<strong>SAG581126000</strong> System Application Guide<br />
Issue AE, July 23, 2010 Spec. No. 581126000 (Model 700NVBA)<br />
� Optional DC-DC Converter Modules<br />
Where –48VDC load power is also required, DC-DC Converter Modules are<br />
Home<br />
available. Refer to PD588705100 (PD588705101, PD588705102, PD588705103,<br />
PD588705104) for more information.<br />
Family: NETSURE<br />
Spec. No.: 581126000<br />
Model: 700NVBA<br />
Rectifier Input Voltage Nominal 208-240 volts AC, single phase, 50/60 Hz, with an operating<br />
range of 180 to 264 volts. Acceptable input frequency range is 47 to 65<br />
Hz.<br />
Rectifier Output Voltage: +24 Volts DC<br />
Converter Output Voltage:<br />
Output Capacity:<br />
-48 Volts DC<br />
System: 4000 Amperes, maximum<br />
Bay: 2000 Amperes, maximum (1500A maximum when equipped with List<br />
AH; 1200A maximum when equipped with List RA or RB)<br />
Distribution Bus Panel: 500 Amperes, maximum (List ND rated for 960A)<br />
Rectifier Module (PCU): 87.7A @ +28.5VDC to 104.2A @ +24.0VDC, 2500 Watts<br />
Converter Module: 31 Amperes (1500W)<br />
Agency Approval: UL 1801 Listed (“c UL”), NEBS (pending)<br />
Framework Type: Relay Rack<br />
Mounting Width: 23 Inches, nominal<br />
Mounting Depth:<br />
Distribution Cabinet: 18 Inches (single-bay), 21 Inches (multi-bay)<br />
(List RC, RD, and RE adds 5.25 inches to back of system, see Overall<br />
Dimensions Illustrations)<br />
Module Mounting Assembly: 22.34 Inches<br />
Access: Front, Sides, and Rear for Installation and Maintenance,<br />
Front for Operation<br />
Supplemental Bay(s) Available: One<br />
Control: Microprocessor<br />
Color: Bay and Rectifier Module Faceplates: Textured Gray (Spec. M500-147)<br />
Rectifier Shelf and Rectifier Modules Bodies: Bright Zinc Plating (Spec.<br />
M500-53)<br />
List Options: Main Bay, Supplemental Bay (located next to Main Bay), Supplemental<br />
Bay 'Distribution Only' Option, Supplemental Bay (located away from<br />
Main Bay), MCA (standard), MCA (special application), MCA (special<br />
application), MCA (special application), 1-Row Distribution Cabinet,<br />
2-Row Distribution Cabinet, 3-Row Distribution Cabinet, 4-Row<br />
Distribution Cabinet, Distribution Cabinet Top Shield, Module Mounting<br />
Assembly Interface Components, Field Expansion Kit (One [1] 8-Position<br />
Module Mounting Assembly), Rectifier Module (PCU), DC-DC Converter<br />
Option Interface Component Kit, DC-DC Converter Module, Audible<br />
Alarm and Alarm Termination Card, MCA Interface Modem Option, MCA<br />