Dip-switch No. dip Status Function<br />

A<br />

Dip-switch<br />

B<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12<br />

ON Machine set as heat pump<br />

OFF Machine set for cooling only<br />

ON Defrosting only by cycle reversal<br />

OFF Defrosting by hot gas injection<br />

ON Glycol water: anti-freeze setting can be modified<br />

OFF Anti-freeze setting (parameter B) blocked<br />

ON Output control deactivated<br />

OFF Output control activated<br />

ON Safety capacity controls deactivated<br />

OFF Safety capacity controls activated<br />

ON Algorithm for check of low water content deactivated<br />

OFF Algorithm for check of low water content activated<br />

ON Condensation pressure control device present (accessory DCP)<br />

OFF Condensation pressure control device absent (accessory DCP)<br />

ON Configuration of the card for ANR unit (R407C)<br />

OFF Configuration of the card for ANL unit (R410A)<br />

ON Configuration of the card for inverter unit<br />

OFF Configuration of the card for ON/OFF chiller unit<br />

ON Configuration of the card for condenser unit<br />

OFF Configuration of the card for chiller unit<br />

ON Not used<br />

OFF Not used<br />

ON Not used<br />

OFF Not used<br />

Dip combinations Function<br />

DIP 1 DIP 2<br />

OFF OFF Factory settings<br />

ON OFF Factory settings<br />

ON ON Factory settings<br />

OFF ON Factory settings<br />