Technische Daten<br />
Maintenance<br />
If repair is necessary, the affected component must be sent to the production<br />
location. Repairs can only be carried there.<br />
Special Conditions<br />
1. The diagnostic repeater must be installed in a cabinet or metal housing. These<br />
must comply with the IP 54 degree of protection as a minimum. The<br />
environmental conditions under which the equipment is installed must be taken<br />
into account. There must be a manufacturer's declaration for zone 2 available<br />
for the housing (in accordance with EN 50021).<br />
2. If a temperature of > 70 °C is reached in the cable or at the cable entry of this<br />
housing under operating conditions, or if a temperature of > 80 °C can be<br />
reached at the junction of the conductors under operating conditions, the<br />
temperature-related properties of the cables must correspond to the<br />
temperatures actually measured.<br />
3. The cable entries used must comply with the required IP degree of protection<br />
and Section 7.2 (in accordance with EN 50021).<br />
4. All devices (including switches, etc.) that are connected to the inputs and<br />
outputs of fail-safe signal modules must be approved for EEx nA or EEx nC<br />
explosion protection.<br />
5. Steps must be taken to ensure that the rated voltage through transients cannot<br />
be exceeded by more than 40 %.<br />
6. Ambient temperature range: 0° C to 60° C<br />
7. A sign containing the following warning must be put up inside the housing in an<br />
easily visible position when the housing is opened:<br />
Warning<br />
The housing can only be opened for a short time (e.g. for visual diagnostics). If<br />
you do this, do not operate any switches, remove or install any modules or<br />
disconnect any electrical cables (plug-in connections).<br />
You can disregard this warning if you know that the atmosphere is not<br />
hazardous (i.e. there is no risk of explosion).<br />
List of Approved Modules<br />
You will find the list of approved modules under the ID 13702947 on the Internet:<br />
http://www4.ad.siemens.de/view/cs/.<br />
<strong>Diagnose</strong>-<strong>Repeater</strong> für PROFIBUS-<strong>DP</strong><br />
A5E00103897-02 8-15