.4. Guest Area Standards Details<br />

Page<br />

TYPICAL GUESTROOM ELECTRICAL REQUIREMENTS<br />

WITH FURNITURE 130<br />

TYPICAL GUESTROOM ELECTRICAL ELEVATIONS 131<br />

DESK 132<br />

TYPICAL GUESTROOM CLOSET DETAILS 133<br />

FIXED PERSONAL BAR 134<br />

TYPICAL TUB SHELF DETAIL 135<br />

TYPICAL SHOWER ENCLOSURE DETAILS 136<br />

TYPICAL SHOWER ENCLOSURE 137<br />

REV. MARCH 2006 129<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

REV. MARCH 2006 130<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

REV. MARCH 2006 131<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

REV. MARCH 2006 132<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

REV. MARCH 2006 133<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

REV. MARCH 2006 134<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

REV. MARCH 2006 135<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

REV. MARCH 2006 136<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

GUESTROOM AREAS<br />

REV. MARCH 2006 137<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

D. BACK-OF-HOUSE<br />

1. OFFICE AREAS<br />

1.1. Front Desk Support<br />

Provide space for functions, which could include the following:<br />

• Front Office Manager<br />

• Rooms Division Manager<br />

• Reservations Manager<br />

• Reservations clerks and secretary<br />

• Communication/Telephone Operator’s room<br />

• Cashier’s Desk<br />

• Guest safety deposit box room<br />

• Security Office<br />

• Fire Control and Elevator Control Room<br />

• Luggage Storage<br />

• Concierge Storage<br />

• Bellmen's Store<br />

• Car Valet’s Room<br />

• Parking Cashier<br />

1.2. Executive Office, Administration, Accounting and Security<br />

Provide space for functions, which could include the following:<br />

• General Manager<br />

• Resident Manager<br />

• Assistant General Manager<br />

• Secretarial<br />

• Director of Food and Beverage<br />

• Assistant Director of Food and Beverage<br />

• Director of Catering<br />

• Catering Coordinators<br />

REV. MARCH 2006 138<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Executive Office, Administration, Accounting & Security (continued)<br />

• Director of Sales and Marketing<br />

• Assistant Director of Sales and Marketing<br />

• Sales Representatives<br />

• Public Relations Manager<br />

• Boardroom<br />

• Mail and Copy room<br />

• Beverage counter<br />

• Controller<br />

• Assistant Controller<br />

• Head Cashier<br />

• Staff Cash-out Work area and Night Deposit area<br />

• Dead Storage and Storage areas<br />

• Credit Manager<br />

• Payroll Manager<br />

• Secretary, clerks and filing<br />

• Computer Manager<br />

• Computer room<br />

• Telephone equipment room with UPS<br />

• TV pay per view head end room<br />

• Security Manager<br />

• Assistant Security Manager<br />

1.3. Human Resources<br />

Provide space for functions, which could include the following:<br />

• Reception and secretary<br />

• Director of Human Resources<br />

• Language Training room (foreign countries)<br />

• Training Manager<br />

• Meeting/training room<br />

REV. MARCH 2006 139<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Human Resources (continued)<br />

• Library<br />

• Interview room<br />

• Copy and beverage station<br />

• Files and storage<br />

REV. MARCH 2006 140<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

1.4. Outline of Finishes and Materials<br />

The following schedule of finishes has been prepared to establish a standard of finish<br />

for the major types of hotel areas. Its purpose is to direct the Consultants in their design<br />

and in the preparation of their own detailed room finish schedule<br />

Legend<br />

AT-CG<br />

AT-EG<br />

AT-M<br />

CP<br />

CT<br />

G<br />

ES<br />

LH<br />

M<br />

MONO<br />

QT<br />

RB<br />

RCB<br />

SGP<br />

SP<br />

VT<br />

VWC<br />

WD<br />

CPT<br />

12” x 12" (30 x 30 cm) textured ceiling tiles with concealed grid<br />

4' 0" x 2' 0" (1.2 x 0.6 m) lay in textured ceiling tiles with exposed grid.<br />

Tiles and grid finished white<br />

An acoustic tile ceiling that will resist heat, steam, water etc. and is<br />

easily cleaned e.g. metal tile with acoustic pad<br />

Carpet<br />

Ceramic tile, thin set. Joint between CT and bathtubs and WC’s shall be<br />

caulked with white, silicone caulking specially designed for this purpose<br />

Granite laid to special pattern<br />

Exposed structure including all exposed services<br />

Smooth trowelled concrete with liquid hardener and dustproofer<br />

Marble laid to special pattern<br />

Monolithic floor finish e.g. Duron Resolast<br />

Slip resistant quarry tile<br />

2 ½" (6.4 cm) flat rubber or vinyl covered (use cheaper)<br />

2 ½" (6.4 cm) rubber or vinyl-coved base (use cheaper)<br />

Three coats semi-gloss enamel paint<br />

Smooth plaster with two coats flat latex paint<br />

12" x 12" (30 x 30 cm) vinyl tile<br />

Vinyl wall covering<br />

Stained or painted hardwood<br />

Carpet tiles<br />

REV. MARCH 2006 141<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Outline of Finishes and Materials (continued)<br />

No. Area Floor Base Wall Ceiling<br />

1 All stores, engineers, maintenance<br />

areas, valet, uniform issuing, janitor’s<br />

closets, housekeeping, linen and<br />

service rooms on guestroom floors,<br />

service elevator foyers*, service<br />

corridors **, staff entrance including<br />

stairs<br />

VT<br />

RCB<br />

SGP-ES<br />

SGP-ES<br />

* At service sink<br />

** See General Requirements 1.5<br />

VT<br />

RCB<br />

CT to 4' 0”<br />

(1.2 m)<br />

SGP-ES<br />

Service corridor behind main ballroom<br />

and meeting rooms **<br />

CPT<br />

WB<br />

SGP-ES<br />

SGP-ES<br />

2 Staff locker VT RCB SGP-ES AT-M<br />

3 Staff washrooms and washroom areas<br />

in locker rooms<br />

CT/VT CT CT Drywall<br />

4 Public Washrooms G G G at urinals,<br />

elsewhere,<br />

M.WD<br />

cornice and trim<br />

VWC<br />

5 Swimming Pool Changing M M M SGP<br />

6 Truck Dock & Receiving LH - SGP-ES SGP-ES<br />

7 a. Kitchen, including staff dining room<br />

kitchen, and food pick-up area &<br />

pantries<br />

Flower Work Room<br />

QT QT CT to 7' 0”<br />

(2.1 m)<br />

AT-M<br />

SGP<br />

above<br />

7 b. Walk-in refrigerators and freezers QT QT<br />

By equipment<br />

manufacturer<br />

By equipment<br />

manufacturer<br />

8 Kitchen cashiers’ office, chef’s office,<br />

housekeeper’s office<br />

VT RCB SGP-ES AT-EG<br />

9 Swill Room, Can Wash, Garbage<br />

Compactor, Garbage Store<br />

QT<br />

4" QT<br />

(10<br />

cm)<br />

CT to 4'<br />

(SGP<br />

above)<br />

SGP-ES<br />

REV. MARCH 2006 142<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Outline of Finishes and Materials (continued)<br />

No. Area Floor Base Wall Ceiling<br />

10 Administration, Sales, Personnel and<br />

Accounting Offices and Telephone<br />

Operators’ Room<br />

CP RCB VWC AT-CG<br />

11 Swimming Pool Attendant VT RCB Drywall<br />

SGP<br />

Drywall<br />

12 a) Laundry VT RCB SGP-ES AT-EG<br />

12 b) Laundry Trench 1/8"<br />

(0.3 cm)<br />

Mono<br />

1/8"<br />

(0.3 cm)<br />

Mono<br />

- -<br />

13 Fire Escape Stairs & Corridors - metal<br />

balustrade SGP<br />

LH - SGP-ES SGP-ES<br />

14 Telephone Equipment Room VT RCB SGP-ES AT-EG<br />

15 Employees’ Dining Room<br />

Computer Room<br />

VT<br />

VT<br />

RCB<br />

RCB<br />

VWC<br />

SGP<br />

AT-EG<br />

AT-EG<br />

16 Employees Lounge CP RB VWC AT-EG<br />

17 Mechanical/Electrical LH - SGP-ES SGP-ES<br />

18 Service vestibule to public area<br />

(vestibule to ballroom and meeting<br />

room shall include rubbing rails)<br />

19 Main Driveway, Sidewalks, Public<br />

Areas and Swimming Pool area<br />

RB RB SGP SGP-ES<br />

Special paving and finishes as selected by<br />

Interior Designer<br />

20 Patios, Terraces and Gardens Special paving, finishes and planting as<br />

selected by landscape architect<br />

21 Exposed Roofs visible from hotel<br />

rooms<br />

Patterned treatment in coloured gravels.<br />

Equipment to be attractively concealed in<br />

architectural housings<br />

22 Parking LH and parking<br />

and direction lines<br />

- lines painted<br />

green<br />

Painted - directional<br />

signs and stall numbers<br />

REV. MARCH 2006 143<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

1.5. General Requirements<br />

Each separate office group is to have one thermostat. Individual offices do not require<br />

thermostats.<br />

Each office area is to have a coat closet and general storage closet for everyday<br />

stationary supplies.<br />

Each individual office is to have three duplex electrical outlets, two telephone outlets<br />

and computer systems outlets as required by the LAN requirements.<br />

The offices of the Members of the Hotel’s Executive Committee are to have upgraded<br />

finishes and three telephone outlets, and additional duplex electrical outlet and<br />

computer outlets.<br />

Catering coordinators area to have a built in counter with a wall telephone outlet<br />

mounted 54” (137 cm) to centre line AFFL, duplex electrical outlets and computer<br />

outlets.<br />

All built in counters, shelves, cupboards, etc. to have velvetex finished plastic laminate<br />

finish with exposed hardwood edge strips.<br />

The following offices are to have all walls constructed to meet an FSTC rating of 54: (i)<br />

General Manager, (ii) Credit Manager, (iii) perimeter walls of washrooms where they<br />

are adjoining offices, (iv) perimeter walls of offices where they are adjoining public<br />

areas and (v) Director of Human Resources and interview room.<br />

Administration offices must have easy and direct access for the public. Front Desk<br />

Support should be adjacent to the Front Desk. Reception areas should be designed to<br />

reflect the elegance of Fairmont Hotels and Resorts as should senior management<br />

offices, especially that of the General Manager’s and Director of Catering. Accounting<br />

should be located in the back-of-the-house, to be accessible by Staff. Human Resources<br />

must be located near Staff Entrance and Security. Back-of-the-house spaces should have<br />

separate access away from public circulation.<br />

Secretarial positions must each have two telephone outlets and two duplex electrical<br />

outlets as well as two computer systems outlets for connection to LAN and printers.<br />

Offices with exterior windows must have incandescent lighting and special window<br />

treatment.<br />

Each office area is to have separate washrooms with vanity for male and female staff.<br />

In locations which are subject to frequent power outages, all duplex electrical outlets for<br />

administration assistants, secretaries and staff using computers must be on the<br />

uninterrupted power supply (UPS).<br />

VWC requires sealed drywall or smooth plaster as base construction to obtain<br />

acceptable finish.<br />

All exposed grilles, diffusers, sprinkler escutcheons, speakers, alarm bells, access<br />

panels, downlight trims, etc. required to be painted to match adjacent surface.<br />

REV. MARCH 2006 144<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

General Requirements (continued)<br />

All ductwork behind grilles and diffusers in public spaces to be painted matt black.<br />

Where access doors and fire hose cabinets occur in walls finished with VWC, these are<br />

to finish flush with the surface of the wall and the VWC is to be carried over the door<br />

and frame, with a knife cut between the door and the frame.<br />

Where a suspended ceiling is required to create a plenum for HVAC, it shall be drywall.<br />

All edges to ceramic tiles are to round edge tiles as no exposed edges will be accepted.<br />

Wall finishes around very hot equipment e.g. ranges, fat fryers, etc. shall be stainless<br />

steel fixed to a heat resistant backing.<br />

Where high temperature producing equipment is located beneath public spaces, a<br />

special insulating ceiling shall be provided to prevent heat transmission to these public<br />

spaces.<br />

Counter sunk stainless steel corner guards, size 3”x 3” x 4’0” (7.6 cm x 7.6 cm x 1.2 m)<br />

long should be provided to all external corners of back of house walls which will be<br />

subject to damage by hotel carts and trolleys where rubbing rails are not required e.g.<br />

kitchen areas.<br />

Rubbing rails are to be installed in all service corridors, service elevators foyers and<br />

vestibules. Mounted 35” (83.5 cm) to centre line AFFL and 9” (23 cm) to centre line<br />

AFFL.<br />

Doors are to be a 1 ¾” (4.4 cm) thick and a minimum of 7’0” (2.1 m) high and of the<br />

following widths: (i) 2’8” (0.8 m) to all offices, (ii) 2’6” (0.7 m) to all washrooms, (iii)<br />

3’0” (0.9 m) to all other single doors, (iv) 5’0” (1.5 m), to all other double doors and (v)<br />

3’6” (1.1 m) to all service doors into public rooms.<br />

All doorframes are to be pressed steel with welded mitres.<br />

The finish to all doors and frames is to be paint.<br />

All double acting doors as well as door in service corridors are to have a single glass<br />

vision panel 6” wide x 12” high (15 x 30 cm).<br />

Dutch doors are required in the following locations:<br />

a) Food stores<br />

b) Beverage stores<br />

c) Valet/uniform issuing<br />

d) Housekeeping stores<br />

e) Cashiers office (without shelf)<br />

f) Housekeeper’s office (without shelf)<br />

g) Security office (without shelf)<br />

h) Receiving office.<br />

REV. MARCH 2006 145<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

General Requirements (continued)<br />

Doors to the following rooms shall be hollow metal for security reasons and shall<br />

incorporate a card access with keypad lockset:<br />

a) Food stores<br />

b) China and silver dead storage areas<br />

c) Beverage stores.<br />

Glazed interior screens, typically of hollow metal with clear glass are essential in the<br />

following offices:<br />

a) Executive housekeeper’s office and general housekeeping<br />

b) Chief and assistant engineer’s offices<br />

c) Secretary’s and general maintenance offices<br />

d) Laundry manager and laundry area<br />

e) Chef’s office and kitchen<br />

f) Baker’s office<br />

g) Bake shop and kitchen<br />

h) Dishwashing steward’s office and dishwashing area<br />

i) Receiver’s office<br />

j) Security office<br />

k) Human resources reception area<br />

l) Assistant controller’s office and accounting offices<br />

m) Head cashier and staff cash-out room<br />

n) Garde manger and kitchen<br />

o) Rooms division manager, reservations and clerk’s office<br />

p) Purchasing office<br />

q) Computer manager’s office and computer room<br />

r) Telephone operator’s room and reservations<br />

s) Room service cashier’s office with opening for pass<br />

through<br />

t) Valet parking cashier’s office with opening for pass<br />

through.<br />

REV. MARCH 2006 146<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

General Requirements (continued)<br />

Employee lockers should be located on the same level as the entrance and adjacent to<br />

uniform store and issuing.<br />

Employee dining should be located adjacent to banquet kitchen in order to eliminate a<br />

separate dishwash area.<br />

Food and beverage stores, as well as engineering maintenance areas should be located<br />

on the same level as the truck dock and receiving area.<br />

REV. MARCH 2006 147<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

1.6. Standard Lighting Fixtures<br />

Back-of-house lighting in areas with exposed ceiling and/or T-bar ceilings shall be energy<br />

efficient recessed fluorescent fixtures complete with hinged acrylic lens. Fixture sizes shall be<br />

standardized to l<strong>amp</strong> sizes with a preference for 1’0” x 4’ 0” (0.3 x 1.2m) or 2’0” x 4’0’<br />

(0.6 x 1.2m) light fixtures. Fixtures in kitchens, laundry or other d<strong>amp</strong> locations shall be<br />

gasketted. Fixtures in service and storage rooms may be strip lights complete with wire guards.<br />

a) All fluorescent fixtures throughout the hotel shall be warm white<br />

with rapid start premium electric type for T-8 l<strong>amp</strong>s.<br />

b) Standardize lengths of fluorescent light fixtures where possible<br />

c) All storerooms and offices shall have room lighting controlled by<br />

local switches located inside the room and adjacent to the entrance<br />

door. Where a room has more than one entrance, three way<br />

switching shall be provided. The switches in storerooms shall<br />

incorporate a power outlet for housekeeping purposes<br />

d) In mechanical rooms, a fluorescent light fixture shall be mounted<br />

at each motor control centre and shall be on emergency power<br />

supply<br />

e) Exit lighting to have the minimum wattage l<strong>amp</strong>s permitted by<br />

code.<br />

f) Public area exits shall have thin line exit fixtures with bronze<br />

finish and fitted with a long life electronic circuit.<br />

g) Back-of-house exits shall have standard width exit fixtures with a<br />

paint finish and fitted with a long life electronic circuit.<br />

h) Fixtures in fire escape stairs shall be mounted on main landings<br />

only unless otherwise stated by local code.<br />

1.7. Other Offices<br />

Coffee/Tea Room to include the following features:<br />

a) A built in counter 2’0” wide and 3’0” (0.6 x 0.9 m) AFFL<br />

(incorporating a stainless steel sink with adjustable shelving<br />

below counter and lockable cabinets above<br />

b) One 110V 15 <strong>amp</strong> duplex outlet (refrigerator)<br />

c) Three 110V 15 <strong>amp</strong> duplex outlets (both of separate circuits) at<br />

4’0” (1.2 m) to centre line AFFL (kettle and coffee maker).<br />

REV. MARCH 2006 148<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Other Offices (continued)<br />

Mail Room to include the following features:<br />

a) A built in counter 2’0” wide and 3’0” (0.6 x 0.9 m) AFFL with<br />

adjustable shelving above and below counter<br />

b) One 220V single phase 30 <strong>amp</strong> outlet (separate circuit) for<br />

photocopier<br />

c) Three 110V 15 <strong>amp</strong> duplex outlets mounted 4’0” (1.2 m) to centre<br />

line AFFL (post meter, electric pencil sharpener)<br />

d) Two telephone outlets and two duplex electrical outlets (fax<br />

machines)<br />

e) Wall telephone.<br />

Telephone Operators Room to have the following features:<br />

a) A special two level built-in counter approximately 4’6” (1.4 m)<br />

long for three operators<br />

b) Duplex electrical outlet, telephone outlet and 1’6” (0.5 m) wide<br />

adjustable shelving at supervisor’s desk<br />

c) White marker board 6’0” wide x 4’0” high (1.8 x 1.2 m)<br />

d) Cork board 2’0” wide x 2’0” high (0.6 x 0.6 m)<br />

e) The lighting to this room must be on emergency power supply<br />

f) Each operator requires the following features:<br />

i) Duplex electrical outlet (UPS) and computer systems outlets<br />

(CRT and keyboard)<br />

ii) Two telephone outlets (console and paging telephone).<br />

The following must be located in the telephone operators’ room in full view of all the<br />

operators:<br />

a) Closed circuit TV monitors (slave security system)<br />

b) Remote door alarm indicator panel<br />

c) Cashier’s alarm indicator panel<br />

d) Walk-in coolers and freezers alarm indicator panel<br />

e) Fire alarm annunciation panel<br />

f) Smoke detector alarm annunciation panel.<br />

The following requirements are to be installed immediately above the telephone<br />

operators’ counter:<br />

REV. MARCH 2006 149<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Other Offices (continued)<br />

a) Duplex electrical outlets (UPS) and food and beverage point-ofsale<br />

cable outlets (error printers)<br />

b) Duplex electrical outlets (wake-up clocks)<br />

Accounting Offices to have the following features:<br />

a) An additional space (approximately 20 ft 2 – 1.9 m 2 ) is required for<br />

the printer (connected to LAN and UPS), copier and paper storage<br />

b) Document storage room (approximately 70 ft 2 – 6.5 m 2 ) with 2’0”<br />

(0.6 m) wide adjustable shelving running the full length and full<br />

height of the longest wall<br />

c) Each clerical position requires the following: (i) Two duplex<br />

outlets, (ii) Two computer systems outlets (connected to LAN)<br />

and (iii) Two telephone outlets.<br />

Computer manager and computer manager’s assistant office and computer room<br />

(approximately 400 ft 2 – 37.2 m 2 ) to have the following features:<br />

a) Access to the computer room must be through the computer<br />

manager’s office<br />

b) Door to computer room should be 3’0” (0.9 m) wide to allow<br />

equipment to pass through easily<br />

c) Special mechanical and electrical provisions must be installed in<br />

the computer room. This must be coordinated with the equipment<br />

specified.<br />

Reservations Office to have the following features:<br />

a) The reservations area is to have a number of workstations each<br />

4’6” (1.4 m) long with lockable drawers at one end and shelving<br />

over<br />

b) Each workstations requires the following: (i) Two telephone<br />

outlets, (ii) Two duplex electrical outlets (one on UPS) and (iii) A<br />

connection to LAN<br />

c) An additional two duplex electrical outlet and two telephone<br />

outlet at front desk cash out position<br />

d) A 5’3” wide x 3’3” high x 1’0” deep (1.6 x 1.0 x 0.3 m) fixture,<br />

divided into approximately sixty 6” x 6” cubicles to hold disputed<br />

cheques<br />

e) Duplex electrical outlets (UPS) and Point of Sale outlet (error<br />

printer).<br />

REV. MARCH 2006 150<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Other Offices (continued)<br />

Cashier’s Office to have the following features:<br />

a) Glazed panel (approximately 18’’ wide x 24” high-<br />

(45.7 x 60.1 cm)<br />

b) Dutch entry door<br />

c) All electrical outlets and lighting on emergency power<br />

d) Trouble alarm button (connected to telephone operators room)<br />

e) Duplex electrical outlets<br />

f) Telephone outlets<br />

g) LAN outlets<br />

h) Drop safe (N.I.C. approximately 2’0” wide x 2’6” deep x 3’9”<br />

high (06. x 0.8 x 1.1. m), with door opening on Cashier’s Office<br />

side)<br />

Staff Safety Deposit Box Room to have the following features:<br />

a) Plastic laminated work counter<br />

b) Duplex electrical outlets<br />

c) Safety deposit boxes (N.I.C approximately 3’6” wide x 2’0” deep<br />

x 3’8” high – 1.1 x 0.6 x 1.1 m)<br />

d) CCTV camera<br />

e) Call button<br />

1.8. Minimum Finished Ceiling Heights:<br />

Kitchens 9’6” (2.9 m)<br />

Back of house 8’0” (2.4 m)<br />

Truck dock and compactor room 14’0” (4.3 m)<br />

Laundry 12’0” (3.7 m)<br />

Main entrance driveway 14’0” (4.3 m)<br />

1.9. Garbage Compact Room<br />

The garbage compact room shall incorporate the following features:<br />

a) 60 Amp electrical power supply mounted 5’0” (1.5 m) on centre<br />

line AFFL (connection to compactor)<br />

REV. MARCH 2006 151<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Garbage Compact Room (continued)<br />

1.10. Maintenance Areas<br />

b) 110 V x 15 <strong>amp</strong> duplex electrical outlet mounted 6’0” (1.8 m) on<br />

centre line AFFL (air purifier)<br />

c) 110 V x 15 <strong>amp</strong> weatherproof duplex electrical outlet mounted<br />

4’6” (1.4 m) on centre line AFFL (maintenance)<br />

d) 110 V x 15 <strong>amp</strong> electrical outlet mounted 6’0” (1.8 m) on centre<br />

line AFFL (bug killer equipment – leased)<br />

e) ½” (1.3 cm) Hose connector, connected to disinfectant wash down<br />

system (system leased)<br />

f) Can wash area (approximately 10 ft 2 – 0.9 m 2 ) with ½” (1.3 cm)<br />

cold water supply and shut-off valve and 3” (7.5 cm) diameter<br />

“wet” floor drain<br />

g) 3’6” (1.1 m) Wide entrance door with weather strip, threshold and<br />

door closer with 90 degree hold open<br />

h) Trench drain with sectional removable cover<br />

i) Electrically operated insulated overhead door (controls in<br />

receiver’s office)<br />

j) Refrigeration unit to maintain air temperature at 55 F (13 C).<br />

Director of engineering’s office (approximately 150 ft 2<br />

following features:<br />

– 14 m 2 ) shall have the<br />

a) Electrical outlets<br />

b) Computer systems outlets<br />

Director of engineering’s secretary and assistance engineer’s office (approximately<br />

180 ft 2 – 17 m 2 ) shall have the following features:<br />

a) Electrical outlets<br />

b) Computer systems outlets<br />

c) Terminal for BMS (Building Management System).<br />

The maintenance areas shall require the following features:<br />

REV. MARCH 2006 152<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Maintenance Area (continued)<br />

a) In addition to what is indicated below, the following number of<br />

single phase electrical outlets, each mounted at 4’0” (1.2 m) on<br />

centre line AFFL and on a separate circuit will be provided<br />

throughout the maintenance areas:<br />

i) Five 110V x 15<strong>amp</strong> duplex<br />

ii) Two 110V x 30<strong>amp</strong><br />

iii) Three 220V x 15<strong>amp</strong><br />

iv) One 220V x 50<strong>amp</strong><br />

v) One TV antenna outlet and two 110V x 15<strong>amp</strong> duplex outlet<br />

mounted at 4’0” (1.2 m) on centre line AFFL (TV repair<br />

desk)<br />

vi) Wall mounted telephones<br />

vii) TV antenna outlet and duplex electrical outlet, both<br />

mounted at 4’6” (1.4 m) on centre line AFFL (secured<br />

storage room).<br />

b) Work bench system along full length of two walls, consisting of<br />

the following:<br />

i) Hardwood work top 2’6” (0.8 m) wide, at a height of 3’0”<br />

(0.9 m) AFFL with lockable drawers under (see Fairmont<br />

Hotels & Resorts Standard Details)<br />

ii) Hardwood and metal work top 2’6” (0.8 m) wide, at a height<br />

of 3’0” (0.9 m) AFFL with lockable drawers and doors<br />

under (see Fairmont Hotels & Resorts Standard Details)<br />

iii) TV work bench with mirror above (see Fairmont Hotels &<br />

Resorts Standard Details).<br />

c) Shift engineer requires the following features:<br />

i) Electrical outlets<br />

ii) Computer systems outlets<br />

iii) Remote terminal for BMS (Building Management System)<br />

iv) Plan table and plan hanging rack.<br />

REV. MARCH 2006 153<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

1.11. Paint Shop<br />

Each maintenance area shall include a separate paint shop with separate exhaust system.<br />

In addition, the shop will have a 10’0” (3 m) long hardwood work bench (see Fairmont<br />

Hotels and Resorts Standard Details) and deep stainless steel double bowled sink on<br />

floor mounted frame with wall mounted tap set with swivel spout.<br />

1.12. Carpentry Shop<br />

Each maintenance area shall include a carpentry shop with special, local filters on the<br />

return air system. In addition, the shop will have a hardwood work bench (see Fairmont<br />

Hotels & Resorts Standard Details) and include the following features:<br />

a) One 208V x 30<strong>amp</strong> single phase outlet at 7’6” (2.3 m) on centre<br />

line AFFL<br />

b) Three 110V x 15<strong>amp</strong> outlets at 4’0” (1.2 m) on centre line AFFL<br />

c) Three 110V x 15<strong>amp</strong> outlets at 1’0” (0.3 m) on centre line AFFL<br />

d) One 110V x 15<strong>amp</strong>-outlet flush mounted in floor in centre of<br />

room (circular saw outlet).<br />

REV. MARCH 2006 154<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

2. EMPLOYEE FACILITIES<br />

2.1. Employee Entrance<br />

Provide main access and point of control for staff. The employee entrance must be<br />

located on a separate elevation, away from the main guest entry and separate from the<br />

truck dock and adjacent to the security office. The entrance should be close to the<br />

employee facilities and human resources and it should not require staff to walk through<br />

food and beverage areas.<br />

Telephone on exterior wall adjacent to entry door with direct ring to security office.<br />

Electric latch on entry door, operated from security office so security officer can open<br />

door upon identification of person into back of house area.<br />

A CCTV camera positioned so as to clearly identify person at entry door.<br />

2.2. Security Office<br />

Provide an office space adjacent to the staff entrance for the Security officers and<br />

