The <strong>DS</strong> <strong>100SE</strong> has passed extensive testing and complies with the following specifications and uses:<br />
LISTED to ANSI/UL 1480-2005<br />
Fire Protective Signaling Use – UL Category UUMW, File Number S 3241.<br />
Control Number 42S9 when installed with a junction box (on-wall or in-wall).<br />
Not for use with DC-supervised systems.<br />
General Purpose Use – UL Category UEAY, File Number S 5591 Control Number 3N89.<br />
Suitable for use outdoors in wet locations.<br />
Suitable for installation using Class 1, Class 2, or Class 3 wiring methods in accordance with NFPA 70, National Electric Code, 2002,<br />
Article 640.<br />
Suitable for use with fire alarm circuit wiring methods in accordance with NFPA 70, National Electric Code, 2002,<br />
Article 760.<br />
The <strong>DS</strong> <strong>100SE</strong> has been designed to the requirements defined in the following European regulatory specification for combination systems:<br />
British Standard Code of Practice BS 5839, Part 8.<br />
Tested to IEC60268-5.<br />
UL Sensitivity Wattage Tap Sound Pressure Level dBA at 3.1 meters (10 feet):<br />
SPLs given are per the UL 1480 specified reporting method.<br />
Frequency response:<br />
Fire alarm: 400 Hz to 4 kHz<br />
General signaling: 80 Hz to 16 kHz (±3dB)<br />
Wire gauge<br />
The <strong>FreeSpace</strong> ® <strong>DS</strong> <strong>100SE</strong> loudspeaker bracket is designed to work with 18 AWG (0.8 mm 2 ) to 14 AWG (2.0 mm 2 ) size wire only.<br />
30<br />
Wattage ANSI/UL 1480-2005<br />
Tap 70V 100V<br />
12.5 Watt 84 dBA –<br />
25 Watt 86 dBA 86 dBA<br />
50 Watt 88 dBA 88 dBA<br />
100 Watt 91 dBA 91 dBA<br />
8 Ohm 89 dBA<br />
Safety and Regulatory Compliance