10. SPEZIFIKATIONEN<br />
VA Rating<br />
Model 1KVA 2KVA 3KVA<br />
Apparent Output Power <strong>1000</strong>VA 2000VA <strong>3000</strong>VA<br />
Active Output Power PF=0.7 700Watts 1400Watts 2100Watts<br />
Power Factor 0.7<br />
Topology<br />
Type<br />
Agency Approvals<br />
Input<br />
Voltage Window<br />
Voltage<br />
Range<br />
Frequency<br />
Phase<br />
PF<br />
Low Line<br />
Transfer<br />
Low Line<br />
Comeback<br />
High Line<br />
Transfer<br />
High Line<br />
Comeback<br />
Typical Transfer Time<br />
AC Leakage current<br />
Surge Protection<br />
Output<br />
Output<br />
(INV. mode)<br />
Efficiency<br />
Voltage<br />
Voltage Regulation<br />
115V<br />
230V<br />
115V<br />
230V<br />
115V<br />
230V<br />
115V<br />
230V<br />
115V<br />
230V<br />
115V<br />
230V<br />
115V<br />
230V<br />
Frequency(Synchronized<br />
Range)<br />
Frequency(Battery Mode)<br />
Double conversion On-Line<br />
Rack/Tower<br />
115V Models: UL, cUL, FCC<br />
230V Models: CE<br />
60/70/80 - 144Vac<br />
120/140/160 - 288Vac<br />
Base on load percentage (0~33/33~66/66~100%)<br />
60/70/80Vac<br />
120/140/160Vac (1.5KVA not available)<br />
85Vac<br />
170Vac (1.5KVA not available)<br />
144Vac<br />
288Vac (1.5KVA not available)<br />
139Vac<br />
278Vac (1.5KVA not available)<br />
50/60 Hz auto-select, ± 5Hz<br />
Single phase with ground<br />
>0.99 at full rated linear load<br />
0 ms.<br />
≤ 5mA<br />
≤ 3.5mA (1.5KVA not available)<br />
400 joules<br />
300 joules (1.5KVA not available)<br />
115V 115V,adjustable to 100/110/115/120/127<br />
230V 230V,adjustable to 200/208/220/230/240 (1.5KVA not available)<br />
≤± 1% until low battery warning<br />
3Hz or 1Hz (setting by software)<br />
±0.1% (0.05~0.06Hz) unless synchronized to line<br />
Current Crest Factor 3:1<br />
Harmonic Distortion<br />
Transient Response(ms)<br />
Waveform<br />
Battery <strong>System</strong><br />
1KVA,2KVA, 3KVA≦3% THD(Linear Load)<br />
1.5KVA≦4% THD(Linear Load)<br />
≦7% THD(Non-Linear Load)<br />
7min. >7min. >5min.<br />
Recharging Time 4 Hours to 90%<br />
Charging Current (Max.) 1.8A 2.16A 2.7A<br />
Charging Voltage 41.0Vdc±0.5V 82.0Vdc±0.5V 82.0Vdc±0.5V<br />
Hot Swappable Battery<br />
Yes