Security Manager.<br />

The security office shall incorporate the following features:<br />

a) Glazed screen with speak through opening<br />

b) CCTV monitors and VCR<br />

c) Remote door alarm console<br />

d) Duplex electrical outlets (UPS)<br />

e) Worktops and cupboards above and under<br />

f) Remote fire alarm panel<br />

g) Dutch entry door<br />

h) Full height laminated glass window (at entrance)<br />

i) Button to operate electric strike on main staff entry door<br />

j) Power bar with a minimum of 40 outlets (radio and pager chargers)<br />

k) Duplex electrical outlet and two telephone outlets (pager master<br />

control unit).<br />

REV. MARCH 2006 155<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

2.3. Primary Service Corridor<br />

Provide circulation for employees, goods and servicing. In the corridor servicing the<br />

ballroom, locate food service equipment in alcoves. Provide vestibule towards different<br />

ballroom access.<br />

Main service corridor to be a minimum of 8’0” (2.4 m) wide. Elsewhere, provide 6’6”<br />

(2.0 m) service corridor, except behind ballrooms (see ballroom standards for details).<br />

A double set of rubbing rails shall be installed in all service corridors, service elevators,<br />

service elevator foyers and vestibules. They shall be 2” wide x 6” high (5 x 15 cm) and<br />

installed at 9” (23 cm) at centerline AFFL and 2’11” (0.9 m) at centerline AFFL.<br />

2.4. Men’s and Women’s Locker Rooms<br />

Provide toilets, showers, wet vanity, grooming area and changing area with lockers for<br />

female and male employees; toilets should be separate from public toilets.<br />

Provide barrier-free WC stall as per local code requirements.<br />

Refer to specific program requirements to determine areas and quantities of lockers<br />

required.<br />

Unless otherwise indicated, female employees represent 60% of staff; male employees<br />

represent 40% of staff.<br />

Formula for calculating the locker area is (i) in cold climates is quantity of lockers x<br />

4.5 ft 2 – 0.4 m 2 ) and (ii) in warm climates is quantity of lockers x 3 ft 2 – 0.3m 2<br />

Should be located near Employee Entrance and Uniform issue.<br />

Provide janitor closet (approximately 36 ft 2 – 3.3 m 2 ).<br />

The lockers shall have sloping tops, infill pieces and bases.<br />

The rows between the lockers shall be 4’0” (1.2 m).<br />

Locker dimensions in (i) cold climates shall be 10” wide x 16” deep x 6’0” high – 03 x<br />

05 x 1.8 m (excluding base) and in (ii) warm climates they shall be 8” wide x 16” deep<br />

x 6’0” high – 20 cm x 0.5 m x 1.8 m (excluding base).<br />

One wall mounted notice board size 4’0” long x 3’0” high (1.2 m x 0.9 m).<br />

Duplex electrical outlet for shoeshine machine.<br />

Full-length mirror at entrance (on locker side) size 2’6” wide x 6’6” high (0.8 x 2 m)<br />

REV. MARCH 2006 156<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

2.5. Employee Cafeteria<br />

Provide lounge (approximately 1,300 ft 2 – 121 m 2 ) and dining facilities dedicated for<br />

employee use. Allow for non-fixed tables and chairs. Accommodate hot cooking line<br />

and food service support area.<br />

The minimum number of seats required should be calculated according to the following<br />

formula: number of guestrooms x 0.67 divided by 4.<br />

Allow 20 ft 2 (1.9 m 2 ) per seat.<br />

Locate off service circulation, near kitchen. Exterior views are desirable.<br />

Duplex electrical outlets for housekeeping, TVs and pay phones.<br />

Separate circuit 110V x 20 <strong>amp</strong> electrical outlet for drink vending machine and cold<br />

water drinking fountain.<br />

Ceiling speakers for background music with volume control in food servicing area.<br />

One wall mounted notice board size 4’0” long x 3’0” high (1.2 x 0.9 m).<br />

Wooden chair rail 34” (86 cm) at center line AFFL.<br />

2.6. Employee Washrooms<br />

The main washrooms form part of the staff locker room and must be carefully, but<br />

functionally designed to demonstrate Fairmont Hotels and Resorts’ concern for its staff.<br />

Provide an employee washroom at each guestroom floor adjacent to maids closet.<br />

2.7. First Aid Station<br />

Provide an office/first aid facility (approximately 300 ft 2 – 28 m 2 ) to attend to<br />

employees’ first aid needs. Allow for concealed space to accommodate a bed. Provide a<br />

first aid counter and storage.<br />

Preferably locate first aid service off service circulation near human resources offices.<br />

2.8. Training Room, Staff Meeting Room<br />

Provide a meeting room facility (approximately 450 ft 2 – 42 m 2 ) to accommodate<br />

education, staff meetings and other personnel activity.<br />

Located near the human resources office the room shall have the following features:<br />

a) Recessed motorized projection screen<br />

b) Marker board and pin up type wall covering<br />

c) Presentation rail<br />

REV. MARCH 2006 157<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Training Room, Staff Meeting Room (continued)<br />

d) Duplex electrical outlets for A/V equipment<br />

e) Wall telephone at entry door<br />

f) Storage closets<br />

g) Computer systems outlets.<br />

REV. MARCH 2006 158<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

2.9. Functional Diagram: Employee Facilities Layout<br />

Receiving<br />

Dock<br />

Human<br />

Resources<br />

Employee<br />

Entrance<br />

Security<br />

Office<br />

Housekeeping<br />

Laundry<br />

and<br />

Uniform Issue<br />

Training<br />

Room<br />

Training<br />

Manager<br />

Main<br />

Kitchen<br />

Employee<br />

Cafeteria<br />

Men’s<br />

and<br />

Women’s<br />

Locker<br />

Room<br />

Toilets<br />

REV. MARCH 2006 159<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

3. HOUSEKEEPING, LAUNDRY & VALET<br />

3.1. General Requirements<br />

The laundry will be an on-site, full-service facility including dry cleaning and a 24-hour<br />

valet service.<br />

The laundry facility should be located adjacent to the housekeeping and service elevator<br />

core and should be easily accessible from main service corridor.<br />

The valet dry cleaning equipment is to be in a separate room accessible from the dryer<br />

end of the wash line and by housekeeping for after-hours service.<br />

Provide a laundry chute to send linen directly from guestroom floors to the laundry's<br />

soil sort room. Allow for cart stacking at both the soiled sorting and folding areas.<br />

Linen chutes are to have the following features :<br />

a) A 2’6” (0.8 m) diameter, 18 gauge aluminium or galvanized steel<br />

linen chute is required to serve all guestroom floors and discharge<br />

into the laundry soiled linen area<br />

b) Intake doors shall be stainless steel and of the bottom hinged, selfclosing<br />

hopper type with a clear opening 2’0" x 2’0" ( 0.6 x 0.6 m)<br />

and complete with lock and bar support and name plate “soiled<br />

linen”<br />

c) The outlet door shall be stainless steel and of the top hinged type<br />

normally held in the open position by a fusible link set at 165 F<br />

(74 C)<br />

d) Bottom of linen chute (chute discharge point) shall be located at<br />

8' 6" (2.6 m) AFFL<br />

e) Door discharge section shall be supported on a pipe pedestal<br />

mounted on the floor or similar means<br />

f) The bottom “turning” section of the chute shall be suitably<br />

reinforced to resist damage caused by bottles or similar items being<br />

inadvertently dropped down the chute<br />

g) The chute securing brackets shall be securely fixed to the various<br />

floor slabs. However, the chutes themselves shall be isolated from<br />

the floor slabs to minimize noise transmission to adjacent rooms<br />

h) The chute itself should also be insulated to minimize vibration and<br />

sound transmission<br />

i) Provide vent and protected sprinkler heads as required<br />

j) Provide chute wash-down system including drain<br />

REV. MARCH 2006 160<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Housekeeping, Laundry & Valet/General Requirements (continued)<br />

k) Where hotels have long corridors, additional linen chutes will be<br />

required to reduce travel distance for maids<br />

l) Each chute should be accessed from a small service room<br />

(approximately 50 ft 2 – 4.6 m 2 ), requiring a linen sorting room<br />

complete with sorting slide at the termination of the chute. These<br />

termination rooms are to be on the same level as the laundry.<br />

Clean linens are to be returned to the guestroom floors for storage.<br />

The valet, housekeeper’s office and related storerooms shall all be entered off the main<br />

housekeeping area.<br />

The following features are to be provided at the entrance to this area:<br />

a) Electrical outlets at 4’6” (1.4 m) on centre line AFFL (time st<strong>amp</strong>)<br />

b) Cork bulletin board 4’0” long x 3’0” high (1.2 x 0.9 m).<br />

The following items are to be provided within the main housekeeping area:<br />

a) Duplex electrical outlets (if not located in valet area)<br />

b) Telephone outlets<br />

c) Soaking sink<br />

d) Lost and found cabinet<br />

e) Housekeeping counter<br />

f) Linen clerk station<br />

g) Issue counter<br />

h) Cubicle with two robe hooks (staff try on uniforms) with fulllength<br />

mirror.<br />

Formula for calculating area of housekeeping including daily linen and uniforms, day<br />

stores, seamstress, lost and found and issuing is:<br />

Quantity of guestrooms x 3 = ft 2 required.<br />

Housekeeper’s office (approximately 150 ft 2 – 14 m 2 ) to include the following features:<br />

a) Cork bulletin board 2’0” wide x 3’0” high (0.6 x 0.9 m)<br />

b) Electrical outlets<br />

c) One duplex electrical outlet (UPS)<br />

d) Telephone outlet<br />

The valet (approximately 550 ft 2 – 51 m 2 ) will provide full dry cleaning and pressing of<br />

guests’ clothes, staff uniforms, drapes and blankets seven days a week.<br />

REV. MARCH 2006 161<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Housekeeping, Laundry & Valet/General Requirements (continued)<br />

One hour pressing of guests’ clothes will be offered generally between the hours of 7<br />

am and 8 p.m. seven days a week as well as overnight pressing.<br />

The valet area shall incorporate the following features:<br />

a) Duplex electrical outlet and telephone at valet’s desk location<br />

b) Duplex electrical outlet at sewing machine location<br />

c) Duplex electrical outlet and telephone at shoe shine location<br />

d) Special exhaust duct system over dry cleaning unit<br />

e) Blocking in ceiling for support of slick rails for valet equipment<br />

f) Allow 20 ft 2 (1.9 m 2 ) for perc drum storage<br />

g) Guest check-in table/bins unit<br />

h) All compressor air lines to have quick disconnects and automatic<br />

moisture traps with a water leg and drain valve<br />

i) Direct exhaust outlet to vacuum unit.<br />

The laundry will be designed to process all the hotel’s textiles and also to provide same<br />

day full guest laundry, seven days a week.<br />

Fairmont Hotels and Resorts’ laundries are designed based upon the following criteria:<br />

a) Average load produced per room in (a) City Hotels is 25 lbs<br />

(11.4 kg) and in (b) Resorts is 38 lbs (17.2 kg, in (c) Hotels with<br />

Willow Stream Spa’s is 35 lbs (20.4 kg) and in (d) Resorts with<br />

Willow Stream Spa’s is 48 lbs (21.7 kg)<br />

b) Equipment to be designed to suit 100% occupancy based upon 1.2<br />

loads per washer and dryer per hour<br />

c) Laundry will operate 6 days per week and will be staffed 48 hours<br />

per week, although washmen’s shifts will be staggered to allow<br />

equipment to start early.<br />

The formula for calculating the area of the laundry production space and soil sort area is:<br />

a) City Hotel: Quantity of Guestrooms x 25 x 7 x 3.5 divided by 48,<br />

(b) Resort Hotel: Quantity of Guestrooms x 38 x 7 x 3.5 divided by<br />

48, (c) Hotels with Willow Stream Spa’s: Quantity of guestrooms<br />

x 35 x 7 x 3.5 divided by 48 and (d) Resorts with Willow Stream<br />

Spa’s: quantity of guest rooms x 48 x 7 x 35 divided by 48.<br />

b) The 3.5 ft 2 (0.32 m 2 )/lb./hour is calculated from 28 ft 2<br />

(0.26 m 2 )/lb./hour for laundry including laundry manager’s office<br />

and 0.7 ft 2 (0.07 m 2 )/lb./hour for linen chute discharge and soil sort<br />

REV. MARCH 2006 162<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Housekeeping, Laundry & Valet/General Requirements (continued)<br />

c) 3.3 Days of textile supply in circulation and 1.1 in storage for a<br />

Total of 4.4 pars<br />

d) Washer equipment safety factor is 20% of required production in<br />

pounds/hour.<br />

The access corridor from the truck dock to the laundry shall be 10’0” ( 3.0 m) wide with<br />

a pair of 6’0” (1.8 m) wide entry doors into the laundry and a 4’0” (1.2 m) wide<br />

removable side panel.<br />

Extreme care must be taken to ensure that vibration and acoustics ramifications are fully<br />

resolved.<br />

The dryer exhaust duct to have a lint filter and thermal insulation outside the dryer<br />

enclosure to the lint filter room.<br />

All dryer ducts must have clean out panels every 20’0” (6.1 m) of horizontal length.<br />

Softened hot and cold water to laundry and valet to 0-2 grains hardness.<br />

Hot water supply to washers must be at 160 F (71 C) in adequate volume to fill the<br />

washers in the required time period.<br />

Water hammer arresters must be used on washer water lines.<br />

Room to be conditioned to not exceed 80 F (27 C).<br />

Formula for calculating the area for the soil sort room, including slide: Quantity of<br />

guestroom x 25 (City Hotels), 38 (Resort Hotels), or 38 (Hotel and Willow Stream Spa)<br />

and 48 (Resort and Willow Stream Spa) x 7 x 0.7 divided by 48.<br />

The soil sort room to have the following features:<br />

a) A duplex electrical outlet located at 5’6” (1.7 m) on centre line<br />

AFFL and floor sink<br />

b) Chute to be as manufactured by Wilkinson Chute Company Inc.<br />

with a truncation at 8’6” (2.6 m) on centre line AFFL<br />

c) Soil sort table width and length to suit hotel volume and to<br />

manufactured of plastic laminated. Height to slope from 3’0”<br />

(0.9 m) at back to 1’0” (0.3 m) at front to move work to front of<br />

platform<br />

d) Flooring to epoxy floor finish behind washers and dry cleaning<br />

machine. Elsewhere to be vinyl tiles with 4” (10 cm) high vinyl<br />

baseboard<br />

e) Chemical supplies and detergent to be stored in separate laundry<br />

chemical room. Size to be based upon 30-day delivery period.<br />

Provide storage for housekeeping functions:<br />

REV. MARCH 2006 163<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Housekeeping, Laundry & Valet/General Requirements (continued)<br />

a) Linen storage<br />

b) Glassware storage (glasswashing)<br />

c) Cleaning materials storage<br />

d) Hotel bulk storage<br />

e) Hotel dead storage<br />

f) Hotel stationary/paper storage<br />

g) Lost and Found storage<br />

h) Uniform storage<br />

i) Valet equipment area.<br />

Formula for calculating storage areas for typical city and resort hotel (where properties<br />

are offshore or remote with less predictable delivery periods increase allowance by<br />

50%):<br />

a) Bulk storage: Quantity of guestrooms x 1 = ft 2 (0.09 m 2 )<br />

b) Dead storage: Quantity of guestrooms x 1 = ft 2 (0.09 m 2 )<br />

c) Stationery and Paper storage: 100 ft 2 (9.3 m 2 ) per 200 guestrooms<br />

d) New textile (“unissued”) storage (calculations per 100 guestrooms<br />

at 100% occupancy): (a) City hotels-room textiles 60 ft 2 (5.6 m 2 ) x<br />

1.25 and F and B textiles 75 ft 2 (7.0 m 2 ) x 0.25 and (b) Resort<br />

hotels – as city hotels plus 25%<br />

e) Food and Beverage Textiles (“in circulation”) storage (based on a<br />

storage height of 6’0” and shelving 2’0” wide):<br />

i) Ballroom and Meeting rooms: 2 ft 3 (0.06 m 3 ) per 100 ft 2 (9.3<br />

m 2 ) of meeting space, plus<br />

ii) Restaurants: ½ ft 3 (0.02 m 3 ) per seat, plus<br />

iii) Room service: ½ ft 3 (0.02 m 3 ) x 75% of quantity of<br />

guestrooms (for Resort hotels) x 50% of quantity of<br />

guestrooms (for City hotels)<br />

iv) Add (i) + (ii) + (iii) / 6 (convert from ft 3 to ft 2 ) x 1.25<br />

(aisles) x 2 (separate parts) = total storage area required in<br />

ft 2 .<br />

REV. MARCH 2006 164<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Housekeeping, Laundry & Valet/General Requirements (continued)<br />

Provide distribution for housekeeping functions:<br />

a) Distribution of housekeeping supplies<br />

b) Uniform distribution<br />

c) Provide an office for the Housekeeping Manager<br />

d) Provide a desk/work area for Housekeeping Assistant Manager.<br />

Size and areas to be determined by specific program requirements.<br />

Housekeeping functions should ideally be grouped together adjacent to the Laundry,<br />

service circulation and the Service Elevator.<br />

3.2. Night Cleaner’s Storeroom<br />

The night cleaner’s store (approximately 150 ft 2 – 14 m 2 ) is to have direct access from<br />

the service corridor.<br />

Night cleaner’s store to include the following features:<br />

a) Floor sink with hot and cold water, hose bib and tile surround and<br />

mop rack<br />

b) Floor drain<br />

c) Heavy duty shelving 6’0” long x 3’0” wide (1.8 x 0.9 m) and full<br />

room height<br />

d) Waterproof duplex electrical outlet<br />

e) Wall mounted telephone.<br />

REV. MARCH 2006 165<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

3.3. Functional Diagram : Typical Layout for Housekeeping & Laundry<br />

Soil<br />

Sort<br />

Room<br />

Laundry/<br />

Dry Cleaning<br />

Receiving<br />

Dock<br />

Employee<br />

Entrance<br />

Service<br />

Elevators<br />

Housekeeping<br />

Supplies<br />

Distribution<br />

Housekeeping<br />

Storage<br />

Area<br />

Uniform<br />

Distribution<br />

Employee<br />

Facilities<br />

Housekeeping<br />

Manager<br />

REV. MARCH 2006 166<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

4. KITCHEN AND FOOD PREPARATION<br />

4.1. General Requirements<br />

Provide kitchen space for Hotel and Function needs. A single main production kitchen<br />

is preferred but could be subdivided into different preparation kitchens when the<br />

Restaurants or the Ballroom and other Functions spaces are on different levels. The<br />

kitchen is to be planned into specific and separated areas:<br />

a) Receiving food and beverage goods<br />

b) Main production<br />

c) Bakery<br />

d) Butcher shop<br />

e) Food preparation<br />

f) Garde manger<br />

g) Food pick-up, beverage and service stations<br />

h) Pot and pan washing areas<br />

i) Trash rooms<br />

j) Chef’s office<br />

k) Assistant Chef’s office<br />

l) Director of Food and Beverages office<br />

m) Flower work shop<br />

n) Banquet kitchen.<br />

Configuration and planning of kitchen areas to be determined by specific program<br />

requirements.<br />

The main kitchen should be adjacent to the restaurants and also to the ballroom and<br />

other meeting rooms. It should be linked to these spaces by generous service corridors.<br />

Provide separate internal circulation between the different kitchen spaces. Close<br />

proximity to the receiving space and to the service elevator. Service stands near food<br />

preparation and pick-up lines. Conditioned trash room adjacent to the receiving dock.<br />

4.2. Storage<br />

Provide separate storage areas for dry, refrigerated and frozen goods (approximately<br />

40% of net kitchen area).<br />

Provide modular walk-in freezers and refrigerator.<br />

All main storage areas to be close to the production Kitchen and located between the<br />

Receiving Dock and the Kitchen receiving space.<br />

REV. MARCH 2006 167<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

4.3. Room Service<br />

The purpose of this space is to provide a room service set-up area and an office for<br />

room service order.<br />

Allow space for orders, preparation and cart set-up.<br />

This space should be part of the main kitchen, separated from the main production line<br />

and located close to the service elevators.<br />

Room service cashier’s office shall have the following features:<br />

a) Two duplex electrical outlets (UPS) and three for “point of sale”<br />

system and one electrical outlet and computer outlet (both UPS)<br />

b) Three 110V 15 <strong>amp</strong> duplex electrical outlets and three telephone<br />

outlets all mounted 33” (84 cm) on centre line AFFL (credit card<br />

related equipment)<br />

c) Built in counter 10’0” (3 m) long (minimum) x 2’6” x 3’0” high<br />

(0.8 x 0.9 m) with lockable drawers under at each end<br />

d) 110V 15<strong>amp</strong> electrical outlet 12” (30 cm) on centre line AFFL on<br />

wall opposite counter<br />

e) Provide intercom between cashier’s office (microphone) and room<br />

service set up (loudspeaker). Also between cashier’s office and<br />

kitchen hot line if the latter is not directly visible from Room<br />

Service Office. Microphone and loudspeakers at both locations<br />

f) Shelf 9” wide x 24” long 60” (23 x 60 x 152 cm) on centre line<br />

AFFL with duplex electrical outlet 6” (15 cm) above top of shelf<br />

(pagers and charger).<br />

4.4. Flower Work Room<br />

The flower workroom (approximately 300 ft 2 – 28 m 2 ) is to have the following features:<br />

a) Air conditioning is to be 65 F (18 C)<br />

b) A double bowl sink<br />

c) Full height reach-in refrigerator<br />

d) Stainless steel work counter with drawers under<br />

e) Duplex electrical outlets<br />

f) Telephone outlets.<br />

REV. MARCH 2006 168<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

5. RECEIVING AND PURCHASING<br />

5.1. Loading Area<br />

The loading dock is the main lifeline of the hotel and is where loading and unloading<br />

hotel supplies, food, furnishing and other related items take place.<br />

Truck access should be completely concealed from guest view and hearing.<br />

Provide a minimum of two service bays and one additional bay for the trash<br />

compactor/container.<br />

Overhead clearance for the service bays: 14’0” (4.3 m).<br />

Height of dock may vary due to building floor elevations. However height of 3’0”<br />

(0.9 m) to 3’6” (1.1 m) is desirable. A 4’0” (1.2 m) wide r<strong>amp</strong> should be incorporated<br />

for hand trucks as well as a recessed ladder or steps.<br />

Locate near service elevator core and service circulation areas and preferably close to<br />

the kitchen dry and cold storage.<br />

Deep stainless steel double sink unit and work surface, on floor mounted frame with<br />

two wall mounted tap sets with swivel spouts and two flexible spray faucets with wall<br />

brackets (see Fairmont Hotels and Resorts Standard Details)<br />

The loading dock area should incorporate the following features:<br />

a) Duplex electrical outlet for weigh scale adjacent to receiver’s<br />

office<br />

b) Floor drain adjacent weigh scale<br />

c) Cold water hose connector for washing down<br />

d) 110V 20 <strong>amp</strong> electrical outlet (separate circuit) adjacent to hose<br />

connector for high pressure water wash down unit<br />

e) Electric dock levelers<br />

f) Weatherproof duplex electrical outlets<br />

g) Truck bumpers at edge of truck dock<br />

h) Floor drains<br />

i) In colder climates truck dock to be heated by thermostatically<br />

controlled forced air unit heaters<br />

j) All exposed vertical edges to have 3” x 3” x ¼” (7.6x7.6x 0.6 cm)<br />

thick x 4’6” (1.4 m) long (steel angle<br />

k) Protect exposed overhead door guides with bollards<br />

l) Intercom from exterior of truck dock gates to receiver’s office<br />

REV. MARCH 2006 169<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

Loading Area (continued)<br />

m) CCTV cameras<br />

n) Horizontal 2” thick x 12” high (5 x 30 cm) wood or plastic<br />

robrails, mounted 3’6” (1.1 m) to center line AFFL on all exposed<br />

walls<br />

o) Wall mounted telephone adjacent to intercom at truck gate and at<br />

truck dock receiver’s office.<br />

5.2. Offices<br />

Provide space for purchasing functions and for loading dock control office<br />

(approximately 250 ft 2 – 23 m 2 ).<br />

The purchasing offices should be located near the loading dock with the control office<br />

adjacent to the loading dock and linked to other back-of-house activities by the main<br />

service corridor.<br />

REV. MARCH 2006 170<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

5.3. Back-of-House Standards Details<br />

Page<br />

TYPICAL ENGINEER’S WORK BENCH 172<br />

TYPICAL ENGINEER’S WORK COUNTER 173<br />

TYPICAL ENGINEER’S TV WORK BENCH 174<br />

TYPICAL CARPENTRY WORKSHOP 175<br />

TYPICAL CARPENTRY WORK BENCH DETAILS 176<br />

TYPICAL LAYOUT – LOADING DOCK AREA 177<br />

TYPICAL STAFF TRAINING ROOM 178<br />

TYPICAL SOIL SORT TABLE 179<br />

TYPICAL ROOMS SERVICE CASHIER’S OFFICE 180<br />

TYPICAL MAILROOM COUNTER 181<br />

TYPICAL MAIL SORTING UNIT 182<br />

TYPICAL LAYOUT TELEPHONE OPERATORS ROOM 183<br />

TYPICAL TELEPHONE OPERATORS WORKSTATION 184<br />

TYPICAL STAFF CASH DEPOSIT OFFICE 185<br />

TYPICAL SECURITY OFFICE AND DETAILS 186<br />

TYPICAL COMPUTER ROOM 187<br />

COMPUTER ROOM ELECTRICAL REQUIREMENTS 188<br />

4-PLEX JACK DETAIL 189<br />

REV. MARCH 2006 171<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 172<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 173<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 174<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 175<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 176<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 177<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 178<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 179<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 180<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 181<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 182<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 183<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 184<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 185<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 186<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 187<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 188<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

REV. MARCH 2006 189<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

E. SERVICES AND SYSTEMS<br />

1. MECHANICAL<br />

1.1. General Requirements<br />

The requirements for air conditioning, ventilation and heating for Fairmont Hotels and<br />

Resorts will vary widely due to the differences in climates of the cities in which the<br />

hotels or resorts are to be located. All latest ASHRAE standards 62-(latest edition) and<br />

55-(latest edition) must be strictly adhered to unless directed otherwise.<br />

The system is to be designed for all spaces except mechanical and electrical plant rooms<br />

to be air-conditioned.<br />

The design of the system is to take into account the following design criteria:<br />

a) Humidity, especially where hotels are in hot and humid climates<br />

b) Condition and/or ventilation air in all enclosed corridors having direct<br />

access to guestroom, as well as stairways and storage rooms adjacent to<br />

guestrooms<br />

c) Ceiling plenums will not be used for corridor air distribution<br />

d) Sizing of guestroom cooling loading should be based upon 97 ½ %<br />

ASHRAE, 1 person occupancy per king room, 2 person occupancy per<br />

double/double, (these numbers are to be doubled for resort hotels), 1,250<br />

watts of lighting, drapery sheets closed, no outside air infiltration and<br />

75 F (24 C) desired room cooling temperature<br />

e) Double directional, fully adjustable louver deflectors on fan coil air<br />

diffusers<br />

f) Guestroom are to be designed to maintain positive pressure<br />

g) High-rise hotels to be provided with toilet exhaust roof-top fans (to<br />

shutdown or limit speed during midday and night-time)<br />

h) All supply and return air grilles in public areas, when exposed to the<br />

public, are to linear type<br />

i) The design is to take into consideration both latent heat gain and<br />

dehumidification performance of air conditioning system as part of the<br />

energy analysis computer program<br />

j) Cooling load for health clubs and spa exercise rooms are to be calculated<br />

on a basis of a the room being fully occupied, with guests doing a<br />

vigorous workout<br />

k) Chilled water piping systems are to be designed with balancing capability<br />

l) The design is to take into consideration both latent heat gain and<br />

dehumidification performance of air conditioning system as part of the<br />

energy analysis computer program<br />

REV. MARCH 2006 190<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

m) Cooling load for health clubs and spa exercise rooms are to be calculated<br />

on a basis of a the room being fully occupied, with guests doing a<br />

vigorous workout<br />

n) Chilled water piping systems are to be designed with balancing capability<br />

o) In tropical and salty environments, cooling towers are to be constructed<br />

of corrosion resistant fiberglass reinforced polyester and all other<br />

components, including nuts and bolts are to be “rust resistant quality”<br />

stainless steel<br />

p) Guest toilet exhaust fans are to be designed to maintain negative pressure<br />

with respect to adjacent rooms and positive pressure with respect to<br />

outside air<br />

q) Make up air for toilet rooms and other exhaust systems should be<br />

designed to be continuously conditioned air and not filtrating outside air,<br />

nor natural ventilation.<br />

The steam service equipment is to be designed to meet the following criteria:<br />

a) Laundry and valet equipment, unless otherwise specified by the<br />

equipment manufacturer is to be supplied with a pressure of 125 psi<br />

(8.8 kqf/cm 2 )<br />

b) Kitchen and dishwashing equipment, unless otherwise specified by the<br />

equipment manufacturer is to be supplied with a minimum pressure of<br />

12 psi (0.8 kqf/cm 2 ) and a maximum of 30 psi (2.1 kqf/cm 2 )<br />

Boiler plant equipment is to be designed to meet the specific load requirements and<br />

consideration must be made for the following criteria:<br />

a) Types of fuel available and their associated costs<br />

b) Hot water heaters, reheat for humidity control, direct heating and air<br />

tempering is to be supplied with a pressure of 5 to 10 psi (0.35 kqf/cm 2 to<br />

