UL 1449 Safety Testing<br />

• MOVs/SPDs have multiple failure scenarios<br />

(Any single failure mode test is inadequate)<br />

• UL simulates various scenarios by:<br />

– Testing at L-L voltage (i.e., 208V, 480V, 600V, etc.)<br />

– Controlling / limiting fault current (i.e., 1/8-200kA)<br />

• Fault Current tests in every mode `at:<br />

– 0.5A, 2.5A, 5A, 10A, 100A, 500A, 1000A & SCCR<br />

• Tests are seven (7) hours or until temperature<br />

stabilizes or clears from circuit<br />

• Cannot show any outward signs of failure<br />

Copyright © 2009 Advanced <strong>Protection</strong> Technologies (800) 237-4567<br />