14 HEAT REGULATION SYSTEM FOR RETURN FLOW<br />
14.1.1 Application example<br />
Example of use<br />
Boiler/heat source<br />
14.1.2 Setting the reflux temperature<br />
The temperature setting range lies between 40 °C and<br />
65 °C. The desired temperature of the regulated heating<br />
circuit can be set at the top of the component’s<br />
thermostat and can be read from the thermometer in<br />
the return (blue).<br />
Note:<br />
The temperature in the regulated heating circuit is<br />
not immediately set after altering the top of the thermostat<br />
meaning that the temperature can be read<br />
after an appropriate operating time of the regulated<br />
heating circuit.<br />
14.2 Return line raising MK DN 5 (1“) /<br />
electronically controlled<br />
The function corresponse to the thermostatic type<br />
(page 26). The difference is the 3-way T-mixer and<br />
3-point actuator (230 V AC/50 Hz), including return<br />
temperature regulation (adjustment range 20 °C to<br />
80 °C).<br />
Technichal data:<br />
DN: 25<br />
Upper connection/Hot<br />
boiler connection:<br />
Lower connection/<br />
boiler connection:<br />
1 1/2“ IG<br />
(flat-sealing)<br />
1“ IG<br />
Axial separation: 125 mm<br />
Components of: Brass, EPP insulation<br />
Dimensions: Approx.<br />
H 420 x B 250 x D 255 mm<br />
Sealing materials: PTFE, asbestos-free fibre<br />
sealing, EPDM<br />
Temperature display: 0 to 120 °C<br />
Usage range (max.): 110 °C<br />
Operational pressure: PN 6<br />
GC-KBN: CPGRAE<br />
Pressure loss (bar)<br />
Volume flow-pressure loss-diagram<br />
Return booster with 3-point actuator<br />
Volumetric flow rate (l/h)<br />
7