0.7 kqf/cm 2 )<br />

c) Dependability of the local fuel supply<br />

d) Daily and seasonal variations of load<br />

e) Availability and quality of the local supplier’s organization<br />

f) Whether or not licensed operators are required (unlicensed operators are<br />

preferred)<br />

g) The need for winter heating and the possible utilization of steam during<br />

cooling season and air conditioning refrigeration plant<br />

h) The boilers are not to be sized to merely meet the anticipated peak load<br />

condition, but must be selected to provide sufficient excess capacity to<br />

REV. MARCH 2006 191<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

permit one unit to be removed from service for repairs and maintenance<br />

without seriously affecting the operations of the hotel. The minimum<br />

boiler selection must be two units each sized to provide approximately<br />

two thirds of the peak load<br />

i) If boilers are to be oil fired then the capacity of the fuel storage facilities<br />

must be designed to accommodate a two-week supply.<br />

All air conditioning installations are to be of the central plant type, supplying chilled<br />

water to the various air-handling units.<br />

As the equipment is to be designed to operate on a 24 hours, 365 day per year basis it<br />

must be selected in multiple units with sufficient spare capacity to maintain comfort of<br />

the guests during periods of average weather conditions and occupancy during times<br />

when one unit may be taken out of service.<br />

The selection of the refrigeration plant equipment, excluding the kitchen refrigeration<br />

equipment, which will be supplied under the kitchen equipment contract, must take into<br />

consideration the following criteria:<br />

a) Climatic conditions and degree of discomfort expected if breakdown<br />

occurs<br />

b) Availability and reliability of supply<br />

c) Cost of water<br />

d) Chemical and physical properties of available water<br />

e) Availability, quality and cost of electrical energy supply<br />

f) Availability and cost of hotel produced steam<br />

g) Availability of skilled maintenance labor<br />

h) Type of equipment with which local maintenance labor is familiar<br />

i) Availability of manufacturer’s local service organization and their skill<br />

levels<br />

j) Availability of replacement parts<br />

k) Chiller quantity and capacity calculations are to be based upon the same<br />

criteria as for boilers<br />

l) All condensers are to be water cooled and piped to a complete cooling<br />

tower water system<br />

m) If the cooling towers for the air conditioning plant do not operate year<br />

round, then a separate cooling tower is to be installed for the refrigeration<br />

plant and ice makers<br />

REV. MARCH 2006 192<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

n) Cooling towers must be located so that the noise generated by them, as<br />

well as their discharge air will not be objectionable to the hotel guests.<br />

Circulating pumps are to be designed and specified to meet the following criteria:<br />

a) Motor driven, centrifugal type<br />

b) Large pumps are to be horizontally split case, double suction type<br />

c) Smaller pumps are to be vertically split case, end suction type<br />

d) All pumps to have shut off valves and strainers in the suction side and<br />

check valves and throttling valves on the discharge side<br />

e) The design pressure for each pump must be at least equal to one and a<br />

half times their working pressure<br />

f) Pumps must be installed on spring-isolated concrete inertia blocks, etc to<br />

ensure that noise and vibration is not be transmitted to the building<br />

structure<br />

g) Chilled water and condenser water pumps are to have factory mechanical<br />

seals installed<br />

h) Each chiller is to have a minimum of one chilled water pump and one<br />

condenser water pump and shall be piped to allow cross-use<br />

i) Each boiler is to have one circulating pump.<br />

Heat exchangers are to be designed and specified to meet the following criteria:<br />

a) Steam to water and water to water heat exchangers are to be of the shell<br />

and tube type<br />

b) Heat exchangers are to be mounted in cast iron or welded steel cradles on<br />

structural steel frames or concrete piers.<br />

Pressure reducing stations are to be self-contained or air pressure operated.<br />

A central air compressor plant is to be designed to meet the following criteria:<br />

a) The plant is to be consist of at least two compressors, a receiver, water<br />

cooler, moisture and oil elimination and reducing station<br />

b) Discharge air pressure is to be a minimum of 100 psi (7 kqf/cm 2 )<br />

c) A separate air compressor is to be designed and installed for the laundry<br />

and valet shop.<br />

A vacuum piping system is to be provided which will supply the laundry and valet<br />

equipment.<br />

The following areas must be air conditioned when outside design criteria for summer is<br />

above 75° dry bulb and 65° wet bulb:<br />

REV. MARCH 2006 193<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

a) Kitchen to have a required temperature of 80 F (27 C) dry bulb at 60%<br />

b) Bake shop, pastry shop, laundry and valet to have a required temperature<br />

of 80 F (27 C)<br />

c) Garde manger, chocolate shop, butcher shop and beverage stores to have<br />

a required temperature of 65 F (18 C)<br />

d) Computer room to have a required temperature of 72 F (22 C)<br />

e) Telephone equipment room to have a required temperature of 78 F (26).<br />

The VAV systems are to be designed using the following criteria:<br />

a) Maintain absolute minimum total system static<br />

b) Maintain absolute minimum duct velocities commensurate with economic<br />

and space limitations:<br />

i) Hotel bedroom and general offices – 1000 FPM<br />

ii) Boardrooms – 1200 FPM<br />

iii) Meeting rooms, ballrooms and pre-function areas – 800 FPM<br />

iv) Restaurants – 1500 FPM.<br />

c) Ducting should avoid components such as mitred elbows, conventional<br />

and acoustical turning valves, bullhead tees, etc in order to ensure that<br />

noise is kept to a minimum<br />

d) The air distribution ductwork must be sized on the basis of the Static<br />

Regain Method (SRM)<br />

e) Pressure-independent low-pressure VAV regulators must be selected to<br />

serve each occupied space<br />

f) Supply duct connection must be either galvanized metal or a maximum of<br />

five feet of bonded aluminum flex with no more than a 45° bend<br />

g) Terminal ceiling diffusers or booted-plenum slots specifically designed<br />

for VAV air distribution from the standpoint of minimum “dumping”<br />

action at reduced air volumes and from the standpoint of sound levels at<br />

maximum cfm delivery is to be selected.<br />

Quiet operating centrifugal fans are to be designed following:<br />

a) Rated in accordance with AMCA procedure and shall bear the AMCA<br />

seal<br />

b) Class I, II or II as recommended by AMCA based upon both operating<br />

pressures and maximum tip speed<br />

REV. MARCH 2006 194<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

c) Blades continuously welded to hub and inlet rim, are to be backward<br />

inclined from the direction of the rotation for non overloading power<br />

characteristic<br />

d) Bearings are to be precision anti-friction, pillow-block, either ball or<br />

roller type with an average minimum life of 60,000 full load hours<br />

e) Vibration isolators are to be provided.<br />

Cabinet type air supply units are to be designed and specified to meet the following<br />

criteria:<br />

a) Allow for maintenance access<br />

b) Fans are to be centrifugal non overloading silent type with double-inlet,<br />

multi-blades<br />

Steam coils are to be designed and specified to meet the following criteria:<br />

a) Coils to be of the steam distributing type-within-a-tube construction with<br />

heated return headers<br />

b) Coils are to be provided with an outlet for complete drainage of<br />

condensation<br />

c) Where temperatures fall below freezing, preheat coils are to have a<br />

minimum of two steam traps<br />

d) Each section of preheat coils is to have an individual control.<br />

Water-cooling and heating coils are to be designed and specified to meet the following<br />

criteria:<br />

a) Water heating and cooling coils are to be of the continuous tube type with<br />

vertical fins, tested to 300 psi (21.1 kqf/cm 2 ) pneumatic pressure and<br />

provided with positive methods of draining and venting<br />

b) Electric heating coils are to have finned tubular heating elements and are<br />

to be resistance wire centered in copper plated steel tubes<br />

c) Direct expansion coils are to have fins copper bonded to the tubes by<br />

hydraulic expansion of the tubes and tested to 300 psi (21.1 kqf/cm 2 )<br />

pneumatic pressure.<br />

Filters are to be designed and specified to meet the following criteria:<br />

a) Central air conditioning systems are to have high efficiency, high<br />

capacity bag type filters with pre-filters<br />

b) Ventilation systems serving utility areas are to have disposable filters<br />

REV. MARCH 2006 195<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

c) Where disposable or replaceable type filters are used, one set of spare<br />

filters is to be provided in addition to the new filter being installed.<br />

Guestroom air conditioning is to be designed and specified to meet the following<br />

criteria:<br />

a) Air conditioning units are to be of the fan coil type and where<br />

heating/cooling is required, the unit is to be a double coil four row type<br />

suitable for a Four Pipe System<br />

b) The unit is to be located over the entry vestibule and is to have a<br />

combined removable return air grill and access door located in the<br />

ceiling, with a supply grill in the face of the guestroom and to have piped<br />

drain connections in addition to secondary water connections<br />

c) The unit is to be provided with on/off and three-speed room thermostat<br />

control and selected for cooling at low fan speed. The unit having a rating<br />

of NC 30 night/day at low speed and NC 35 at medium speed with the fan<br />

running continuously at the selected speed and the thermostat provided<br />

with a deadband setting of a maximum of 75 F (24 C) and a minimum of<br />

68 F (20 C)<br />

d) The unit are to be generally controlled by the thermostat and pneumatic<br />

or electric modulating throttling valve<br />

e) Drain pans are to be provided and designed so that all valves and controls<br />

are directly over the pans.<br />

Radiators and convectors are to be designed and specified to meet the following criteria:<br />

a) In areas that experience severe winters, radiators and convectors must be<br />

provided below all glass areas not protected by air conditioning units.<br />

b) Heating units in unconditioned spaces are to be designed to handle the<br />

entire heating load, while in conditioned spaces, they are to be sized to<br />

operate in conjunction with the air conditioning system<br />

c) Hot water is preferable as a source of heat<br />

d) Temperature and humidity test readings are to be taken during periods of<br />

full occupancy of each area.<br />

Unit heaters are to be used in the following areas:<br />

a) Centrifugal blower type heaters are to be used at entrances<br />

b) Propeller type heaters are to be used at loading docks and equipment<br />

rooms.<br />

Control s<strong>amp</strong>les of the following materials are to be submitted to Fairmont Hotels and<br />

Resorts for approval, prior to ordering:<br />

REV. MARCH 2006 196<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

a) Supply grills<br />

b) Return grills<br />

c) Thermostats<br />

d) Guest bathroom exhaust grills.<br />

Electric motors are to be designed and specified to meet the following criteria:<br />

a) Motors and controls driving heating, ventilating and air conditioning<br />

equipment are to be supplied and installed by the Mechanical Contractor.<br />

The wiring for this equipment is to be supplied and installed by the<br />

Electrical Contractor<br />

b) All motors are to be of the quiet operating type and preferably should be<br />

from one manufacturer<br />

c) All motors and accessories are to comply in all aspects with NEMA<br />

standards, are to include a service factor and to be energy efficient<br />

d) Exhaust fans for guestroom dishwashers are to be wired so that the fan<br />

only works when the dishwasher is in operation.<br />

Ducts are to be designed and specified to meet the following criteria:<br />

a) Kitchen range hood exhaust ducts are to be manufactured from 16 gauge<br />

black iron and are to be provided with clean-outs are each bend, every 10<br />

(3 m) feet horizontally and every 20 feet (6 m) vertically<br />

b) Dishwashers and laundry flat ironers are to be manufactured from<br />

stainless steel for a minimum distance of 25 feet (7.6 m) from the<br />

equipment.<br />

c) Horizontal ducts from dishwashers are to pitch toward the equipment at<br />

one inch per ten feet<br />

d) Swimming pool supply air ducts are to be manufactured from aluminum,<br />

while exhaust ducts are to be manufactured from stainless steel<br />

e) Laundry dryer exhaust ducts are to be manufactured from galvanized<br />

steel with water tight joints and the interiors are to be smooth and free<br />

from any intrusions<br />

f) Fire d<strong>amp</strong>ers are to be installed in all ducts piercing shaft walls and shall<br />

have suitable eyes and standard fusible links as well an exterior device,<br />

which will visibly show the position of the d<strong>amp</strong>er.<br />

Grilles, registers and diffusers are to be designed and specified to meet the following<br />

criteria:<br />

REV. MARCH 2006 197<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

a) All side wall supply registers are to be the double deflection type with<br />

opposed blade d<strong>amp</strong>ers<br />

b) All return and exhaust registers are to be the single deflection type with<br />

opposed blade d<strong>amp</strong>ers<br />

c) Ceiling diffusers in public areas are to be linear<br />

d) The inside of supply and return ducts and plenums in public areas are to<br />

painted matt black for any portion visible through the grill<br />

e) Registers and diffusers are to be factory prime coated.<br />

Sound levels due to air conditioning and ventilation equipment, pipes, ducts, etc are to<br />

be designed to not exceed the following criteria:<br />

a) Guestrooms and suites - NC 30 with FCU on low speed<br />

b) Ballrooms, conference rooms, executive offices and massage rooms - NC<br />

30<br />

c) Public spaces, general offices, lobby lounge, main dining and general<br />

office - NC 35<br />

d) Staff cafeteria, swimming pool and health club – NC 40<br />

e) Kitchen and laundry – NC 50.<br />

Neoprene or vinyl coated fiberglass of 1 ½ pounds density acoustic duct lining of at<br />

least 1” thickness is to provided and installed to the following areas:<br />

a) Discharge and intake ducts of every low pressure handling unit for a<br />

minimum distance of 15’0” (4.6 m)<br />

Insulating materials shall be provided and installed to all piping,<br />

mechanical equipment, ductwork, etc.<br />

REV. MARCH 2006 198<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

2. PLUMBING<br />

2.1. General Requirements<br />

The scope of the plumbing for the hotel will include the following:<br />

a) Water supply to the property including storage<br />

b) Storm water disposal<br />

c) Sanitary waste disposal<br />

d) Cold water supply throughout the property<br />

e) Hot water supply (120 F – 49 C) throughout the property, with provision<br />

for (160 F – 71C) water for the laundry<br />

f) Swimming pool and whirlpool circulation and filtration system<br />

g) Fire standpipe system<br />

h) Sprinklers<br />

i) Systems for kitchens and laundry<br />

j) Softened water system.<br />

Total flow water meters are to be installed on the following services:<br />

a) Main incoming water supply<br />

b) Kitchen hot and cold water supply<br />

c) Laundry hot and cold water supply<br />

d) Domestic hot water supply<br />

e) Cooling towers<br />

f) Irrigation.<br />

Specific manufacturers for white plumbing fixtures and polished chrome trim are<br />

mentioned to establish a standard. Other manufacturers products may be used provided<br />

they are equal in design and quality and are approved by Fairmont Hotels and Resorts.<br />

Water closets for guestrooms are to be Kohler “San Raphael” model K-3384 with<br />

Broadway “Old Dominion” toilet paper holder, robe hook and spare toilet roll holder.<br />

Baths for guestrooms are to be Kohler “Steeping Bath” model K-790 with a pair of grip<br />

rails, wall mounted Kohler hand shower model K-110 with six prong handles and clear<br />

PVC coated metal chrome hose and Broadway Collection grab handle 18” (46 cm) long<br />

and soap and sponge basket. Bathroom are to be Broadway “Old Dominion” robe<br />

hooks.<br />

Baths for luxury suite guestrooms are to be Kohler “Caribbean” model K-810 with all<br />

fixtures as described previously.<br />

REV. MARCH 2006 199<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Plumbing/General Requirements (continued)<br />

Under counter lavatories for guestrooms are to be Kohler “Claxton” model K-2211<br />

complete with overflow and Broadway* Collection “Old Dominion Suite” 12” (30 cm)<br />

spreadset faucet with lever handles.<br />

Bidet for guestrooms are to be Kohler “San Tropez” model K-4854 complete with<br />

integral overflow, flushing rim and spray and Broadway Collection “Old Dominion”<br />

bidet model 6DM10.<br />

Separate shower stall for guestrooms are to be fitted with a Kohler “Triton Rite-Temp”<br />

model K-T6910-4A/K-304-K or Symmons “Allura” model 76-1XLR pressure<br />

balancing valve with K-7351 CP City Club showerhead or Sloan Actomatic model<br />

#AC-10 showerhead or Speaman model S-2252-AF showerhead<br />

Water closets for public washrooms are to be wall mounted Kohler “Kingston” model<br />

K-4330 with a seat less and Sloan “Royal” flush valve.<br />

*Acceptable alternative suppliers are: Hansgrohe, Harden and Ginger.<br />

REV. MARCH 2006 200<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

3. ELECTRICAL<br />

3.1. General Requirements<br />

The scope of the electrical for the hotel will include the following:<br />

a) Distribution system<br />

b) A system of lighting including dimmer control<br />

c) A telephone system<br />

d) A video antenna system<br />

e) A fire alarm system, including central evacuation<br />

f) Communication control and alarm system<br />

g) A pocket pager system<br />

h) A hand held portable radio system<br />

i) Empty conduit and power only for a data transmission system<br />

j) A CCTV system<br />

k) Background music system.<br />

A standby emergency generator and power distribution system is to be designed and<br />

specified for the following (as well as local code requirements):<br />

a) Fire alarm system which will include voice communication<br />

b) Fire pumps<br />

c) Emergency lighting and exiting signage (as required by local code)<br />

d) Emergency lighting (in addition to item c above) to<br />

i) Front desk<br />

ii) Telephone operators’ room<br />

iii) Cashiers’ office and each position<br />

iv) Safety deposit box room (both guest and staff)<br />

v) Work areas involving danger to occupants i.e. kitchens,<br />

maintenance areas and laundry<br />

vi) Security office<br />

vii) Fire control room.<br />

viii) Provide a minimum of one fixture or l<strong>amp</strong> on the emergency<br />

circuit to each of the following areas in a normal power outage<br />

condition:<br />

REV. MARCH 2006 201<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Electrical/General Requirements (continued)<br />

a) Public restrooms<br />

b) Each ballroom and pre-function section<br />

c) Meeting rooms<br />

d) Spa/Fitness Center<br />

f) Flood, sump and sewage pumps<br />

g) Automatic transfer equipment to bring all elevators to main lobby level,<br />

each one at a time, while at the same time keeping the fireman’s elevator<br />

continually operational<br />

h) Telephone systems<br />

i) Freezers, refrigerators and circulation pumps for refrigeration cooling<br />

j) All computer equipment and computer room HVAC equipment<br />

k) Fire protection and life safety<br />

l) HVAC equipment used for smoke control, stairwell and elevator shaft<br />

pressurization<br />

m) Uninterrupted power supply<br />

n) Oil heaters for chillers<br />

o) All paging systems<br />

p) Security systems including CCTV<br />

q) Automatic door.<br />

The main distribution system using at least two transformers, secondary and/or primary<br />

tie or transfer switches, standby cable or equivalent, is to be designed and specified to<br />

prevent total loss of power in the event of maintenance or a failure of any single piece<br />

of equipment, bus or cable in the primary and main secondary distribution.<br />

An automatic load limiting system is to be designed and specified to shut down the<br />

following loads when the loads exceeds the predetermined limit:<br />

a) Toilet exhaust fans<br />

b) Miscellaneous general ventilation systems<br />

c) Public space air-conditioning systems (provide over-ride)<br />

d) Chillers (only as a last resort)<br />

e) Electric water heating.<br />

Panel boards are to be designed and specified to meet the following general criteria:<br />

REV. MARCH 2006 202<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Electrical/General Requirements (continued)<br />

a) Branch circuit panels are to have a minimum of 20% spare or bussed<br />

spaces<br />

b) Power and distribution panels are to have a minimum of 15% spare or<br />

bussed spaces<br />

c) Main switchboard is to have a minimum of 10% spare or bussed space.<br />

In general feeders are to be designed and specified based upon the following demand<br />

requirements:<br />

a) Individual branch circuit panel – 100% of full capacity*<br />

b) Two grouped branch circuit panels – 90% of full capacity*<br />

c) Three grouped branch circuit panels – 80% of full capacity*<br />

d) Four grouped branch circuit panels – 70% of full capacity*<br />

e) Lighting distribution boards – 80% of full capacity*<br />

f) Power troughs, starter racks, etc – 90% of full capacity*.<br />

Note: *Full capacity indicates actual connected load plus nominal spare capacity for<br />

future.<br />

In order to eliminate adverse affects from electric systems operating at low power<br />

factor, automatic power factor correction equipment is to be designed and specified in<br />

such a way that it increases the power factor to the desired value of 0.95.<br />

All wires and cables for power, control and lighting distribution, telephones and low<br />

Voltage system is to be run in sheradized or hot dipped galvanized rigid heavy wall<br />

steel conduits. Thin wall conduit may be used where approved by local codes.<br />

Voltage drop shall not be more than 2.5% from the transformers to the final distribution<br />

point except where approved by local codes.<br />

All permanently installed lighting fixtures designed and specified by the Interior<br />

Designer, Lighting Consultant, Architect or Consulting Engineer are to be supplied and<br />

installed by the General Contractor.<br />

Lighting levels are to be designed and specified to meet the following minimum foot<br />

candles criteria:<br />

Valet 50 (ambient) (538 lm/m 2 )<br />

- 100 task (1075 lm/m 2 )<br />

Administration & BOH office areas (at desk level) 60 (645 lm/m 2 )<br />

Ballrooms, Front Desk, Kitchens, Housekeeping and Laundry 50 (538 lm/m 2 )<br />

REV. MARCH 2006 203<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Electrical/General Requirements (continued)<br />

Mechanical, electrical equipment areas<br />

20 (215 lm/m2)<br />

w/task lighting at each<br />

motor control center and<br />

electical switchboard<br />

Housekeeping and Laundry 50 (538 lm/m 2 )<br />

Maintenance Areas 50 (538 lm/m 2 )<br />

with 75 (810 lm/m 2 )<br />

on all work surfaces<br />

Kitchen Areas 50 (538 lm/m 2 )<br />

Meeting Rooms 50 (538 lm/m 2 )<br />

Ballroom Foyers 35 (376 lm/m 2 )<br />

Main Lobby and Employee lockers 30 (322 lm/m 2 )<br />

Assembly and Circulation 25 (269 lm/m 2 )<br />

Food and Beverage outlets and Porte Cochere 20 (215 lm/m 2 )<br />

Mechanical, electrical general areas 20 (215 lm/m 2 )<br />

Elevator foyer and guest corridors 10-20 (108 – 215 lm/m 2 )<br />

Lighting fixtures in public areas are to be recessed and/or surface mounted<br />

incandescent. The exception to this will be coved or display cases and where specialist<br />

millwork requires individual lighting treatment. The recessed lighting fixtures for<br />

general illumination in the public areas is to be, in general, of the low brightness type,<br />

parabolic aperture cones, open apertures with ellipsoidal reflectors, baffle aperture<br />

down lights, etc., supplemented with adjustable accent lights, decorative chandeliers,<br />

etc.<br />

Recessed fluorescent fixtures are to be installed in all the Administrations Offices,<br />

except the General Manager’s and any other BOH areas that have windows overlooking<br />

public areas. These are to have incandescent lighting fixtures.<br />

Outdoor parking, garden and street lighting are to be super metal halide or low pressure<br />

sodium.<br />

All fluorescent lighting fixtures are to be warm white with rapid start ballast.<br />

In mechanical rooms, a fluorescent light fixture is to be mounted at each motor control<br />

center and is to be on emergency power.<br />

3.2. Dimming Equipment<br />

Dimming equipment is to be Lutron. Similar equipment manufactured by other<br />

dimming equipment companies are acceptable, subject to approval by Fairmont Hotels<br />

& Resorts.<br />

REV. MARCH 2006 204<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Dimming Equipment (continued)<br />

Dimming equipment is to be provided for lighting control in each public area.<br />

Separate individual dimmers are to be provided for the general lighting, decorative<br />

chandeliers and wall brackets, accent lighting, entertainment and special effects fixtures<br />

for each room or subdivision.<br />

Generally, all dimmer controllers are to be of the calibrated type arranged in control<br />

panels, which may be located away from the main dimmer assembly.<br />

Selector switches are to be provided in each ballroom console to allow control of<br />

general lighting from individual room stations.<br />

Dimmers are to be electronic, solid state and are to be designed specifically for light<br />

control.<br />

The main dimmer rack is to contain a phase-to-phase coil magnetically held, multiple,<br />

double-throw transfer relay to automatically transfer at least one general lighting circuit<br />

in each room to an external emergency supply in the event of a power failure to the<br />

dimmer.<br />

Restaurants, entertainment areas, bars, main lobby, foyers and corridors are to have four<br />

presets. One for breakfast, lunch, dinner and housekeeping. Activation of these presets<br />

is to be provided by an astronomic time clock capable of activation 1-11/2 hours before<br />

sunset.<br />

Ballrooms, ballroom foyers and meeting rooms are to have individual controls for each<br />

subdivision with one central master control panel.<br />

All switches, receptacles and cover plates are to be white with matching securing<br />

screws.<br />

Exterior weatherproof switches and receptacles are to be either galvanized steel or<br />

stainless steel.<br />

3.3. Telephone System<br />

The telephone switch room (allow approximately 300 ft 2 – 28 m 2 ) is to allow rear<br />

access to the switch panels and have a floor designed to carry approximately<br />

110 lbs/ft 2 (50 kg/m 2 ). This room must not have exterior windows and is to be built<br />

from block walls and finished with a vinyl tiled floor, painted walls and lay-in ceiling<br />

tiles.<br />

Where required by local authorities, an additional room (allow approximately 75ft 2 –<br />

7 m 2 ) may be necessary for the local telephone company termination of entrance<br />

facilities.<br />

Fairmont Hotels and Resorts preferred system is a direct current powered Northern<br />

Telecom Meridian 1 telephone switch with the latest “state-of-the-art” PBX technology<br />

switch and hardware in release at the time of installation.<br />

REV. MARCH 2006 205<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Telephone Systems (continued)<br />

Similar equipment manufacturers by other telephone systems manufacturers are<br />

acceptable, subject to approval by Fairmont Hotels and Resorts.<br />

Air-conditioning provided for the telephone switch and associated equipment must be a<br />

stand alone system capable of handling 16,000 BTU’s/hour and must be on emergency<br />

power<br />

There should be at least two risers enclosed in risers serving the guest levels, or if<br />

construction dictates, risers between each vertical line of rooms. In some cases separate<br />

risers may be necessary for elevator and service lobby telephones as well as upper floor<br />

function areas.<br />

One intermediate distribution frame is required on each hotel floor for each riser. A<br />

conduit is to be run down the guest corridor from the intermediate distribution frame<br />

and stubbed into each room. Refer to the Data Cabling Specifications for details.<br />

Voice Mail<br />

Provides guest and administrative voice main; interface to telephone switch, property<br />

management system for message notification. For Nortel supplied systems, Meridian<br />

