<strong>Type</strong> <strong>EGS</strong><br />
DC power supplies to VDE 0570-2-6/EN 61558-2-6<br />
Application<br />
For general applications, e. g., for supplying control circuits in switchgear systems,<br />
distribution boards, machines, etc. with safety extra-low voltage (SELV). Suited in particular, as power supply<br />
of programmable logic controllers (PLC).<br />
available ex stock Recommended fuses see page 63<br />
Accessories see pages 70 - 71
<strong>Type</strong> <strong>EGS</strong><br />
DC POWER SUPPLIES<br />
Construction<br />
� Open construction (IP 00, incorporation up to max. IP 23))<br />
� DC power supply to VDE 0570-2-6/ EN 61558-2-6<br />
with built-in safety isolating transformer<br />
� Line-side variable tapping<br />
� Fastening dimensions to DIN 41308<br />
� Connection to safe-to-touch screw clamping terminals<br />
with self-releasing clamp<br />
� Output configuration: varistor, filter capacitor (105°C) and<br />
discharge resistance<br />
� Output components covered safe-to-touch<br />
acc. to. VDE 0106,part 100<br />
� High-grade, tropicalized vacuum impregnations in<br />
black polyester impregnating resin<br />
� Performance data with circuit diagram printed on product<br />
� Products are overload and short circuit resistant<br />
due to integrated fuse links<br />
� No additional fusing required if incorporated<br />
� Output voltage indicated by green LED<br />
<strong>SBA</strong>-TrafoTech GmbH<br />
Winkelleite 14<br />
91332 Heiligenstadt, Germany<br />
Telephone +49 (0)9198/8 09-19<br />
Facsimile +49 (0)9198/8 09-30<br />
sales@sba.de info@sba.de<br />
<strong>SBA</strong>-Trafobau Jena GmbH<br />
Ilmstraße 18<br />
07743 Jena, Germany<br />
Telephone +49 (0)3641/4514-14<br />
Facsimile +49 (0)3641/4514-30<br />
With VDE test label<br />
Specifications<br />
Output range 72 W – 192 W<br />
Input voltage AC 220/230/240 V or<br />
AC 380/400/420 V<br />
Output voltage SELV DC 24 V<br />
to EN 61131-2<br />
Ripple factor (typ.) < 5 %<br />
Frequency 50-60 Hz<br />
Vector group Ii0 shielding winding<br />
Protection class I<br />
Protection index IP 00<br />
Ambient temperature max. 60°C<br />
Interference emmission EN 61000-6 -3/-4, (class B)<br />
Interference immunity EN 61000-6 -1/-2<br />
Overview<br />
Input voltage: 220/230/240 V<br />
<strong>Type</strong> Article no. Rated output Fuse No-load Total Dimensions<br />
current<br />
A<br />
voltage<br />
V<br />
weight<br />
appr. kg<br />
a1 b1 a2 b2 approx. mm<br />
a3 b3 c<br />
<strong>EGS</strong> 2403 043-0259 3 5 A (5x20 mm) 27.1 2.3 94 94 64 64 4.8 8 120<br />
<strong>EGS</strong> 2405 073-0052 5 15 A (FKS) 27.1 3.8 101 113 84 87 5.8 9 139<br />
<strong>EGS</strong> 2408 075-0078 8 20 A (FKS) 27.1 5.4 130 109 90 85 5.8 12 175<br />
<strong>Type</strong> <strong>EGS</strong> 2403 also available ex stock for top hat rail snap-on to DIN EN 50022(article no. 043-0390).<br />
Input voltage: 380/400/420 V<br />
<strong>Type</strong> Article no. Rated output Fuse No-load Total Dimensions<br />
current<br />
A<br />
voltage<br />
V<br />
weight<br />
appr. kg<br />
a1 b1 a2 b2 approx. mm<br />
a3 b3 c<br />
<strong>EGS</strong> 4002403 043-0264 3 5 A (5x20 mm) 27.1 2.3 94 94 64 64 4.8 8 120<br />
<strong>EGS</strong> 4002405 073-0063 5 15 A (FKS) 27.1 3.8 101 113 84 87 5.8 9 139<br />
<strong>EGS</strong> 4002408 075-0092 8 20 A (FKS) 27.1 5.4 130 109 90 85 5.8 12 175<br />
<strong>Type</strong> <strong>EGS</strong> 400 2403 also available ex stock for top hat rail snap-on to DIN EN 50022(article no. 043-0391).<br />
The values in the table above are for the thermal steady state at 60°C ambient temperature.<br />
Internet: www.sba.de<br />