M038 Tensione S-T (RMS)<br />
M038 Range 0 ÷ 10000 0 ÷ 1000.0 V<br />
Address 1688<br />
Tensione S-T (RMS) Level BASIC<br />
Function Valore efficace della tensione concatenata V ST lato rete.<br />
M039 Tensione T-R (RMS)<br />
M039 Range 0 ÷ 10000 0 ÷ 1000.0 V<br />
Address 1689<br />
Tensione T-R (RMS) Level BASIC<br />
Function Valore efficace della tensione concatenata V TR lato rete.<br />
M040 Corrente RMS di Linea Fase R<br />
M040 Range ± 32000 ± 3200.0 A<br />
Address 1690<br />
Corrente RMS di<br />
Linea Fase R<br />
Level BASIC<br />
Function Valore efficace della corrente di linea fase R lato rete.<br />
M041 Corrente RMS di Linea Fase S<br />
M041 Range ± 32000 ± 3200.0 A<br />
Address 1691<br />
Corrente RMS di<br />
Linea Fase S<br />
Level BASIC<br />
Function Valore efficace della corrente di linea fase S lato rete.<br />
M042 Corrente RMS di Linea Fase T<br />
M042 Range ± 32000 ± 3200.0 A<br />
Address 1692<br />
Corrente RMS di<br />
Linea Fase T<br />
Level BASIC<br />
Function Valore efficace della corrente di linea fase T lato rete.<br />
M043 Stato PLL per Aggancio Rete<br />
M043 Range 0 ÷ 4 Vedi Tabella 13<br />
Stato PLL per<br />
Aggancio Rete<br />
Address 1693<br />
Level BASIC<br />
Visualizza lo stato del PLL che verifica il senso ciclico di rete. In<br />
funzionamento normale, il valore visualizzato deve essere 3:LOCK POS o<br />
Function<br />
4:LOCK NEG, rispettivamente per senso ciclico positivo o negativo della<br />
terna trifase in ingresso.<br />