Mail is the standard.<br />

Call Accounting<br />

Provides costing of all calls made by telephones on the property, interfaces to the<br />

telephone switch and property management system (to post guest charges to accounts).<br />

The standard is XETA.<br />

Long Distance Carriers<br />

Fairmont Hotels and Resorts competitively bids direct dial services where markets<br />

permits. Operator services are evaluated on a country by country basis. Our current<br />

North American suppliers are:<br />

Direct Dial Service US:<br />

Direct Dial Service, Western Canada:<br />

Direct Dial Service, Eastern Canada:<br />

Operator Services:<br />

Sprint<br />

Telus<br />

Bell<br />

Canopco<br />

Standard Guestrooms are to have the following features:<br />

a) Bedroom at the night table a Cordless Teledex CL2210 (2-line) or CL1210<br />

(single line) phone. These phones have Securechek technology which<br />

stops cross billing between rooms, which is experienced with lesser<br />

models in large installations. This is a true hospitality cordless set with<br />

Message Waiting l<strong>amp</strong> and speaker phone, 10 speed dial buttons, and full<br />

faceplate. See http://www.teledex.com/telephones/cordless/index.html<br />

Simplex telephone jacks with RJ-11C termination at the bed<br />

REV. MARCH 2006 206<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Telephone Systems (continued)<br />

b) At the desk a Teledex Opal Series 2011S (2 line) or 1010S (single line).<br />

Features full faceplate, speakerphone, speed dial buttons, hold, and<br />

volume control. See http://www.teledex.com/telephones/opal/index.html<br />

Jacks, comprising one RJ-11C and one RJ–45 terminations (one for a two<br />

line telephone, one for data) is to be installed at the desk Wiring to be 1 x<br />

4 pair enhanced category 5 serving the onejack and 1 x 4 pair category 5<br />

data grade servicing the other jack<br />

c) In the bathroom a Teledex Trimline I or II, small mountable phone with<br />

buttons on the handset only. See<br />

http://www.teledex.com/telephones/trimline/index.html<br />

Simplex wall mounted telephone jack with RJ-11C termination in the WC<br />

(telephone is not to be mounted directly on wall)<br />

One, Two, and Three Bedroom Suites are to have the following features:<br />

a) Living room phone has same extensions as master bedroom.<br />

b) All bathrooms have bridged first extension off related bedroom.<br />

c) Pantry phone and maid’s closet phones have separate extensions from<br />

suite main number.<br />

Boardrooms<br />

Provide multi-line digital speaker telephone,the Northern Telecom 2616. Provide<br />

fourplex outlet in boardroom with one voice RJ-11C (digital), one fax/modem (analog)<br />

RJ-11C and two data RJ-45 jacks.<br />

Back-of-the-House Areas<br />

Within the Administration and Accounting areas of the hotel, data grade cable should<br />

run from the localized intermediate distribution frame from each position, either to a<br />

concentrator/hub located at the intermediate distribution frame or home directly back to<br />

the computer room without intermediate splices or cross-connects.<br />

Back of house offices and secretarial and front desk positions to be provided with the<br />

following:<br />

a) A quad jack, comprising RJ-11C and two RJ-45 terminations<br />

b) Wiring to be 1 x 4 pair category 5 serving the upper jacks and 2 x 4 pair<br />

category 5 data grade servicing the lower jacks.<br />

Multi-button, digital display phones are to be provided to the following locations.<br />

Positions identified with an asterisk shall be hands-free speaker phones, all guest<br />

contact positions (i.e. housekeeping, accounting, room service) shall have guest name<br />

recognition capability:<br />

REV. MARCH 2006 207<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Telephone Systems (continued)<br />

a) Human Resources (Director *, Assistant, Secretary)<br />

b) Housekeeping (Director*, Assistant, Clerks, Laundry, Valet)<br />

c) Purchasing/Receiving (Buyer*, Receiving Clerck, Secretary)<br />

d) Technical Services (Director*, Assistant, Secretary)<br />

e) Kitchen (Chef*, Room Service)<br />

f) Accounting (Comptroller*, Asst., Secretary., Payroll, Cashier, Clerks,<br />

Systems Manager*)<br />

g) Front Office (Front Office Manager*, Director of Reservations,<br />

Reservations Agents, Assistant Managers)<br />

h) Executive Offices (General Manager, Resident, Director of<br />

Marketing/sales, Director of Catering, Sales Managers, Catering<br />

Managers, Coordinators, Secretaries, Reception)<br />

i) Business Centre (Manager, clerks, workstations)<br />

j) Restaurant Maitre d’= stations<br />

k) Bars for bartender/guest use (including pool bar)<br />

l) Front Desk (reception/cashiering)<br />

m) Concierge Desk<br />

n) Bell Stand/Doorman’s station<br />

Single line analogue wall phones are to be provided in the following areas:<br />

a) Meeting Room Service Corridors (no ring w/flashing light)<br />

b) Room Service<br />

c) Health Club (reception, massage rooms, exercise area, lockers)<br />

d) Restaurant Service Stations<br />

e) Service elevator foyers<br />

f) Laundry and valet work areas<br />

g) Engineering Shops, chiller plant, boiler room, main electrical room<br />

h) Kitchen (main kitchen, banquet kitchen, service bar, food lines, butcher,<br />

bakery, dry stores, flower shop)<br />

i) Loading dock<br />

j) Staff Cafeteria<br />

k) Administration Boardroom<br />

REV. MARCH 2006 208<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Telephone Systems (continued)<br />

l) Staff Locker Rooms<br />

m) Housekeeping Service Rooms on Guest Floors<br />

n) Each floor of Car Parking Garage (next to exit stair or elevator)<br />

Provide direct outside lines (i.e. by-passing the main switch) in the main switch room,<br />

telephone operator’s room and security.<br />

There will be a minimum of 10 phones designated on the telephone switch as power<br />

fail telephones, which may be activated and provide external telephone service in the<br />

event of a failure of the telephone switch. The locations will be determined at the time<br />

the switch is installed.<br />

Public Areas<br />

Provide phones which ring direct to operator in the following locations in the Main<br />

Lobby (2 or more), near the Front Desk (2 or more), in Ballroom Foyer (2) and near<br />

Meeting Rooms or group of Mtg Rms (2 per floor or group). Standard will be the<br />

Teledex Opal 1001, see http://www.teledex.com/telephones/opal/opal1001.html<br />

located in the same location as house phones of which one in each area shall be<br />

mounted for handicapped use. All phones to be fully recessed.<br />

Provide outdoor phones in weatherproof boxes for exterior games areas such as tennis<br />

courts, waiting and service areas and swimming pool locations.<br />

Provide cordless phones for pool area and restaurants (2 for each area).<br />

All telephone operator consoles to have guest name display capability.<br />

The following areas are to be provided with active at all times, single line telephones<br />

with direct access to the outside without passing through the telephone switch:<br />

a) Telephone Operator’s room<br />

b) Security<br />

c) Telephone Switch room.<br />

The following areas are to be provided with two house telephones with dial pads (must<br />

ring down to the operator):<br />

a) Each ballroom foyer<br />

b) Near each meeting room<br />

c) Near the front desk<br />

d) Main hotel lobby.<br />

Note: House telephones are to be installed adjacent the pay telephones.<br />

REV. MARCH 2006 209<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

3.4. Television System<br />

Television signal systems from satellites will be used wherever excellent reception and<br />

coverage is available. Where a satellite system is not available, a cable system is to be<br />

installed.<br />

The television terminal equipment will be located in a room (allow approximately<br />

75 ft 2 – 7 m 2 ) adjacent to the telephone equipment room.<br />

Pay per view television, where available, will be located in a room (allow<br />

approximately 150 ft 2 – 14 m 2 ) adjacent to the telephone equipment room. This<br />

equipment shall be supplied and installed by an independent supplier.<br />

The general contractor will be responsible for supplying the whole system, excluding<br />

the television sets. Televisions complete with remote controls will be supplied and<br />

installed by FF and E.<br />

A television signal outlet together with its attendant duplex electrical outlet is to be<br />

provided at the following locations:<br />

a) All guest bedrooms and living rooms<br />

b) All presidential and special suite bathrooms<br />

c) All public bars and lounges<br />

d) Secured storage rooms in maintenance areas<br />

e) At television repair workbench in maintenance area<br />

f) Employee dining room and employee lounge<br />

g) Ballroom, ballroom pre-function areas and meeting rooms<br />

h) Staff training room<br />

i) Health club relaxation areas and exercise rooms.<br />

Provide different designated equipment rooms for the hotel and meeting facilities<br />

operation.<br />

3.5. Closed Circuit Television Security and Assistance Systems<br />

A closed circuit television system shall be provided with wall mounted cameras located<br />

in the following areas:<br />

a) Swimming pool (wide angle type)<br />

b) Staff entrance<br />

c) All remote, unsecurable and unattended entrances or exits<br />

d) Food and beverage entrance doors<br />

e) Main lobby and front desk area (pin hole type)<br />

f) Cashier’s desk<br />

REV. MARCH 2006 210<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Closed Circuit Television Security and Assistance Systems (continued)<br />

g) Guests safety deposit box room<br />

h) Truck dock/receiving area (wide angle type)<br />

i) Cardiovascular room (monitor at health club reception desk and security<br />

office).<br />

All externally mounted cameras are to include weatherproof housing.<br />

Colored monitors with the capacity to divide the screen into four different pictures<br />

simultaneously shall be provided as follows:<br />

a) One for “holding on any selected camera<br />

b) One for every 12 cameras, connected to sequential switcher for automatic<br />

switching<br />

c) One for replaying from video tape player<br />

d) One in executive assistant manager’s office with switcher to select<br />

camera.<br />

All monitors are to be located in a special display unit in the security office. A duplicate<br />

set of monitors is to be provided in the telephone operator’s room.<br />

The cashier’s office is to be provided with a dedicated video recorder. This recorder is<br />

to be activated by means of the cashier’s security buzzer switch and is to record for up<br />

to an hour after the switch has been depressed and should stop automatically.<br />

Each front desk cashier’s position, cashier’s office and staff safety deposit box room is<br />

to have a silent alarm system, comprising a push button to illuminate a flashing red light<br />

in the telephone operator’s room. Each area is to have its own separate light.<br />

Each front desk position is to have a push button to illuminate a flashing blue light in<br />

the front manager’s office.<br />

A push button is to be installed at the guest safety deposit collection counter, which<br />

when pushed by the guest will activate a buzzer at the front desk.<br />

Entry door into guest safety deposit box “viewing” room to be provided with an electric<br />

strike activated by a button adjacent to the staff entry door into the safety deposit room.<br />

3.6. Background Music and AV Systems<br />

The media center (approximately 120 ft 2 – 11 m 2 ) is to act as the central point for<br />

audiovisual activity. The media center will house a high quality <strong>amp</strong>lified monitor and<br />

all background music and source equipment.<br />

REV. MARCH 2006 211<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Background Music and AV Systems (continued)<br />

Layout of loudspeakers is to be coordinated with the Interior Designer’s reflective<br />

ceiling plans. Loudspeakers must be positioned in ceilings such that the listener is not<br />

more than 45 degrees off axis from the nearest loudspeaker (as measured to the listeners<br />

ear) and that the distance from the loudspeaker within a given area to the listeners ear<br />

does not vary in more than a ratio of 2:1.<br />

An audiovisual system suitable for video presentation is to be furnished and installed to<br />

the following areas:<br />

a) Circulation areas including restrooms, public corridors, lobby parlor and<br />

lobbies<br />

b) Staff Cafeteria<br />

c) Restaurants and Lounges*<br />

d) Bars*<br />

e) Pool Areas<br />

f) Outdoor circulations areas<br />

g) Outdoor function areas<br />

h) Board rooms and meeting rooms*<br />

i) Spa/Fitness Center*<br />

j) Ballrooms*.<br />

Note: All areas marked * are to have independent source and volume background<br />

music controls.<br />

Circulation area source and control equipment is to be located as follows:<br />

a) All elevator lobbies to be on one control zone with source at media<br />

center, with on/off and volume controls at the front desk<br />

b) General public areas and main lobby, but excluding meeting areas, to be<br />

on one control zone with source at media center, with on/off and volume<br />

controls at front desk<br />

c) Lobby parlor to be on one control zone with source at media center, with<br />

on/off and volume controls at pantry<br />

d) All public washrooms to be on one control zone with source, on/off and<br />

volume controls at media center<br />

e) All areas described above to have the same source.<br />

A system of audio and video tie lines is to be provide from the media center to each of<br />

the following areas:<br />

REV. MARCH 2006 212<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Background Music and AV Systems (continued)<br />

a) One audio and one video to meeting rooms less than 1,000 ft 2 (93 m 2 ).<br />

b) Two audio and two video to each subdivision of meeting rooms over.,<br />

1,000 ft 2 (93 m 2 ) ballrooms and ballroom pre-functions.<br />

c) Four audio and five videos to up-link location for satellite truck adjacent<br />

to truck dock.<br />

Each restaurant and lounge to have its own unique music source originating within the<br />

area itself or from the media center.<br />

Each restaurant and lounge is also to have a feed from the background music source<br />

serving the circulation areas.<br />

Bars and live entertainment areas are to be equipped with the additional two line level<br />

and four microphone level input receptacles with on/off and volume control at the stage<br />

areas.<br />

The pool areas are to be equipped with weather resistant loudspeakers.<br />

A separate unique music source is to be provided at the children’s pool area.<br />

Outdoor circulation areas are to have loudspeakers positioned so they provide an even<br />

coverage in areas served, particularly in outdoor function areas, however, deliberately<br />

omit music provisions from areas directly adjacent to guestrooms and at least half of all<br />

circulation pathways and outdoor seating areas. Loudspeakers in outdoor function areas<br />

are to be able to be switched to transfer circuit from background music <strong>amp</strong>lifier to<br />

local loudspeaker level input receptacle served by a portable sound rack with integral<br />

<strong>amp</strong>lifier.<br />

The Fairmont Gold lounge is to be provided with a residential style stereo system.<br />

Location of speakers and controls are to be coordinated with the Interior Designer. All<br />

wiring and cabling is to be housed in concealed conduits.<br />

Presidential and special suites are to be provided with residential style stereo system as<br />

well as DVD players. All devices are to be of the same manufacturer and to be<br />

compatible with the television receiver and controlled by a single remote control device.<br />

Loudspeakers are to be provided in an outdoor patio area. These loudspeakers are to<br />

have a dedicated <strong>amp</strong>lifier connected to the suite’s audio system.<br />

Staff training rooms and staff meeting rooms are to be provided with permanent,<br />

remotely controlled motorized projection screen.<br />

Boardrooms are to be provided with a permanent, remotely controlled motorized<br />

projection screen with remote tie line from projector to front of room and background<br />

music.<br />

Each subdivision of all meeting rooms, ballrooms and pre-function areas are to be<br />

provided with four sources of background music as well as local input. A recessed<br />

mount control panel housed within a control niche adjacent to an entrance doors is to<br />

REV. MARCH 2006 213<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Background Music and AV Systems (continued)<br />

house the on/off and volume controls. These rooms are to be equipped with empty<br />

conduit provisions and audio-video distribution systems. All systems are to operate in<br />

conjunction with the lighting and drapery controls as well as the adjacent subdivisions<br />

of each room.<br />

The audio signals are to have a combining system that will provide a graphic visual<br />

representation of the room status as well as automatic equalization switching upon<br />

change of status for meeting rooms and ballroom subdivisions. These rooms must also<br />

be capable of selecting a local source or background music from within the room itself.<br />

When the rooms are in a combined mode, the controls within each room sub-division<br />

will also be combined such that the manipulation of one control will affect the source<br />

throughout the combined area and provide an indication of the relative level as well as<br />

the source selection at each control location.<br />

REV. MARCH 2006 214<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

4. ELEVATORS<br />

4.1. General Requirements Public Elevators<br />

Specifications are based upon Otis elevator equipment to establish a type and level of<br />

quality. Similar equipment manufactured by other elevator companies is acceptable,<br />

subject to approval by Fairmont Hotels and Resorts.<br />

The following standard features are required in each elevator:<br />

a) Average waiting time of under 30 seconds<br />

b) Load factor of approximately 30%<br />

c) Total trip time of less than 70 seconds<br />

d) (For the purposes of calculating items a, b and c assume an average of 1<br />

½ persons per room for a urban hotel and 2 persons per room for a resort<br />

at 100% occupancy.)<br />

e) Duty to be 3,500 lbs (1,580 kg)<br />

f) Speed for a hotel of less than ten floor 350 feet (107 m) per minute and<br />

exceeding ten floors of 500 (152 m) feet per minute<br />

g) Every guest or public floor is to have a stop and an opening<br />

h) Public area floors are to have 3’6” (1.1 m) centre opening, flush doors<br />

with polished bronze, acid etched doors<br />

i) Guestroom floors are to have 3’6” (1.1 m) centre opening, flush doors<br />

with decorative door design<br />

j) Door frames are to be concealed filler frame type with painted finish and<br />

electronic detector<br />

k) Door sill to be bronze<br />

l) Hall lanterns are to type 6646DK with chimes and located adjacent to the<br />

door frames<br />

m) Each car is to have two car operating panels with round buttons,<br />

emergency stop switch, emergency call button, emergency service switch,<br />

close and open door buttons, interface with electronic card readers for<br />

Fairmont Gold floors and descriptive engraving for public facility floors<br />

buttons, background music speakers and an exhaust fan with sound level<br />

not exceeding NC 30<br />

n) The 8’6” (2.6 m) high car interiors will be based upon the Interior<br />

Designer’s drawings incorporating a handrail, mirrors, millwork,<br />

stonework and advertising panels<br />

o) The car is to incorporate emergency power with automatic selection and<br />

automatic levelling.<br />

REV. MARCH 2006 215<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

4.2. Service Elevators<br />

Specifications are based upon Otis elevator equipment to establish a type and level of<br />

quality. Similar equipment manufactured by other elevator companies is acceptable,<br />

subject to approval by Fairmont Hotels and Resorts.<br />

The service elevators are to have the following features:<br />

Not less than two service cars and one freight elevator or approximately 75% of the<br />

quantity of passenger cars, whichever the greater<br />

Duty to be 4,000 lbs (1,815 kg)<br />

Speed to be 400 feet (122 m) per minute<br />

Every floor to have a stop and an 3’6” (1.1 m) wide opening<br />

Cars to have flush doors with baked enamel finish and electronic detector<br />

Each car to have a single stainless steel operating panel with emergency stop switch,<br />

emergency call button, emergency service switch and close and open buttons<br />

The 8’6” (2.6 m) high car interior is to have carpeted walls (if permitted by code, if not<br />

to be off white baked enamel) with a 12” x 12” (300 x 300 cm) mono dark brown<br />

rubber floor tiles, hardwood handrail and cart rail and hooks for protective pads<br />

The car is to incorporate emergency power with automatic selection and automatic<br />

levelling.<br />

REV. MARCH 2006 216<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

5. ELECTRONIC LOCKING SYSTEM<br />

TimeLox or other approved non-hardwired electronic lock system supplier are to<br />

provide a project specific package, inclusive of all items outlined below unless other<br />

stated, for approval by Fairmont Hotels and Resorts corporate office before a contract to<br />

supply and install can be executed:<br />

Software requirements to be Windows NT based software<br />

a) One TimeLox modem package for “on-line” diagnostics and<br />

support<br />

b) One TimeLox 2300 Windows software package and user licence<br />

c) One handheld communications unit used to program and<br />

interrogate TimeLox locks together with TimeLox external power<br />

up contact card.<br />

Hardware to have the following features:<br />

a) One TimeLox server for system (located in computer room)<br />

b) Cabling from all terminals using CAT 5e cable<br />

c) Computer with CD RW ROM and 17” (43 cm) colour VDU,<br />

Pentium 4 with a minimum speed of 500 Mhz, Windows NT and<br />

licence and associated slots<br />

d) Computer, and all equipment to be connected to UPS.<br />

TimeLox automatic card encoder with 110V x 15A dedicated electrical duplex outlet to<br />

the following positions:<br />

a) One at each front desk position<br />

b) One at each Fairmont Gold front desk position<br />

c) One at each concierge desk position<br />

d) One at security<br />

e) One at MIS<br />

f) One spare.<br />

Encoders should use Ethernet cabling between front desk terminals and must be oneline<br />

to server.<br />

a) One management terminal for each of the following:<br />

b) Administration at front desk<br />

c) Administration at vacation ownership<br />

REV. MARCH 2006 217<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Electronic Locking System (continued)<br />

d) Security desk.<br />

Three handheld communications units (for engineering, security and one spare)<br />

a) Necessary network switches/hubs to be placed as required to<br />

service all above locations.<br />

System to include the following features:<br />

a) Must be able to upgrade from magstripe card to smartcart without<br />

changing lockset hardware<br />

b) Shall have a minimum of eight failsafe cards per room (in the<br />

event of power failure, property will continue to be able to check<br />

guests in)<br />

c) Shall have a minimum of thirty user types (or levels) and a<br />

minimum of two hundred and fifty six user groups (employee<br />

access areas) and should be able to issue up to ten thousand user<br />

cards<br />

d) A custom built configuration according to the property wants the<br />

electronic system to be configured<br />

e) Have the ability to interface or integrate with the property<br />

management system<br />

f) Shall have a system access to the system operations with a<br />

password and operator card protection, and user defined by<br />

g) property with regards to what functions can be done with what<br />

security level<br />

h) Keycard information encoded on track 3 of a standard American<br />

banking card<br />

i) Keycard encoding information must be in an encrypted form<br />

j) Guest cards must have a start time, end time and issue time<br />

encoded at the time the card is encoded<br />

k) Guest cards must be able to be encoded in advance to start at a<br />

specific date and time in the future<br />

l) Must be able to issue unlimited number of master keycards<br />

m) Shall have a device for elevator control, whereby certain hotel<br />

floors can be access by both date and time.<br />

n) TimeLox to supply appropriate number of bland keycards,<br />

customized with specific Hotel artwork to cover the first twelve<br />

months of operation.<br />

REV. MARCH 2006 218<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

5.1. Services and Systems Standards Details<br />

ALARM / VIP / ASSISTANCE BUTTON SYSTEM RISER DIAGRAM 220<br />

Page<br />

REV. MARCH 2006 219<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

REV. MARCH 2006 220<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

6. TECHNOLOGY SERVICES – DATA CABLING SPECIFICATIONS<br />

6.1. Equipment Price Breakdown<br />

a) The network cabling contractor shall provide a price breakdown, included in<br />

response to defined scope of work, for voice and data cabling, terminations, patch<br />

panels and certification as specified below. Rough in consisting of conduit, boxes<br />

and pull string to be included as specified. Conduiting to be provided by the<br />

electrical contractor.<br />

b) The network cabling contractor shall provide a closet-by-closet price breakdown as<br />

outlined in the ex<strong>amp</strong>le below. This will start with the main computer room, then<br />

move up to subsequent wiring closets on each of the guest floors. The network<br />

cabling contractor will supply a summarized grand total at the end of the quote.<br />

c) Additional items requested will be itemized in the same manner as shown below.<br />

The contractor will supply a separate summarized grad total with those numbers<br />

included.<br />

d) The need to amend or modify the installation specification may arise. The hotels<br />

representative prior the installation must approve any changes or amendments.<br />

Ex<strong>amp</strong>le of a price breakdown per floor data<br />

Main Computer Room<br />

Product/Manufacturer Quantity Price<br />

CAT 5e plenum rated jacket horizontal wiring<br />

RJ45 Data connection in guest room<br />

10 ft. CAT 5e patch cord for guest room<br />

48 Port HD horizontal termination<br />

24 Port HD horizontal termination<br />

4 ft. CAT 5e patch cords for IDF<br />

6 Strand 50/125 um Multi mode fiber backbone, with flex<br />

conduit to computer room.<br />

Fiber rack mount patch panel “ 6 port SC termination”<br />

SC connectors<br />

6 ft. SC – SC fiber patch cables<br />

4 ft Wall mount cabinet with fan.<br />

19 inch. Rack mount surge protected power bar. “Min 6 port”<br />

TOTAL MATERIAL<br />

LABOR<br />

TOTAL<br />

REV. MARCH 2006 221<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

6.2. Summary of Project<br />

Overview<br />

a) The scope of this project includes the complete supply and installation of a Cabling<br />

System for Voice, Data, Video and Control applications.<br />

b) This cabling system shall be based on a physical star cabling topology that is<br />

designed with a single manufactures end-to-end solution, as specified herein.<br />

c) The proposed cabling system must be applications-independent and network<br />

technology-neutral.<br />

End-to-End System Requirements<br />

To ensure all performance requirements are met, a single manufacturer for each copper and<br />

optical fiber cabling shall be defined, designed, installed, tested, and warranted as an end-toend<br />

system. All components of the offered system shall be from the manufacturers product<br />

portfolio. If a single manufacturer’s components are not used, then the cabling contractor must<br />

be certified to install the various components. A structured cabling system is to be made up of a<br />

number of interdependent subsystems, including amongst others:<br />

a) The Work Area subsystem, where station equipment is connected to the<br />

Telecommunications Outlet/Connector or the Multi-User Telecommunications<br />

Outlet Assembly (MUTOA) with modular cords (the cords may be equipped with<br />

baluns, media filters and/or adapters, if required).<br />

b) The Horizontal Cabling subsystem, which may include a Consolidation Point.<br />

c) The Horizontal Cross-connect subsystem, which is located in the<br />

Telecommunications Closet.<br />

d) The Backbone Cabling subsystem, which provides the in-building cabling to link<br />

the Horizontal Cross-connect to the Main/Intermediate Cross-connect.<br />

e) The Main/Intermediate Cross-connect subsystem, which is generally located in the<br />

Equipment Room.<br />

f) The C<strong>amp</strong>us subsystem, which provides the inter-building cabling to link the Main<br />

Cross-connect in the central c<strong>amp</strong>us building to the Intermediate Cross-connect(s)<br />

in the satellite building(s) on c<strong>amp</strong>us.<br />

REV. MARCH 2006 222<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Figure 1 - A Structured Cabling System<br />

HC<br />

Work Area<br />

HC<br />

Horizontal<br />

Cabling<br />

HC<br />

Telecommunications<br />

Closet<br />

Backbone Cabling<br />

MC<br />

Equipment room<br />

Entrance<br />

Facilities<br />

Access<br />

lines or<br />

to other<br />

buildings<br />

REV. MARCH 2006 223<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

6.3 Specification Summary<br />

Computer Room Specifications<br />

All cable shall be 4-pair enhanced category 5, unshielded twisted pair cable. All cabling shall<br />

be in a metal or PVC conduit.<br />

The Computer room should have CAT5e cables run to other critical rooms as follows:<br />

- 2 CAT5e cables to the PBX room<br />

- 2 CAT5e cables to the Head End room for Pay TV Systems<br />

Guest Room Specifications<br />

All cable shall be 4-pair enhanced category 5, unshielded twisted pair cable. All cabling shall<br />

be in a metal or PVC conduit. Where conduit is not provided in existing hotels, cable shall be<br />

plenum rated where regulation require.<br />

a) Voice<br />

b) Data<br />

Each telephone line will be run with Cat 5 e cable (see section 3.1, distance<br />

applies to Data only), as well all jacks must terminated on RJ-11 jacks and<br />

installed onto a dual jack faceplate. Voice RJ-11 jacks must be terminated with a<br />

BLACK Connector/Jack.<br />

Each room shall have (suites have special configurations):<br />

One two-line jack at the bed.<br />

One two-line jack at the desk.<br />

One single line jack in the guestroom washroom (where applicable)<br />

NOTE: For Voice only, a single cable can be run into one of the locations (Desk<br />

area preferably) and the other phone connections can be daisy chained from that<br />

location.<br />

Each data line will be run with Cat 5 e cable (see section 7.1), terminated on an 8<br />

wire, 8-position jack. Each RJ-45 Data connection will be terminated with a<br />

BLUE Data jack.<br />

Each room shall have (suites have special configurations):<br />

One data port at the desk.<br />

One port for the TV<br />

REV. MARCH 2006 224<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Administration Specifications<br />

