Therefore the new operating<br />
parameters are:<br />
C) Free - outlet sound data<br />
From table 5.2, for a<br />
<strong>TZAF</strong> 630, the following<br />
values of ∆Lwcorr can be<br />
obtained:<br />
LwoctA6, A-weighted values,<br />
are consequently:<br />
DOUBLE INLET AIRFOIL FANS – <strong>TZAF</strong> <strong>FF</strong><br />
ZWEISEITIGSAUGENDE AIRFOIL VENTILATOREN – <strong>TZAF</strong> <strong>FF</strong><br />
VENTILATEURS AIRFOIL DOUBLE ASPIRATION – <strong>TZAF</strong> <strong>FF</strong><br />
VENTILATORI AIRFOIL A DOPPIA ASPIRAZIONE – <strong>TZAF</strong> <strong>FF</strong><br />
Als Folge ergeben sich die<br />
neuen Betriebsdaten mit:<br />
η’t =<br />
Pw =<br />
Octave Band Mid Frequency<br />
Oktavband Mittefrequenz<br />
Fréquence moyenne de la Bande d'Octave<br />
Frequenza media della Banda d'Ottava<br />
n = 1688 min -1 ;<br />
LwA4 = 90,4 dB(A);<br />
pdyn = 88 Pa;<br />
ηt x ∆ptot<br />
∆’ptot<br />
V<br />
=<br />
85 x 1800<br />
1826<br />
° .x ∆ptot<br />
η't x 36000<br />
=<br />
28000 x 1800<br />
83,8 x 36000<br />
C) Schalleistungsdaten bei<br />
freien Ausbas:<br />
Aus Graphik 5.2. können für<br />
den <strong>TZAF</strong> 630 folgende<br />
∆Lwcorr Faktoren entnommen<br />
werden:<br />
Par conséquence les<br />
nouveaux paramètres de<br />
fonctionnement seront:<br />
= 83,8 %<br />
= 16,71 kW<br />
C) B<strong>ru</strong>it avec refulement<br />
libre:<br />
Du tableau 5.2 on deduit<br />
pour le <strong>TZAF</strong> 630 les<br />
corrections, ∆Lwcorr<br />
suivantes:<br />
63 Hz -6 dB; 125 Hz -3 dB; 250 Hz -1 dB<br />
ohne D<strong>ru</strong>ckkanalanschluss<br />
ergeben sich folgende LwoctA6<br />
Werte:<br />
par conséquence nous<br />
aurons les valeurs suivantes<br />
LwoctA6:<br />
C-0075 December 2004<br />
Di conseguenza i nuovi<br />
parametri di funzionamento<br />
sono:<br />
C) Rumorosità con bocca di<br />
mandata libera:<br />
Dalla tabella 5.2, si ricavano<br />
per il <strong>TZAF</strong> 630 le correzioni<br />
∆Lwcorr seguenti:<br />
Da cui i valori di LwoctA6, sono<br />
i seguenti:<br />
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz<br />
LwoctA4 71 76 84 83 84 79 74 68<br />
∆Lwcorr -6 -3 -1 0 0 0 0 0<br />
LwoctA6 65 73 83 83 84 79 74 68<br />
D) Altitude and temperature<br />
correction<br />
If the temperature and the<br />
altitude at which the fan will<br />
operate are not standard, the<br />
pressure value used for the<br />
selection must be previously<br />
re-calculated:<br />
Let’s consider the following<br />
parameters:<br />
Air volume: 28000 m 3 /h<br />
Total pressure: 1530 Pa<br />
Temperature: 40 °C<br />
Altitude: 1000 m a.s.l.<br />
From Graph 4.5, the value of<br />
Kρ = 0,85 is obtained. The<br />
corrected pressure, to be<br />
used for the selection on the<br />
performance chart, is therefore:<br />
The selected fan will be the<br />
same as selected in the<br />
example (paragraph (A)),<br />
with the same characteristics<br />
but the absorbed power<br />
will be:<br />
D) Korrektur für Temperatur-<br />
und Höhenabweichungen<br />
Weichen Temperatur oder<br />
Aufstellunshöhe ab, so ist<br />
die D<strong>ru</strong>ckerhöhung<br />
entsprechend zu korrigieren.<br />
z.B.<br />
Volumenstrom: 28000 m 3 /h<br />
Gesamtd<strong>ru</strong>ckdifferenz:1530 Pa<br />
Temperatur : 40 °C<br />
Höhe:1000 m über Meeresspiegel.<br />
Aus der Grafik 4.5 wird der<br />
Korrekturfaktor � Kρ = 0,85<br />
ermittelt.<br />
Damit ergibt sich:<br />
∆ptot corr =<br />
∆ptot<br />
Kρ<br />
Der ausgelegte Ventilator<br />
wird derselbe des Beispiels<br />
im (Paragraph (A)) sein, mit<br />
den gleichen Eigenschaften,<br />
allerdings wird die<br />
aufgenommene Leistung<br />
betragen:<br />
=<br />
D) Correction pour température<br />
et altitude différente<br />
Pour températures<br />
différentes de +20 °C et<br />
altitudes supérieures à 0 m<br />
s.n.m., les valeurs de la<br />
pression doivent être<br />
corrigées avant la sélection:<br />
En considérant les données<br />
suivantes:<br />
Débit: 28000 m 3 /h<br />
Pression totale: 1530 Pa<br />
Température: 40 °C<br />
Altitude: 1000 m s.l.m.<br />
Du graphique 4.5 on obtient<br />
Kρ = 0,85, donc la valeur de<br />
pression à utilizer pour la<br />
sélection sera:<br />
1530<br />
0,85<br />
= 1800 Pa<br />
Le ventilateur sélectionné<br />
sera par conséquent le<br />
même que celui de l’exemple<br />
(paragraphe (A)) avec les<br />
mêmes caractéristiques,<br />
mais la puissance<br />
absorbée sera:<br />
Pwcorr = Pw x 0,85 = 16,47 x 0,85 = 13,99 kW<br />
21<br />
D) Correzione per<br />
temperatura e altitudine<br />
Per temperature ed altitudini<br />
diverse dai valori standard, i<br />
valori di pressione devono<br />
essere corretti prima della<br />
selezione.<br />
Consideriamo i dati seguenti:<br />
Portata: 28000 m 3 /h<br />
Pressione totale: 1530 Pa<br />
Temperatura: 40 °C<br />
Altitudine: 1000 m s.l.m.<br />
Dal grafico 4.5 si ottiene<br />
Kρ = 0,85 per cui il valore di<br />
pressione da utilizzare nella<br />
scelta sarà:<br />
Il ventilatore selezionato sarà<br />
pertanto lo stesso<br />
dell'esempio (paragrafo (A)),<br />
con le medesime<br />
caratteristiche, ma la<br />
potenza assorbita sarà: