54<br />

<strong>Alco</strong> <strong>Controls</strong><br />

Technical Data<br />

Supply Voltage Nominal 24 Vdc Sensor lifetime<br />

Range (polarity protected) 7 ... 30 Vdc at full stroke at 25°C > 10.000.000 cycles<br />

Operating current max. ≤ 24 mA output Burst pressure see selection chart<br />

Protection class acc. to EN 60529 IP65 Medium compatibility HFC, HCFC, CFC<br />

Load resistance<br />

R ≤ L<br />

U - 7.0V<br />

B<br />

0.02A<br />

not suitable for ammonia and<br />

inflammable refrigerants!<br />

Temperatures PT5 Materials PT5<br />

Operating ambient housing -25 ... 80 °C Housing cover, pressure connector, Stainless steel<br />

Medium -40 ... 100 °C diaphragm with medium contact 1.4534 / AISI 316L<br />

Transportation and storage -25 ... 80 °C Materials PT6<br />

Temperatures PT6 Housing cover, pressure connector, Brass body W614N<br />

Operating ambient housing -20 ... 80 °C diaphragm with medium contact Ceramic sensor cell<br />

Medium -20 ... 80 °C Al O , Gasket CR70<br />

2 3<br />

Transportation and storage -20 ... 80 °C Chloroprene<br />

Accuracy Performance PT5<br />

Temperature range Total error*<br />

PT5-07M/T -40 ... +80°C ≤ ± 1 % FS<br />

PT5-18M/T -20 ... +60°C ≤ ± 1 % FS<br />

PT5-30M/T 0 ... +40°C ≤ ± 1 % FS<br />

-20 ... +60°C ≤ ± 2 % FS<br />

-40 ... +80°C typically ≤ ±2 % FS<br />

PT5-50M/T 0 ... +40°C ≤ ± 1 % FS<br />

-20 ... +60°C ≤ ± 2 % FS<br />

-30 ... +80°C typically ≤ ±2 % FS<br />

*) Total error includes non-linearity, hysteresis, repeatability as well as offset and span<br />

drift due to the temperature changes.<br />

Note: % FS is related to Percentage of Full sensor Scale.<br />

Electrical connection<br />

Pressure transmitters PT5 with current output (2-wire<br />

connection) offer following advantages:<br />

1. More suitable for signal transmission over long<br />

distances<br />

2. Higher immunity to electromagnetic interference<br />

Note: Changing the length of the electrical connection<br />

lead beyond 1.5 m can have a negative impact on electromagnetic<br />

compatibility. Additional protection may be<br />

required.<br />

BN = brown, supply voltage 24V<br />

WH = white, output signal 4 … 20mA<br />

(5) = Electronic Controller e.g. EC2 & EC3 Series<br />

Vibration at 10 ... 2000 Hz max. 4 g<br />

A2.5.1/1003/E