All cable shall be 4-pair enhanced category 5, unshielded twisted pair cable. All cabling shall<br />

be in a metal or PVC conduit. Where conduit is not provided in existing hotels, cable shall be<br />

plenum rated where regulation require.<br />

a) Voice<br />

b) Data<br />

Each telephone line will be run with Cat 5 e cable (see section 7.1, distance<br />

applies to Data only), as well all jacks must terminated on RJ-11 jacks and<br />

installed onto a quad jack faceplate. Voice RJ-11 jacks must be terminated with a<br />

BLACK Connector/Jack.<br />

Each workstation area shall have:<br />

Two RJ-11C terminations.<br />

Each data line will be run with Cat 5 e cable (see section 7.1), terminated on an 8<br />

wire, 8-position jack. Each RJ-45 Data connection will be terminated with a<br />

BLUE Data jack.<br />

Each workstation area shall have:<br />

Two RJ-45 terminations.<br />

Meeting and Ballrooms Specifications<br />

All cable shall be 4-pair enhanced category 5, unshielded twisted pair cable. All cabling shall<br />

be in a metal or PVC conduit. Where conduit is not provided in existing hotels, cable shall be<br />

plenum rated where regulation require.<br />

Each meeting room and divisible section of meeting rooms or ballrooms shall have at least, one<br />

quad jack faceplate with two RJ-11C terminations and two RJ-45 terminations for data. Each<br />

voice and data line will be run with Cat 5 e cable (see section 7.1, distance applies to Data<br />

only). This jack shall be mounted in an appropriate A/V niche to provide maximum service to<br />

the space, usually at the front or side of the room. Voice RJ-11 jacks must be terminated with a<br />

BLACK Connector/Jack.<br />

Each divisible section of a large meeting rooms and all sections of ballrooms shall have one 6-<br />

plex jack with each jack terminated as RJ-11 C for voice. In addition it shall also have at least,<br />

one quad jack faceplate with two RJ-45 terminations for data. Each voice and data line will be<br />

run with Cat 5 e cable (see section 7.1, distance applies to Data only). These jacks shall be<br />

mounted in an appropriate A/V niche to provide maximum service to the space, usually at the<br />

front or side of the room.<br />

REV. MARCH 2006 225<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Meeting and Ballroom Specifications (continued)<br />

Each meeting room and divisible section of meeting rooms or ballrooms shall have. Sufficient<br />

additional voice jacks in A/V niches to provide the required level of service.<br />

The pre-function space to large meeting rooms and ballrooms and main meeting room corridors<br />

of function space shall have sufficient voice and data cables to provide computer, registration<br />

and telephone service at the entrances to these rooms for groups using these facilities. Each<br />

voice and data line will be run with Cat 5 e cable (see section 7.1, distance applies to Data<br />

only).<br />

Meeting room and Ballroom convention facilities will run all voice and data lines to a specified<br />

IDF. These lines will be terminated on separate patch panel blocks, one for voice and one for<br />

data. The voice patch panel will allow connections between the end or room point of the voice<br />

connection to the patch block in the cross connect closet, both end with RJ-11 connectors. In a<br />

similar set-up there will be a block in the cross connect closet that will connect to a block in the<br />

PBX room also using RJ-11 connector panel blocks. The Data Connection will be terminated<br />

and mounted on an appropriate rack system that will allow for network equipment to be<br />

mounted as well.<br />

In open areas, gathering areas of convention space, CAT5E should be placed outside the actual<br />

meeting rooms themselves. Power should also be made available near the CAT5E connection.<br />

This will allow Technology Services to add Wireless Access points to allow wireless laptops<br />

and devices to be used for the convention.<br />

6.4 Food & Beverage Point of Sales Cabling<br />

All cable shall be 4-pair enhanced category 5, unshielded twisted pair cable. All cabling shall<br />

be in a metal or PVC conduit. Where conduit is not provided in existing hotels, cable shall be<br />

plenum rated where regulation require.<br />

Standards and specification<br />

All Food & Beverage point of sale cables shall be 4-pair, enhanced category 5, unshielded<br />

twisted pair cable. It shall meet all of the same performance criteria as for the Local Area<br />

Network (Section 7.1). Each RJ-45 Data connection will be terminated with a BLUE Data jack.<br />

Point of Sale jack locations<br />

Restaurant, bar, service stand terminal positions:<br />

A quad jack faceplate, two RJ-11 C terminations for voice. In addition there will be two RJ-45<br />

connections for data.<br />

Order printer locations:<br />

One simplex faceplate with an RJ-45 termination.<br />

REV. MARCH 2006 226<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

6.5 Intermediate Distribution Frame (IDF)<br />

All cable shall be 4-pair enhanced category 5, unshielded twisted pair cable. All cabling shall<br />

be in a metal or PVC conduit, all conduits to be sized 20% larger than minimum recommended<br />

size for number of cable runs. Where conduit is not provided, cable shall be plenum rated<br />

where regulation require.<br />

a) Voice:<br />

b) Data<br />

All voice cables in meeting rooms, pre-function rooms and main Meeting room<br />

corridors shall terminate on a patch panel close to the meeting space or located in<br />

an A/V control room near the meeting space. This will permit the hotel to patch a<br />

variety of services to any meeting room.<br />

All guest room voice (telephone, fax, modem) wiring will terminate as practical<br />

on intermediate distribution frames supporting the voice cabling for the building.<br />

Guest room voice and modem/fax lines will run live to the telephone switch. All<br />

guest room modem wiring will terminate on a patch panel (unless otherwise<br />

specified) to be located in the PBX/PABX switch room to permit switching of<br />

ISDN to guest rooms. See later section describing the patch panel requirements.<br />

Administration and back of house voice (telephone, fax, modem) wiring will<br />

terminate as practical on intermediate distribution frames arranged to support the<br />

cabling on a given administration floor or area. It may be more practical to route<br />

such cabling direction to the telephone switch room; however, the intent is to<br />

design a cabling structure that minimizes the total amount of cable and conduit<br />

required to keep costs down while adhering to the operating requirements of the<br />

hotel.<br />

Voice riser cable or backbone cable (cable that links the intermediate distribution<br />

frames to the main distribution frame in the switch room) shall be run from each<br />

intermediate distribution frames to the main distribution frame in the telephone<br />

switch room utilizing 25,50, 100 or 200 pair bundles of category enhanced<br />

category 5 cable. If circumstances require (e.g. a large spread out resort with<br />

multiple buildings), this backbone cabling may be more efficiently run using<br />

Fiber optics (see section 7.1).<br />

Guest room data wiring will terminate on an enhanced category 5 patch panel in<br />

each floor’s intermediate distribution frames (or the intermediate distribution<br />

frames serving that floor). There must be sufficient space and electricity to power<br />

data concentrators/hubs in each location. (See section 7.2 & 7.3)<br />

Administration data wiring will be routed wherever possible to the hotel computer<br />

room and terminated on an enhanced category 5 patch panel located there. If it is<br />

REV. MARCH 2006 227<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Intermediate Distribution Frame (IDF) continued<br />

more practical, or the 90 m distance limitation from wall jack to hub in computer<br />

room will be exceeded, the cabling may be routed to an mF serving those<br />

administration locations. There must be sufficient space and electricity to power<br />

data concentrators/hubs in each location where the patch panels are located. (See<br />

section 7.2 & 7.3)<br />

Data intermediate distribution frames will be linked to the hotel computer room<br />

using either Fiber optic cables. (See section 7.1 & 7.5).<br />

6.6. Network Equipment<br />

All network connectivity will be achieved by using Cisco 10/100 switching products.<br />

Equipment specifications and Pricing shall go through the Technology Services to utilize<br />

Fairmont Hotels & Resorts special pricing with Cisco Systems.<br />

6.7. Uninterruptable Power/Dedicated Power<br />

Provide uninterruptible power for all equipment in the main wiring closet (server room). This<br />

UPS is connected to the hotel generator. Sufficient battery time must be available at full load to<br />

enable the system to remain operating until the switch to generator power or be shut down<br />

gracefully.<br />

UPS power “15 <strong>amp</strong>s, 110 V/60/1 “ must also provided (North American Specification;<br />

equivalent for local power in other countries) to each IDC that houses network<br />

connectivity.<br />

All Isolated ground and UPS receptacles should be identified using a different colour, e.g.<br />

orange or red.<br />

6.8 Vendor Qualification<br />

Purchaser<br />

The General Contractor shall be referred to as the Purchaser.<br />

Manufacturer<br />

Manufacturer refers to the company that is responsible for the manufacturing of the copper and<br />

optical fiber cabling.<br />

The manufacturer is to be responsible for producing all design and installation<br />

guidelines and training required by a vendor to provide an end-to-end cabling system.<br />

REV. MARCH 2006 228<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Manufacturer (continued)<br />

The manufacturer, in conjunction with the vendor, is to be responsible for providing<br />

the product warranty and the lifetime application performance assurance for the<br />

cabling system.<br />

All cabling, termination hardware, and cordage shall be sourced from a single manufacturer to<br />

ensure the product quality necessary for end-to-end system performance and to obtain the<br />

product warranty and lifetime application performance assurance for the manufacturers cabling<br />

system.<br />

Vendor<br />

The bidder, including any subcontractor, shall show proven expertise in the implementation of<br />

cabling projects. This expertise can be illustrated through the inclusion of details of at least<br />

three projects involving the design and installation of enhanced Category 5 unshielded twistedpair<br />

(hereafter referred to as UTP) and optical fiber cabling systems within the past two year<br />

period. Names, addresses and telephone numbers of references for the three projects shall be<br />

included.<br />

The successful bidder shall hereafter be referred to as the Vendor.<br />

The Vendor shall accept complete responsibility for the design, installation, acceptance testing<br />

and certification of the manufactures copper optical fiber cabling system.<br />

The Vendor shall provide proof of current manufacturer certification status, and shall deliver<br />

certification of the installed manufactures cabling system to the Purchaser.<br />

Installer<br />

Either employees of the Vendor or subcontractors shall perform the installation of the<br />

manufactures copper and optical fiber cabling system. Organizations assigned as subcontractors<br />

shall be required to provide proof of manufactures authorization to install copper and optical<br />

fiber cabling.<br />

All work shall be performed and supervised by technicians and managers qualified to install<br />

and test the manufactures optical fiber cabling system in accordance with the manufacturers<br />

requirements.<br />

In the event that subcontractors are used for any portion of the installation or acceptance<br />

testing, the Vendor shall be responsible for any subsequent corrective action required on that<br />

portion.<br />

REV. MARCH 2006 229<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

6.9. Reference Standards<br />

The components and systems shall meet all the applicable requirements of the latest issue of the<br />

following specifications:<br />

a. ANSI/TIA/EIA-568<br />

b. ANSI/TIA/EIA-569<br />

c. ANSI/TIA/EIA-606<br />

d. ANSI/TIA/EIA-607<br />

e. TIA/EIA TSB67<br />

TIA/EIA TSB72<br />

f. TIA/EIA TSB75<br />

g. ISO/IEC 11801<br />

h. IEC 603-7<br />

i. CENELEC EN50173<br />

j. ANSI/ICEA S-90-661<br />

k. ANSI/ICEA S-80-576<br />

l. ANSI/ICEA S-83-596<br />

m. ANSI/ICEA S-83-640<br />

ANSI/EIA/TIA-492AAAA<br />

n. ANSI/TIA/EIA-472CAAA<br />

o. ANSI/TIA/EIA-472DAAA<br />

p. ANSI/TIA/EIA-598<br />

q. ANSI/TIA/EIA-455<br />

r. ANSI/TIA/EIA-604<br />

6.10. Warranties<br />

Qualification of System<br />

a) A certification program provided by the manufacturer and the vendor will cover the installed<br />

copper and optical fiber cabling system.<br />

b) Telecommunications spaces and pathways in new buildings or in those buildings<br />

having undergone major renovations in the preceding three years should conform to<br />

the requirements per TIA/EIA-569. In cases of installations in restrictive spaces<br />

and pathways, where it is impossible to implement the aforementioned<br />

requirements, the cabling runs shall not exceed the maximum distances specified in<br />

ANSI/TIA/EIA-568 and shall not in any manner diminish the performance of the<br />

manufactures copper and optical fiber cabling system.<br />

c) The installed manufactures copper and optical fiber cabling system shall conform<br />

to all applicable local building and electrical codes.<br />

REV. MARCH 2006 230<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Certification<br />

a) To qualify for system certification, a manufactures copper and optical fiber cabling<br />

system shall be designed, engineered, installed and tested by a manufacturer<br />

certified vendor.<br />

b) To qualify for system certification, the installed cabling system shall fully comply<br />

with all relevant manufacturer design guidelines, including acceptable deviations as<br />

specified in the latest release of the manufacturers certification guide.<br />

c) To qualify for system certification, only a single manufactures approved products<br />

shall be used to ensure end-to-end system performance. The full manufactures<br />

product warranty and lifetime performance assurance can only be provided to<br />

systems built using products supplied by the chosen manufacturer.<br />

Lifetime Application Assurance<br />

a) The manufacturers certification shall provide the assurance that all present and<br />

future applications engineered for the performance level of the cabling system used<br />

will work for the lifetime of the certified copper and optical fiber cabling system.<br />

b) Should the certified copper and optical fiber cabling system fail to support the<br />

application(s) designed to operate over it—whether at the time of cutover to the<br />

new cabling system, during subsequent use, or after upgrading to a newer<br />

supported application (for ex<strong>amp</strong>le, to a Fast Ethernet or an ATM network from a<br />

lower-speed network environment) the manufacturer and the vendor shall take<br />

prompt corrective action.<br />

Product Warranty<br />

The manufacturers certification shall provide a twenty-five year product warranty for all<br />

passive components used in the installed copper and optical fiber cabling system.<br />

Defective and/or improperly installed products shall be replaced and/or correctly installed at no<br />

cost Fairmont Hotels & Resorts.<br />

6.11. Vendor Submittals<br />

The Vendor shall provide Fairmont Hotels & Resorts with the following:<br />

a) A hard copy of all test results for approval and system acceptance.<br />

b) Manufacturers users manual, at the completion of the project.<br />

c) Manufacturers application guidelines (where available) for network technologies,<br />

which will operate over the manufacturers copper and optical fiber cabling system<br />

at the completion of the project.<br />

REV. MARCH 2006 231<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

6.12. Testing Requirements<br />

UTP System Testing<br />

a) There are two primary field test parameters for an UTP-based end-to-end cabling<br />

system. These are continuity/wire mapping and a visual inspection, both to be<br />

performed by the vendor.<br />

b) Continuity/wire mapping is used to verify consistency pair-to-pin terminations at<br />

each end of a given cable. It also checks for faulty connections in the run. For each<br />

of the eight conductors in the cable, continuity/wire mapping indicates:<br />

Continuity of the channel to the remote end.<br />

Shorts between any two or more conductors.<br />

Crossed pairs.<br />

Reversed pairs.<br />

Split pairs.<br />

Any other mis-wiring.<br />

Optical Fiber System Testing<br />

a) There is one primary field test parameter for an optical fiber-based end-to-end<br />

system. This is attenuation testing, to be performed by the Vendor.<br />

b) Since optical signal attenuation at one wavelength is independent of the attenuation<br />

at a second wavelength, the attenuation of the channel should be measured at both<br />

standard wavelengths (850 nm and 1300 nm) for backbone links. Either wavelength<br />

can be used for the testing of horizontal links.<br />

c) Optical fiber field-test light sources must operate within 820-880 nm and/or 1280-<br />

1320 nm wavelength range(s) for multimode system testing.<br />

Additional UTP System Testing<br />

All the parameters per TIA/EIA TSB67 must be verified using a Level II accuracy field tester.<br />

TIA/EIA TSB67 defines two post-installation test configurations for UTP telecommunications<br />

cabling systems designed in accordance with ANSI/TIA/EIA-568 requirements—a channel test<br />

configuration and a basic link test configuration. The required test configuration for this end-toend<br />

structured cabling system is the channel configuration as all the components and all<br />

possible sources of installation error are included in the testing.<br />

REV. MARCH 2006 232<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

7. TECHNOLOGY SERVICES – PRODUCT SPECIFICATIONS<br />

7.1. Cabling Overview<br />

Enhanced Category 5 UTP specifications<br />

a) The UTP-based cabling system shall have a 160 MHz channel bandwidth over a<br />

maximum distance of 100m (328 ft) and a channel power sum attenuation-tocrosstalk<br />

ratio (PSACR) of 9.6 dB @ 100 MHz using an interconnect or BIX cross<br />

connect configuration.<br />

b) The UTP-based cabling system shall use matched components from a single<br />

manufacturer, certified to deliver system performance over the lifetime of the<br />

applications that the cabling system was originally designed to support.<br />

c) All components used in the UTP-based cabling system shall be warranted for a<br />

period of 25 years from date of installation against defects in materials and<br />

workmanship.<br />

d) The UTP-based cabling system shall comply with the following standards:<br />

Enhanced Category 5 - TIA/EIA Addendum<br />

Category 5 - ANSI/TIA/EIA-568, TIA/EIA TSB67<br />

Class D - CENELEC EN50173<br />

Class D - ISO/IEC 11801<br />

Optical Fiber Cabling System<br />

a) The optical fiber-based cabling system shall provide a 160 MHz-km bandwidth @<br />

850 nm and 500 MHz-km bandwidth @ 1300 nm using 50/125 micron 6 strand<br />

multimode optical fiber.<br />

b) The optical fiber-based cabling system shall use matched components from a single<br />

manufacturer, certified to deliver system performance over the lifetime of the<br />

applications that the cabling system was originally designed to support.<br />

c) All components used in the optical fiber-based cabling system shall be warranted<br />

for a period of 25 years from date of installation against defects in materials and<br />

workmanship.<br />

d) The optical fiber-based cabling system shall comply with the following standards:<br />

ANSI/TIA/EIA-568<br />

CENELEC EN50173<br />

ISO/IEC 11801<br />

e) The optical fiber-based cabling system shall be capable of supporting the following<br />

native fiber-based applications as well as environments where native copper-based<br />

electrical signals are converted to an optical stream:<br />

Gigabit Ethernet (1000BASE-SX and LX)<br />

Fast Ethernet (100BASE-FX)<br />

REV. MARCH 2006 233<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

7.2. Horizontal Cabling<br />

HC<br />

Horizontal<br />

Cabling<br />

a) The intended use is to provide a 100 ohm UTP signalling path between the Horizontal<br />

Cross-connect in the Telecommunications Closet and the Telecommunications<br />

Outlet/Connector serving the Work Area(s).<br />

b) The horizontal UTP cable shall meet or exceed the enhanced Category 5 transmission<br />

characteristics per the latest issue of ANSI/TIA/EIA-568.<br />

c) The plenum version of the horizontal UTP cable shall be ETL or UL Listed and CSA<br />

Certified as Type CMP, in accordance with the Bi-national Standard for Communications<br />

Cable, UL 444/C22.2 No. 214-94.<br />

d) The non-plenum version of the horizontal UTP cable shall be ETL or UL Listed and CSA<br />

Certified as Type CMR or CM, in accordance with the Bi-national Standard for<br />

Communications Cable, UL 444/C22.2 No. 214-94.<br />

e) The horizontal UTP cable shall comply with Class A limits of FCC Part 15, Subpart J for<br />

computing devices for electromagnetic radiation when tested with appropriate<br />

networking protocols.<br />

REV. MARCH 2006 234<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

7.3. Cross-connect/Interconnect Systems<br />

HC<br />

Communications<br />

Closet<br />

MC<br />

Equipment<br />

Room<br />

Data Interconnect / Rack Mount Patch Panel System<br />

a) The intended use is to provide a centralized, rack mounted termination, identification and<br />

service assignment point for UTP horizontal, backbone and equipment cabling at the<br />

horizontal or main cross connect, using modular cord assemblies.<br />

b) The connection module used in the rack mount UTP cross-connect/interconnect system<br />

shall be Power Sum rated, with a Power Sum NEXT performance equal to or better than<br />

ANSI/TIA/EIA-568 Category 5 pair-to-pair NEXT performance specifications.<br />

c) The connection module used in the rack mount UTP cross-connect/interconnect system<br />

shall be available in both the T568A-ISDN and T568B-ALT wiring configurations.<br />

REV. MARCH 2006 235<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

7.4. Data Communications Outlets<br />

Legend<br />

Work Area<br />

Telecommunications<br />

Outlet/Connector<br />

Cord Assemblies<br />

UTP Outlets<br />

a) The outlet UTP connection module and its optional cover shall be available in the<br />

following colors: grey, almond, white, black, orange, red, yellow, green, blue, purple, and<br />

brown.<br />

b) The outlet UTP connection module shall be Power Sum rated, with a Power Sum NEXT<br />

performance equal to or better than ANSI/TIA/EIA-568 Category 5 pair-to-pair NEXT<br />

performance specifications, and shall have a PS5 marking to indicate compliance.<br />

c) The eight-position outlet UTP connection module shall accommodate six-position<br />

modular plug modular cords without damage to either the cord or the module.<br />

d) It shall be possible to inspect and/or re-terminate the UTP cable at the outlet through<br />

front access at the faceplate.<br />

e) The faceplate housing the outlet UTP connection modules shall have aperture plugs to<br />

cover any unused openings in the faceplate.<br />

f) It shall be possible to install the outlet UTP connection modules in wall mounted single<br />

and dual-gang electrical boxes, utility poles and modular furniture (cubicle) access points<br />

using manufacturer-supplied faceplates and/or adapters, equipped with front, side or<br />

angled-entry options for modular cords.<br />

g) The faceplate housing the outlet UTP connection modules shall be available in the<br />

following colors: grey, almond, white, and black.<br />

REV. MARCH 2006 236<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

UTP Cables<br />

a) The modular cord assembly shall meet or exceed the short link NEXT requirements of 38<br />

dB when tested with enhanced Category 5 connecting hardware.<br />

b) The modular cord cable shall be 4-pair, with 24 AWG solid or stranded copper<br />

conductors.<br />

c) The modular cord assemblies shall be 10 feet in the guest rooms, and 4 feet for patching<br />

in the wiring closets.<br />

d) Modular cross over cables will be four feet in length with a yellow cable jacket.<br />

e) The modular cord assembly shall meet the requirements per the latest issue of<br />

ANSI/TIA/EIA-568.<br />

f) The modular cord assembly shall meet the requirements per the latest issue of ISO/IEC<br />

11801.<br />

REV. MARCH 2006 237<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

7.5. Optical Fiber Backbone Cabling System<br />

HC<br />

MC<br />

Backbone<br />

Cabling<br />

Backbone Cabling<br />

a) The intended use is to provide a multimode 50/125-micron optical fiber signalling path<br />

between the Main/Intermediate Cross-connect and the Horizontal Cross-connect.<br />

b) The in-building backbone optical fiber cable shall be available with a minimum of six<br />

strand fibers placed in a color-coded subunit bundle with armoured strength elements.<br />

c) The in-building backbone optical fiber cable shall be available with multimode 50/125-<br />

micron construction, with either Riser (OFNR) or Plenum (OFNP) fire rating.<br />

Optical Fiber Rack Mount System<br />

a) The intended use is to provide a centralized, rack-mounted termination, identification and<br />

service assignment point for optical fiber.<br />

b) The optical fiber cross-connect/interconnect system rack mount shall be a 12, 24 or 48-<br />

fiber unit, with a double-density option to double the number of connections to 24, 48 or<br />

96 without requiring additional rack space.<br />

c) The optical fiber cross-connect/interconnect system rack mount shall be equipped with<br />

either a swing out or a sliding drawer mechanism for access to fibers.<br />

d) The optical fiber cross-connect/interconnect system rack mount shall be capable of<br />

terminating tight buffered or loose tube optical fiber cables and all popular connector<br />

types.<br />

e) The optical fiber cross-connect/interconnect system rack mount shall provide for bend<br />

radius control throughout the panel as well as storage space for slack cabling.<br />

REV. MARCH 2006 238<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Optical Fiber Interconnect Systems<br />

a) The optical fiber field-installable connector shall be an SC format, for installation onto<br />

multimode 50/125-micron fiber.<br />

b) The optical fiber connectors shall have a typical Insertion Loss of 0.3 dB.<br />

c) The optical fiber connectors shall have a typical Reflectance of -30 dB.<br />

Optical Fiber Patch Cables<br />

a) Fiber pigtails will be 50/125 um, multimode with SC terminations at both ends.<br />

b) The fiber pigtails will be 0.9 meters in length.<br />

REV. MARCH 2006 239<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

8. TECHNOLOGY SERVICES – COMMUNICATION SYSTEMS<br />

8.1. Room Specifications<br />

Telephone Equipment Room<br />

a) The telephone equipment room should have an area of approximately 25 m 2 .<br />

Provide adjacent entrance facilities where required by local telephone service<br />

provider. Size and configuration of room to be confirmed with equipment<br />

manufacturer(s).<br />

b) Electrical requirements should be sufficient to supply a Northern Telecom<br />

Meridian system or Fairmont Hotels approved equivalent. Consultants to confirm<br />

with manufacturer of switching equipment to confirm actual power supply, cabling<br />

and conduit requirements prior completing design.<br />

c) The equipment room should be located as close as possible to main cable risers and<br />

computer room.<br />

d) UPS : Emergency evaporative or gel type battery back-up to be provided with<br />

system.<br />

e) Provide supports for equipment and HVAC as per equipment manufacturer’s<br />

requirements.<br />

Telephone Operators’ Room<br />

a) Room should have an area of approximately 20m 2 (based on a 300-400 rooms<br />

hotel) to accommodate two or three attendants with one supervisor. Supervisory<br />

equipment terminals (security, fire alarm etc...) must also be accommodated in this<br />

room.<br />

b) This room may be included with Fairmont Hotel’s Royal Service which combines<br />

other telephone-dependant guest services (room service, concierge, etc...). To be<br />

determined by FHR in final design brief.<br />

REV. MARCH 2006 240<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Computer Room<br />

a) A main central computer shall be provided in the accounting offices area to house<br />

all network servers. The Systems Manager’s office should be located next to the<br />

computer room with glazed partition between.<br />

b) The floor finish should be anti-static VAT, ceiling w/suspended acoustic tiles.<br />

c) All cabling to be installed in ceiling mounted open cable trays.<br />

d) The room should be air conditioned with an independent unit hooked up to the<br />

emergency power supply to maintain the room at 20°C (± 3°C) and 50% RH.<br />

e) Ventilation and AC system to be provided with high efficiency filters.<br />

f) Provide temperature sensors connected to the EMS to enable low/high temperature<br />

alarm.<br />

g) No pipes or equipment containing liquid are to be installed above the computer<br />

room except for sprinkler pipes where they are required by local bylaws or building<br />

code.<br />

h) Smoke detector and fire extinguisher to be provided in computer room.<br />

i) Lighting to be recessed fluorescent fixtures on emergency power supply.<br />

j) Electrical supply to on dedicated circuits from the hotel’s main distribution panel.<br />

k) A minimum of 10 KVA power supply is required.<br />

l) UPS (Uninterruptible Power Supply) must be provided (10 KVA, 3 phase, 208/120<br />

