Therefore the new operating<br />

parameters are:<br />

C) Free - outlet sound data<br />

From table 5.2, for a<br />

<strong>TZAF</strong> 630, the following<br />

values of ∆Lwcorr can be<br />

obtained:<br />

LwoctA6, A-weighted values,<br />

are consequently:<br />

DOUBLE INLET AIRFOIL FANS – <strong>TZAF</strong> <strong>FF</strong><br />

ZWEISEITIGSAUGENDE AIRFOIL VENTILATOREN – <strong>TZAF</strong> <strong>FF</strong><br />

VENTILATEURS AIRFOIL DOUBLE ASPIRATION – <strong>TZAF</strong> <strong>FF</strong><br />

VENTILATORI AIRFOIL A DOPPIA ASPIRAZIONE – <strong>TZAF</strong> <strong>FF</strong><br />

Als Folge ergeben sich die<br />

neuen Betriebsdaten mit:<br />

η’t =<br />

Pw =<br />

Octave Band Mid Frequency<br />

Oktavband Mittefrequenz<br />

Fréquence moyenne de la Bande d'Octave<br />

Frequenza media della Banda d'Ottava<br />

n = 1688 min -1 ;<br />

LwA4 = 90,4 dB(A);<br />

pdyn = 88 Pa;<br />

ηt x ∆ptot<br />

∆’ptot<br />

V<br />

=<br />

85 x 1800<br />

1826<br />

° .x ∆ptot<br />

η't x 36000<br />

=<br />

28000 x 1800<br />

83,8 x 36000<br />

C) Schalleistungsdaten bei<br />

freien Ausbas:<br />

Aus Graphik 5.2. können für<br />

den <strong>TZAF</strong> 630 folgende<br />

∆Lwcorr Faktoren entnommen<br />

werden:<br />

Par conséquence les<br />

nouveaux paramètres de<br />

fonctionnement seront:<br />

= 83,8 %<br />

= 16,71 kW<br />

C) B<strong>ru</strong>it avec refulement<br />

libre:<br />

Du tableau 5.2 on deduit<br />

pour le <strong>TZAF</strong> 630 les<br />

corrections, ∆Lwcorr<br />

suivantes:<br />

63 Hz -6 dB; 125 Hz -3 dB; 250 Hz -1 dB<br />

ohne D<strong>ru</strong>ckkanalanschluss<br />

ergeben sich folgende LwoctA6<br />

Werte:<br />

par conséquence nous<br />

aurons les valeurs suivantes<br />

LwoctA6:<br />

C-0075 December 2004<br />

Di conseguenza i nuovi<br />

parametri di funzionamento<br />

sono:<br />

C) Rumorosità con bocca di<br />

mandata libera:<br />

Dalla tabella 5.2, si ricavano<br />

per il <strong>TZAF</strong> 630 le correzioni<br />

∆Lwcorr seguenti:<br />

Da cui i valori di LwoctA6, sono<br />

i seguenti:<br />

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz<br />

LwoctA4 71 76 84 83 84 79 74 68<br />

∆Lwcorr -6 -3 -1 0 0 0 0 0<br />

LwoctA6 65 73 83 83 84 79 74 68<br />

D) Altitude and temperature<br />

correction<br />

If the temperature and the<br />

altitude at which the fan will<br />

operate are not standard, the<br />

pressure value used for the<br />

selection must be previously<br />

re-calculated:<br />

Let’s consider the following<br />

parameters:<br />

Air volume: 28000 m 3 /h<br />

Total pressure: 1530 Pa<br />

Temperature: 40 °C<br />

Altitude: 1000 m a.s.l.<br />

From Graph 4.5, the value of<br />

Kρ = 0,85 is obtained. The<br />

corrected pressure, to be<br />

used for the selection on the<br />

performance chart, is therefore:<br />

The selected fan will be the<br />

same as selected in the<br />

example (paragraph (A)),<br />

with the same characteristics<br />

but the absorbed power<br />

will be:<br />

D) Korrektur für Temperatur-<br />

und Höhenabweichungen<br />

Weichen Temperatur oder<br />

Aufstellunshöhe ab, so ist<br />

die D<strong>ru</strong>ckerhöhung<br />

entsprechend zu korrigieren.<br />

z.B.<br />

Volumenstrom: 28000 m 3 /h<br />

Gesamtd<strong>ru</strong>ckdifferenz:1530 Pa<br />

Temperatur : 40 °C<br />

Höhe:1000 m über Meeresspiegel.<br />

Aus der Grafik 4.5 wird der<br />

Korrekturfaktor � Kρ = 0,85<br />

ermittelt.<br />

Damit ergibt sich:<br />

∆ptot corr =<br />

∆ptot<br />

Kρ<br />

Der ausgelegte Ventilator<br />

wird derselbe des Beispiels<br />

im (Paragraph (A)) sein, mit<br />

den gleichen Eigenschaften,<br />

allerdings wird die<br />

aufgenommene Leistung<br />

betragen:<br />

=<br />

D) Correction pour température<br />

et altitude différente<br />

Pour températures<br />

différentes de +20 °C et<br />

altitudes supérieures à 0 m<br />

s.n.m., les valeurs de la<br />

pression doivent être<br />

corrigées avant la sélection:<br />

En considérant les données<br />

suivantes:<br />

Débit: 28000 m 3 /h<br />

Pression totale: 1530 Pa<br />

Température: 40 °C<br />

Altitude: 1000 m s.l.m.<br />

Du graphique 4.5 on obtient<br />

Kρ = 0,85, donc la valeur de<br />

pression à utilizer pour la<br />

sélection sera:<br />

1530<br />

0,85<br />

= 1800 Pa<br />

Le ventilateur sélectionné<br />

sera par conséquent le<br />

même que celui de l’exemple<br />

(paragraphe (A)) avec les<br />

mêmes caractéristiques,<br />

mais la puissance<br />

absorbée sera:<br />

Pwcorr = Pw x 0,85 = 16,47 x 0,85 = 13,99 kW<br />

21<br />

D) Correzione per<br />

temperatura e altitudine<br />

Per temperature ed altitudini<br />

diverse dai valori standard, i<br />

valori di pressione devono<br />

essere corretti prima della<br />

selezione.<br />

Consideriamo i dati seguenti:<br />

Portata: 28000 m 3 /h<br />

Pressione totale: 1530 Pa<br />

Temperatura: 40 °C<br />

Altitudine: 1000 m s.l.m.<br />

Dal grafico 4.5 si ottiene<br />

Kρ = 0,85 per cui il valore di<br />

pressione da utilizzare nella<br />

scelta sarà:<br />

Il ventilatore selezionato sarà<br />

pertanto lo stesso<br />

dell'esempio (paragrafo (A)),<br />

con le medesime<br />

caratteristiche, ma la<br />

potenza assorbita sarà: