Alco Controls
Alco Controls
Alco Controls
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
54<br />
<strong>Alco</strong> <strong>Controls</strong><br />
Technical Data<br />
Supply Voltage Nominal 24 Vdc Sensor lifetime<br />
Range (polarity protected) 7 ... 30 Vdc at full stroke at 25°C > 10.000.000 cycles<br />
Operating current max. ≤ 24 mA output Burst pressure see selection chart<br />
Protection class acc. to EN 60529 IP65 Medium compatibility HFC, HCFC, CFC<br />
Load resistance<br />
R ≤ L<br />
U - 7.0V<br />
B<br />
0.02A<br />
not suitable for ammonia and<br />
inflammable refrigerants!<br />
Temperatures PT5 Materials PT5<br />
Operating ambient housing -25 ... 80 °C Housing cover, pressure connector, Stainless steel<br />
Medium -40 ... 100 °C diaphragm with medium contact 1.4534 / AISI 316L<br />
Transportation and storage -25 ... 80 °C Materials PT6<br />
Temperatures PT6 Housing cover, pressure connector, Brass body W614N<br />
Operating ambient housing -20 ... 80 °C diaphragm with medium contact Ceramic sensor cell<br />
Medium -20 ... 80 °C Al O , Gasket CR70<br />
2 3<br />
Transportation and storage -20 ... 80 °C Chloroprene<br />
Accuracy Performance PT5<br />
Temperature range Total error*<br />
PT5-07M/T -40 ... +80°C ≤ ± 1 % FS<br />
PT5-18M/T -20 ... +60°C ≤ ± 1 % FS<br />
PT5-30M/T 0 ... +40°C ≤ ± 1 % FS<br />
-20 ... +60°C ≤ ± 2 % FS<br />
-40 ... +80°C typically ≤ ±2 % FS<br />
PT5-50M/T 0 ... +40°C ≤ ± 1 % FS<br />
-20 ... +60°C ≤ ± 2 % FS<br />
-30 ... +80°C typically ≤ ±2 % FS<br />
*) Total error includes non-linearity, hysteresis, repeatability as well as offset and span<br />
drift due to the temperature changes.<br />
Note: % FS is related to Percentage of Full sensor Scale.<br />
Electrical connection<br />
Pressure transmitters PT5 with current output (2-wire<br />
connection) offer following advantages:<br />
1. More suitable for signal transmission over long<br />
distances<br />
2. Higher immunity to electromagnetic interference<br />
Note: Changing the length of the electrical connection<br />
lead beyond 1.5 m can have a negative impact on electromagnetic<br />
compatibility. Additional protection may be<br />
required.<br />
BN = brown, supply voltage 24V<br />
WH = white, output signal 4 … 20mA<br />
(5) = Electronic Controller e.g. EC2 & EC3 Series<br />
Vibration at 10 ... 2000 Hz max. 4 g<br />
A2.5.1/1003/E