VAC with non-evaporative type battery back-up).<br />

m) Number of outlets varies depending on equipment provided by FHR. Generally one<br />

duplex 120 VAC, 15A outlet will be required for each Server, and one outlet for<br />

each PC, Monitor, printer, modem and network hub. A typical 400-room hotel will<br />

require approximately 16 duplex outlets in the computer room. Exact number of<br />

outlet will be confirmed with FHR prior to completing construction documents and<br />

specifications.<br />

n) The computer equipment shall be mounted on a shelving system; this system will<br />

allow equipment to be plugged in.<br />

REV. MARCH 2006 241<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

REV. MARCH 2006 242<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

F. APPENDICES<br />

1. HARDWARE<br />

1.1. General Requirements<br />

A. This Section includes door hardware items that are required for swing, sliding<br />

and folding doors, except special types of unique hardware specified in the same<br />

sections as the doors and door frames on which they are to be installed.<br />

B. This Section includes, but is not limited to, the following:<br />

a) Hinges<br />

b) Pivots<br />

c) Spring hinges<br />

d) Key control systems<br />

e) Lock cylinders and keys<br />

f) Lock and latch sets<br />

g) Bolts<br />

h) Exit devices<br />

i) Push/pull units<br />

j) Closers<br />

k) Overhead holders<br />

l) Miscellaneous door control devices<br />

m) Door trim units<br />

n) Protection plates<br />

o) Sliding door equipment<br />

p) Weatherstripping for exterior doors<br />

q) Sound stripping for doors<br />

r) Automatic drop seals (door bottoms)<br />

s) Astragals or meeting seals on pairs of doors<br />

t) Thresholds<br />

REV. MARCH 2006 243<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

General Requirements (continued)<br />

C. Items not included in this section:<br />

a) Cabinet hardware<br />

b) Roll-up door hardware<br />

1.2. Submittals to Fairmont Hotels & Resorts (FHR)<br />

A. The Contractor shall submit two bound binders containing the manufacturer’s<br />

technical product data for each item of door hardware, installation instruction,<br />

maintenance of operating parts and finish, together with other information<br />

necessary to show compliance with requirements.<br />

B. The Contractor shall also submit a final hardware schedule coordinated with<br />

doors, frames, and related work to ensure proper size, thickness, hand, function,<br />

and finish of door hardware.<br />

1. Based on hardware indicated, organize schedule into “hardware sets”<br />

indicating complete designations of every item required for each door or<br />

opening. Include the following information:<br />

Fastenings and other pertinent<br />

a) Type, style function, size, and finish of each hardware item.<br />

b) Name and manufacturer of each item<br />

c) Location of each hardware set cross referenced to indications<br />

on drawings, both on floor plans and in door and frame<br />

schedule<br />

d) Explanation of all abbreviations, symbols, and codes<br />

contained in schedule<br />

e) Mounting locations for hardware<br />

f) Door and frame sizes and materials<br />

g) Keying information<br />

2. An initial draft of the final schedule along with essential product data in<br />

order to facilitate the fabrication of other work that is critical to the<br />

construction schedule shall also be submitted by the Contractor. A final<br />

schedule shall also be submitted, but only after s<strong>amp</strong>les, product data,<br />

coordinated with shop drawings of other work, delivery schedules, and<br />

similar information has been completed and accepted.<br />

3. A separate detailed schedule indicating clearly how the keying of locks<br />

has been scheduled shall also be submitted by the Contractor. A meeting<br />

is to be arranged between the Contactor and FHR to finalize keying<br />

requirements and obtain final instructions in writing.<br />

REV. MARCH 2006 244<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Submittals to Fairmont Hotels & Resorts (continued)<br />

C. The Contractor shall submit s<strong>amp</strong>les of each type of exposed hardware unit in<br />

finish indicated and tagged with full description for coordination with schedule.<br />

Submit s<strong>amp</strong>les prior to submission of final hardware schedule.<br />

D. The Contractor shall furnish a complete set of specialized tools and maintenance<br />

instructions as needed for FHR’s continued adjustment, maintenance and<br />

removal and replacement of door hardware.<br />

1.3. Quality Assurance<br />

A. Obtain each type of hardware (latch and lock sets, hinges, closers, etc.) from a<br />

single manufacturer.<br />

1.4. Approved Manufacturers<br />

A. Manufacturers: Subject to compliance with requirements, provide products by<br />

one of the following:<br />

1. Butts and Hinges:<br />

a) Hager Hinge Co.<br />

b) McKinney Product Co.<br />

c) Stanley Hardware, Div. Stanley Works<br />

2. Pivots:<br />

a) Rixson-Firemark, Div. Yale Security Inc.<br />

b) H.B. Ives, Div. Ingersoll-Rand Door Hardware Group<br />

3. Key Control System:<br />

a) Key Control Systems, Inc.<br />

b) Telkee Inc.<br />

4. Cylinders and Locks:<br />

a) Corbin & Russwin Architectural Hardware<br />

b) Sargent Manufacturing Company<br />

c) Schlage Lock, Div. Ingersoll-Rand Door Hardware Group<br />

5. Bolts<br />

a) Builders Brass Works Corp.<br />

b) Rockwood Manufacturing<br />

c) H.B. Ives, Div. Ingersoll-Rand Door Hardware Group<br />

REV. MARCH 2006 245<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Approved Manufacturers (continued)<br />

6. Exit/Panic Devices<br />

a) Corbin & Russwin Architectural Hardware<br />

b) Precision Hardware, Inc.<br />

c) Sargent Manufacturing Company<br />

d) Von Duprin, Div. Ingersoll-Rand Door Hardware Group<br />

7. Push/Pull Units:<br />

a) Baldwin Hardware Corp.<br />

b) Rockwood Manufacturing<br />

c) Don-Jo<br />

d) H.B. Ives, Div. Ingersoll-Rand Door Hardware Group<br />

e) Triangle Brass Manufacturing Company (Trimco)<br />

f) Custom push/pull to be as selected by Owner<br />

8. Overhead Closers:<br />

a) Corbin & Russwin Architectural Hardware<br />

b) LCN, Div. Ingersoll-Rand Door Hardware Group<br />

c) Norton Door Controls, Div. Yale Security Inc.<br />

d) Sargent Manufacturing Company<br />

9. Smoke-Activated Closers:<br />

a) Corbin & Russwin Architectural Hardware<br />

b) Norton Door Controls, Div. Yale Security Inc.<br />

c) Rixson-Firemark, Div. Yale Security Inc.<br />

d) LCN, Div. Ingersoll-Rand Door Hardware Group<br />

10. Floor Closers<br />

a) Dorma Door Controls International<br />

b) Rixson-Firemark, Div. Yale Security Inc.<br />

11. Door Control Devices:<br />

a) Baldwin Hardware Corp.<br />

b) Builders Brass Works Corp.<br />

c) Rockwood Manufacturing<br />

d) Glynn-Johnson Corp., Div. Ingersoll-Rand Door Hardware Group<br />

e) H.B. Ives, Div. Ingersoll-Rand Door Hardware Group<br />

f) Triangle Brass Manufacturing Company (Trimco)<br />

12. Door Trim Units:<br />

a) Baldwin Hardware Corp.<br />

b) Builders Brass Works Corp.<br />

c) H.B. Ives, Div. Ingersoll-Rand Door Hardware Group<br />

d) Triangle Brass Manufacturing Company (Trimco)<br />

REV. MARCH 2006 246<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Approved Manufacturers (continued)<br />

e) Don-Jo<br />

f) Rockwood Manufacturing<br />

13. Kick, Mop, and Armor Plates:<br />

a) Baldwin Hardware Corp.<br />

b) Rockwood Manufacturing<br />

c) H.B. Ives, Div. Ingersoll-Rand Door Hardware Group<br />

d) Triangle Brass Manufacturing Company (Trimco)<br />

e) Don-Jo<br />

14. Door Stripping and Seals:<br />

a) National Guard Products, Inc.<br />

b) Pemko Manufacturing Co., Inc.<br />

c) Reese Enterprises, Inc.<br />

d) Zero International, Inc.<br />

15. Thresholds:<br />

a) National Guard Products, Inc.<br />

b) Pemko Manufacturing Co., Inc.<br />

c) Reese Enterprises Inc.<br />

d) Zero International, Inc.<br />

16. Automatic Drop Seals:<br />

a) National Guard Products, Inc.<br />

b) Pemko Manufacturing Co. Inc.<br />

c) Reese Enterprises Inc.<br />

d) Zero International, Inc.<br />

17. Astragals:<br />

a) National Guard Products, Inc.<br />

b) Pemko Manufacturing Co. Inc.<br />

c) Reese Enterprises Inc.<br />

d) Zero International, Inc.<br />

1.5 Hardware Designation<br />

A. Requirements for design, grade, function, finish, size, and other distinctive<br />

qualities of each type of finish hardware are indicated at the end of this Section.<br />

Products are identified by using hardware designation numbers of the following:<br />

1. ANSI/BHMA designations used elsewhere in this Section or in<br />

schedules to describe hardware items or to define quality or function are<br />

REV. MARCH 2006 247<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Hardware Designation (continued)<br />

derived from the following standards. Provide products complying with<br />

these standards and requirements specified elsewhere in this Section.<br />

a) Butts and Hinges: ANSI/BHMA A156.1<br />

b) Bored and Pre-assembled Locks and Latches: ANSI/BHMA<br />

A156.2<br />

c) Exit Devices: ANSI/BHMA A156.3<br />

d) Door Controls – Closers: ANSI/BHMA A156.4<br />

e) Auxiliary Locks and Associated Products: ANSI/BHMA A156.5<br />

f) Architectural Door Trim: ANSI/BHMA A156.6<br />

g) Template Hinge Dimensions: ANSI/BHMA A156.7<br />

h) Door Controls – Overhead Holders: ANSI/BHMA A156.8<br />

i) Interconnected Locks and Latches: ANSI/BHMA A156.12<br />

j) Mortise Locks and Latches: ANSI/BHMA A156.13<br />

k) Sliding and Folding Door Hardware: ANSI/BHMA A156.14<br />

l) Closer Holder Release Devises: ANSI/BHMA A156.15<br />

m) Auxiliary Hardware: ANSI/BHMA A156.16<br />

n) Self-Closing Hinges and Pivots: ANSI/BHMA A156.17<br />

o) Materials and Finishes: ANSI/BHMA A156.18.<br />

1.6. Materials and Fabrication<br />

A. Do not use manufacturers’ products that have manufacturer’s name or trade<br />

name displayed in a visible location (omit removable name plates) except in<br />

conjunction with required fire-rated labels.<br />

B. Produce hardware units of basic metal and forming method indicated using<br />

manufacturer’s standard metal alloy, composition, temper, and hardness, but in<br />

no case of lesser (commercially recognized) quality than specified for applicable<br />

hardware units for finish designations indicated.<br />

C. Do not provide hardware that has been prepared for self-tapping sheet metal<br />

screws, except as specifically indicated.<br />

D. Finish exposed (exposed under any condition) screws to match hardware finish<br />

or, if exposed in surfaces of other work, to match finish of this other work as<br />

closely as possible “prepared for paint” surfaces to receive painted finish.<br />

1.7. Hinges, Butts, and Pivots<br />

A. Templates: Except for hinges and pivots to be installed entirely (both leaves)<br />

into wood doors and frames, provide only template-produced units.<br />

REV. MARCH 2006 248<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Hinges, Butts, and Pivots (continued)<br />

B. Screws: Provide Phillip flat-head screws complying with the following<br />

requirements:<br />

1. The metal doors and frames install machine screws into drilled and<br />

tapped holes.<br />

2. The wood doors and frames install wood screws.<br />

3. For fire-rated wood doors install #12 x 1-1/4”, threaded-to-the-head steel<br />

wood screws.<br />

4. Finish screw heads to match surface of hinges or pivots.<br />

C. Hinge Pins: Except as otherwise indicated, provide hinge pins as follows:<br />

1. The metal doors and frames install machine screws into drilled and<br />

tapped holes.<br />

2. The wood doors and frames install wood screws.<br />

3. For fire-rated wood doors install #12 x 1-1/4”, threaded-to-the-head steel<br />

wood screws.<br />

4. Finish screw heads to match surface of hinges or pivots.<br />

D. Number of Hinges: Provide number of hinges indicated but not less than 1 1/2<br />

pair per door leaf for doors 90 inches or less in height and one additional hinge<br />

for each 30 inches of additional height.<br />

1. Fire-Rated Doors: Not less than 3 hinges per door leaf for doors 86<br />

inches of less in height with same rule for additional hinges.<br />

1.8. Lock Cylinder and Keying<br />

A. The Contractor shall provide a new grandmaster key system for the Project and<br />

equip all locks with manufacturer’s special 6-pin tumbler cylinder with<br />

construction master key feature that permits voiding of construction keys<br />

without cylinder removal.<br />

B. The Contractor shall, except as otherwise indicated, provide individual change<br />

key for each lock that is not designated to be keyed alike with a group of related<br />

locks within the approved master keying system and permanently inscribe each<br />

key with number of lock that identifies cylinder manufacturer’s key symbol, and<br />

notation, “DO NOT DUPLICATE”.<br />

REV. MARCH 2006 249<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Lock Cylinder and Keying (continued)<br />

C. The Contractor shall provide keys of nickel silver only and furnish 3 change<br />

keys for each lock, 5 master keys for each master system, and 5 grandmaster<br />

keys for each grandmaster system.<br />

1. Furnish on extra blank for each lock.<br />

2. Furnish ten (10) construction keys.<br />

3. Deliver keys to FHR resident Chief Engineer.<br />

1.9. Key Control System<br />

A. The Contractor shall provide a key control system including envelopes, labels,<br />

tags with self-locking key clips, receipt forms, 3-way visible card index,<br />

temporary markers, permanent markers, and standard metal cabinets, all as<br />

recommended by system manufacturer, with capacity for 150 percent of the<br />

number of locks required for the Project. All keys to be housed within wallmounted<br />

hinged-panel type cabinet.<br />

1.10 Locks, Latches, and Bolts<br />

A. The Contractor shall provide the manufacturer’s standard wrought box strike for<br />

each latch or lock bolt, with curved lip extended to protect frame, finished to<br />

match hardware set, unless otherwise indicated.<br />

B. A throw of 5/8 minimum of latch on pairs of doors. UL requirements for throw<br />

of bolts and latch bolts on rated fire openings are to be complied with.<br />

C. A throw of ½” minimum for other bored and pre-assembled types of locks, ¾”<br />

minimum throw of latch for mortise locks and 1” minimum throw for all dead<br />

bolts.<br />

D. Flush Bolt Heads: Minimum of ½” diameter rods of brass, bronze, or stainless<br />

steel with minimum 12” long rod for doors up to 7’0” in height. Longer rods as<br />

necessary for doors exceeding 7’0” in height.<br />

E. Except on fire-rated doors where closers are provided on doors equipped with<br />

exit devices, equip the units with keyed dogging device to keep the latch bolt<br />

retracted when engaged.<br />

F. Where rabbeted door stiles are indicated, provide special rabbeted front on lock<br />

and latch units and bolts.<br />

REV. MARCH 2006 250<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

1.11 Door Trim Units<br />

A. The Contractor shall provide manufacturer’s standard exposed fasteners for door<br />

trim units consisting of either machine screws or self-tapping screws and<br />

fabricate edge trim of stainless steel to fit door thickness in standard lengths or<br />

to match height of protection plates. All protection plates not more than 2” less<br />

than door width on hinge side and not more than 1” less than door width on pull<br />

side by height indicated (Stainless steel, brass or bronze 0.050” – US 18 gauge).<br />

1.12. Hardware for Sliding Doors<br />

A. The Contractor shall provide only those items indicated in the project schedule.<br />

Balance of hardware to be furnished by door supplier.<br />

1.13 Weatherstripping and Seals<br />

A. The Contractor shall provide continuous weatherstripping on exterior doors and<br />

smoke, light, or sound seals on interior doors where indicated or scheduled and<br />

resilient or flexible seal strip which is easily replaceable and readily available<br />

from stocks maintained by manufacturer.<br />

1.14 Thresholds<br />

A. Except as otherwise indicated, the Contractor shall provide standard metal<br />

threshold unit of type, size, and profile as shown or scheduled.<br />

1.15 Hardware finishes<br />

A. The Contractor shall provide finishes that matches architect’s s<strong>amp</strong>le and<br />

provide protective lacquer coating on all exposed hardware finishes of brass,<br />

bronze, and aluminium, except as otherwise indicated. The suffix “-NL” is used<br />

with standard finish designations to indicate “no lacquer”.<br />

B. The designations used in schedules and elsewhere to indicate hardware finishes<br />

are the industry-recognized standard commercial finishes, except as otherwise<br />

noted.<br />

For iron and steel base metal required for exterior work and in areas shown as<br />

“High Humidity” areas (and also when designed with the suffix-RR), provide<br />

0.2-mil-thick copper coating on base metal before applying brass, bronze,<br />

nickel, or chromium-plated finishes.<br />

REV. MARCH 2006 251<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

1.16 Installation<br />

A. Hardware shall be units mounted at heights directed by the Architect.<br />

Each hardware item shall be installed in strict compliance with the<br />

manufacturer’s instructions and recommendations level, plumb, and true to line<br />

and location.<br />

1.17 Adjusting, Cleaning, and Demonstrating<br />

A. The Contractor shall adjust and check each operating item of hardware and each<br />

door to ensure proper operation or function of every unit and replace units that<br />

cannot be adjusted to operate freely and smoothly or as intended for the<br />

application made.<br />

1. Where door hardware is installed more than one month prior to<br />

acceptance or occupancy of a space or area, return to the installation<br />

during the week prior to acceptance or occupancy and make final check<br />

and adjustment of all hardware items in such space or area. Clean<br />

operating items as necessary to restore proper function and finish of<br />

hardware and doors. Adjust door control devices to compensate for final<br />

operation of heating and ventilating equipment.<br />

B. Clean and repair adjacent surfaces soiled by hardware installation.<br />

C. Instruct FHR’s personnel in the proper adjustment and maintenance of door<br />

hardware and hardware finishes.<br />

D. Approximately six months after the date of Substantial Completion, the<br />

Contractor, accompanied by representatives of the manufacturers of latchsets<br />

and locksets and of door control devices, and of other major hardware suppliers,<br />

shall return to the Project to perform the following work:<br />

1. Examine and re-adjust each item of door hardware as necessary to<br />

restore function of doors hardware to comply with specified<br />

requirements.<br />

2. Consult with and instruct FHR’s personnel in recommended additions to<br />

the maintenance procedures.<br />

3. Replace hardware items that have deteriorated or failed due to faulty<br />

design, materials, or installation of hardware units.<br />

4. Prepare a written report of current and predictable problems (of<br />

substantial nature) in the performance of the hardware.<br />

REV. MARCH 2006 252<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

1.18 Hardware Schedule<br />

A. The Contractor shall provide hardware for each door to comply with<br />

requirements as set out within these Standard’s hardware set numbers indicated<br />

in door schedule, and in the hardware schedule.<br />

1. Hardware sets indicate quantity, item, manufacturer and product<br />

designation, size, and finish or color, as applicable.<br />

1.19 TimeLox Locking System Requirements<br />

TimeLox are to provide a project specific package, inclusive of all items below unless<br />

otherwise stated, for approval by Fairmont Hotels & Resorts Corporate Office San<br />

Francisco before a contract to supply and install can be executed.<br />

1. Software Requirements to be Windows NT based software<br />

One (1) TimeLox Modem Package for on line diagnostic and support<br />

One (1) TimeLox 2300 Windows software package and user license<br />

One (1) Handheld Communications Unit, used to program and interrogate<br />

TimeLox locks. Should also include TimeLox external power up contact card.<br />

2. Hardware Requirements<br />

Flat colour monitor<br />

One (1) Timelox server for system to be located in the computer room<br />

Contractor to provide cabling from all terminal and encoders to server computer<br />

using CAT5e cable<br />

Computer requires one (1) dedicated 110V 15 <strong>amp</strong> AC power duplex outlet<br />

All equipment to be connected to the uninterrupted power supply (UPS)<br />

Computer to have the following requirements:<br />

• CD ROM<br />

• Latest Pentium CPU<br />

• 100 Base T nic<br />

• One (1) current standard internal hard drive with a minimum of 3.2 gb<br />

• Two (2) serial ports and one (1) parallel port<br />

REV. MARCH 2006 253<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

TimeLox/ Hardware Requirements (continued)<br />

• Two (2) internal slots for interface cards<br />

• Windows NT Client Operating System, including license<br />

TimeLox “Automatice Card Encoder” with 110 V, including communication<br />

port.<br />

• One (1) encoder for each check-in position at the front desk and vacation<br />

ownership<br />

• One (1) encoder for concierge<br />

• One (1) encoder for remote check-in<br />

• One (1) encoder for security<br />

• One (1) encoder for spare<br />

• One (1) encoder for MIS<br />

• One (1) encoder for engineering<br />

• One (1) encoder for club reception floor<br />

Encoders should use ethernet cabling between front desk terminals and must be<br />

one-line to the server.<br />

One (1) management terminal for each of the following: administration near<br />

hotel front desk, administration near vacation ownership front desk and security<br />

office.<br />

Three (3) Handheld Communications Units (one for engineering, security and<br />

for spare).<br />

Network hubs to be placed as required to service all above locations.<br />

3. System Features<br />

Windows based, and having the ability to be interfaced or integrated with<br />

“Fidelio Opera” Property Management System. Fidelio side of interface to be<br />

provided by Fairmont Hotels & Resorts.<br />

System to have the ability to upgrade from magstripe card to smartcard without<br />

Changing lock hardware.<br />

REV. MARCH 2006 254<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

TimeLox/System Features (continued)<br />

System should have a minimum of eight (8) failsafe cards per room (in the event<br />

of power failure, property will continue to be able to check guests in).<br />

System should have a minimum of thirty (30) user types (or levels) and a<br />

minimum of two hundred and fifty-sic (256) User Groups (employee access<br />

areas) and should be able to issue up to ten thousand (10,000) user cards.<br />

System should have a custom built configuration according to the way the<br />

property wants the electronic key system to be configured.<br />

System access to the system operations must be by password and operator card<br />

protected, and user defined by the property with regards to what functions can<br />

be done with what security level.<br />

Keycard information encoded on track 3 of a standard American banking card.<br />

All keycard encoding information must be in an encrypted form.<br />

System must have a minimum of eight (8) time zones, for employee and guest<br />

access.<br />

Guest cards must have a start time, end time and issue time encoded at the time<br />

the card is encoded. Issue time is for pre-registered cards. Cards can be made in<br />

advance to start at a specific date and time in the future.<br />

System to have a built-in Help program.<br />

Pool doors, health club, etc., should be able to be controlled by time.<br />

System should be able to issue an unlimited number of master keycards.<br />

System should have a device for elevator control, whereby hotel floor access can<br />

be limited by time of day of week.<br />

4. Supplies<br />

TimeLox to supply appropriate number of blank keycards, customized with<br />

Hotel desired artwork to cover the first twelve (12) months of operation.<br />

REV. MARCH 2006 255<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

5. Warranty<br />

TimeLox to supply twelve (12) month warranty covering all equipment from<br />

date of installation.<br />

6. Training<br />

On-site training in use of system to all necessary staff as well as Chief Engineer<br />

and Systems manager.<br />

Provide four (4) bound copies of operational manuals.<br />

7. Back of House Requirements<br />

a) Guest Floor Back of House Doors<br />

The following doors shall be connected to the back of house side of the<br />

system:<br />

• Maids’ closets<br />

• Pantries<br />

• Presidents Club Lounge<br />

Each door shall be equipped with:<br />

One (1) standard mortise TimeLox 9050 with standard handle with<br />

matching cap.<br />

b) Elevators<br />

Provide one (1) flush mounted cardreader in each guest elevator cab,<br />

mounted in the cab control panel, with finish specified by the interior<br />

designer.<br />

c) Back-of-House Doors<br />

The following high security area doors will be connected to the TimeLox<br />

system using TimeLox 2300 mortise with standard handle and keypad.<br />

• General food and beverage entrance<br />

• Wine and Liquor storage<br />

• China/Glass/Silver storage<br />

REV. MARCH 2006 256<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

2. TYPICAL HARDWARE SPECIFICATIONS (PER DOOR) BY LOCATION<br />

2.1. Guestroom Entry Door:<br />

a) Hinges (HA) 1 ½ pr AB 700 4 ½ “ x 4 ½” US10B<br />

(2 pr at Presidential Suite)<br />

b) Entry TimeLox complete with US10B<br />

selected handles<br />

c) Closer (LC) 2031 BUMP US10B<br />

d) Guard (RO) 604 with 605 edge guard US10B<br />

e) Viewer (RO) 622 mounted at 5’0” US10B<br />

(1.5m) AFFL<br />

Additional viewer at<br />

4’0” (1.2 m) AFFL in<br />

handicap rooms<br />

f) Stop-wall (RO) 404<br />

g) Sound seal (DH) Cush n’ Seal White<br />

h) Automatic door<br />

bottom (PE) 434 ARL x 36”<br />

2.2. Guestroom Sliding Balcony Door:<br />

a) Hardware by aluminium glass door manufacturer, including lockset<br />

b) Doors to gardens, etc., to have security chain or similar security device.<br />

2.3 Guestroom Balcony French Door (Pair):<br />

a) Hinges (HA) 1/2 pr 700 BB 1360 4 ½” x 4 ½” US10B<br />

b) Flush bolts (RO) 1 pr 555 US10B<br />

c) Dust Proof Strike (RO) 570 US10B<br />

d) Lockset (AD) ME 1850 A 313<br />

e) Closer (LC) 1 2033 BUMP US10B<br />

f) Threshold (PE) 2055 BV x 72”<br />

g) Mortise Latchset (HB) 5302 x CA Knob US10B<br />

or AU Lever<br />

REV. MARCH 2006 257<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Guestroom Balcony French Door (continued)<br />

h) Decorative pull to be selected US10B<br />

i) Sound seal (DH) Cush n’ Seal White<br />

j) Automatic door<br />

button (PE)<br />

434 ARL x door width<br />

2.4 Guestroom Bathroom Door:<br />

a) Hinges (HA) 1 ½ pr AB 800 4 ½” x 4 ½” US15B<br />

b) Full dummy trim (HL) 160 x 53 x HL71 US15B<br />

c) Roller latch (TR) 1554 626<br />

d) Strike (TR) 1559B 626<br />

e) Dome stop (RO) 441 US26D<br />

2.5. Guestroom Water Closet Door:<br />

a) Hinges (HA) 1 ½ pr AB 800 4 ½” x 4 ½” US15<br />

b) Privacy lock (HL) 102 x 53 x HL 71 US15<br />

c) Dome stop (RO) 441 US26D<br />

2.6. Guestroom Connecting Door:<br />

a) Hinges (HA) AB 700 4 ½” x 4 ½” US15<br />

b) Passage (one sided) (HL) 100UL x 53 x HL71 US15<br />

c) Deadlock (one sided) (HL) 391 US15<br />

d) Dome stop (RO) 441 US26D<br />

e) Sound seal (DH) Cush n’ Seal White<br />

f) Auto door bottom (PE) 434 ARL x 36”<br />

REV. MARCH 2006 258<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

2.7. Guestroom Closet Door (Single):<br />

a) Hinges (HA) 1 ½ pr AB 800 4 ½” x 4 ½” US15<br />

b) Passage set (HL) 101 x 53 x HL71 US15<br />

c) Dome stop (RO) 441 US26D<br />

2.8. Guestroom Closet Doors (Pair):<br />

a) Hinges (HA) 1 ½ pr AB 800 4 ½” x 4 ½” US15<br />

b) Full dummy trim (HL) 166 x 53 x HL71 US15<br />

c) Roller catch (TR) 1554 626<br />

d) Strike (TR) 1559B 626<br />

e) Dome stop (RO) 441 US26D<br />

2.9. Gold Wing Guestroom Corridor Entry Doors (Pair):<br />

a) Hinges (HA) 2 pr AB800 4 ½” x 4 ½” US10B<br />

b) Power transfer (VO) EPT 2 SP313<br />

c) Exit device (SA) WD 8674 F ETY US10B<br />

d) Exit device (SA) WD 8610 F ETY-DT US10B<br />

e) Mortise cylinder (HL) as required US10B<br />

f) Closer (LC) 2031 STD US10B<br />

g) Wall bumper (RO) 409 US10B<br />

h) Door silencer (RO) 608<br />

i) Power supply (SA) 3550<br />

j) Card reader lockset TimeLox complete US10B<br />

with selected handles<br />

2.10 Gold Lounge Entry Doors (Pair):<br />

a) Sliding door lock (BA) 8595 102 US10B<br />

b) Mortise cylinder (HL) as required US10B<br />

c) Dummy trim (BA) 8571 150 US15<br />

d) Edge pull (IV) 230 B US10B<br />

* Balance of hardware by door manufacturer<br />

REV. MARCH 2006 259<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

2.11 Maids’ Closet, Pantry, Computer Room and Secured Storage Room Doors:<br />

a) Hinges (HA) 1 ½ pr AB 800 4 ½ “ x 4 ½” US10B<br />

b) Card reader lockset TimeLox Complete US10B<br />

with selected handles<br />

c) Closer (NO) 7500 BF 689<br />

d) Kickplate (KP) .050 8” x 34” 630<br />

e) Wall bumper 409 US32D<br />

f) Door silencer (RO) 608<br />

2.12 Janitors’ Closet Doors:<br />

a) Hinges (HA) 1 ½ pr AB 700 4 ½ “ x 4 ½” US10A<br />

b) Storeroom lock (HL) 607 x 53 x HL71<br />

c) Closer (NO) 7500 BF 689<br />

d) Wall bumper (RO) 409 US10B<br />

f) Door silencer (RO) 608<br />

2.13 Guestrooms’ Ice Machine Room Door:<br />

a) Hinges (HA) 1 ½ pr AB 700 4 ½ “ x 4 ½” US10A<br />

b) Passage Set (HL) 601 x 53 x HL71<br />

c) Closer (NO) 7500 BF Plated M/cover 690<br />

613 Plated cover x 613<br />

Plated Soffit<br />

d) Wall bumper (RO) 409 US10B<br />

e) Door silencer (RO) 608<br />

2.14 Hotel Main Entry Doors (Pair):<br />

a) Hinges (HA) 2 pr AB 800 4 ½” x 4 ½” US32D<br />

b) Flush bolts (RO) 555 US26D<br />

c) Door pull (RO) 105 x 70C CC US32D<br />

d) Push plate (RO) 70 C 4 x 16 CC US32D<br />

e) Mortise deadlock (HC) SGL cylinder US26D<br />

REV. MARCH 2006 260<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Hotel Main Entry Doors (Pair) (continued)<br />

f) Closer (NO) 7500 BF 689<br />

g) Kick plate (KP) .050 8” x 34” 630<br />

h) Wall bumper (RO) 409 US32D<br />

i) Door silencer (RO) 608<br />

2.15 Guest Safety Deposit Box Door:<br />

a) Hinges (HA) 2 pr AB 800 4 ½” x 4 ½” US10B<br />

b) Storeroom lock (HL) 607 x 53 x HL71<br />

c) Closer (LC) 2031 BUMP US10B<br />

d) Wall bumper (RO) 409<br />

e) Door silencer (RO) 608<br />

f) Electric strike (HN) 1003 24D 613 KM 613 2005<br />

g) Transformer (HN) 2002 – 24<br />

i) Push button (SA) 4241<br />

* Door normally closed and secured. Access by electric strike at all times<br />

by push button at front desk.<br />

2.16 Public Washroom Entry Door:<br />

a) Hinges (HA) 2 pr AB 800 4 ½” x 4 ½” US10B<br />

b) Passage set (HL) 601 x 53 x HL71<br />

c) Closer (LC) 5031 REG US10B<br />

d) Wall bumper (RO) 409<br />

e) Door silencer (RO) 608<br />

2.17 Public Washroom Stall Door:<br />

a) Spring Hinge (HN) 1 pr 1250 4 ½” x 4 ½” US10A<br />

b) Hinge (HA) ½ pr AB 800 4 ½” x 4 ½” US10B<br />

c) Passage set (HL) 101 x 53 x HL71<br />

d) Indicator deadlock (FL) D871 613<br />

REV. MARCH 2006 261<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Public Washroom Stall Door (continued)<br />

e) Wall bumper (RO) 409 US10B<br />

f) Coat hook (VA) Interior Designer to select US10B<br />

g) Door silencer (RO) 608<br />

2.18 Ballroom and Meeting Room Entry Doors – (Pair with standard exiting devices):<br />

a) Floor closers (DM) BTS 80 EMB/F 613E<br />

b) Pivots (DM) 75233 613<br />

c) Power transfer (VO) EPT2 SP313<br />

d) Exit devices (SA) 12 56 WD 8610 F113 less pull US10B<br />

e) Mortise cylinder as required<br />

f) Decorative pulls Interior designer to select<br />

g) Sound seal (DH) Cush n’ seal White<br />

h) Power supply (SA) 3530<br />

i) Key switch (SA) 4374<br />

* Doors normally closed and secured. Access by key at all times. Egress free at<br />

all times. When power is turned on by key switch, doors may be held in open<br />

position by floor closer. Power on by second key switch holds exit device<br />

latches retracted, allowing doors to be “push/pull”. Fire alarm condition cuts<br />

power allowing doors to close and latch.<br />

2.20 Ballroom and Meeting Room Service Doors (Pair):<br />

a) Floor closer (DM) BTS 80 EMB/F 613E<br />

b) Pivot (DM) 75233 613E<br />

c) Power transfer (VO) EPT 2 SP313<br />

d) Exit device (SA) 12 56 8810 G US10B<br />

e) Wall bumper (RO) 409 US10B<br />

f) Sound seal (DH) Cush n’ Seal White<br />

g) Power supply (SA) 3530<br />

h) Key switch (SA) 4370<br />

REV. MARCH 2006 262<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Ballroom and Meeting Room Service Doors (Pair) (continued)<br />

* Door normally closed and secured. Access by key at all times. Egress free at all<br />

times. When power is turned on by key switch, doors may be held in open<br />

position by floor closer. Power on by second key snitch holds exit device<br />

latches retracted, allowing doors to by “push/pull”. Fire alarm condition cuts<br />

power allowing doors to close and latch.<br />

2.21 Security Office (Dutch) Door:<br />

a) Hinges (HA) 2 pr AB 800 4 ½” x 4 ½” US32D<br />

b) Card reader lockset TimeLox with selected handles<br />

c) Flush boldt (RO) 640 US26D<br />

d) Closer (NO) 7500 H 689<br />

e) Kick plate (KP) .050 8” x 34” 630<br />

f) Wall bumper (RO) 509 US32D<br />

g) Door silencers 608<br />

* Meeting rail to be rabbeted by door manufacturer.<br />

2.22 Head Cashier’s Office Door:<br />

a) Hinges (HA) 2 pr AB 800 4 ½” x 4 ½” US32D<br />

b) Card reader lockset TimeLox with selected handles US26D<br />

c) Flush bolt (RO) 640 US26D<br />

d) Overhead holder (AB) 4014 US26D<br />

e) Wall bumper (RO) 409 US32D<br />

f) Door silencer (RO) 608<br />

2.23 Back-of-House Office Doors:<br />

a) Hinges (HA) 1 ½ pr AB800 4 ½” x 4 ½” US32D<br />

b) Office Lock (HL) 604 x 51 x HL59 US26D<br />

c) Closer (NO) 7500 BF 689<br />

d) Wall bumper (RO) 409 US32D<br />

e) Door silencer (RO) 608<br />

REV. MARCH 2006 263<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

2.24 Housekeeping Office (Dutch) Door:<br />

a) Hinges (HA) 2 pr AB 800 4 ½” x 4 ½” US32D<br />

b) Office lock (HL) 604 x 51 x HL59 US26D<br />

c) UL Deadlatch (HL) 399 2-3\4” BS US26D<br />

d) Closer (NO) 7500 BF 689<br />

e) Kick plate (KP) .050 8” x 34” 630<br />

f) Wall bumper (RO) 409 US32D<br />

g) Magnetic holder (AB) 2210 12 VA/DC, 24 VAC/DC 52<br />

h) Door silencer (RO) 608<br />

* Door normally closed and secured. Upper leaf may be held open by wall<br />

magnet. Fire alarm condition releases the magnet allowing upper leaf to close<br />

and latch. Astragal at meeting rail assures top and bottom leafs close.<br />

2.25 Staff Main Entry Door:<br />

a) Hinges (HA) 1 ½ pr AB 800 4 ½” x 4 ½” NRP US32D<br />

b) Power transfer (Vo) EPT2 SP2B<br />

c) Exit device (SA) 12 8876 F ETL US32D<br />

d) Mortise cylinder (HL) As required<br />

e) Closer (NO) 7500 BF 689<br />

f) Wall bumper (RO) 409 US32D<br />

g) Power supply (SA) 3530<br />

h) Push button (SA) 4241 US32D<br />

* Door normally closed and secured. Push button in security office releases trim on exit<br />

device allowing access. Egress free at all times.<br />

2.26 Staff Change Room Entry Door:<br />

a) Hinges (HA) 1 ½ pr AB 800 4 ½” x 4 ½” US32D<br />

b) Passage set (HL) 601 x 51 x HL59 US26D<br />

c) Closer (NO) 7500 BF 689<br />

d) Kick plate (KP) .050 8” x 34” 630<br />

e) Mop plate (KP) .050 4” x 34” 630<br />

f) Wall bumper (RO) 409 US32D<br />

g) Door silencer (RO) 608<br />

REV. MARCH 2006 264<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

2.27 Kitchen Entry (off Service corridor) Doors:<br />

a) Hinges (HA) 1 ½ pr AB 850 5” x 4 ½” US32D<br />

b) Office lock (HL) 604 x 51 x HL59 US26D<br />

c) Closer (NO) 7500 BF 689<br />

d) Kick plate (KP) .050 8” x 46” 630<br />

e) Mop plate (KP) .050 4” x 46” 630<br />

f) Wall bumper (RO) 409 US32D<br />

g) Door silencers (RO) 608<br />

h) Trim protector bar (RO) R115LPS US32D<br />

2.28 Flower Shop Door:<br />

a) Hinges (HA) 1 ½ pr AB 800 4 ½” x 4 ½” US32D<br />

b) Storeroom lock (HL) 607 x 51 x HL59 US26D<br />

c) Closer (NO) 7500 BF 689<br />

d) Kick plates .050 8” x 34” 630<br />

e) Wall bumper (RO) 409 US32D<br />

f) Droor silencer (RO) 608<br />

g) Trim protector bar (RO) R115LPB US32D<br />

2.29 Health Club and Spa Treatment Entry Door:<br />

a) Hinges (HA) 2 pr AB 4 ½” x 4 ½” US10B<br />

b) Lockset (AD) MS 1850A 313<br />

c) Mortise cylinder as required<br />

d) Mortise T- turn as required<br />

e) Decorative pull Interior designer to select<br />

f) Closer (LC) 2033 BUMP US10B<br />

g) Threshold (PE) 2005 BV x 36<br />

REV. MARCH 2006 265<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

2.30 Maintenance Entry Doors (Pair):<br />

a) Hinges (HA) 1 ½ pr AB 850 5” x 4 ½” US32D<br />

b) Flush bolts (RO) 555 US26D<br />

c) Door pull (RO) 105 x 70C CC US32D<br />

d) Push plates (RO) 70C 4 x 16 CC US32D<br />

e) Mortise deadlock (HL) SGL cylinder US26D<br />

f) Closer (NO) 7500 BF 689<br />

g) Kick plate (KP) .050 8” x 34” 630<br />

h) Wall bumper (RO) 409 US32D<br />

i) Door silencer (RO) 608<br />

2.31 Mechanical and Electrical Entry Doors (Pair):<br />

a) Hinges (HA) 1 ½ pr AB 800 4 ½” x 4 ½” US32D<br />

b) Flush bolt (RO) 555 US26D<br />

c) Dust proof strike (RO) 570 US26D<br />

d) Storeroom rack (HL) 607 x 51 x HL59 US26D<br />

e) Closer (NO) 7500 BF (active leaf only) 689<br />

f) Kick plates (KP) .050 8” x 34” 630<br />

g) Wall bumper (RO) 409 US32D<br />

h) Door silencer (RO) 608<br />

REV. MARCH 2006 266<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

3. MECHANICAL QUESTIONNAIRE<br />

YES<br />

NO<br />

<strong>DESIGN</strong> CRITERIA<br />

Does the design criteria meet FHR’s Standards, ASHRAE 62-1989 and<br />

ASHRAE 55-1992?<br />

Do the outdoor design dry bulb and wet bulb temperatures meet or exceed<br />

the greater of the ASHRAE fundamentals handbook or local climactic<br />

data?<br />

Have all public spaces been based on ASHRAE 62-1989 and ASHRAE<br />

55-1992 occupancy rates for load calculation purposes? (The furniture<br />

layout shall not be used to establish occupancy as it may change).<br />

Have all areas except mechanical plant rooms been air-conditioned?<br />

Are the lighting and equipment loads consistent with the interior<br />

designer/lighting consultant drawings?<br />

Does the suite occupancy rate for the living/dining areas reflect those listed<br />

in FHR Standards, i.e. Special suite living/dining, two-bedroom suite<br />

living/dining, and one bedroom suite living/dining?<br />

Does the noise criteria meet FHR Standards?<br />

Have meeting rooms greater than 650 ft 2 been treated as a place of<br />

assembly (as indicated in ASHRAE 62-1989 and summarized in Appendix<br />

“A”) in lieu of standard meeting rooms?<br />

MAIN SYSTEMS<br />

Air Handling Systems/Air Conditioning Systems<br />

General<br />

Are air handling units located relatively close to the areas they serve?<br />

Is the air handing unit casing construction not less than No. 18 gauge hot<br />

rolled sheet steel?<br />

Have return fans been provided to allow for free cooling and appropriate<br />

pressurization?<br />

Are the air-handling units equipped with economizers, so that free cooling<br />

may be utilized? (Providing the local climate warrants).<br />

Have silencers been provided for supply and return ductwork to all air<br />

handling units?<br />

When the ceiling is used as a return air plenum, have the return ductwork<br />

been extended to within 150 ft of the furthest return air grille?<br />

Have stack effect issues in high-rise projects been addressed appropriately?<br />

Have mechanical devices such as VAV boxes, drainage cleanouts and<br />

isolation valves been provided with access, which have been carefully<br />

coordinated with the interior designer?<br />

Has adequate maintenance access been provided for air handling unit<br />

servicing?<br />

REV. MARCH 2006 267<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

In humid climates, has dehumidification been provided?<br />

Have the cooling load calculations been performed for each room? Are<br />

adequate and reasonable air quantities provided?<br />

Does each air-handling unit have high efficiency filters and prefilters?<br />

Public Space<br />

Do the ballroom, prefunction and banquet rooms each have independent<br />

systems? Has zoning to suit moveable partitions been provided?<br />

Do the ballroom, prefunction or banquet room areas have dedicated zones?<br />

Does each restaurant have a dedicated constant volume system?<br />

Are there any private dining areas within the restaurant?<br />

If yes, have measures been provided for independent temperature control?<br />

Does the lobby have a dedicated VAV system?<br />

In cold climates, has the main entrance vestibule been provided with<br />

heating?<br />

Does the bar have its own zone controls?<br />

Are administration offices provided with a VAV system?<br />

Has a VAV system been provided for each meeting room?<br />

Does the health club and spa have a dedicated VAV system?<br />

Has special attention been given to health club and exercise equipment<br />

loads and carefully reviewed with the interior designer? (see Appendix C,<br />

for preliminary lighting and power load estimates)<br />

Has individual temperature control been provided for areas, which may<br />

have a varying usage profile or exposure?<br />

Does the location of thermostats suit the interior designer and furniture<br />

layouts?<br />

Have all the public washrooms been provided with air conditioning in<br />

addition to exhaust?<br />

Has an exhaust grille been provided for each full-height toilet stall in the<br />

public washrooms?<br />

Has the indoor swimming pool been provided with a dedicated system<br />

complete with dehumidification?<br />

Is the indoor swimming pool ductwork constructed of aluminum?<br />

Has a cut sheet of the thermostat and/or sensor cover been reviewed by<br />

FHR and the interior designer? And approved by them? Has the Interior<br />

Designer signed off on thermostat locations for public spaces?<br />

Have linear diffusers in public space areas been coordinated with the<br />

interior designer?<br />

Back-of-House<br />

Have individual temperature controls been provided for areas which may<br />

have varying usage profiles or exposures?<br />

Does the banquet kitchen have a dedicated make-up air system?<br />

Do the kitchen exhaust hoods have dedicated make-up air system?<br />

Do the back-of-house areas have dedicated VAV systems?<br />

YES<br />

NO<br />

REV. MARCH 2006 268<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Has spot cooling been provided for hot spot areas i.e. laundry area, chef’s<br />

office and valet?<br />

Does the computer room have an independent air conditioning unit?<br />

Is the computer room unit on emergency power?<br />

Has a dedicated/independent air conditioning unit on emergency power<br />

been provided for the PABX room?<br />

Is the garbage room refrigerated?<br />

Is the bakery chocolate room refrigerated?<br />

Has the grease room been provided with a separate exhaust system?<br />

Is a paint booth required?<br />

Hot Water Plant<br />

What is the redundancy factor for the hot water boilers?<br />

When sizing the boilers, has only a partial credit been taken for all air-toair<br />

heat reclaim systems (if applicable)?<br />

Have the internal gains from lighting, power and people used to reduce the<br />

size of the boiler plant? (They should not be).<br />

Is there one hot water pump for each boiler?<br />

Is primary/secondary pumping being utilized?<br />

Have energy-conserving features such as variable speed pumping been<br />

utilized?<br />

Refrigeration Plant<br />

What are the chiller redundancy factors?<br />

Does each chiller have a condenser water pump?<br />

Is the location of the source of condenser water, i.e. cooling tower, dry<br />

coolers etc. located so that the noise generated by this equipment will not<br />

be objectionable to the occupants of the hotel?<br />

Is the refrigerant environmentally friendly, i.e. is R-134a or R-123 being<br />

used?<br />

Has hydronic winter free cooling, utilizing a winterized cooling tower,<br />

been provided to avoid operating the chiller during the winter months?<br />

(Note that this applies to climates with cooler winters).<br />

Have refrigerant leak detectors and a leak evacuation/exhaust system been<br />

provided for in the chiller room?<br />

Have dedicated pumping systems been provided for all hotel suite fan coil<br />

units, air handling units, or any equipment which requires year-round<br />

cooling?<br />

Is chilled water available for year-round cooling?<br />

Has the capacity of the plant been confirmed, i.e. have block load<br />

calculations been performed and reviewed?<br />

Have energy-conserving features such as variable speed pumping been<br />

utilized?<br />

Has chilled or condenser water been provided for the ice machines on the<br />

guest floor?<br />

YES<br />

NO<br />

REV. MARCH 2006 269<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Plumbing<br />

Does the domestic hot water load for the suites reflect the following:<br />

10 gal. - storage per bedroom<br />

15 gal. - recovery rate per bedroom<br />

Has additional domestic hot water tanks been provided for the Laundry,<br />

Kitchen, Suites and Public space areas respectively?<br />

Do the temperatures for domestic hot water correspond to the following:<br />

120 F - for bedrooms, public areas<br />

140 F - for kitchens<br />

160 F - for laundry<br />

Has cold water storage been provided where the water source is unreliable<br />

or required by local authorities?<br />

Has adequate water softening been provided?<br />

Has adequate water treatment been provided as required by world health<br />

organization standards?<br />

Has the domestic hot water system been provided with a recirculation<br />

system to maintain temperature throughout the system during low usage<br />

periods?<br />

Have dedicated isolation valves for DHW and DCW been provided within<br />

each hotel suite for the respective suite?<br />

Do the types of plumbing fixtures conform to the FHR Standards?<br />

Have lavatories and water closets been provided as indicated in FHR’s<br />

Standards?<br />

Have steeping bathtubs been provided in each of the guestrooms?<br />

Have showerheads been provided with a minimum flow rate of 5 USGPM?<br />

Have pressure balancing mixing valves been provided for showers?<br />

Is the water pressure provided in each hotel suite as required by the<br />

showerhead manufacturer?<br />

Have DCW and drainage piping been provided for ice machines?<br />

Has the can wash equipment been specified?<br />

Is the drainage piping for the hotel guestrooms cast iron?<br />

Has at least one drain been provided for each public or back-of-house<br />

washroom area?<br />

Has the maintenance work shop and the paint shop areas each been<br />

provided with a sink?<br />

Has the loading dock and porte cochere been provided with a hose bibb to<br />

serve a power spray wash?<br />

Hotel Guestrooms<br />

Are the fan coil units serving the guest suites capable of three-speed<br />

operation and temperature control as per FHR’s Standards?<br />

Are the fan coil unit sizes for guest suites based on medium speed, with<br />

NC levels of 35 for daytime operation, and low speed, with NC levels of<br />

30 for nighttime operation? (High speed must be provided for quick cool<br />

down)<br />

YES<br />

NO<br />

REV. MARCH 2006 270<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Is the sizing of the hotel suite fan coil units in accordance with FHR’s<br />

Standards?<br />

Has a return air grille complete with filter been provided for each hotel fan<br />

coil unit?<br />

Has acoustic lining been provided on the discharge ductwork of all hotel<br />

fan coil units?<br />

Has a reverse return piping arrangement for the hotel suite fan coil units<br />

for chilled and hot water distribution been provided? (This will reduce<br />

noise at automatic control valves particularly in high-rise buildings).<br />

Have access doors been provided for all fan coil units located within the<br />

hotel guestrooms and coordinated with the interior designer?<br />

Do the fan coil units for the hotel guestrooms meet FHR’s Standards, in<br />

terms of control and construction?<br />

Have the access doors for isolation valves been carefully coordinated with<br />

the interior designer to ensure the access is not visible, i.e. behind wall<br />

picture or under counter?<br />

Have dedicated isolation valves for heating water supply and return and<br />

chilled water supply and return been provided within each suite for each<br />

respective FCU?<br />

Are the hotel guestroom floors maintained under positive pressure relative<br />

to the suites?<br />

Are the guestrooms maintained under a positive pressure relative to the<br />

outdoors?<br />

Is the quantity of exhaust air in the guestroom bedroom equal to or larger<br />

than 70 CFM?<br />

Do each of the guestrooms have a minimum of two (2) exhaust grilles (one<br />

exhaust grille for the shower and one for the water closet)?<br />

Have all pantries been provided with sinks and kitchen appliances with<br />

appropriate exhaust?<br />

Is the make-up air supplying both the hotel guestroom and the corridor?<br />

If yes, are reheat coils and smoke d<strong>amp</strong>ers provided on the main branch<br />

ductwork so that the appropriate temperature and humidity can be<br />

maintained?<br />

Is the make-up air supplying the guestrooms and corridors dehumidified?<br />

Has the make-up air to the hotel guestrooms been provided to the ceiling<br />

space vestibule?<br />

Is the air quantity serving the corridor capable of handling the loads in the<br />

corridor?<br />

In cold climate conditions, have washrooms located on exterior walls or<br />

windows been provided with heating?<br />

Is the location of the double adjustable supply air diffuser within the hotel<br />

guestrooms been located such that the supply air stream is away from the<br />

bed?<br />

YES<br />

NO<br />

REV. MARCH 2006 271<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Fire Protection<br />

Are the sprinkler heads for public spaces the concealed type?<br />

Have hose bibs been provided in all washrooms (typically located beneath<br />

the counter out of sight)?<br />

Have sprinklers been installed throughout the building?<br />

Has the building been provided with a stand pipe system?<br />

For fire protection, are FHR standards and National Fire Protection<br />

Agency North American code being followed?<br />

Has fire protection water storage, which is non-depletable from the DCW<br />

system, been provided if the region has an unreliable water source or is<br />

required by the local authorities?<br />

Laundry Area<br />

Are steam boilers being provided to serve the laundry area?<br />

Are the steam boilers serving the laundry sized for 100% stand-by?<br />

Do the steam pressures suit the pressures given for the laundry equipment<br />

(multiple pressures are required for different equipment)?<br />

Are barometric d<strong>amp</strong>ers utilized for laundry exhaust? If not, how is partial<br />

load operation being handled?<br />

Has a dedicated make-up air system been provided for the laundry area?<br />

Is the laundry make-up air system complete with cooling in order to<br />

maintain design conditions?<br />

Have the dryers been provided with lint filters prior to connecting to the<br />

laundry exhaust system? (Lint filters should be located as close to the<br />

source of lint as possible).<br />

Has compressed air been provided for the laundry equipment?<br />

Does the laundry exhaust terminate upblast at high levels, away from the<br />

air intakes?<br />

Has the laundry been provided with a trench drain complete with a lint<br />

screen?<br />

Has the type of ductwork provided for the laundry in accordance with<br />

FHR’s Standards?<br />

Kitchen<br />

Are all kitchen areas maintained under a negative pressure (to ensure there<br />

is no odor migration to other areas)?<br />

Does the kitchen have an independent, water-cooled refrigeration system<br />

for all refrigerators, freezers and cold rooms?<br />

Has a separate exhaust system been provided for the dishwasher?<br />

Has the type of ductwork provided for the kitchen in accordance with<br />

FHR’s Standards?<br />

Does kitchen exhaust terminate at high level away from intakes in lieu of<br />

ecology units? (Requires ductwork extending up through the building).<br />

Are grease traps provided for kitchens as required with floor access in an<br />

appropriate location for ease of maintenance?<br />

YES<br />

NO<br />

REV. MARCH 2006 272<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Is the kitchen make-up air system complete with cooling in order to<br />

maintain design conditions?<br />

Miscellaneous<br />

Has electric tracing been provided on pipe work in areas where there is no<br />

heating and has the potential of freezing?<br />

Have the steam rooms within the fitness center been provided with<br />

dedicated stand-alone steam generators?<br />

Do the pipes and ducts have insulation?<br />

Has a building management system utilizing DDC complete with computer<br />

graphic workstation been provided? (Workstations to be located in the<br />

assistant chief engineer’s office).<br />

Has an outlet, connected to the building management system, been<br />

provided within the maintenance workshop for access to the service and<br />

maintenance computer program?<br />

Has a modem for offsite connection been provided to DDC?<br />

Are spare parts adequately specified?<br />

If a parking area exists below grade, has mechanical ventilation been<br />

provided?<br />

If a parking area exists, are the exhaust fans controlled by CO/Nox<br />

detectors?<br />

Has mechanical ventilation been provided to the golf club parking areas (if<br />

covered)?<br />

YES<br />

NO<br />

REV. MARCH 2006 273<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

TYPICAL OCCUPANCY REQUIREMENTS & LIGHTING/EQUIPMENT LOAD<br />

ESTIMATES<br />

Areas Serviced<br />

Recommended Load<br />

Occupancy Lighting/Equipment Notes<br />

Range<br />

Bedrooms 2P 1250 w Refer to (A)<br />

Restaurant 1P/15 ft 2 45-65 w/10 ft 2<br />

Banquet Hall 1 P/9 ft 2 108-135 w/10 ft 2<br />

Bar 1 P/11 ft 2 30-55 w/10 ft 2<br />

Meeting Rooms < 700 ft 2 1 P/22 ft 2 55-75 w/10 ft 2<br />

Meeting Rooms > 700 ft 2 1 P/11 ft 2<br />

Shops 1 P/55 ft 2 30-55 w/10 ft 2<br />

Offices 1 P/110 ft 2 30-55 w/10 ft 2 Refer to (B)<br />

Lobby 1 P/38 ft 2 55-65 w/10 ft 2<br />

Reception Hall 1 P/18 ft 2 55-65 w/10 ft 2<br />

Spa/Fitness Center 1 P/55 ft 2 30-55 w/10 ft 2 Refer to (C)<br />

Computer Center<br />

Review with FHR<br />

Autocom<br />

Review with FHR<br />

Personal Dining Room 1 P/15 ft 2 30-55 w/10 ft 2<br />

Note:<br />

A) The following occupancy rates should be followed for the areas listed below:<br />

• Presidential Suites living/dining area: 15 - 20 ft 2 per person<br />

• Two bedroom suite living/dining area: 15 - 20 ft 2 per person<br />

• One bedroom suite living/dining area: 4 persons<br />

The preliminary lighting and power load estimate used in corridor areas typically range between<br />

35 – 45 w/10 ft 2 .<br />

B) The lighting and power loads in office areas typically range between 30-55<br />

w/10 ft 2 for lighting with electronic ballasts and 55-75 w/10 ft 2 for lighting with standard<br />

ballasts.<br />

C) The cooling load for Fitness Center exercise rooms should be calculated based on a fully<br />

occupied room with guests doing a vigorous workout. The Spa and Fitness Center lighting and<br />

power loads should range between 30-55 w/10 ft 2 . However, for the exercise rooms located<br />

within the Fitness Center, lighting and power loads typically range between 100-160 w/10 ft 2 .<br />

This is primarily due to the heat generated from the number of exercise machines located in<br />

these rooms.<br />

D) The activity level for each person is a function of the usage for the specific area served. A<br />

substantially greater quantity of heat is dissipated in activities like dancing or exercising as<br />

opposed to sedentary type of activities. ASHRAE Standard 55-1992 should be followed.<br />

REV. MARCH 2006 274<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

4. ELECTRICAL QUESTIONNAIRE<br />

YES<br />

NO<br />

<strong>DESIGN</strong> CRITERIA AND GENERAL REQUIREMENTS<br />

Will the power distribution design follow North American Standards<br />

Will the design of the fire alarm system be based on North American NFPA<br />

Standards?<br />

Are illumination levels based on FHR’s Standards?<br />

SYSTEMS<br />

Dimming System<br />

Has an electronic, solid state dimming system been specified for the control<br />

of all public and circulation areas?<br />

Confirm the following controls:<br />

• Pre-sets in main lobby, restaurants, dining rooms and<br />

entertainment rooms?<br />

• Local controls in “control niches” with capability of “combining<br />

rooms” in meeting rooms and ballrooms?<br />

• Two-way cleaning switch in ballrooms and meeting rooms?<br />

Has emergency lighting been integrated with the dimming system?<br />

Have dimming schedules complete with lighting control zones been<br />

prepared?<br />

Is there an interconnection to the dimming system to raise levels of dimmed<br />

controls if a fire alarm signal is activated?<br />

Background Music and Local Sound Reinforcement<br />

Confirm the following arrangement of background music systems:<br />

• Main background music rack with 2 x 10 CD player for<br />

circulation spaces such as:<br />

- lobby<br />

- public corridors<br />

- public washrooms<br />

- spa/fitness center/pool<br />

- staff dining<br />

• Does each area served by the main sound rack have individual<br />

volume controls?<br />

Have local sound reinforcement systems with interconnection back to main<br />

(circulation area) rack been provided for:<br />

• Each restaurant, lounge or bar (10 CD player)?<br />

• Each meeting room (no CD player)?<br />

• Each ballroom (2 x 5 CD player)?<br />

Are there provisions for “combining” sound systems for interconnected<br />

meeting rooms and ballrooms?<br />

Is there a portable, wireless, integrated lighting and volume control for each<br />

ballroom for lectern or tabletop use?<br />

REV. MARCH 2006 275<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Have audio inputs and microphone jacks been provided in baseboard “AV”<br />

units in meeting rooms, ballrooms and prefunction areas?<br />

Are there residential sound systems for the Two-Bedroom and Presidential<br />

Suites?<br />

Confirm that residential built-in individual stereos are to be provided in<br />

FF&E.<br />

Is there an interconnection to the sound systems to override the music if a<br />

fire alarm signal is initiated?<br />

Fire Alarm System<br />

Has a two-stage fire alarm system with emergency voice communication<br />

provisions been provided?<br />

Is the fire alarm system sequence of operation based on the “floor<br />

above/alarm floor/floor below” evacuation with an alert signal elsewhere?<br />

Confirm that the system automatically goes into evacuation mode if not<br />

responded to within a predetermined period of time?<br />

Confirm that fire alarm system smoke detectors have been provided<br />

throughout the hotel (i.e. everywhere except where false alarms are possible<br />

such as laundry, kitchen, etc.).<br />

Is the fire alarm system based on analog addressable devices or hardwired<br />

type? (Analog addressable is preferred).<br />

Confirm that guestroom smoke detectors have local audible alarm only with<br />

central annunciation. Smoke detector to be identified at central panel.<br />

Is there remote fire alarm annunciation in the telephone operator’s room and<br />

main security office? Where is location of main annunciator?<br />

If background music speakers are used for life safety, then ensure that<br />

cabling is suitable for a fire alarm system.<br />

In a high rise building, have the following smoke control provisions been<br />

provided:<br />

• Individual fan control switches at main fire alarm control<br />

location?<br />

• Automatic start of pressurization fans and smoke exhaust fans?<br />

• Smoke control and smoke venting fans fed from emergency<br />

power?<br />

Have fire fighter’s handsets been provided or are they not recognized or<br />

used by the local Fire Department?<br />

Are special requirements necessary for the physically challenged?<br />

Structured Cabling System for Voice and Data Communication<br />

Systems<br />

Has a structured cabling system been provided based on Category 5E<br />

cabling for voice and data?<br />

Confirm that the basic distribution is a “star” originating from the computer<br />

room for data and telephone equipment room for voice.<br />

YES<br />

NO<br />

REV. MARCH 2006 276<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Have “Intermediate Distribution Frames” (IDF’s) been provided in the<br />

following location:<br />

• Administration<br />

• Ballroom/Meeting Rooms<br />

• Typical guestroom floor (not required on each floor)<br />

Has the maximum distance requirement of 295 ft from each LAN room to<br />

outlet been maintained?<br />

If the building is very large or a high rise, does the distance between LAN<br />

Rooms and main computer room and telephone room exceed 295 ft, such<br />

that a fiber optic backbone is required?<br />

Confirm that the quad faceplate outlets for administration have 1 x 4 pair<br />

Category 5E (voice) with two pair punched down on each RJ11C and 2 x 5<br />

pair Category 5E (date) cables.<br />

Confirm that the two double outlet faceplates for the guestrooms have<br />

1 x 4 pair Category 5E (voice) with two pair punched down on each RJ11C<br />

and 2 x 4 pair Category 5E (data) cables.<br />

Confirm that a fax patch panel has been provided in the telephone operators<br />

room.<br />

Have P.O. S. power and data outlet locations been coordinated with the<br />

Food Service consultant and Interior Designer?<br />

Telephone Systems<br />

Verify that the telephone switch and handsets are provided in the general<br />

contract based on FHR Specifications.<br />

Card Access and Door Alarm Security System<br />

The preferred method for card access control is to integrate door alarm<br />

points and hardwired card reader locations into the “Time Lox” or<br />

equivalent electronic door locking system.<br />

Card readers controlling electric strikes along with door alarm contacts to<br />

monitor forced entry are required at the following locations:<br />

• Staff entry (with remote release from security office, door alarm<br />

contacts may be deleted).<br />

• Access doors from parking garage into back-of-house corridors<br />

for frequent use by employees.<br />

Access doors from the loading dock into back-of-house service corridor.<br />

• Access door into valet cashier’s room (if direct access from<br />

exterior).<br />

• Any other secure location which has access from an unsecured<br />

area and where employees require frequent access (i.e., silver<br />

storage, liquor storage, etc.).<br />

Have magnetic door alarm contacts been provided at unsupervised exterior<br />

perimeter doors?<br />

YES<br />

NO<br />

REV. MARCH 2006 277<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Have Category 5E data cable rough-in provisions for electronic card key<br />

encoding equipment been provided at the following locations?<br />

• Front desk<br />

• Security office<br />

• Concierge desk<br />

Pushbutton Alarm and Assistance Systems<br />

Have the following systems been provided?<br />

• VIP arrival system consisting of pushbutton at front desk (1) and<br />

each doorman’s stand with a buzzer annunciation in general<br />

manager’s office. (Number of pushbuttons varies depending on<br />

length of desk and number of workstations).<br />

• Help/Assistance request buttons at each front desk registration<br />

location and at the front desk cashier location (if separate) with a<br />

blue flashing light in the front office manager’s office.<br />

• Doorman’s Help/Assistance request buttons at each doorman’s<br />

stand with a buzzer annunciation at the concierge desk.<br />

• Concierge Help/Assistance system with button at concierge desk<br />

and a buzzer in the concierge work room.<br />

• Alarm pushbuttons at:<br />

- front desk cashier’s locations<br />

- main cashier’s office<br />

- staff safety deposit box room<br />

- valet or parking cashier’s room<br />

with separate flashing red lights in the telephone operator’s<br />

room.<br />

• Guest Safety Deposit Security System consisting of:<br />

- pushbutton inside guest safety deposit box viewing room<br />

with a buzzer to front registration desk<br />

- electric strike controlled from front registration desk for<br />

guest access.<br />

• Cashier’s VCR Activation System consisting of a pushbutton in<br />

the cashier’s office to start the VCR connected to the CCTV<br />

camera automatically for one (1) hour<br />

• Sauna Emergency System consisting of pushbuttons inside or<br />

outside steam and sauna rooms with buzzers in Health Club<br />

Reception Desk. (The pushbutton systems shall be<br />

interconnected to the buzzer via a latching panel which sends a<br />

signal to a flashing light in the telephone operator’s room if the<br />

alarm is not responded to within 30 seconds).<br />

YES<br />

NO<br />

REV. MARCH 2006 278<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Closed Circuit TV and Audio Monitoring System<br />

Since there are numerous cameras providing output signals to TV monitors<br />

in a variety of locations, a matrix switching arrangement provides the<br />

optimum solution. Has a microprocessor based matrix switcher been<br />

provided for the CCTV system?<br />

Have the following minimum quantity of cameras been provided?<br />

• Swimming pool (with two-way loudspeaker)<br />

• Staff entrance (with intercom)<br />

• Main lobby (pinhole type, no loudspeaker)<br />

• Front desk (pinhole type, no loudspeaker)<br />

• Cashier’s office (pinhole type, no loudspeaker)<br />

• Guest safety deposit box room – staff side (no loudspeaker)<br />

• Loading dock (outdoor type, with two-way loudspeaker)<br />

• Health Club exercise room (with two-way loudspeaker)<br />

• Underground parking areas (as applicable)<br />

Have the following color TV monitors been provided?<br />

• Approximately 4-5 monitors in both the security office and<br />

telephone operator’s room in sequential switching mode for<br />

entire system (i.e. one monitor for 4 cameras).<br />

• One (1) holding monitor in security office to view any one<br />

selected camera on full-time basis.<br />

• Duplicate monitor and switcher for Health Club exercise room<br />

and pool in health club desk.<br />

Have time lapse VCR’s (both recording and playback) been provided in the<br />

security office along with a separate VCR for the cashier’s office?<br />

Has an audio monitoring system complete with microphone control at the<br />

security desk been provided?<br />

Has a remote microphone and speaker been provided in the Health Club and<br />

Spa Reception desk for the pool area CCTV camera?<br />

Intercom System<br />

Has a “room service intercom’ system between the room service office and<br />

set-up area been provided (additional intercom to kitchen hot line if line not<br />

visible)?<br />

Has a “loading dock intercom” system between the receiving office and<br />

loading dock entrance door been provided?<br />

Has a “staff entrance intercom” system between the security office and staff<br />

entrance been provided?<br />

Television System<br />

Either an underground cable television system or satellite/terrestrial antenna<br />

system may be used to provided television signals for the hotel<br />

Channel selection shall include the minimum of:<br />

YES<br />

NO<br />

REV. MARCH 2006 279<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

• Local channels<br />

•<br />

• English speaking channel (NBC)<br />

• CNN<br />

• Movie channel<br />

• In-house safety movie<br />

Have TV outlets been located in the following locations:<br />

• All guest bedrooms and living rooms<br />

• All public area bars and entertainment rooms<br />

• Staff dining<br />

• Ballrooms and meeting rooms in the “AV” baseboard provision<br />

• Health Club exercise room adjacent to each piece of equipment<br />

• Staff boardroom and training room<br />

• In TV storage room and TV repair area<br />

Miscellaneous Communication Systems<br />

Have the following communication systems been provided under the<br />

general contract?<br />

• Portable handheld radios including repeater station, microphone<br />

control console and transmission line. (Approximate quantity of<br />

11 for city hotels and 20 for resorts).<br />

• Portable pagers including transmitter, base station and<br />

transmission line. (Approximate quantity of 20 keynote and 10<br />

Bravo for city hotels; 32 keynote and 15 Bravo for resorts).<br />

• Wireless remote sound system for the hearing impaired in the<br />

large ballroom as per Local Code requirements.<br />

Power Distribution System and Electric Service<br />

The power distribution system design shall comply with the applicable<br />

Local Code, however, the following minimum requirements should be<br />

provided:<br />

• Two (2) main power transformers with secondary switchboard<br />

interconnections with a tie breaker. Ideal design is each<br />

transformer loaded 50% with full redundancy, however, 66%<br />

loading with generator in the event of transformer failure is<br />

acceptable. 100% loading of transformers is acceptable only if<br />

transformers are utility-owned with rapid replacement in the<br />

event of failure.<br />

• Power factor correction capacitors for main switchboard.<br />

• Distribution panels and motor control centers located adjacent to<br />

large loads such as kitchens, laundry, function rooms,<br />

mechanical plant, etc.<br />

• Separate automatic transfer switch for fire pumps as per North<br />

American Standards.<br />

YES<br />

NO<br />

REV. MARCH 2006 280<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

• Separate automatic transfer switch for firefighter’s elevator in<br />

high-rise buildings.<br />

• One-hour fire rated conductors (MICC) for life-safety equipment<br />

in high-rise buildings.<br />

• Reduced voltage starters shall be provided for motors 20 HP and<br />

larger unless local codes are more stringent.<br />

• Total voltage drop from electric service to final branch outlet<br />

device shall be 5% or 4% to suit local code.<br />

Is there redundancy in the number of high voltage services serving the main<br />

substation (i.e. more than one)? Two services in a looped configuration is<br />

recommended.<br />

Emergency Power<br />

Is the emergency power generator serving essential equipment?<br />

For high-rise hotels, is the emergency generator suitably sized with capacity<br />

to service the smoke-control and smoke-venting fans?<br />

In resort areas or areas where power outages are frequent or longer than<br />

four (4) hours, has emergency power been extended into guestrooms and<br />

other important areas?<br />

In third world countries or other locations where power is very unreliable,<br />

have provisions been made for 100% emergency power?<br />

Does the emergency generator room layout and design include acoustic<br />

plenums and silencers on the intake and exhaust to limit noise to adjacent<br />

properties?<br />

Lighting Systems<br />

Depending on the project, lighting system equipment is generally divided<br />

into the following responsibilities:<br />

• Back-of-house utility lighting specified by the electrical<br />

engineer, supplied and installed by the electrical contractor.<br />

• Front-of-house lighting (such as downlights) specified by the<br />

electrical engineer, supplied and installed by the electrical<br />

contractor.<br />

• Decorative and architectural grade front-of-house lighting<br />

specified by the interior lighting designer; supplied and installed<br />

by the electrical contractor.<br />

• Exterior decorative lighting specified by the exterior lighting<br />

designer; supplied and installed by the electrical contractor.<br />

• Custom decorative chandeliers, wall sconces and guestroom<br />

lighting specified and/or selected by the interior lighting<br />

designer after tender; supplied by FF&E or in general contract,<br />

assembled and installed by the electrical contractor.<br />

Has the split in responsibility been agreed with all members of the design<br />

team and construction team?<br />

YES<br />

NO<br />

REV. MARCH 2006 281<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Special Audio/Visual Equipment<br />

Is all equipment such as projectors included in FF&E or in general contract?<br />

CONSULTANT CHECK-LIST<br />

Back-of-House Areas<br />

Loading Dock & Garbage Area:<br />

• Rodent sentry and fly eliminator<br />

• Ecolo-matic<br />

• Miscellaneous power for compactor and dumper<br />

• Overhead door(s) with control in receiving office<br />

• Special mounting heights of devices<br />

• Power for refrigeration unit for garbage room<br />

• Power for pressure washer<br />

• Payphone and house phone<br />

• Intercom to receiving office<br />

• CCTV<br />

• Card access for security<br />

• Cart wash “jet” washer connection<br />

• Baler and crusher connection in recycling<br />

• Cold temperature ballasts for lighting (if applicable)<br />

• Power for dock leveler (if applicable)<br />

Staff Entrance:<br />

• Intercom to security office<br />

• CCTV camera<br />

• Card reader access to electric latch with additional remote<br />

release pushbutton in security office<br />

Security Office:<br />

• CCTV monitors integrated into millwork along with CCTV<br />

controls and VCR’s<br />

• Audio monitoring console and microphone (for CCTV)<br />

• Door alarm and card access system printer (from electronic card<br />

locking system)<br />

• Remote fire alarm printer<br />

• Intercom to staff entrance<br />

Staff Lockers and Washroom:<br />

• Hand and hair dryers<br />

• Outlet for shoe shine<br />

• Shaver outlets in men’s washrooms and outlets<br />

• Payphone and house phone<br />

• Miscellaneous receptacles for cleaning equipment<br />

• Waterproof lighting in showers<br />

YES<br />

NO<br />

REV. MARCH 2006 282<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Staff Training Room:<br />

• Motorized projection screen<br />

• Power and signal for TV/Video center<br />

• Quadplex voice/data<br />

• Multi-level switching of fluorescent lighting<br />

• Wall phone<br />

Staff Dining:<br />

• Background music system for circulation space source with local<br />

volume control<br />

• Power and signal for TV<br />

• Power for vending machine<br />

• Two payphones and house phones<br />

• Power outlets for housekeeping<br />

• Kitchen equipment connections<br />

• Incandescent lighting in lounge area<br />

Back-of-House Offices:<br />

• Quadplex power adjacent P.C. plus additional duplex<br />

• Quad voice/Data<br />

• Individual switch for control of lighting<br />

• Fluorescent lighting (except where visible from exterior).<br />

• UPS power where described in FHR’s Standards<br />

Interior Parking Areas:<br />

• Lighting levels for security purposes<br />

• Telephone at every stairwell<br />

• CCTV at foyer (as applicable)<br />

• Card access for security<br />

• Upgraded lighting and power at car washing area<br />

• Miscellaneous power throughout the parking area<br />

• Power and signal connection for payment and parking control<br />

system<br />

Maintenance and Engineering Area:<br />

• Power and signal outlets for TV in TV storage room and TV<br />

work bench<br />

• 15 <strong>amp</strong>, 30 <strong>amp</strong> and 50 <strong>amp</strong> power required in general work<br />

area as per FHR’s Standards<br />

• Connection to separate exhaust system in paint shop<br />

• Connection to radial arm saw, compressor, moveable table saw,<br />

bandsaw, drill press in carpentry shop<br />

Computer Room:<br />

• Contains hubs and network servers in shelf or rack mounted<br />

configuration (minimum 16 duplex outlets in UPS)<br />

YES<br />

NO<br />

REV. MARCH 2006 283<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

• Room contains floor mounted UPS and separate air conditioning<br />

unit, all on emergency power<br />

• Interconnection to PBX equipment room and telephone<br />

operator’s room<br />

• Termination point of all fiber or copper backbone cabling from<br />

hubs<br />

Telephone Operator’s Room:<br />

• Lighting and emergency power<br />

• Each workstation with normal and UPS power, Quad data/voice<br />

outlet, 25 pair telephone cable outlet and paging telephone outlet<br />

• CCTV monitors and audio monitoring controls<br />

• VCR’s<br />

• Red alarm lights for front desk cashier, main cashier office, staff<br />

safety deposit box, valet/parking cashier and sauna<br />

• Remote fire alarm printer or annunciator<br />

• Master pocket paging station<br />

• Walk-in cooler/freezer alarm annunciation<br />

• UPS power and data outlet for POS printer<br />

• Power bar for battery chargers for portable radios and pagers<br />

Luggage Storage:<br />

• CCTV camera<br />

• House phone<br />

• One power outlet<br />

Valet/Parking Cashier<br />

• UPS power<br />

• Quadplex voice/data<br />

• Alarm pushbutton (to telephone operator’s room)<br />

• Card access entry (to be reviewed on each project)<br />

Prefunction Area<br />

“AV-1”, “AV-2”, “AV-3” GR and 200 <strong>amp</strong> power panels in ballroom,<br />

meeting rooms and prefunction areas.<br />

“AV-2”, “AV-3” and “AV-4” panels in meeting rooms depending on size.<br />

Control niches for telephone, lighting, volume and screen controls in each<br />

room and associated prefunction area.<br />

Independent sound systems with capability for “combining” into one room.<br />

Door hold-open devices.<br />

Power for food warming carts in service corridor.<br />

“Do Not Disturb” light in service corridor of function room.<br />

Lighting bar and ceiling power in ballroom with dimmer in control niche.<br />

Separate electrical room and sound system equipment room.<br />

YES<br />

NO<br />

REV. MARCH 2006 284<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Spa/Fitness Center<br />

Reception Desk:<br />

• Workstations with power and computer outlets (usual quantity of<br />

2)<br />

• Power and computer outlet for printer<br />

• Telephone outlets for guest and staff use<br />

• Miscellaneous power supply<br />

• Power for battery chargers<br />

• CCTV monitor and switches for pool and exercise room<br />

• Microphone for two-way audio monitoring of pool (indoor pool<br />

only)<br />

• Volume control for background music system for circulation<br />

space<br />

• Buzzers for sauna emergency alarm<br />

Exercise Area:<br />

• Separate circuit for each piece of equipment<br />

• Power and TV outlet at base of each piece of equipment<br />

• Local music volume control<br />

• CCTV camera<br />

• Emergency telephone<br />

• Two wall-mounted TV signal and power outlets<br />

• Portable sound system<br />

Sauna and Steam:<br />

• Emergency pushbutton to alarm at reception desk<br />

• Sauna temperature control outside of sauna room<br />

Pool Area:<br />

• CCTV camera and speaker<br />

• Minimum two underwater lights in pool and minimum one light<br />

in whirlpool<br />

• Underwater speakers in pool (Resort only)<br />

• Emergency telephone<br />

• Separate times switch for whirlpool<br />

Massage Rooms:<br />

• Dimmer control for lighting<br />

• Local volume control to ceiling speaker for background music<br />

• Power above shelf for portable cassette/CD player<br />

• Wall telephone<br />

• Three duplex power outlets at low level and one above counter<br />

Locker/Showers:<br />

• Built-in swimsuit dryer<br />

YES<br />

NO<br />

REV. MARCH 2006 285<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

• House and payphone<br />

• Power for hair dryer<br />

• Cleaning receptacle<br />

Front-of-House Areas<br />

Front Desk:<br />

• VIP pushbutton(s) (to General Manager)<br />

• Help/Assistance pushbutton (to front office manager)<br />

• Alarm pushbutton (to telephone operator’s room)<br />

• Guest safety deposit box room electric door release pushbutton<br />

• Buzzer from guest safety deposit box room<br />

• Normal (IG) and UPS power<br />

• Telephone outlets<br />

• Credit card verification outlet (telephone line)<br />

• Data outlets<br />

• Data cable rough-in for electronic card key encoder<br />

• CCTV camera<br />

Concierge Desk:<br />

• Buzzer annunciation from doorman’s stand for Help/Assistance<br />

• Help/Assistance pushbutton (to concierge work room)<br />

• Normal (IG) and UPS power outlets<br />

• Telephone<br />

• Data<br />

• Credit card verification outlet (telephone)<br />

• CCTV camera<br />

Concierge Work Room:<br />

• Buzzer annunciation from concierge desk<br />

• Facsimile<br />

• Data/telephone for airline tickets<br />

• Normal (IG) power outlets<br />

• Quadplex voice/data<br />

• Location of volume controls for circulation spaces (optional)<br />

• Photocopier power<br />

• Dimmer control location for lobby (optional)<br />

Porte Cochère<br />

• CCTV camera (as required)<br />

• Power for pressure washer<br />

• Miscellaneous power<br />

• Doorman’s stand(s) with power, voice/data, VIP pushbutton and<br />

Help/Assistance pushbutton<br />

• Snowmelting and radiant heating (as applicable)<br />

YES<br />

NO<br />

REV. MARCH 2006 286<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Lobby:<br />

• Two (2) telephone outlets for guests<br />

• CCTV camera<br />

• Power for table l<strong>amp</strong>s as per interior designer<br />

• Background music speakers<br />

• Illuminated display cabinets (as applicable)<br />

• Reception desk and concierge desk<br />

Guest Safety Deposit Box Viewing Room<br />

• Electric strike released from front desk and GSDB (staff side)<br />

• Chandelier and wall sconce lighting<br />

• Pushbutton above counter to operate buzzer at front desk<br />

• CCTV camera (staff side)<br />

• Duplex power receptacle<br />

Main Dining Room and Café:<br />

• Dimmer controls and background music controls adjacent to<br />

service stand<br />

• Independent sound system with interconnection to main<br />

background music rack<br />

• Service stand with local lighting, UPS and normal (IG) power,<br />

data (POS), telephone and credit card verification outlets<br />

• Maitre D’ position with quadplex voice/data, power and local<br />

lighting<br />

• Power for cleaning outlets, table l<strong>amp</strong>s, etc. as per interior<br />

designer<br />

Typical Guestroom Floor<br />

Corridor:<br />

• Cleaning receptacles on 40 ft centres<br />

• Power for table l<strong>amp</strong>s and picture lights as per interior designer<br />

• House telephone at elevator lobby<br />

• Life-safety and fire alarm devices in unobtrusive location.<br />

Includes smoke detectors, EVC speakers, pull station and fire<br />

fighter’s handsets<br />

• Decorative lighting as per interior designer<br />

• Are cable trays located in corridor ceiling? If so, what access<br />

provisions have been made?<br />

Maid’s Rooms:<br />

• House phone<br />

• Separate lighting switch<br />

Ice Machine Room:<br />

• Incandescent lighting with separate switch<br />

• Two separate circuits for ice machine<br />

YES<br />

NO<br />

REV. MARCH 2006 287<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Electrical and LAN Closet:<br />

• Separate room for LAN equipment<br />

Typical Guestroom Provisions:<br />

• Power, telephone, lighting and TV outlets as per interior<br />

designer<br />

• Confirm if 120 volt (US) outlet is required at desk<br />

• Handicapped provisions such as strobes, vibrating pillow, etc. as<br />

per local code<br />

Special Guestrooms Sound System:<br />

• Residential stereo conduit rough-in for Two-Bedroom and<br />

Presidential Suites. Includes two systems with two speakers in<br />

master bedroom and four speakers in living room and dining<br />

room. Homerun location is armoire unit in each room.<br />

SPECIFICATIONS<br />

Power Distribution<br />

Have copper conductors and bus been specified?<br />

Has electrical equipment been suitably dearated for temperature in areas<br />

where ambient temperatures are in the range of 105 F ?<br />

Have concealed conduit and devices been specified in all front-of-house<br />

areas and back-of-house areas except storage and service rooms?<br />

Have lamacoid nameplates been specified for all equipment?<br />

Is the interrupting capacity of all distribution panels and switchgear been<br />

specified to ensure that the equipment can safely withstand the available<br />

fault current?<br />

Have one or all of the following wiring methods been described?<br />

• Enclosed bus duct for main transformers<br />

• Multi-core armored cables or cables in conduit for large feeders<br />

to distribution pads, motor control centers and branch<br />

panelboards<br />

• Small branch circuit wiring in conduit or unarmored double<br />

insulated cable in tray for devices in ceiling space or in hollow<br />

cavity walls<br />

Emergency Power<br />

Does the generator specification include a statement for “the generator to<br />

handle a 100% load step”?<br />

Does the transfer switch specification include bypass provisions in order to<br />

avoid shutting down the load or maintenance?<br />

YES<br />

NO<br />

REV. MARCH 2006 288<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved


Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

In certain locations, local codes require a central battery or inverter to<br />

supply power to designated emergency luminaires for the 10 second outage<br />

during which the generator starts. Is this specified?<br />

Lighting<br />

Lighting fixture selection shall be based on FHR’s Standards and on input<br />

from the interior lighting designer, however, the following minimum<br />

requirements should be met:<br />

• Fluorescent luminaires shall be energy efficient type with T-8<br />

l<strong>amp</strong>s and electronic ballasts. Ballasts shall be HPF type with<br />

low harmonic content.<br />

• Fluorescent back-of-house luminaire selection shall be based on<br />

the lowest cost for the local region, hower, 1’ x 4’ and 2 x 4’ are<br />

recommended.<br />

• Line voltage, architectural grade, open reflector downlights shall<br />

have standard l<strong>amp</strong>s.<br />

• Low voltage luminaires shall be specified with integral<br />

transformers.<br />

Does the electrical specification include the dimming specification and<br />

lighting “cuts” from the interior lighting designer?<br />

Fire Alarm System<br />

Have smoke detectors in guestrooms been specified with their own local<br />

audible alarm?<br />

For high-rise buildings, has a fire rated riser cable been specified?<br />

Lighting Protection System<br />

Two systems are available – North American based with independent<br />

copper down conductors in conduit, or European based, where the structural<br />

steel may be used as down conductors. Which is specified?<br />

If upright air terminals are specified at the top of the building, are they<br />

visible? The alternative is a flat copper tape.<br />

YES<br />

NO<br />

REV. MARCH 2006 289<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved